Durant-Eaton AMBASSADOR SERIES Instruction Manual

Durant
®
INSTALLATION AND OPERATION MANUAL Number 57600-905-03
AMBASSADOR SERIES COUNT CONTROL
MODELS:
57600-405 (10-15 VDC) 57600-415 (10-15 VDC) 57600-465 (10-15 VDC) 57601-405 (115 VAC) 57601-415 (115 VAC) 57601-455 (115 VAC) 57601-465 (115 VAC) 57602-405 (230 VAC) 57602-415 (230 VAC) 57602-465 (230 VAC)
• Six Digit, Four Preset Main Counter
• Six Digit, Single Preset Batch Counter
• Red or Green Display
• Eight Digit Totalizer
• 1/Tau Rate Meter
• Four User-Configurable Control Inputs
• Two Output Relays
• Two Solid State Outputs
• RS-485 Serial Communications
• Feet/Inches Control, Red or Green Display
Durant
®
C 123456 P1 10000
RST CLR
EXIT ENT SEL
RUN
PGM
PRNT
N A E D
ASSOCIATE
TABLE OF CONTENTS
1 Introduction 2 Block Diagram
3 Installation Wiring and Programming - Quick Start 10 Rear Terminal Description 12 Program Mode 22 Description of Program Options 26 Wiring 29 Calculating Scale Factors 30 Run Mode 33 Feet/Inches Control 34 Troubleshooting 36 Specifications 37 Parts / Accessories 38 Dimensions
Durant
INTRODUCTION
This manual describes the Ambassador 5760X-405 count control, and is intended to be a guide in the installation and operation of the control.
The control itself is like an electronic erector set, full of counter and ratemeter "parts" which the user must "as­semble". The majority of this manual is concerned with installation, describing the parts of the counter, helping the user determine the wiring and programming necessary to "assemble" his counter into the tool he needs to do a specific job, and documenting those choices. The operation section, which describes the operator functions, follows in the section Run Mode. The following description of the control and the block diagram is recommended reading for those new with this device. Those installers who are familiar with controls and counter terminology are welcome to attack the Quick Start section after examining the block diagram. The Quick Start uses a logical inputs-to-outputs approach to decide how to wire and program this control to do the job. Detailed programming and wiring information follow the Quick Start section, providing guidance to the first time installer.
MAIN COUNTER
The main counter is a six digit, bi-directional count register designated by the letter C on the display. The user can assign up to four presets to this counter. The main counter is the workhorse of this control. Note its central location in the block diagram and the number of "connections" to it. This register increments and decrements from scaled count input pulses. The "favored" count direction is up in reset to zero mode and down in reset to final preset mode. The favored count direction feature affects only the function of the count inputs, and the direction of the totalizer count, and the preset selected for the current preset display. The main count display screen can be customized to identify what type of units are being counted.
RATEMETER
The control uses the frequency of the count pulses at input A to calculate rate. The rate scaler accommodates the "weight" of each pulse and the time units in order to display rates such as revolutions per minute, barrels per hour, etc. The rateme­ter average and zero times are programmable. Two alarm setpoints are assigned to the ratemeter. The rate display text can be customized.
OUTPUTS
Two form C relay and two open collector NPN transistor outputs are available. Each output is individually assignable to rate or count. Count outputs can turn on or off at any combination of eight preset and control events. These out­puts can be timed or latched, and each has a programmable on-delay timer. Rate based outputs turn on based upon comparison to one of two rate alarm setpoints. Rate outputs turn off after timeout (pulsed), external control signal (latched), or when the rate crosses the setpoint back to the non-alarm state (follows).
COUNT INPUTS
Count inputs A and B are DIP switch settable to accept sinking or sourcing single ended DC or differential count signals. Input A is used by the ratemeter. Inputs A and B are programmable to affect the main counter and totalizer in eight count modes and three count/control modes.
CONTROL INPUTS/RESET KEY
Four control inputs are available. These inputs are single ended DC, sink only and are programmable to one of 14 functions. The reset key may be programmed to reset one, all, or none of the count registers.
TOTALIZER
The totalizer is an eight digit, bi-directional count register that counts in parallel with the main counter. The totalizer counts up when the main counter counts in the favored count direction, and down when the main counter counts in the non­favored direction. The totalizer display can be customized to show units of count. The totalizer does not have preset or output capability.
