Dunkirk Q90 150, Q90 175, Q90 125, Q90 200 Installation Manual And Operating Instructions

Q90 125-200 GAS-FIRED DIRECT VENT
CONDENSING HOT
DUNKIRK 85 Middle Rd.
Dunkirk, NY 14048
www. dunkirk, com
P/N# 240004826D, Rev. 1.3 [01/06] Printed in USA Made In USA
I. Introduction ........................................................ 2
II. Safety Symbols ................................................ 2
III. Rules For Safe Installation and Operation ......... 3
IV. Boiler Ratings and Capacities ......................... 4
V. Before Installing The Boiler .............................. 5
VI. Placing The Boiler ........................................... 9
VII. Near Boiler Piping .......................................... 9
VIII. Combustion Air and Vent Pipe .................... 11
IX. Gas Supply Piping ........................................ 13
X. Electrical Wiring ............................................. 15
XI. Controls and Accessories ............................. 17
XII. Startup ......................................................... 19
XIII. Checkout Procedures and Adjustments ........ 23
XIV. Maintenance and Cleaning ......................... 26
XV. Detailed Sequence of Operation .................. 28
XVl. Troubleshooting .......................................... 33
XVlI. Installation and Checkout Certificate ......... 40
forces the resulting flue gases from the boiler unit
and provides a positive removal of the flue gases
from the building through inexpensive and readily
available PVC and CPVC vent pipes.
The following defined symbols are used throughout this manual to notify the reader of potential hazards
of varying risk levels.
KEEP THIS MANUAL NEAR BOILER AND
RETAIN FOR FUTURE REFERENCE.
This appliance is a gas-fired direct vent cast aluminum hot water boiler. A revolutionary cast
aluminum heat exchanger means better heat transfer and thermal storage than similarly sized cast iron boilers, which results in higher efficiency. The heating system water absorbs large amounts of heat from the cast aluminum heat exchanger,
cooling the flue gases and causing condensation. Sealed combustion, premix gas burner, and low flame temperature means drastically reduced CO and NOx emissions, which contribute to a cleaner
and healthier environment.
i:
ndicates a potential hazardous situation I
hich, if not avoided, MAY result in minor or I oderate injury. It may also be used to alert I
gainst unsafe practices. J
MPORTANT: Read the following instructionsj_
OMPLETELY before instatlingH
This appliance, unlike normal residential atmospheric and induced draft units, takes its combustion air directly from the outdoors (sealed combustion) and does not compete with building occupants for fresh
air. Sealed combustion (also known as "direct vent") is the safest and best way to obtain plenty of clean
combustion air. The forced draft fan draws in the outside combustion air to mix with gas, which flows
into the pre-mix burner and combusts. The fan then
c@:s
®@
OPENING FOR AIR VENT
OPENING FOR RELIEF VALVE AND EXPANSION TANK DISCHARGE PIPE CONNECTION
_t _ STANDARD
SUPPLY & RETURN OPENINGS
1 1/4 NPT CONNECTIONS
t ,+,+,,+,o,oo,+,c++.
JUNCTION BOX FOR 120V+ POWER
& 2,€ V. THERktOSTAT LEADS
_ _ TOP
COMBUSTION AIR INTAKE FITTING (2" PVC)
GAS SUPPLY _ X_ _ '/+
OPENING _ \
(1/2" NPT)
r_l
FITTING (1/2" PVC)
LEVELING FEET
IMPORTANT: Failure to follow these instructions
could cause a malfunction of the boiler and result
in death, serious bodily injury, and/or property
damage.
For assistance or additional information, consult
a qualified installer, service agency, or the gas
VENT CONNECTION (2" CPVC)--
may result in too much air for the pre-mix burner causing poor or loss of combustion.
5. Never vent the products of combustion from this boiler to an enclosed space, Always vent to
the outdoors, Never vent to another room or to inside a building,
1. Check all applicable state and local building
codes and utility company requirements before
installation. This installation must conform with
these requirements in their entirety. In the absence of these codes, use NFPA installation codes and
good industry practice.
2. Before servicing the boiler, allow it to cool. Always shut off any electricity and gas supply connected to the boiler prior to servicing.
