DuraVent DuraLiner User Manual

Page 1
Installation Instructions
High-Temperature, Factory Insulated Double-Wall Masonry Relining system 5" Round 6", 8" Round and Oval
DuraLiner
®
Page 2
A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE
TO COMBUSTIBLE MATERIALS. IT IS OF THE UTMOST
IMPORTANCE THAT DURALINER BE INSTALLED ONLY IN
ACCORDANCE WITH THESE INSTRUCTIONS.
IMPORTANT: Read through all of these instructions before beginning your installation. Failure to install this product as described in these instructions will void the manufacturer’s
warranty, may create a re or other safety
hazard, and may affect your homeowner’s insurance and safety listing of your appliance.
Keep these instructions for future reference.
Dear Customer, Installer, or End User:
We welcome any comments, ideas, or input pertaining to DuraVent products.
If you are searching for tech support or product information, please phone us at 800-835-4429. Or email us at: techsupport@duravent.com
MH14420
Page 3
DURALINER INSTALLATION INSTRUCTIONS
For the most up-to-date installation instructions, see www.duravent.com
CONTENTS
APPLICATION AND LISTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
GENERAL INSTALLATION INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . .5
OPEN HEARTH INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
MASONRY BREACH INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
COMBUSTIBLE WALL BREACH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
EXTEND-A-CAP INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
INSULATING FLEX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
TRANSITION ANCHOR PLATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
DURALINER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
DuraLiner
®
3
Page 4
IMPORTANT MEASUREMENTS
1
1. Flue size I.D.:
_____________________
2. Opening of replace:
height _____________
width ______________
depth ______________
4
length______________
width ______________
3. Damper opening:
3
6
4. Total chimney and replace height:
___________________
5. Total chimney height to tee opening:
2
Figure 1
1
___________________
6. Height to rst tile:
___________________
7. Height of appliance:
___________________
A
5
4
B
3 1/2”
TYPE A B
6" ROUND 7" 7"
8" ROUND 9" 9"
6" OVAL 8" 5 1/2"
8" OVAL 11 5 1/2" - 6"
Figure 2
Figure 3
4
Page 5
APPLICATION AND LISTING
DuraLiner is a double-wall, insulated all­fuel reliner for masonry chimneys, used for natural draft venting of gas, liquid and solid fuel appliances. DuraLiner is listed to UL
1777 and ULC S635 under listing le number
MH14420, where maximum continuous
ue gas outlet temperatures do not exceed
1000°F/538°C (UL 1777) or 1200°F/650°C (ULC S635). DuraLiner is approved for installation with zero clearance between the liner and masonry, plus zero clearance between the masonry and combustibles. When the Transition Anchor Plate is used, Round DuraLiner pipe can be coupled to a Duravent factory built 103HT chimney system at the end of a masonry enclosure.
GENERAL INSTALLATION INSTRUCTIONS
Follow both these and the appliance manufac­turer’s instructions and manual for maximum
efciency and safety. Connect only one ue
liner per appliance. DO NOT mix or match with other products or improvise solutions­(You may void warranties). DO NOT modify parts.
Contact your local building ofcial or re
department regarding permits, restrictions, and installation inspection in your area. Have a professional installer thoroughly inspect (to code requirements) and clean the existing
masonry ue of tar glaze creosote before
relining. The chimney should be checked for cracked, loose or missing bricks, mortar, or other materials that could inhibit correct installation of the liner system. Make necessary repairs prior to starting install.
Do not place insulation or other materials
other than specied in these instructions
around the liner or in required air spaces.
Determine if your setup is an open hearth (Fig.1) or wall breach installation (Fig.2). Also determine the available size of your chimney and the corresponding allowable DuraLiner size. (Fig.3)
If you have an open hearth setup, verify
your ue size, and the replace opening
and depth before you purchase your appliance and reliner.
If you have a wall breach tee installation
setup, verify your ue size and chimney
height from tee, before you purchase your appliance and reliner.
DuraLiner shall be sized not less than that
specied in the appliance manufacturer’s
instructions. Vent sizing is especially important in areas with low ambient temps and low
temp ue products. Determine the required
size of DuraLiner and the correct Appliance Connector (follow appliance manufacturer’s recommendations). There are three different types of appliances connections (Fig.4).