BATCH COUNTER
The batch counter counts the number of "batches" of the main counter, incrementing every time the main counter autocycles or reaches the final preset. This register is six digits and counts up only. The batch counter has one preset, and always autocycles whenever it reaches the setpoint. The batch count display can be customized to show units of count.
RS 485 SERIAL COMMUNICATIONS
The control uses RS-485 serial communications in either host mode: to respond to a host computer, or printer mode: to dump selected values to a printer. The print transmission is initiated by either the Print key or a control input. The communication capability is described in a separate manual. If you need information on the serial communications, con­tact the Literature Department at 1-800-540-9242.
FEET/INCHES CONTROL
Models 57601-415 (green display) and 57601-465 (red dis­play) have a readout in feet and inches with a fixed decimal point separating them. These models also have a floating prewarn that adjusts itself to the final preset. See page 33 for more details.
1
BLOCK DIAGRAM
A in
20
B in 19
15 16 17 18
RST CLR
COUNT
LOGIC
R
CONTROL
INPUT
ASSIGNMENT
Total Count
Main Count
R
R, SC, BP1, PU, DO
COUNT
SCALER
Scaled Total
Scaled Main
RATE METER (Rate Scaling) Not available on feet/inches control.
R
TOTALIZER
C
MAIN
C
COUNTER
BP1 SC R
BATCH
C
COUNTER
R
P1 P2 P3
*P4
P1/PF
Pb
A1 A2
PU, DO
PU, DO
PU, DO
PU
PU
PU
DO
PU
DO
PU
DO
TRANSISTOR 1 OUTPUT LOGIC
TRANSISTOR 2 OUTPUT LOGIC
RELAY 1 OUTPUT
RELAY 2 OUTPUT
14
13
10
9
8
7
6
5
Key
R
SC
BP1
Reset Stop Count Bypass P1
Pick Up
PU
Drop Out
DU
Screw Terminal
C Count *P4 is the prewarn (Pw) on the
The block diagram shows the major internal "parts" of the control. A general description of each block was given on the previous page. The block diagram shows how the parts relate to each other. The flow through the control is generally left to right; inputs are designated by screw terminal number on the left side of the block, and output terminals are shown on the right side. In between, arrows lead from block to block from the count inputs (19 and 20) to the count and rate registers. The open ended arrows indicate "connections" that can be made by programming.
Feet/Inches control.
The block diagram shows that the control will not respond to the control inputs; (15, 16, 17, 18 and RST key) until they are programmed to a specific function, and the outputs are also oblivious to the count and rate registers until a programming "connection" is made.
2
INSTALLATION WIRING AND PROGRAMMING - QUICK START
This section is a step-by-step process for determining pro­gram selections and I/O wiring. If the installer has a basic knowledge of counter terminology and uses the block dia­gram for a reference, the configuration process should be straightforward. Detailed descriptions of programming choices are listed on pages 22 to 25. Detailed I/O wiring diagrams are shown on pages 26 to 28. Instructions on calculating scale factors are on page 29.
For each programming choice, a program item number is listed. A selection space is provided to record the desired selection. These numbers can be also recorded in the programming menu chart on pages 14 to 21, in order to
D
document the application.
in the choice lists indicates
default setting. I/O terminals used in the application can be labeled in the
space provided on page 10.
Phase I - The Vital Ingredients
1. Count Logic/Main Counter/Totalizer behavior determined by:
PROGRAM COUNT IN
A. Count Mode
Program Item 10 Selection __________ Consider: Type of count input sensor(s), main
counter and totalizer functions, and input B as a count or control input.
Choices:
D
CNT + TOT A-B
CNT + TOT A, B DIR
CNT + TOT QUAD X1
TOT A CNT B
C. Input B Response
Program Item 12 Selection __________ Consider: Input speed <40Hz? If yes, use contact.
This item is not visible if a QUAD count mode or B RST is selected (forced to SOLID ST) or if B DIR is selected (forced to CONTACT).
Choices:
D
INPUT B SOLID ST
INPUT B CONTACT
D. Input B Reset
Program Item 13 Selection __________ Consider: Which count register(s) should input B
reset? This item is only visible if B RST count mode is selected.