3. Inspect gas line for leaks.
6. Be sure there is adequate outdoor air supply to boiler for complete combustion.
7. Follow a regular service and maintenance schedule for efficient and safe operation.
8. Keep boiler area clean of debris and free of combustible and flammable materials.
9. Proper through-the-watt or through-the-roof combustion venting shall be in accordance with the
materials and methods described in this manual. Installation must comply with local codes.
4. Be certain gas input rate is correct. Overfiring may result in early failure of the boiter components.
This may cause dangerous operation. Underfiring
10. This boiler and related hot water heating systems are not do-it-yourself items. They must be installed and serviced by qualified professionals.
125 125 112.5 150 150 135 175 175 157.5 200 200 180
(1)1MBH=1,000 Btuh(British ThermalUnits PerHour)
98
117 137 157
284 284 284 284
90 90 90 90
2" CPVC & 3" PVC 2" CPVC & 3" PVC 2" CPVC & 3" PVC 2" CPVC & 3" PVC
(2)AFUE (Annual Fuel Utilization Efficiency) and Heating Capacity is based on Department of Energy test procedure.
Ratings shown are for sea level applications. The boiler automatically derates input as altitude increases. No alterations to boiler are required for altitudes above sea level.
Vent Lengths Vent Lengths Vent Lengths Vent Lengths
Altitude
0 200,000 200,000 175,000 175,000 150,000 150,000 125,000 125,000
1,000 197,000 196,500 172,400 172,200 147,800 147,400 123,500 123,000
2,000 194,000 193,000 169,800 169,400 145,600 144,800 122,000 121,000
3,000 191,000 189,500 167,200 166,600 143,400 142,200 120,500 119,000
4,000 188,000 186,000 164,600 163,800 141,200 139,600 119,000 117,000
5,000 185,000 182,500 162,000 161,000 139,000 137,000 117,500 115,000
6,000 182,000 179,000 159,400 158,200 136,800 134,400 116,000 113,000
7,000 179,000 175,500 156,800 155,400 134,600 131,800 114,500 111,000 8,000 176,000 172,000 154,200 152,600 132,400 129,200 113,000 109,000
9,000 173,000 168,500 151,600 149,800 130,200 126,600 111,500 107,000
10,000 170,000 165,000 149,000 147,000 128,000 124,000 110,000 105,000
Vent Lengths VentLengths Vent Lengths VentLengths
Altitude
0 200,000 200,000 175,000 175,000 150,000 150,000 125,000 125,000
1,000 195,900 195,750 171,900 171,200 146,900 146,700 123,050 122,250
2,000 191,800 191,500 168,800 167,400 143,800 143,400 121,100 119,500
3,000 187,700 187,250 165,700 163,600 140,700 140,100 119,150 116,750
4,000 183,600 183,000 162,600 159,800 137,600 136,800 117,200 114,000
5,000 179,500 178,750 159,500 156,000 134,500 133,500 115,250 111,250
6,000 175,400 174,500 156,400 152,200 131,400 130,200 113,300 108,500
7,000 171,300 170,250 153,300 148,400 128,300 126,900 111,350 105,750 8,000 167,200 166,000 150,200 144,600 125,200 123,600 109,400 103,000
9,000 163,100 161,750 147,100 140,800 122,100 120,300 107,450 100,250
10,000 159,000 157,500 144,000 137,000 119,000 117,000 105,500 97,500
These low pressure gas-fired hot water boilers are design certified by CSA International, for use with natural and propane gases. The boilers are constructed and hydrostatically tested for a maximum work- ing pressure of 50 psig (pounds per square inch gauge) in accordance with A.S.M.E. (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code, Section IV Standards for heating boilers.
The Boilers are certified in accordance with ANSI (American National Standards Institute) Z21.13 standards as gas-fired, direct vent, condensing, hot water boilers.