ROUND CONNECTOR
HIGH TEMPERATURE SEALANT
APPLIANCE
APPLIANCE INSERT
HIGH TEMPERATURE SEALANT
ROUND CONNECTOR
OVAL CONNECTOR
HIGH TEMPERATURE SEALANT
APPLIANCE
Figure 4
5
Page 6
From the appliance up through the damper
area to the rst ue tile, it is not mandatory to insulate ex pipe. Above the rst ue tile, ex pipe must be insulated. NOTE:
For improved draft and re safety, we recommend ALL ex pipes be insulated
(Fig.5)- (See "Installing Insulation" later in these instructions for detail).
in this document). Note: If using an Oval pipe, this will need to be inserted prior to the plate. DuraLiner is supported from the top, and the top plate is designed to support the weight of a relining system up to 50 feet (the minimum height of the system must be at least 10-feet to ensure proper drafting performance). (Fig.6)
ZERO CLEARANCE TO MASONRY IN THIS AREA IF INSULATION SLEEVE IS USED
FLUE TILE STARTS AT THIS POINT
ZERO CLEARANCE TO MASONRY IN THIS AREA
Figure 5
OPEN HEARTH INSTALL (Fig.1)
STEP ONE: Clear the ue of obstructions
for Duraliner to be installed. If applicable, remove the existing damper from your
replace (not needed) and in some cases part
of the smoke shelf to allow DuraLiner to pass through this area freely.
Note: DuraLiner ex pipe is available in both round and oval shapes to ease installation.
STEP TWO: Prepare the top of the Masonry chimney and install the top plate assembly (Reference "Extend-A-Cap" instructions later
TOP PLATE
TOP SUPPORT CLAMP ASSEMBLY
Figure 6
STEP THREE: Start with your rst component (ex pipe, rigid pipe, or tee). If a tee is used,
the branch may be removed for installation (Fig.7).
REMOVEABLE BRANCH AND HARDWARE
Figure 7
DuraLiner pipe (ex and rigid) has male and
female connectors with (4) pre-punched holes and slots that line up and are connected with stainless steel pop rivets (Fig.8). Do not use
screws. When connecting sections of ex pipe, it is necessary to rst align the holes with the slots, and then drill through the ex
6
Page 7
pipe with a 5/32” (4 mm) diameter twist drill bit. Next, install the pop rivets. Drilling is not needed to connect sections of rigid pipe.
Connect rst rigid section of DuraLiner on top of ex section with (4) stainless steel pop
rivets. Note: For insulating DuraLiner Flex, refer to the "Insulating Flex" Instruction section later in this document.
RIVET PIPE SECTIONS
Connector ts on top vented appliances with
oval or rectangular openings. STEP FIVE: Connect appliance to DuraLiner. (Fig.9)
FLEX PIPE
STOVE CONNECTOR
POP RIVET OR SCREW FLEX PIPE TO STOVE CONNECTOR
1/2"
Figure 8
After pipe is riveted together, lower through the Top Plate and clamp the pipe to support (Fig.6). Attach next pipe section- Alternately tighten and loosen the Top Plate clamp assembly to hold and lower the pipe sections.
Repeat until the ex section reaches the
smoke shelf area. As the pipe is being
lowered down, bend the ex pipe to t through
the damper area. Lower DuraLiner to nal position. STEP FOUR: Connect appropriate DuraLiner adapter to appliance (Fig.4). The DuraLiner
round Appliance Connector ts either a top vented or rear vented round ue appliance. Place the proper sized connector over the ue
exit and mark on the appliance the locations of the holes where the connector will be attached. Drill and tap hole in top or rear of appliance or use self tapping screws. Before attaching permanently, put a bead of high temperature sealant between appliance connector and insert. The DuraLiner oval appliance
Figure 9
FLEX PIPE
OVAL OR
ROUND
STOVE
CONNECTOR
RIGID TEE OVAL OR ROUND
ADJUSTABLE SLEEVE (MIN. OVERLAP 2")
Figure 10
Note: If you have a round ue outlet on your
appliance, and you have used Oval Flex or
Oval-To-Round ex through the damper area, a Round-To-Oval ex piece or adapter will be
needed for the appliance connection. If appliance has a round rear exit, align tee with exit of appliance. An adjustable sleeve
7
Page 8
can be used to connect appliance to the tee using the pre-formed buttons for connection. The buttons snap into the branch ring. Slide appliance into proper position. Secure
Adjustable Sleeve in nal position with sheet metal screws. Rear ue exit should look like
Fig.10.
