DuraVent FasNSeal - Fixed Damper User Manual

Installation Instructions
FasNSeal Fixed Blade Damper
instruction- Fixed Damper
FasNSeal- Supplemental
®
A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF THE UTMOST IMPORTANCE THAT FASNSEAL BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS.
LISTED
INTRODUCTION
The purpose of the Fixed Blade Damper is to ensure optimum pressures through an appliance. The Damper will aid in the proper operation and eciency of the appliance by preventing higher than desired draft readings.
INSTALLATION
IMPORTANT: The max rated temperature for the xed blade damper is 392°F (200°C). When the damper is installed, the entire FNS system is to be de-rated in maximum temperature to this value.
• Always follow appliance manufacturer’s installation instructions for proper appliance setup and venting requirements.
• Refer to the FasNSeal SW & W2 Installation Instructions for correct installation to FasNSeal vent lengths and adapters.
• It is important to note that the Damper can be installed vertically, diagonally and horizontally.
• If the Damper is going to be installed horizontally, make sure the Damper Axis is horizontal (Fig.1). Make sure the venting is pitched towards the boiler by a value of ¼” drop for every foot of vent length (Fig.2 and
Fig.3) for proper condensate management. The weight on the damper is a fail safe to make certain that the damper will be open in the event of failure. Ensure that the weight is at the top of the damper plate when closed in the Horizontal (Fig.1).
Horizontal Installation (Fig.1, Fig.2, Fig.3)
• To prevent the build up of condensation in horizontal installations, it is required to use an Eccentric Increaser rather than Tapered Increasers at the male connection of the damper (Fig.2).
• Installation of the Damper in the ue venting of an appliance should be at the breech of the appliance or as close as possible.
• Lock the Damper position to the 90 degree value so that it is in the full open position.
• Ensure the female end is pointing away from the appliance.
• Once the damper has been correctly installed in the venting ue, lock the damper to 90° and then operate the burner until the appliance is suciently warmed up and chamber pressure has stabilized.
• After the chamber pressure is lower than what is prescribed by the OEM, proceed
WEIGHT
WEIGHT
CORRECT ORIENTATION OF SHAFT AXIS
INCORRECT ORIENTATION OF SHAFT AXIS
Figure 1
2
Loading...
+ 2 hidden pages