The Heating Capacity indicates the amount of heat available after subtracting the losses up the stack. Most of this heat is available to heat water. A small portion is heat loss from the jacket and surfaces of the boiler, and it is assumed that this heat stays in the structure. The Net I=B=R Rating represents the
portion of the remaining heat that can be applied to heat the radiation or terminal units (i.e. finned tube baseboard, cast iron radiators, radiant floor, etc.). The difference between the Heating Capacity and the Net I=B=R Rating, called the piping and pickup allowance, establishes a reserve for heating the volume of water in the system and offsetting heat losses from the piping. The Net I=B=R Ratings shown are based on a piping and pickup factor of 1.15 in accordance with the I=B=R Standard as published by the
Hydronics Institute. The Net I=B=R Rating of the boiler selected should be greater than or equal to the calculated peak heating load (heat loss) for the building or area(s) served by the boiler and associated hot water heating systems. The manufacturer should be consulted before selecting a boiler for installations having unusual piping and pickup requirements.
Complete all of the following prior to installing the boiler.
Oil
This boiler product is a gas-fired, direct vent, con- densing boiler and must be installed in accordance
with all applicable federal, state and local building
codes including, but not limited to the following:
United States - Installation shall conform
with National Fuel Gas Code (NFPA-54/ANSI
Z223.1 - latest revision)
Canada - Installation shall be in accordance
with CSA-B149.1 and .2 installation codes.
Check to be sure you have selected the boiler
with the proper capacity before continuing the in-
stallation. The I=B=R Rating of the boiler selected
should be greater than or equal to the calculated
peak heating load (heat loss) for the building or area(s) served by the boiler and associated hot
water heating systems. See Section IV, "Boiler
Ratings and Capacities, " for more information.
Heat loss calculations should be based on approved industry methods.
Where required by the authority having jurisdiction, the installation must conform to the American Soci-
ety of Mechanical Engineers Safety Code for Con- trols and Safety Devices for Automatically Fired
Boilers, No.CSD-1.
The installation must conform to the requirements of the authority having jurisdiction or, in the ab-
sence of such requirements, to the National Fuel Gas Code, ANSI Z223.1 -latest revision.
Before selecting a location for the boiler, the follow- ing should be considered. Each boiler considered
for installation must be:
Supplied with the correct type of gas (natural
gas or propane).
Connected to asuitable combustion air intake pip- ing system to supply the correct amounts of fresh
(outdoor) air for combustion (max. length 60').
Installers - Follow local regulations with re- Connected to a suitable venting system to re-
spect to installation of CO (Carbon Monox- move the hazardous products of gas combus-
ide) Detectors, Follow maintenance recom- tion (max, length 60'), mendations in this manual,
Connectedto a suitablehot water heating system.
Supplied with a suitable electrical supply for all boiler motors and controls.
Connected to a properly located thermostat or operating control. (not included with boiler)
Placed on level surface (must NOT be in- stalled on carpeting)
Condensate drain line must be pitched down to floor drain or external condensate pump with
reservoir at ¼"per foot (wood frame or blocks may be used to raise boiler).
1. Select a location which is level, central to the
piping systems served and as close to the vent and air intake terminals as possible.
2. Accessibility clearances, if more stringent (i.e. larger clearances) than required fire protection
clearances, must be used for the boiler installa- tion. Accessibility clearances may be achieved
with the use of removable walls or partitions.
3. The boiler is approved for installation in clos-
ets and on combustible floors. This boiler shall
NOT be installed on carpeting.
the front where passage is required for cleaning or servicing, inspection or replacement d any parts
that normally may require such attention. Allow at least 24" at the front and left side and 8" at the top
for servicing. No combustible clearances are re-
quired to venting or combustion air intake piping.
5. Equipment shall be installed in a location
which facilitates the operation of venting and
combustion air intake piping systems as de- scribed in this manual.
6. Advise owner of boiler to keep venting and combustion air intake passages free of obstruc-
tions, Both the venting and combustion air intake piping systems connected to the outdoors must
permit flow through the piping systems without restrictions for the boiler to operate,
7. The boiler shall be installed such that the automatic gas ignition system components are protected from water (dripping, spraying, rain,
etc.) during operation and service (circulator re- placement, control replacement, etc.).
8. The boiler must be located where ambient temperatures (minimum possible room temper- atures where boiler is installed assuming boiler
is not in operation and therefore contributes no heat to the space) are always at or above 32°F
to prevent freezing of liquid condensate.
Top 1" 8"
Left Side 8" 24"
Right Side 1"
Base 1" Front 0" 24" Back 1"
Intake/Vent
0"
Piping
Near Boiler Hot
1"
Water Piping
Aft distances measured from the cabinet of the boiler.