STEP SIX: Complete "Extend-A-Cap" termination. (Reference "Extend-A-Cap" instructions later in this document)
Note: National Fire Protection Association standard #211 states; “Chimneys shall extend at least three feet above the highest point where they pass through roof of a building and at least two feet higher than any portion of a building within ten feet.” (Fig.11)
2 FEET MIN. ABOVE POINT OF ROOF WITHIN 10 FEET
3 FEET MIN. FROM ROOF PENETRATION
10 FEET
Figure 11
WALL BREACHING (Fig.2)
There are two types of wall breaching:
- Masonry
- Masonry and Combustible Wall (Note: Wall penetration assemblies shall not be located directly behind a heating appliance.)
clearance to the ceiling for single wall pipe is 18", and for DuraVent Close Clearance Connector (DVL) Pipe, 8" (Fig.12).
COMBUSTIBLE
CLEARANCES: 18" SINGLE WALL PIPE
8" DURAVENT DVL PIPE
ACCESS DOOR FOR CLEANOUT
Figure 12
Using the center mark punched into the masonry, inscribe a circle of 3- 1/4 inch radius (6-1/2 inch diameter), or 4-1/4 inch radius (8-1/2 inch diameter), depending upon whether 6 inch or 8 inch Dura-Liner Pipe is used. Remove bricks as necessary to approximate a circle (Fig.14). Smooth out the circumference of the hole with high-temperature grout or mortar. Follow "OPEN HEARTH INSTALLATION" instructions for installation of DuraLiner pipe in masonry. The end of the DuraLiner pipe should have a "Tee" for the wall breaching, and will be lowered to the masonry breach.
Masonry Breaching
STEP ONE: If no hole exists in the masonry, mark the center point for the location of penetration. Before cutting or drilling, check the clearance between the top of the connecting pipe to the ceiling. The minimum
8
STEP TWO: As the DuraLiner rigid pipe is
being lowered into nal position, line up the
branch of the Tee with hole in the masonry chimney wall. (Fig. 13). Attach Tee branch to Tee body (Fig.7).
Page 9
STEP THREE: Using DuraVent's Masonry Thimble with Slip Connector, connect slip connector to Tee Branch with the pre­formed buttons. Slide Masonry thimble to slip connector and attach black trim plate to masonry surface using screws. (Fig.13)
MASONRY
THIMBLE
TEE
ANCHOR
SCREWS
ACCESS
SLIP CONNECTOR
FROM MASONRY
THIMBLE
DOOR FOR CLEANOUT
Figure 13
STEP FOUR:
Finish installation to appliance using connector pipe, maintaining required clearances.
Combustible Wall and Masonry
(See completed installation in Fig.15) STEP ONE: If no hole exists in the masonry, mark the center point for the location of penetration into the combustible wall. Before cutting or drilling, check the clearance between the top of the connecting pipe to the ceiling, as shown in Fig.12, Fig.15. The minimum clearance to the ceiling for single wall pipe is 18", and for DuraVent DVL Connector Pipe, 8".
Scribe a circle from the center point on the wall with a 7-1/4 inch radius (14-1/2 inch diameter) (Fig.14). This is the size of the hole required
for the Wall Pass-Through to t through the
combustible wall. Again, before cutting this hole, check the clearance from the top of the Connector Pipe to the ceiling.
STEP TWO: If the minimum clearance to the combustible ceiling is met, then drill a 3/8 inch diameter hole through the combustible wall, at the center of the 14-1/2 inch circle you have inscribed. With a punch, mark the center on the masonry behind the wall. Cut the 14-1/2 inch diameter hole in the wall. If it is necessary to cut through studs, additional framing should be installed to maintain the structural integrity of the wall (Fig.14). STEP THREE: Using the center mark
14 1/2
STUDS ON 16-INCH CENTERS
FRONT VIEW
6 1/2 OR 8 1/2 DIA.