Choices:
D
B RST CNT EDG
B RST BCH EDG
B RST TOT EDG
B RST ALL EDG
E. Final Preset
Program Item 14 Selection __________ Consider: How many setpoints will be needed on
the main counter? Set Pf to that number. Choices:
FINAL P f
D
P 4
FINAL P f P 2
CNT + TOT A+B
CNT + TOT
-A+B
CNT + TOT 2A, B DIR
CNT + TOT A, B RST
CNT + TOT QUAD X2
CNT + TOT QUAD X4
TOT B CNT B
Label the assignment of count inputs A + B (termi­nals 20 and 19) on the diagram on page 10.
B. Input A Response
Program Item II Selection __________ Consider: Input speed <40Hz? If yes, use contact.
This item is forced to SOLID ST and is not visible if a QUAD count mode is selected.
Choices:
D
INPUT A SOLID ST
INPUT A CONTACT
FINAL P f P 3
FINAL P f P 1
F. Reset to Zero/Preset
Program Item 15 Selection __________ Consider: Reset to Preset is considered a down
counting mode for the main counter. Choices:
D
RESET TO ZERO
RESET TO P f
G. Main Counter Auto Cycle
Program Item 16 Selection __________ Consider: Batch counter increments each time the
main counter auto cycles or Pf is reached.
3
INSTALLATION WIRING AND PROGRAMMING - QUICK START
D
RELAY 2 ______
TRANS 1 ______
TRANS 2 ______
Choices:
D
AUTO CYC DISABLED
AUTO CYC P 1
AUTO CYC P f (0)
AUTO CYC P1 P f (0)
2. When appropriate, adjust the count scaler and set up the ratemeter in:
PROGRAM SCALERS
Note: Calculation of scalers and decimal point selection is explained on page 29.
A. Count Scaler
Program Item 0 Selection __________
C SCALER
D
1.00000
B. Count Decimal Point
Program Item 1 Selection __________
C DEC PT
D
- - - - - -
* * *AT THIS POINT, refer to the block diagram. We are almost done with figuring out how the counters and ratemeter are going to behave. All that's left to getting an output to occur at the terminals on the right side when count pulses come in at the terminals on the left is to program some "connections" between the count/rate registers and the output blocks. This is done in step 3.
3. Educating the outputs:
PROGRAM OUT MODE
Note: All four output blocks (Relay 1, Relay 2, Trans 1, and Trans 2) are included in PROGRAM OUT MODE. The choices for all outputs are exactly the same. Only Relay 1 choices will be shown here, but spaces for recording the selections for the other outputs are pro­vided.
RELAY 1 PROGRAM
A. Count or Rate Activated Output
Program Item 300 Selection __________ Consider: Should this output turn on or off based on
a ratemeter setpoint? If yes, choose rate.
C Rate Scaler
Program Item 2 Selection __________
R SCALER
D
1.0000
D. Rate Decimal Point
Program Item 3 Selection __________
R DEC PT
D
- - - - - -
E. Rate Zero Time
Program Item 4 Selection __________ Consider: Maximum ratemeter response time to
the process being considered "stopped".
R ZERO
D
TIME 1.0
F. Rate Average Time
Program Item 5 Selection __________
R AVG
D
TIME 1.0
Choices:
RELAY 1
D
COUNT
RELAY 1 RATE
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
* * * If RATE is selected, skip to N.
B. Output Operation
Program Item 303 Selection __________ Consider: Reverse mode is also known as contrary
mode. Pick Up events are really Drop Out events and vise versa.
Choices:
RELAY 1
D
NORMAL
RELAY 1 REVERSE
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
C. Output Latch / Timeout
Program Item 304 Selection __________ Consider: Latched will require both a Pick Up and
Drop Out event. Choices:
RELAY 1 LATCHED
RELAY 1 PULSED
4
INSTALLATION WIRING AND PROGRAMMING - QUICK START
* * * If LATCHED is selected, skip to E.
D. Output "On" Time
Program Item 305 Selection __________
RELAY 1
D
PUL 1.00
E. Output On Delay Time
Program Item 306 Selection __________ Consider: How many seconds should elapse after
a Pick Up event occurs before the output actually picks up?