4. The clearances shown in Table 4 indicate re-
quired clearances per CSA listing. A min. 1" clear- ance must be maintained between combustible
construction and each of the right, top and back surfaces of the boiler. A min. 8" clearance is re-
quired on the left side, to allow room for the inlet air pipe. An 18" clearance must be maintained at
This boiler requires a dedicated direct vent system.
In a direct vent system, all air for combustion is
taken directly from outside atmosphere, and all flue
)roducts are discharged to outside atmosphere.
ROOF VENTIINTAKE TERMINATIONS
I Figure 1]
Combustion air and vent pipe connections must
terminate together in the same atmospheric pres-
sure zone, either through the roof or sidewall (roof
termination preferred). See Figures 1 and 2 for re- quired clearances.
SIDEWALL VENTIINTAKE TERMINATIONS
I LESS THAN 12 CLE;,R;,riCE J
12" OR MORE CLEARANCE
If the concentnc vent termination is being used, re-
fer to Figure 3 for proper setup
CONCENTRIC VENT TERMINATIONS
12_ P IlNll 1UP 1
I
COt 1EUSTIOH AIR
_1 PCOF
3 E_=H-IIG
t
12 I11PJRIIJ[ _
J
ENT
r1-ff4T_in IC irl CLE-_-NCE
:BC E H;GHEST .NTIC_P-TED SI_ ' LE ELOF = SP-DE
eep boiler area clean of debris and free of I
ammable and combustible materials, vapors, I nd liquids, i,)
FAILURE TO FOLLOW THESE WARNINGS COULD RESULT IN FIRE, PROPERTY
DAMAGE, PERSONAL INJURY, OR DEATH.
When vent pipe is exposed to temperatures below freezing, such as when it passes through
an unheated space or when a chimney is used as a chaseway, vent pipe must be insulated
with l/2"Armaflex or equivalent. In extremely
cold climate areas, use 3/4"Armaflex or equivalent.
Combustion air must be clean outdoor air. Combustion air must not be taken from inside
the structure because that air is frequently contaminated by halogens, which include
fluorides, chlorides, phosphates, bromides and iodides. These elements are found in
aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, paints,
adhesives, and other household products.
Locate combustion air inlet as far away as possible from swimming pool and swimming
pool pump house. All combustion air and vent pipes must be airtight and watertight.
Combustion air and vent piping must also terminate exactly as shown in Figures 1-2. If
a concentric vent termination is being used, refer to Figures 3-5 for proper setup.
Vent connections serving appliances vented by natural draft shall not be connected into any
portion of mechanical draft systems operating under positive pressure.
Solvent cements are combustible. Keep away from heat, sparks, or open flame. Use only in
well ventilated areas. Avoid breathing in vapor
k.or allowing contact with skin or eyes. J
CONCENTRIC VENT
CONCENTRICVENTROOFINSTALLATION
VENT
I MAINTAIN 12 IN
(i8 IN FD_ CANADA>
MINI_UN CLEARANCE
SNO_
MAXINUM OF
IN A_DVE NOOF
NOTE, SbPPORT WUST BE FIELD INSTALLED
TO SECC_RE TERMINAT[0N K!I /O STR/JCTURE
3" Diameter PVC Vent/Exhaust
1W' "_1d1_'
46% _
3" Diameter PVC Intake/Combustion Air
[ Figure 5 I
Boiler must be placed on level surface. Boiler is NOT to be installed on carpeting.
NOTES
1. If boiler is not level condensate drain lines will not function
properly. Adjustable feet are located on the boiler to make up for minor surface irregularities or tilt.
2. Wood frame or blocks may be used to raise boiler to maintain
Wa!np!!chor!obeabovee erna!condensa!epump
When an existing boiler is removed from a common venting system, the common venting system is likely
to be too large for proper venting of the appliances
remaining connected to it. At the time of removal of an existing boiler, the following steps shall be fol- lowed with each appliance remaining connected to
the common venting system placed in operation, while the other appliances remaining connected to
the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or
other deficiencies which could cause an unsafe condition.
3. When it is practical, close all building doors and windows and all doors between the space
in which the appliances remaining connected to the common venting system are located and oth- er spaces of the building. Turn on clothes dryer
and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhaust, so they
will operate at maximum speed. Do not operate
a summer exhaust fan. Close fire dampers.