GROUT
SIDE VIEW
Figure 14
punched into the masonry, inscribe a circle of 3- 1/4 inch radius (6-1/2 inch diameter), or 4-1/4 inch radius (8-1/2 inch diameter), depending upon whether 6 inch or 8 inch Dura-Liner Pipe is used. Remove bricks as necessary to approximate a circle. Smooth out the circumference of the hole with high­temperature grout or mortar. Maintain the concentricity of this hole with the hole cut in the combustible wall. The completed hole should look like (Fig.14).
9
Page 10
STEP FOUR: Push the Adjustable Sleeve from the Wall Pass Through into the branch of the tee. Connect Adjustable Sleeve to Tee Branch with the pre-formed buttons. Recommended to grout in place with a high temperature grout
(Fig.15, Fig.16).
STEP FIVE: Slide the Wall Pass-Through
through the square trim plate and into the
EXTEND-A-CAP ASSEMBLY
Adjustable Sleeve until the base of the Wall
Pass Through is ush against the masonry
(Fig.17) NOTE: The Wall Pass Through must protrude a minimum of 2" into the room (Fig.16).
Attach the 10" Long Rigid Pipe Section to the front of the Wall Pass Through with four sheet screws through the L-brackets (Fig.15, Fig.16)
Position the appliance, at it’s nal location.
10
RIGID PIPE
SPACER
RIGID TEE
ACCESS DOOR
(FOR CLEANING)
1 INCH AIR GAP
Figure 15
MINIMUM
CLEARANCE:
(NOTE BELOW)
COMBUSTIBLE WALL THIMBLE ASSEMBLY
PIPE (AS REQUIRED)
NOTE: MINIMUM CLEARANCE FOR SINGLE WALL STOVEPIPE IS 18 INCHES. FOR DVL PIPE, THE MINIMUM IS 8 INCHES.
Page 11
Check the appliance manufacturer’s
ASSEMBLY)
installation instructions to ensure proper positioning with relation to combustibles.
EXTEND-A-CAP INSTALLATION
The cap may be installed on both round and oval rigid systems.
Complete the installation with Connector Pipe Sections and Fittings as required. Inspect the completed job to ensure it is done in a careful and workman-like manner.
TRIM COLLAR AND SCREWS (COMPONENTS OF WALL PASS-THRU ASSEMBLY)
2" INTO THE ROOM
RIGID PIPE AND SCREWS (COMPONENTS OF WALL PASS-THRU
Figure 16
STEP ONE: Center the base plate on the top of the masonry chimney (Fig.18). Trim to t the chimney as required. Use non-hardening sealant to seal the base plate to the masonry chimney, but this can be done after the liner has been lowered into place. Anchors or screws are recommended but not required, as the base plate will ultimately be supporting the entire weight of the installation.
STEP TWO: Assemble and position the clamp assembly on top of the base (Fig.6, Fig.18). Adjust the bolts on the clamp assembly so that pipe sections will just pass through the clamp.
STEP THREE: Once the desired length of liner has been achieved, tighten the clamp
assembly bolts, until the system is rmly
supported by the base. There should not be a Duraliner pipe joint above the clamp assembly. Attach the storm collar, and seal with non­hardening silicone (500°F) sealant. Install Cap to pipe, using #8 sheet metal screws. (Fig.19).
ADJUSTABLE
TRIM PLATE
INSULATED WALL PASS THROUGH
10" LONG RIGID PIPE SECTION
COMBUSTIBLE WALL
SLEEVE
HARDWARE
THROUGH AGAINST
Figure 17
WALL PASS
MASONRY
11
Page 12
Do not construct chases or other enclosures around DuraLiner pipe sections which extend above the masonry.
CAP AND SPARK
NOTE: MOISTURE MUST NOT ENTER THE LINER SYSTEM!