RELAY 1
D
DEL 0.00
F. Preset 1 Action
Program Item 307 Selection __________ Consider: Should the output Pick Up or Drop Out at
Preset 1 or ignore Preset 1 (No Action)? Choices:
RELAY 1
D
P1 NA
RELAY 1 P1 PU
RELAY 1 P1 DO
G. Preset 2 Action
Program Item 308 Selection __________
RELAY 1
D
P2 NA
RELAY 1 P2 PU
RELAY 1 P2 DO
H. Preset 3 Action
Program Item 309 Selection __________
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
K. Output Control 1 Action
Program Item 30C Selection __________ Consider: This signal comes from a control input
programmed to Output Control 1 (OUT CTL 1). Choices:
D
RELAY 1 OCTL1 NA
RELAY 1 OCTL1 PU
RELAY 1 OCTL1 DO
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
L. Output Control 2 Action
Program Item 30D Selection __________ Consider: This signal comes from a control input
programmed to Output Control 2 (OUT CTL 2). Choices:
D
RELAY 1 OCTL2 NA
RELAY 1 OCTL2 PU
RELAY 1 OCTL DO
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
M. Counter Reset Action
Program Item 30E Selection __________ Consider: This signal comes from a control input
and/or the front panel reset key programmed to Reset Count (RSC EDG, or RSC LVL).
Choices:
RELAY 1
D
RS C NA
RELAY 1 RS C PU
RELAY 1 RS C DO
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
* * * This completes the programming for Relay 1 when
it is programmed for count. Go back to choice A at the
beginning of this step and repeat the process for each remaining output needed.
RELAY 1
D
P3 NA
I. Preset 4 Action
Program Item 30A Selection __________
RELAY 1
D
P4 NA
J. Batch Preset Action
Program Item 30B Selection __________
RELAY 1
D
PB NA
RELAY 1 P3 PU
RELAY 1 P4 PU
RELAY 1 PB PU
RELAY 1 P3 DO
RELAY 1 P4 DO
RELAY 1 PB DO
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
N. Output Setpoint Assignment
Program Item 301 Selection __________ Consider: Which setpoint, A1 or A2, should this
output respond to, and should it turn on above (hi) or below (lo) the setpoint?
Choices:
RELAY 1
D
A 1 HI
RELAY 1 A 1 LO
RELAY 1 A 2 HI
RELAY 1 A 2 LO
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
5
INSTALLATION WIRING AND PROGRAMMING - QUICK START
O. Output Duration
Program Item 302 Selection __________ Consider: Once the output turns on, by what means
will it turn off? Choices:
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
D
RELAY 1 DISABLED
RELAY 1 FOLLOWS
RELAY 1 LATCHED
RELAY 1 PULSED
* * * If PULSED is selected, continue to choice P; if not,
go back to choice A and repeat the process for each remaining output needed.
P. Output "On" Time
Program Item 305 Selection __________
RELAY 1
D
PUL 1.00
RELAY 2 ______ TRANS 1 ______ TRANS 2 ______
* * * This completes the programming for Relay 1 when
it is programmed for rate. Go back to choice A at the
beginning of this step and repeat the process for each remaining output needed.
Choices:
D
INPUT 1 DISABLED
INPUT 1 BYP P 1
INPUT 1 OUT CTL 1
INPUT 1 OUT CTL 2
INPUT 1 RS C EDG
INPUT 1 RS C LVL
INPUT 1 RS B EDG
INPUT 1 RS T EDG
INPUT 1 RS A EDG
INPUT 1 STOP CNT
INPUT 1 PRINT
INPUT 1 LOCK PGM
INPUT 1 LOCK ALL
INPUT 1 UNL ALMS
INPUT 2 ______ INPUT 3 ______ INPUT 4 ______
Label the assignment of control inputs 1, 2, 3, and 4 (terminals 15, 16, 17 and 18) on the diagram on page 10.
2. Allow the operator to view what's important in:
PROGRAM DISPLAY
A. Count with text
Program Item 40 Selection __________ Consider: If all items are set to hide, CNT and TXT
will show. Choices:
Record the assignments of the outputs (terminals 5, 6, 7, 8, 9, 10, 13, 14) on the diagram on page 10.
* * *This completes the wiring and programming selec-
tions for a "bare bones" application. If you check the
block diagram, you can see that count inputs are getting converted to relay and transistor outputs at this point. Most applications will need further dressing up before the control is ready for use by the operator. This is done in Phase 2.
