Dunkirk PWXL Installation, Operation & Maintenance Manual

Page 1
R
PWXL
Cast Iron Gas Fired
Hot Water Boilers
INSTALLATION, OPERATION &
An ISO 9001-2000 Certified Company
DUNKIRK BOILERS
85 Middle Rd. Dunkirk, NY 14048
www.dunkirk.com
P/N 240007958 REV A [09/09]
Page 2
H
TABLE OF CONTENTS
Safety Symbols........................................................................................................................................................4
Boiler Ratings and Capacities ................................................................................................................................5
Before You Start ......................................................................................................................................................6
Locating the Boiler .................................................................................................................................................7
Combustion And Ventilation Air ............................................................................................................................8
System Piping ...................................................................................................................................................... 11
Chimney and Vent Pipe Operation ..................................................................................................................... 13
Vent Damper Operation ...................................................................................................................................... 14
Gas Supply Piping ................................................................................................................................................ 16
Electrical Wiring ................................................................................................................................................... 17
Equipment and Optional Accessories ................................................................................................................ 21
Starting the Boiler ............................................................................................................................................... 22
Initial Operational Boiler Test Check-Out Procedure ........................................................................................ 24
Initial Operational Boiler Test Check-Out Certicate & Signed Receipt .......................................................... 25
Operating Your Boiler .......................................................................................................................................... 26
Checking and Adjusting ...................................................................................................................................... 27
Maintaining Your Boiler ...................................................................................................................................... 27
Sequence of Operation ........................................................................................................................................ 28
Troubleshooting .................................................................................................................................................. 29
Hydrolevel Hydrostat Model 3100 ..................................................................................................................... 29
Service Hints......................................................................................................................................................... 30
C.S.A. Certied for
Natural gas or Propane
Tested for 50 LB. ASME
Working Pressure
2
Page 3
SAFETY SYMBOLS
The following dened symbols are used throughout this manual to notify the reader of potential hazards of varying risk
levels.
DANGER
Indicates an imminently hazardous situation which, if not
!
avoided, WILL result in death, serious injury or substantial property damage.
WARNING
Indicates an imminently hazardous situation which, if not
!
avoided, may result in death, serious injury or substantial property damage.
IMPORTANT: Read the following instructions COMPLETELY before installing!
CAUTION
!
Indicates an imminently hazardous situation which, if not avoided, may result in injury or property damage.
NOTICE
Indicates information which should be followed to ensure proper installation and operation.
NOTICE
ese Instruction must be axed on or adjacent to the boiler. Retain for future reference.
WARNING
All installations of boilers and venting should be done only by a qualied expert and in accordance with the appropri­ate manual. Installing or venting a boiler or any other gas
!
appliance with improper methods or materials may result in serious injury or death due to re or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible.
WARNING
Keep boiler area clear and free from combustible materials, gasoline and other ammable vapors and liquids.
DO NOT obstruct air openings to the boiler room.
Modication, substitution or elimination of factory equipped, supplied or specied components may result in property damage, personal injury or the loss of life.
!
TO THE OWNER - Installation and service of this boiler must be performed by a qualied installer.
TO THE INSTALLER - Leave all instructions with the boiler for future reference.
When this product is installed in the Commonwealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
3
Page 4
Table 1- Boiler Ratings and Capacities
Number of Boiler
Sections
AGA Input *MBH
BOILER RATINGS AND CAPACITIES
Natural or Propane Gas Dimensions
Heating Capacity
*MBH+
Net I=B=R
Rating *MBH
Flue Diameter Dim. A
3 70 57 50 5" 11-1/4"
4 105 85 74 6" 14-1/2"
5 140 113 98 6" 17-3/4"
6 175 142 123 7" 21"
7 210 170 148 7" 24-1/4"
8 245 198 172 7" 27-1/2"
9 280 226 197 7" 30-3/4"
* MBH = 1,000 BTUH = British ermal Unit Per Hour. Boilers are equipped for altitudes up to 2,000 feet only. For altitudes above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level.
+ Heating Capacity based on D.O.E. (Department of Energy) test procedure.
New York City MEA Number 484-84 E Vol. IV.
e Ratings marked “Net I=B=R Ratings” indicate the amount of remaining heat input that can be used to heat the radiation units. e net I=B=R Ratings shown are based on an allowance of 1.15 in accordance with the factors shown on the I=B=R Standard as published by the Hydronics Institute. Selection of boiler size should be based upon “Net I=B=R Rating” being equal to or greater than the calculated heat loss of the building. e Manufacturer should be consulted before selecting a boiler for installations having unusual piping and pickup requirements.
Boilers For Use At High Altitude
is boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level. For use at altitudes above sea level, the input ratings are reduced by a change in main orice size.