ARRESTOR
STORM COLLAR
CLAMP
BASE
and trim the blanket so that the ex end rings
are exposed. Wrap the insulation around the liner lengthwise and trim it so that a butt joint is formed. Seal the joint with aluminum foil tape. Spray adhesive may be used to hold the blanket in place until it can be secured with the foil tape. A minimum of 1/2" of insulation is required. Install ProMesh protective wire mesh over the blanket(s). The ProMesh is used to protect the ProFoil insulation as the liner is lowered into the chimney. Slip the ProMesh over the insulated liner and secure one end with a stainless steel band clamp. Pull the ProMesh towards the other end of the liner so that it tightens snugly around the insulation, then trim off the excess. Secure this end with a stainless steel band clamp or alum tape.
LINER
Figure 18
NO DURALINER PIPE JOINT ABOVE CLAMP
Figure 19
INSULATING FLEX
Duravent requires ex be insulated above the rst Masonry ue tile, and strongly
recommends ALL Flex pipe be insulated.
Method #1: PROFOIL (Fig.20)
Roll out the insulation blanket on a clean
surface, foil face down. Lay the ex liner on top
12
1/2" OF PROFOIL
ALUMINUM TAPE
PROMESH
CLAMP
Figure 20
Method #2: INSULATION SLEEVE
Slip the Insulation Sleeve over the ex
pipe. Install the bottom insulation sleeve clamp, and push the top of the sleeve down 4"-6". Position clamps so the nut and bolt connections are pointing towards the corner of a rectangular chimney.
Page 13
TRANSITION ANCHOR PLATE
Ensure Round DuraLiner Pipe section will be within 12" of the top of the masonry. Secure Hanger to the top piece of DuraLiner pipe. Lower the Transition Anchor Plate (T.A.P) and allow the legs of the Hanger to slide through the oval slots in the T.A.P. Attach T.A.P. to the
top of the existing masonry with eld supplied
hardware. If desired, a bead of 1000°F stove cement may be used as a gasket for this surface. Pull hanger straps tight, fold down, and bolt to plate using provided hardware.
Once the hanger is afxed to the T.A.P., insert
slip connector down through the T.A.P. and into DuraLiner pipe (Fig.21). Place Chimney onto
Transition Anchor Plate and afx with screws
to the brackets as shown.
Note: If using DuraPlus Chimney and enclosing in a chase, the DuraPlus Starter
section MUST be the rst section of Chimney
used at the Transition Anchor Plate.
CHIMNEY
TRANSITION ANCHOR PLATE ASSEMBLY
SLIP CONNECTOR
HOLD DOWN BRACKETS
TRANSITION ANCHOR PLATE
HANGER
DURALINER
Figure 21
DURALINER MAINTENANCE
- Creosote and Soot-Formation and Need for Removal: When wood is burned slowly, it produces tar and other organic vapors, which combine with expelled moisture to form creosote. The creosote vapors may condense on the inside of the chimney liner
during slow-burning ring periods. As a result,
creosote residue accumulates on the chimney liner. When ignited, this creosote makes an
extremely hot re.
- The chimney liner system should be inspected at least once every two months during the heating season to determine if a creosote or soot buildup (3mm or more) has occurred. The spark arrestor screen should be checked more frequently. If creosote or soot has accumulated, it should be removed to
reduce the risk of a chimney re.
1. Access – Chimney liners must be installed to provide access for inspection and cleaning.
2. How to Clean – Recommend to have your chimney liner cleaned by a professional
certied chimney sweep. Use a plastic, wood, or exible steel or wire brush- do not mar the
stainless steel liner surface. To remove the chimney cap for cleaning, unscrew the four screws that attach the cap’s support legs to the cap base.
3. Coal – Clean the chimney thoroughly within 48 hours of shutting down the appliance for the season. Check the chimney for acid corrosion regularly.
4. No Chemical Cleaners – Do not use chemical chimney cleaners. Their use does not eliminate the need for mechanical cleaning and they may be highly corrosive.
6. In case of Fire – If a ue re occurs, close
all appliance draft openings and call your Fire Department. Do not use the chimney again until it is inspected for possible damage.