4. Place in operation the appliance being in- spected. Follow the lighting instructions. Adjust
thermostat so appliances will operate continu- ously.
5. Test for spillage at the draft hood relief open- ing after 5 minutes of main burner operation. Use
the flame of a match or candle, or the smoke
from a cigarette, cigar or pipe.
6. After it has been determined that each ap- pliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust
fans and any other gas-burning appliance to their
previous condition of use.
7. Any improper operation of the common vent- ing system should be corrected so the installation
conforms with the National Fuel Code, NFPA- 54/ANSI -Z223.1-1atest revision, or section 5 of
CSA-B149 for Canadian standards. When resiz- ing any portion of the common venting system,
the common venting system should be resized to approach the minimum size as determined using
the appropriate tables in part 11 in the National Fuel Gas Code, NFPA-54/ANSI- Z223.1-tatest
revision, or section 5 of CSA-B149 for Canadian standards.
The boiler should be placed to provide the most direct connections to the combustion air, vent and
system piping as possible.
Place crated boiler as close to selected location as possible and uncrate boiler. The uncrated boiler
may be moved into position with an appliance dol-
ly or 2-wheel hand truck. The dolly or hand truck should be inserted under the right hand side of
the boiler. It is possible to slide the boiler for a short distance on a smooth floor or surface.
NqNOTE: Refer to "Locating The Boiler" in Section V for re-_
uired clearances for servicing and maintenance.
J
r c.o,,o, .,
Copper supply and return piping must NOT be in- stalled directly into aluminum boiler section castings due to galvanic corrosion between dissimilar met- als. Iron or steel bushings or pipe nipples should be used between copper system piping and boiler
to make final connection to boiler. Also, the use d dielectric unions is acceptable. The packaged boiler
is furnished with iron piping in the front boiler sec-
k_ion for the supply and return connections.
J
When the installation of the boiler is for a new heat- ing system, first install all of the radiation units (pan-
els, radiators, baseboard, or tubing) and the supply and return mains. After all heating system piping and components have been installed, make final con- nection of the system piping to the boiler.
Determine required system fill pressure, system de- sign temperature, and system water content. Boiler
contains 2.6 gallons (U.S.). Size expansion tank ac- cordingly. Consult expansion tank manufacturer for
proper sizing information. Connect properly sized
expansion tank (not furnished) as shown in Figure 6 for diaphragm type expansion tank. For diaphragm
type expansion tanks, adjust the tank air pressure to match the system fill pressure. Install air vent
(furnished) as shown for diaphragm type expansion
tank system only. Install make-up water connec- tions as shown and per local codes. If a pressure
reducing valve is used, adjust to match the system
fill pressure. In connecting the cold make-up water
supply to the boiler, make sure that clean water sup- ply is available. When the water supply is from a well
or pump, a sand strainer should be installed at the
pump.
A hot water boiler installed above radiation level must be equipped with a low water cut off device (included
with boiler). A periodic inspection is necessary, as is flushing of float type devices, per low water cut off manufacturers specific instructions.
DIAPHRAGM TYPE EXPANSION TANK PIPING
E)G_ANSION TANK SER_ICE VALVE {OA_ VALVE Of_ FULL PORT BALL VAL'_)
AUTOMATIC AIR
VENT*
.............\
REDUCING VALVE *- FURNISHED IN
pARTS BAG.
REDUCINGVALVE
I _/ .... 1ST Op_cN FOR FEED WA3ER
WA_R 2ND Opllo_ FOR FEED WAER
DIAPHRAGM TfPE- EXPANSION TANK
RELIEF VALVE DISCHARGE PiPiNG
PRESSURERELIEFDEVICE
Figure 7 ]
The boiler is furnished with a relief valve and tem-
perature pressure gauge in the boiler parts bag. In-
stall vent relief valve as shown in Figure 7. Provide ¾" piping from the relief valve to a local floor drain,
but leave an air gap betweenpiping and drain. No shutoff of any descriptionshall be placedbe-
tweensafetyreliefvalveandthe boiler,or on the dischargepipesbetweensuchsafetyvalveandthe atmosphere.Installationof the safety reliefvalve
shallconformto ANSI/ASMEBoilerand Pressure VesselCode,SectionIV.The manufactureris not
responsibleforanywaterdamage.