Phase 2 - Finishing Touches
1. Assigning the control inputs in:
PROGRAM INPUTS
Input 1 Function Program Item 20 Selection __________
Consider: Use control inputs wisely and save one for one of the lock functions.
D
CNT + TXT HIDE
CNT + TXT SHOW
B. Rate with text
Program Item 41 Selection __________ Choices:
D
RATE + TXT HIDE
RATE + TXT SHOW
C. Batch count with text
Program Item 42 Selection __________ Choices:
D
BCH + TXT HIDE
BCH + TXT SHOW
D. Totalizer count with text
Program Item 43 Selection __________ Choices:
D
TOT+ TXT HIDE
TOT+ TXT SHOW
6
INSTALLATION WIRING AND PROGRAMMING - QUICK START
D
D
E. Count and current preset
Program Item 44 Selection __________ Choices:
CNT+ Pc
D
HIDE
CNT + Pc SHOW
F. Count and preset 1
Program Item 45 Selection __________ Choices:
CNT+ P1
D
HIDE
CNT + P1 SHOW
G. Count and preset 2
Program Item 46 Selection __________ Choices:
CNT+ P2
D
HIDE
CNT + P2 SHOW
H. Count and preset 3
Program Item 47 Selection __________
L. Rate and alarm setpoint A1
Program Item 4B Selection __________ Choices:
RATE + A1 HIDE
RATE + A1 SHOW
M. Rate and alarm setpoint A2
Program Item 4C Selection __________ Choices:
D
RATE + A2 HIDE
RATE + A2 SHOW
N. Count scaler
Program Item 4D Selection __________ Choices:
D
C SCALER HIDE
C SCALER SHOW
O. Count decimal point position select
Program Item 4E Selection __________
Choices:
CNT+ P3
D
HIDE
CNT + P3 SHOW
I. Count and preset 4
Program Item 48 Selection __________ Choices:
CNT+ P4
D
HIDE
CNT + P4 SHOW
J. Batch and batch preset
Program Item 49 Selection __________ Choices:
BCH + Pb
D
HIDE
BCH + Pb SHOW
K. Count and rate
Program Item 4A Selection __________ Choices:
D
CNT + RATE HIDE
CNT + RATE SHOW
Choices:
D
C DEC PT HIDE
C DEC PT SHOW
3. If you intend to use the front panel reset and/or print keys, enable them in:
PROGRAM OPTIONS
A. Reset key function
Program Item 80 Selection __________ Choices:
D
RST KEY DISABLED
RST KEY RS C EDG
RST KEY RS C LVL
RST KEY RS B EDG
RST KEY RS T EDG
RST KEY RS D EDG
RST KEY RS A EDG
B. Print key enable
Program item 81 Selection __________ Consider: If you enable the print key, be sure to
program the item(s) to be printed in PROGRAM SER OUT.
Choices:
PRNT KEY DISABLED
PRNT KEY ENABLED
7
INSTALLATION WIRING AND PROGRAMMING - QUICK START
4. Identify what you're counting in:
PROGRAM TEXT
You have up to eight characters; select each to be alpha A Z, numeric 0 9, or space, comma, dash, decimal point, or slash.
A. Main counter text
Program Item 50 Selection __________
CNT TXT
D
COUNT
B. Ratemeter text
Program Item 51 Selection __________
RATE TXT
D
RATE
C. Batch counter text
Program Item 52 Selection __________
BCH TXT
D
BATCH
D. Totalizer text
Program Item 53 Selection __________
TOT TXT
D
TOTAL
5. Set up your print list in:
Cont. PROGRAM
ITEM
76
77
78
79
7A
7B
7C
DEFAULT CHOICE
P3 SKIP
P4 SKIP
PB SKIP
A1 SKIP
A2 SKIP
C SCALER SKIP
C DEC PT SKIP
P3 SEND
P4 SEND
PB SEND
A1 SEND
A2 SEND
C SCALER SEND
C DEC PT SEND
SELECTION
6. Configure the serial communications for use with a host computer or a dumb printer in:
PROGRAM SER PORT
A. Counter ID number
Program Item 60 Selection __________ Consider: When more than one counter is used in
a system, assign a unique number from the range of 0 99 to each counter.
PROGRAM SER OUT
Remember to set the baud rate and parity and set the port to PRINTER in PROGRAM SER PORT if you are going to initiate a transmission from the counter.