13
Page 14
INSTALLATION NOTES:
14
Page 15
INSTALLATION NOTES:
15
Page 16
M&G DURAVENT LIMITED LIFETIME WARRANTY
M&G DuraVent, Inc. (“DuraVent”) provides this limited lifetime warranty for all of its products with the exception of Ventinox® (lifetime), and PolyPro® (ten years). Subject to the limitations set forth below, DuraVent warrants that its products will be free from defects in material or manufacturing, if properly installed, maintained and used. DuraVent products are fully warranted if installed only by a professional installer. This Warranty is transferable from the original homeowner to the buyer of the home. This warranty does not cover normal wear and tear, smoke damage or damage caused by chimney res, acts of God, or any product that was: (1) purchased other than from an authorized DuraVent dealer, retailer or distributor; (2) modied or altered; (3) improperly serviced, inspected or cleaned; or (4) subject to negligence or any use not in accordance with the installation instructions included with the product as determined by DuraVent. Installation instructions are available online at www.duravent.com under Support/Literature and through our Customer Service Department 800-835-4429 or customerservice@ duravent.com. This limited lifetime warranty applies only to parts manufactured by DuraVent.
DuraVent provides the following warranties for its products: One Hundred Percent (100%) MSRP 15 years from the date of purchase, and Fifty Percent (50%) thereafter, except for the following limitations on: all Termination Caps and DuraBlack® are warranted at One Hundred Percent (100%) for ve years.
All warranty obligations of DuraVent shall be limited to repair or replacement of the defective product pursuant to the terms and conditions applicable to each product line. These remedies shall constitute DuraVent’s sole obligation and sole remedy under this warranty. This warranty provides no cash surrender value. The terms and conditions of this warranty may not be modied, altered or waived by any action, inaction or representation, whether oral or in writing, except upon the express, written authority of an executive ocer of DuraVent.
Corn, bio-fuels, driftwood or other wood containing salt, preservative-treated lumber, plastic and household trash or garbage, or wood pellets containing such materials must not be burned in the appliance or replace. In case of a chimney re, the chimney must be inspected and approved by a certied Chimney Sweep before reuse. After each annual inspection, maintenance, and cleaning, the certied Chimney Sweep must ll out and date the appropriate section of the warranty card provided with the chimney liner.
LIMITATIONS ON INTERNET SALES: Notwithstanding any other terms or conditions of this Limited Lifetime Warranty, DuraVent provides no warranty for the following specic products if such products are not installed by a qualied professional installer: DuraTech®, DuraPlus HTC®, DuraChimney® II, PelletVent Pro®, DirectVent Pro®, FasNSeal®, FasNSeal® W2, FasNSeal® Flex, and PolyPro®, and M&G DuraVent’s relining products including DuraLiner®, DuraFlex® (SW, Pro, 316, 304), and Ventinox®. For purposes of this warranty, a trained professional installer is dened as one of the following: licensed contractors with prior chimney installation experience, CSIA Certied Chimney Sweeps, NFI Certied Specialists, or WETT Certied Professionals.
DuraVent must be notied and given the opportunity to inspect defective product prior to replacement under the terms of this limited lifetime warranty. All warranty claims must be submitted with proof of purchase. Labor and installation costs are not covered under this warranty. To obtain warranty service contact: DuraVent Warranty Service, 877 Cotting Ct., Vacaville CA 95688, or call 800-835-4429.
WHERE LAWFUL, DURAVENT DISCLAIMS ALL OTHER WARRANTIES, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT WILL DURAVENT BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, PUNITIVE OR SPECIAL DAMAGES OR DIRECT OR INDIRECT LOSS OF ANY KIND, INCLUDING BUT NOT LIMITED TO PROPERTY DAMAGE AND PERSONAL INJURY. DURAVENT’S ENTIRE LIABILITY IS LIMITED TO THE PURCHASE PRICE OF THIS PRODUCT. SOME STATES DO NOT ALLOW LIMITATIONS ON IMPLIED WARRANTIES, OR THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS AND EXCLUSIONS MAY NOT APPLY TO YOU. THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS THAT VARY FROM STATE TO STATE.
For the most up-to-date installation instructions, see www. duravent.com
REV 3.22.2012
Manufactured in Vacaville CA and Albany NY
Customer Service Support 800-835-4429 707-446-4740 FAX www.duravent.com
DuraLiner is a registered trademark of the M&G DuraVent, Inc. All rights reserved. Made in the USA. M&G DuraVent is a member of M&G Group. ©2012
L402 09/2012
Loading...