For altitudes above 2,000 feet above sea level, input ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. Consult the latest edition of the National Fuel Gas Code (NFPA54/ANSI Z223.1) for correct orice sizing information. High altitude orices are available from the boiler manufacturer.
4
Page 5
BEFORE YOU START
Check to be sure you have the right size boiler before starting the installation. See rating and capacity table on previous page. Also be sure the new boiler is for the type of gas you are using. Check the rating plate on the right side of the boiler.
You must see that the boiler is supplied with the correct type of gas, fresh air for combustion, and a suitable electrical supply. e boiler must be connected to a suitable venting system and an adequate pip­ing system. A thermostat, properly located, is needed for control of the heating system. If you have any doubts as to the various require­ments, check with local authorities. Take the time to complete all of the steps for SAFE and PROPER operation of the heating system.
If this boiler is installed in a building under construction, special care must be taken to insure a clean combustion air supply during the construction process. Airborne particulates such as from dry­wall dust and from berglass insulation can clog the burner ports, ueway passages and cause incomplete combustion and sooting.
Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boil­ers, No. CSD-1.
e installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest revision.
Installers - Follow local regulations with respect to installation of CO detectors. Follow maintenance recommendations in this instruction manual.
WARNING
Keep boiler area clean and free from combustible materi-
!
als, gasoline and other ammable vapors and liquids. Fail­ure to keep boiler area clean may result in death, serious injury, or substantial property damage.
5
Page 6
LOCATING THE BOILER
Select level location as centralized with piping system, and as
1.
near chimney as possible.
Place crated boiler at selected location, remove crate by pulling
2.
crate sides from top and bottom boards.
is boiler must be set on non-combustible oor or optional
3.
non-combustible Base Plate placed over the top of a combusti­ble oor. Refer to Repair Parts and Optional Kits for additional detals (3-6 section Boiler Base Plate Part #14614031; or 7-9 Section Boiler base Plate Part #14614032). A combustible oor is dened as materials made of or surfaced with wood, com­pressed paper, plant bers, or other materials that are capable of being ignited and burned. Such material shall be considered combustible even thought ame-proofed, re-retardant treated, or plastered. is boiler must not be installed on carpeting.
Boiler is to be level. Metal shims may be used under base legs
4.
for nal leveling.
Additional clearance for service may exceed clearance for re
5.
protection. Always comply with the minimum re protection clearance shown on the boiler. An 18 inch clearance should be maintained on any side where passage is required to access another side for cleaning, servicing, inspection or replacement of any part that may need attention.
To determine minimum clearances to combustibles refer to Ta-
6.
ble 2b, for rooms with a single boiler only. Rooms that are large in comparison with the size of the boiler are dened as rooms having a volume equal to or greater than 16 times the volume of the boiler. Where the actual ceiling height of a room is greater that 8’ the volume of a room shall be gured on the basis of a ceiling height of 8’. Determination of room size should be based on the total volume of all gas red equipment install in the room. Consult the latest revision of the National Fuel Gas Code for further information.
Equipment shall be installed in a location in which the facilities
7.
for ventilation permit satisfactory combustion of gas, proper venting, and maintenance of ambient temperature at safe limits under normal conditions of use. Equipment shall be located so as not to interfere with proper circulation of air. When normal inltration does not provide the necessary air, outside air shall be introduced.
Advise owner to keep air passages free of obstructions. Ven-
8.
(See “Combustion and Ventilation Air”)
tilating and combustion air must enter boiler room without restrictions.
e boiler shall be installed such that the automatic gas ignition
9.
system components are protected from water (dripping, spray­ing, rain, etc.) during appliance operation and service (conden­sate trap, control replacement, etc.).
Table 2a - Determination of Room Size
If room does not contain mimimum volume shown to be considered a
Large Room, use "Small Room or Alcove" values.
Boiler Size Volume (Ft3)
3 Section 5.4 86.6 4 Section 7.0 111.6 5 Section 8.5 136.6 6 Section 10.1 161.7 7 Section 11.7 186.7 8 Section 13.2 211.7
9 Section 14.8 236.7
Minimum Room Volume To Be
Considered a Large Room (Ft3)
Table 2b - Minimum Clearances
Minimum
Clearances
To p
Rear
Right Side
Le Side
Front
Flue/Vent
Near Boiler Piping
Small Room or Alcove Large Room
3-5 section 6-9 section 3-9 section
6" 6" 6"
6" 6" 6"
8" 24" 6"
6" 24" 6"
18" 18" 18"
6" 6" 6"
1" 1" 1"
6
Page 7
COMBUSTION AND VENTILATION AIR
Provision for combustion and ventilation air must be in accordance with the latest revision of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes. You must provide for enough fresh air to assure proper combustion. e re in the boiler uses oxygen. It must have a continuous supply. Outside air must enter the house to replace that used by the burner.
