DuraVent DuraTech Adjustable Length User Manual

Installation Instructions Supplement
Adjustable Length Chimney Section
DuraTech
A MAJOR CAUSE OF CHIMNEY RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF THE UTMOST IMPORTANCE THAT THIS CHIMNEY BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS.
APPLICATION AND LISTING
A DuraTech Adjustable Length is a listed com­ponent of the UL Listed DuraTech Chimney System (MH7399). Installation of the Adjust­able Length must comply with both these supplementary installation instructions and the full DuraTech Chimney Installation Instructions (L150).
INSTALLATION NOTES
Practice good workmanship. Exercise extreme caution when working on roofs. Be sure to wear appropriate safety gear and clothing as needed. You must useonly authorized DuraTech Chimney parts to maintain a listed Chimney system (not including the connector pipe). Do not mix parts or try to match with other products, or use improvised solutions. Do not install damaged or modied parts. Refer to the full DuraTech Chimney Installation Instructions for further safety details.
WARNING
DuraTech Chimney system is listed with a 2” minimum clearance (air space) to com­bustibles. Always maintain a minimum of 2” clearance between chimney pipe and nearby combustibles. Failure to maintain the minimum 2” clearance to combustibles can result in a re hazard.
INSTALLATION
The DuraTech Adjustable Length is used when an exact length of chimney is needed
and standard lengths of chimney are not sufcient. The Adjustable Length spans from minimum of 14” to a maximum of 22” and can be used between any other DuraTech chimney sections (straight pipe lengths, elbows, tees, etc.). The Adjustable Length is a telescoping section of chimney with both male and female sections (Figure 1). Within the male section there are 2” wide strips of insulation that can be removed to allow for a customized length (Figure 2).
MALE END
SECTION
MIN 2”
OVERLAP
FEMALE END
SECTION
IF NEEDED, ADJUST
LENGTH BY REMOVING
STRIPS OF INSULATION
(SEE TABLE 1).
Figure 1
14” - 22”
2” WIDE INSULATION STRIPS
Figure 2
Loading...
+ 2 hidden pages