Dunkirk Q95M-200 User Manual

Page 1
Aluminum Series
High Effi ci ency Gas-Fired Boi ler
DIELECTRIC ISOLA TION & ANTI F REEZ E P ROTECTI O N
ADDENDUM
This addendum applies to series:
UB90, UB95, Q90, Q95M, K90, K95M, BW9 & GWB9, FW95M & OL95M
WARNING
You
MUST
damage to boiler’s heat exchanger caused by inadequate dielectric isolation, incorrect water treatment or antifreeze application. Failure to comply could result in possible severe personal injury, death or substantial property damage.
follow these instructions to prevent
Instructions in this addendum replace all related information in Boiler Installation Manual, User’s Manual, or any other supplemental instruction or addendum.
Apply this information in place of any related information in Installation, Operation &
Maintenance Manual Accompanying this boiler.
• DIELECTRIC ISOLATION Two (2) 1-1/4” X 1-1/4” Female to female
dielectric isolation unions are shipped loose in boiler parts bag. Install Dielectric Isolation unions at boiler supply line and return line. Install isolation fi ttings nearest boiler prior to system piping connections.
• WATER TREATMENT and ANTIFREEZE PROTECTION
MUST
high effi ciency gas-fi red boilers using antifreeze protection.
be applied for
ALL
aluminum series
WARNING
Install boiler so gas ignition system components
!
are protected from water (dripping, spraying, rain, etc) during appliance operation and service (circulator replacement, etc).
P/N# 240006888, Rev. E [06/2011]
Page 2
System and Operating Precautions
Applies to ALL Aluminum High Effi ciency Gas-Fired Water Boilers
WARNING
Clean the System First BEFORE
clean and fl ush system thoroughly. Verify system is free of sediment, fl ux and any residual boiler water additives.
Systems having antifreeze not recommended must be completely fl ushed to ensure no old antifreeze remains. In older systems obviously discolored, murky or dirty water; or pH reading outside acceptable range (between
7.0 and 8.0) are indications the system
should be cleaned or treated. Thoroughly ush system with clean water to remove any sediment or contaminants. Sludge and iron oxide deposits can cause rapid breakdown of inhibitors.
Flushing with clean water. If chemical cleaners are used, use only those recommended for use with aluminum boilers. Follow chemical cleaner manufacturer’s instructions completely.
DO NOT
products.
connecting boiler to heating system,
mix different manufacturer’s
WARNING
WARNING
Eliminate System Leaks
Continuous addition of make-up water will constantly add oxygen to system. Eliminate all system leaks. All system leaks must be repaired immediately.
Verify expansion tank is operational and properly sized. Undersized expansion tanks cause relief valve weeping and substantial make-up water addition.
Operation of this boiler in system containing signifi cant amounts of dissolved oxygen
can cause severe heat exchanger corrosion damage.
This boiler is not designed for use in systems containing regular additions of make-up water. Regular additions of make-up water may cause severe heat exchanger damage. System leaks may not always be visible. An unseen system leak will become obvious if boiler pressure decreases when make-up valve is closed.
This boiler is designed for closed loop hydronic heat system for natural gravity type installations, or any other open type system.
ONLY!
This boiler is not suitable
Fill Water and Chemistry
Verify water used to fi ll system meets these requirements:
System fl uid pH maintained between 7.0 and 8.0.
Maintain water hardness below 7 grains
hardness. Filling with chlorinated potable water is
acceptable. containing chlorine in excess of 100 ppm.
DO NOT
are not listed at the end in this addendum. Consult local water treatment specialist
for recommendations if any of above requirements is outside stated ranges.
DO NOT
use inhibitors or other additives that
fi ll boiler with water
2
Page 3
System and Operating Precautions
Applies to ALL Aluminum High Effi ciency Gas-Fired Water Boilers
General Guidelines When Using Antifreeze
Use only antifreeze products recommended for use with aluminum boilers, as listed in this addendum. See Table 1.
Continuous addition of make-up water • will dilute power of antifreeze and change buffers ability to maintain pH.