SINGLEZONEBOILERPiPiNG
SERVI E S[ PPLY [3 VALVE
SE \/Z(?E
'ALVE
MULTIZONE BOILER PiPiNG
WiTH CIRCULATORS
_-ZONE SERVICE
j" VALVE
FLOW CHECK TO
VALVE ZONES
CIRCULATORS
PRESSURE
REDUClNO VALVE_
VALVE
VAL_
NOTE: When zoning with circulators, the furnished circulator pump should be used as one of the zone pumps. Each stripped end of
the electrical wires for the circulator pump inside the junction box should be taped or wire nutted to prevent short circuits. Unplug the
circulator pump wiring at the integrated boiler control.
MULTIZONE BOILER PIPING
WiTH ZONE VALVES
ZONE SER_CE
ZONE F VALVE
VALVE-
ZONES
PRESSURE
REDUCING VALVE_ VALVE
CAN VENT /
AIR
WATER
ZONES
PRESSURE
BACKFLOW PREVEN_R
VALVE
_ZONE SERVICE
VALVE
IFlguregb]
The packaged boiler unit is set up to receive 1¼"
NPT supply and return piping from top access.
COTE: The circulator and isolation valves fur- _
pump
are
ished within a carton inside the boiler cabinet and can be]
_installed at the installer preferred location, j'
CONDENSATE DRAIN PIPING
Condensate drain line to be pitched down to floor drain at a minimum of ¼" per foot. An external con- densate pump (not furnished) may be used if floor drain is not available. The condensate pump must
be designed for flue gas condensate application.
NOTES
1. Condensate trap is to be built in the field per Figure 10
2. Wood frame or blocks may be used to raise the boiler to maintain drain pitch or to be above external condensate pump reservoir.
3. There is a 115 volt AC receptacle provided on the service
switch junction box which is located at the boiler right side, to
provide power for an external condensate pump (if needed).
\ J
The condensate trap is to be field installed as previ- ously shown in Figure 10. Provided are ½" PVC fit-
tings for the condensate drain trap (assembled in the field). The condensate drain is to be pitched down to the floor drain at a minimum of ¼" per foot.
The ½" diameter schedule 40 PVC condensate drain piping and pipe fittings must conform to ANSI
standards and ASTM D1785 or D2846. Schedule 40 PVC cement and primer must conform to ASTM
D2564 or F493. In Canada, use CSA or ULC certi- fied schedule 40 PVC drain pipe and cement.
A condensate pump with a reservoir (not furnished) may be used to remove condensate to a drain line
(sanitary line) above boiler if a floor drain is not available or is inaccessible.
ON INITIAL START UP THE CONDENSATE TRAP
MUST BE MANUALLY FILLED WITH WATER.
The following are the steps required to initially fill the condensate trap for start up, these steps are only required at the initial start up or if maintenance
requires draining of the condensate trap:
1. Pour about 1 cup of cold tap water into the condensate trap vent.
2. Excess water should go through the conden- sate drain line. Verify proper operation of the drain line (and external condensate pump if used).
The boiler, when used in connection with a refrig- eration system, must be installed so the chiller me-
dium is piped in parallel with the boiler with appro-
priate valves to prevent the chilled medium from entering the boiler.
The boiler piping system of a hot water boiler con-
nected to heating coils located in air handling units where they may be exposed to refrigerated air cir-
culation must be equipped with flow control valves or other automatic means to prevent gravity circu-
lation of the boiler water during the cooling cycle.
I_IPORTANT: To prevent damage to the gas"_
urner and ensure proper operation of the unit, I
stalter must clean and remove all shavings from I
e interior of all PVC pipe used on the air intake.>]
For boilers connected to gas vents or chimneys, vent installations shall be in accordance with part 7, Venting
of Equipment, d the National Fuel Gas Code, ANSI Z223.1-1atest revision, CSA-B149.1 and B149.2, and
applicable provisions d the local building codes.
Provisions for combustion and ventilation air must be in accordance with section 5.3, Air For Com-
bustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1-1atest revision, CSA-B149.1
and B149.2, or applicable provisions of the local building code.
outdoors through the combustion air intake pipe. All flue products are discharged to the outdoors
through the vent pipe.