PROGRAM
ITEM
70
71
72
73
74
75
DEFAULT CHOICE
COUNT SKIP
BATCH SKIP
TOTAL SKIP
RATE SKIP
P1 SKIP
P2 SKIP
COUNT SEND
BATCH SEND
TOTAL SEND
RATE SEND
P1 SEND
P2 SEND
SELECTION
SER PORT
D
ID 0
B. Baud rate
Program Item 61 Selection __________ Consider: Choices are 19200, 9600, 4800, 2400,
1200 and 300.
BAUD
D
19200
C. Parity
Program Item 62 Selection __________ Choices:
PARITY
D
NONE
PARITY ODD
PARITY EVEN
8
INSTALLATION WIRING AND PROGRAMMING - QUICK START
D. Transmission delay time
Program Item 63 Selection __________
D
Tx DELAY
0.002
Tx DELAY
0.100
E. Host or printer port
Program Item 64 Selection __________ Consider: Should the counter initiate the transmis-
sion (printer), or should the counter respond to a serial command (host)?
Choices:
HOST
D
PORT
PRINTER PORT
Label the serial port (terminals 21 and 22) on the diagram on page 10.
***This completes Phase 2 wiring and programming selections. All the necessary selections have been made.
Record the selections you have made that are not the default value in the program menu chart on pages 14 to 21. After you wire the counter up according to the diagram on page 10, go into the program mode and give your counter the personality to do your application.
Phase III - Above and Beyond
A phase 3 installation uses the serial communications port in the host mode. This capability allows a host computer to read all programming and run mode information and to write all programming selections. Furthermore, all of the control input functions are available through the serial port.
A separate manual describing the serial communications is available. If you would like a copy, call 1-800-540-9242.
9
REAR TERMINAL DESCRIPTION
Assignment Assignment
+12 Volt DC DC Common DC Common DC Common Relay 2 N.C.
Relay 2 Com. Relay 2 N.O. Relay 1 N.C. Relay 1 Com. Relay 1 N.O. AC Power Neut AC Power Hot
TERMINAL DESCRIPTIONS 1 - On models 57601 and 57602 this terminal is the +12 VDC
power output. It is used to supply 12 VDC (+/- 25% 100 mA max) for accessories. DC Common is the negative side of this supply.
On the model 57600 this terminal is used for the 10-15 VDC power input. Connect the positive lead of the power supply to terminal 1 and the negative lead to DC Common.
The DC POWER OUTPUT contains a series Positive Tem­perature Coefficient (PTC) resistor that undergoes a large and abrupt increase in resistance when an over-current condition occurs. This resistance change limits the fault current to several milliamps. The PTC device will reset when the unit power has been removed for a time sufficient to cool the device. The overload condition should be removed be­fore unit power is reapplied.
2, 3, and 4 - DC Common: These terminals are connected to the negative side of the counter’s internal DC power supply. Count inputs must be referenced to DC Common. Control inputs are on when connected to DC Common. Transistor outputs conduct to DC Common when picked up.
5, 6 and 7 - Relay 2 contacts 8, 9 and 10 - Relay 1 contacts
Each relay output consists of one electrically isolated form C set of contacts. The user must supply power through a contact to the external load. The contacts remain in the
1 2
3 4 5 6 7 8 9
10 11 12
13 14
15 16 17 18 19 20 21 22
normal state until a pickup signal occurs. The relay remains picked up (on) until a dropout signal occurs (see output programming diagram page 16 and block diagram page 2).
11 and 12 - AC Power Inputs:
Model 57601-405 115VAC Model 57602-405 230VAC Model 57600-405 Not used
13, 14 - Transistor Outputs 2 and 1: These terminals are separate open collector NPN transistor outputs. Each output conducts to DC Common when picked up (see output pro­gramming diagram page 16 and block diagram page 2).
15, 16, 17, and 18 - Inputs 1, 2, 3, and 4: Programmable inputs. The user can assign one of 14 functions to each individual input. The inputs require a current sinking signal (contact or solid state) to DC Common (see input program­ming diagram page 15 and block diagram page 2).
19, 20 - Count Inputs B and A: Connect the count input signal(s) to these terminals. The count input can operate with either a current sinking signal (contact or solid state) to DC Common or a current sourcing signal. (See specifications, programming diagram page 14, and block diagram page 2.) Rate calculations are made from count pulses into Input A only.