Flush old antifreeze from system. • Flush boiler and system separately.
Do not use antifreeze unless required.• Antifreeze, if needed, must be of
type listed on next page due to their operational characteristics of : type 356 T6 aluminum at operating
temperatures between 20°F (-6.7°C) and 250°F (121°C). (See Table 1 for allowable products.)
Always clean system prior to • using antifreeze as stated in this supplement.
WARNING
If system has leaked, water and antifreeze • chemistry will need to be adjusted. To avoid damage to boiler, check pH and chemistry
of boiler solution and consult the antifreeze manufacturer for recommendations.
It is recommended that pH reading be • taken annually, and adjusted as necessary. Follow antifreeze/inhibitor manufacturer’s instructions for details on how to adjust pH.
Antifreeze solutions can break down over • time. Failure to check antifreeze chemistry on annual basis may result in accelerated corrosion of boiler and other system components. Consult with antifreeze manufacturer for recommendations.
Use of antifreeze in any boiler will reduce • heating capacity as much as 10-20%. Take into consideration when sizing heating system, pumps and expansion tank. Consult antifreeze manufacturer’s literature for specific information on reduced capacity.
Be sure to follow antifreeze • manufacturer’s instructions for use, safe handling and storage of their products. Refer to MSDS (Material Safety Data Sheets) provided by antifreeze manufacturer for potential hazards and first aid procedures for exposure or ingestion.
Antifreeze will raise pH of hydronic • solution in heating system above recommended level due to corrosion inhibitors. Solution must be treated to maintain a pH within recommended level. Follow antifreeze manufacturer’s instructions to adjust pH.
Using antifreeze manufacturer’s instructions, • determine freezing temperature needed and use correct amount of antifreeze. Never exceed 50% antifreeze by volume.
Boiler operating pressure must remain below • 15 psi for antifreeze solutions that specify a maximum of 250°F (121°C). Otherwise, increase system operating/tank pressure to 20 psig.
manufacturer instructions for adjusting tank pressure.
Note: Refer to expansion tank
3
Page 4
System and Operating Precautions
Applies to ALL Aluminum High Effi ciency Gas-Fired Water Boilers
Table 1
Antifreeze Products
Compatible Aluminum Antifreeze & Inhibitor Suppliers
Noble Company P. O. Box 350
Noburst AL Antifreeze
Rhogard Antifreeze &
Pro-Tek 922 Inhibitor*
* Pro-Tek 922 Inhibitor may be used to adjust the pH level of the hydronic system, but on occasion may
not resolve the pH issue. In these cases, fl ush the system and refi ll with untreated water and antifreeze suitable for aluminum heat exchangers, as listed in this supplement.
Alphi-11
Intercool NFP-30,40,50 AA
Intercool RPH-15*
Grand Haven, MI 49417 www.noblecompany.com Tel: 800-878-5788 Fax: 231-799-8850
Rhomar Water Management, Inc. P. O. Box 229 Springfi eld, MO 65801 www.rhomarwater.com Tel: 800-543-5975 Fax: 417-862-6410
Hydronic Agencies, Ltd. (Fernox North Distributor) 15363 117 Avenue Edmonton, AB T5M 3X4 Canada www.hydronicagencies.com Tel: 780-452-8661 Fax: 780-488-2304 Fernox www.fernox.com
Interstate Chemical 2797 Freedland Road P.O. Box 1600 Hermitage, PA 16148-0600 www.interstatechemical.com Tel: 800-422-2436 Fax: 724-981-8383
Hercules Chemical Company, Inc. 111 South Street
Hercules cryo-tek™-100/Al
Passaic, NJ 07055 www.herchem.com Tel: 800-221-9330 Fax: 800-333-3456
* This product may be used to adjust pH level of hydronic system, but on occasion may not resolve pH
issue. In these cases it is recommended to fl ush system and refi ll with untreated water and new boiler manufacturer approved antifreeze suitable for Aluminum heat exchangers.
4