1. See Figures 1-2 in Section V, "Combustion Air
and Vent Pipe Requirements," for standard two- pipe roof and sidewall terminations and Figures 3-5 (same section) for concentric vent termina-
tions (roof termination is preferred). Combus- tion air and vent pipes must terminate together in same atmospheric pressure zone as shown.
Construction through which vent and air intake pipes may be installed is a minimum ¼" and max-
imum 24" thickness.
2. Combustion air and vent pipe fittings must con- form to one of the following American National Standards Institute (ANSI) and American Society
for Testing and Materials (ASTM) standards:
D1784 (schedule-40 CPVC)
These boilers require a dedicated direct vent sys- tem. All air for combustion is taken directly from
D1785 (schedule-40 PVC)
D2665 (PVC-DWV) Reduce the maximum vent length 5 feet per each additional elbow.
D2241 (SDR-21 and SDR-26 PVC)
D2661 (ABS-DWV)
F628 (schedule-40 ABS).
Pipe cement and primer must conform to ASTM standards D2564 (PVC) or D2235 (ABS).
In Canada construct all combustion air and vent
pipes for this unit of CSA or U LC certified sched- ule-40 CPVC, schedule-40 PVC, PVC-DWV or
ABS-DWV pipe and pipe cement. SDR pipe is
NOT approved in Canada.
3. Combustion air and vent piping connections on boiler are 2", but must increase to 3". Due to
potential for flue gas temperatures over 155°F, the first 5 feet of vent pipe must be CPVC (fur-
nished), the remaining vent pipe can be PVC.
If any elbows are employed within the first 2 ½'
feet of vent, they must be CPVC. Two 30" pieces of 2" CPVC pipe and one 2" CPVC coupling are
furnished with the boiler. (Figure 11)
COMBUSTION AIR AND VENT PIPING
2 (508MM) CPVC COUPLING
(FURNISHED)
2 (508MM) CPVC VENT PIPING
(FURNISHED & REQUIRED)
2 (50 8MM) COMBUSTION AIR
INTAKE PIPING
(FURNISHED)
NOT IN
HORIZONAL
SECTION
4. Combustion air and vent piping to be pitched back to boiler at minimum ¼" per foot from intake
and vent terminals so that all moisture in com- bustion air and vent piping drains to boiler. Pipes
must be pitched continuously with no sags or low spots where moisture can accumulate and block
the flow of air or flue gas. Combustion air and vent pipes must be airtight and watertight.
5. Consideration for the following should be used when determining an appropriate location for ter-
mination of combustion air and vent piping:
Comply with all clearances required as stated in paragraph 6 (below)
Termination should be positioned where vent vapors wilt not damage plants/shrubs,
air conditioning equipment, or siding on the house.
Termination should be positioned so that it will not be effected by wind eddy, air born leaves, snow, or recircutated flue gases.
Termination should be positioned where it will not be subjected to potential damage by foreign objects, such as stones, balls, etc.
Termination should be positioned where vent vapors are not objectionable.
Put vent on a wall away from the prevailing winter wind. Locate or guard the vent to pre-
vent accidental contact with people or pets.
Terminate the vent above normal snow- line. Avoid locations where snow may drift and block the vent. Ice or snow may cause
the boiler to shut down if the vent becomes obstructed.
NOTE: The exhaust transition from 2" pipe to 3" pipe must_
e made in a vertical run. (Transition pieces not included.)_
6 ft. in length plus 60 ft. in length and up
four (4) 90° elbows to four (4) 90° elbows
The length of pipe is counted from the boiler jack- et (air intake pipe) or from vent tee (vent pipe). The first five feet of "Total Equivalent Length" of
vent pipe must be CPVC.
Under certain conditions, flue gas will con- dense, forming moisture, and may be corro- sive. In such cases, steps should be taken to prevent building materials at the vent from
being damaged by exhaust of flue gas.
6. The venting system shall terminate at least 3 feet above any forced air inlet (except the boiler's
combustion air inlet) within 10 feet. The venting system shall terminate at least 12 inches from any air opening into any building. The bottom
of the vent shall be located at least 12 inches
Loading...
+ 28 hidden pages