21, 22 - RS-485 serial I/O port: Connect terminal 21 to the positive lead of the communications bus. Connect terminal 22 to the negative lead of the communications bus.
Transistor 2 Output Transistor 1 Output Input 1 Input 2 Input 3
Input 4 Count Input B Count Input A Communication + Communication -
RS-485 communication con­nector, RJ-11 modular tele­phone style.
10
REAR TERMINAL DESCRIPTION continued
MODULAR COMMUNICATION JACK
The modular phone jack is an alternate connection to the RS­485 communications port. Pin 3 is positive and is the same as terminal 21. Pin 2 is negative and is the same as terminal
22. Pins 1 and 4 are connected to DC Common and should be used for any shield connections.
Note: This jack is intended only for connection to Ambassa­dor and other RS-485 communication networks. It should
not be connected to any telephone system - dam­age or hazard may result.
!
TERMINAL BLOCKS
Connections to the Ambassador are made through deplug­able, screw terminal blocks to allow for ease of wiring and removal of the counter. The terminals can accommodate stranded, solid or fused wire (preferred) from 14 to 22 gauge.
To remove the terminal block, remove AC power and pry gently underneath each end of the terminal block with small screwdriver. Press straight on to re-install.
GENERAL WIRING PRACTICES
1. Disconnect all power before wiring terminals. A
safety hazard exists if this precaution is not
observed. Treat all control and count inputs as hazardous since they may carry line voltage.
2. Use shielded cables for count signals, control input and communications signals. Connect shield to common (terminal 2, 3 or 4) of counter to terminate properly.
3. Keep all signal lines as short as possible.
4. Do NOT bundle or route signal lines with power or machine control wiring. Use separate conduit for power and signal wires.
5. Provide "clean" power to the counter. In severe cases, power may have to be filtered or a separate power source used. Do not use the same power source that is supplying the loads.
6. Use 18 ga. minimum (0.97mm maximum (2.1mm2, 600V) wire for AC power wiring.
7. See page 26, top drawing, for the correct fuse to be used in the power input wiring.
DIP SWITCH FUNCTIONS
Switch 1: Input A sink/source
Off: input A requires a current sinking input signal. On: input A requires a current sourcing input signal.
Switch 2: Input B sink/source
Off: input B requires a current sinking input signal. On: input B requires a current sourcing input signal.
2
, 600V) and 14 ga.
Switch 3: Input A threshold level
Off: high threshold level — use with DC sensors. On: low threshold level — use with mag pickups. Turn
switch 1 on.
Switch 4: Input B threshold level
Off: high threshold level — use with dc sensors. On: low threshold level — use with mag pickups. Turn
switch 2 on.
Dip switches may be set through an opening on the bottom of the unit. It is located towards the rear of the control.
PANEL MOUNTING
The panel mounting kit includes: (1) mounting gasket, (2) mounting clips and (4) screws.
Refer to the dimension diagram on page 37 for a drawing of the correct installation of these parts.
The mounting gasket is coated on one side with a contact adhesive and a paper backing. Care should be taken during the gasket installation that the gasket be correctly positioned on the panel at the first attempt. Attempting to re-position the gasket once the adhesive has come in contact with the panel is likely to deform or tear the gasket.This may result in an improper seal. For best results, follow these directions:
1. Stand the Ambassador counter on a desk or table with its display down, screw terminals up.
2. Remove and discard the center square of the gasket at the scribe marks in the gasket and paper backing. Do not remove the backing from the remaining outer rim.
3. Slide the gasket down the unit until it is in position at the rear of the unit's front bezel. The paper backing side should be up.
4. Insert the tip of a knife between the paper and the gasket and, while holding the gasket down to the unit with the knife, peel off the paper backing.
5. Slide the unit through the panel cutout until the gasket firmly adheres to the panel.
6. Install the mounting clips and screws as shown in the diagram on page 37. Do not overtighten the mounting screws. The screws should be tight enough to firmly hold the unit in place, but not so tight as to squeeze the gasket out from behind the front bezel.
7. A switch shall be included in the building installation:
• It shall be in close proximity to the equipment and
within easy reach of the operator.
• It shall be marked as the disconnecting device for the
equipment.
• Switches and circuit breakers in Europe must comply
with IEC 947.
11
Loading...
+ 29 hidden pages