EXAMPLE 1: Boiler Located In Unconned Space An unconned space is dened as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour of the total input rating of all appliances installed in that space.
If your boiler is in an open area (non-partitioned basement) in a conventional house, the air that leaks through the cracks around doors and windows will usually be adequate to provide air for combustion. e doors should not t tightly. Do not caulk the cracks around the win­dows.
NOTICE
Equipment located in buildings of tight construction shall be provided with air for combustion, ventilation, and dilution of ue gases using the methods described in example 2 (below) or shall be specially engineered. e authority having jurisdiction must approve specially engineered installations. A building of tight construction is dened as: 1) walls exposed to the outdoor atmo­sphere have a continous water vapor retarder with a rating of one perm or less with openings gasketed or sealed; and 2) openable windows and doors which meet the air leakage requirements of the International Energy Conservation Code, Section 502.1.4; and
3) caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, and at other openings.
EXAMPLE 2: Boiler Located in Conned Space
All Air from Inside the Building:1.
an additional room(s) of sucient volume so that the combined volume of all spaces meets the criteria for an unconned space. e total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each open­ing shall have a minimum free area of one square inch per 1,000 Btu per hour of the total input rating of all gas utilization equipment in the conned space, but not less that 100 square inches. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure. e minimum dimension of air openings shall not be less than 3 inches (see
Figure 1 - Boiler Located in Conned Space
e conned space shall be provided with two permanent openings communicating directly with
Figure 1
WARNING
Be sure to provide enough fresh air for combustion. Enough air insures proper combustion and assures that no hazard will develop due to lack of oxygen.
!
If you use a replace or a kitchen or bathroom exhaust fan, you should install an outside air intake. Otherwise exhaust fans will rob the boiler and water heater of com­bustion air.
).
7
Page 8
COMBUSTION AND VENTILATION AIR
All Air from Outdoors:2.
e conned space shall communicate with the outdoors in accordance with methods A or B. e minimum dimension of air openings shall not be less than 3 in. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
Two permanent openings, one commencing within 12 inches of the top, and one commencing within 12 inches of the bottom, of A. the enclosure shall be provided. e openings shall communicate directly, or by the ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Where directly communicating with the outdoorsI. ducts
(see Figure 3)
, each opening shall have a minimum free area of 1 sq. in, per 4000 Btu per hour of total input rating of all
(see Figure 2)
or where communicating to the outdoors through vertical
equipment in the enclosure.
Figure 2 - Directly Communicating to the Outdoors
Figure 3 - Vertical Ducts Communicating to the Outdoors
FRESH AIR DUCT CAPACITIES (1 Square inch per 4,000 Btuh)
Fresh Air Duct Size
3” x 12” 144,000 108,000 36,000
8” x 8” 256,000 192,000 64,000
8” x 12” 384,000 288,000 96,000
8 ½” x 16” 512,000 384,000 128,000
see Figures - 2 and 3
100% Free Area
1/4” Wire Mesh
Table 3
75% Free Area Metal Louvers
8
25% Free Area Wood Louvers
Page 9
COMBUSTION AND VENTILATION AIR
Where communicating with the outdoors through horizontal ducts (see II. of 1 area of sq. in. per 2000 Btu per hour of total rating of all equipment in the enclosure.
Figure 4 - Horizontal Ducts Communicating to the Outdoors
Figure 4
), each opening shall have a minimum free area
Table 4
FRESH AIR DUCT CAPACITIES (1 Square inch per 2,000 Btuh)
see Figure 3D
Fresh Air Duct Size
3” x 12” 72,000 54,000 18,000
8” x 8” 128,000 96,000 32,000
8” x 12” 192,000 144,000 48,000
8 ½” x 16” 256,000 192,000 64,000
100% Free Area
1/4” Wire Mesh
75% Free Area
Metal Louvers
25% Free Area Wood Louvers
One permanent opening commencing within 12 inches of the top of the enclosure shall be permitted where the equipment has B. clearance of at least 1 inch from the sides and back and 6 inches from the front of the appliance. e opening shall directly commu­nicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or to a crawl space or attic that freely communicate with the out doors, and shall have a minimum free area of:
1 sq. inch per 3000 Btu per hour of the total input of all equipment located in the enclosure (see chart below).I.
Not less than the sum of the areas of all vent connectors in the conned space.II.
Table 5
FRESH AIR DUCT CAPACITIES (1 Square inch per 3,000 Btuh)
Fresh Air Duct Size
100% Free Area
1/4” Wire Mesh
75% Free Area Metal Louvers
25% Free Area
Wood Louvers
3” x 12” 108,000 81,000 27,000
8” x 8” 192,000 144,000 48,000
8” x 12” 288,000 216,000 72,000
8 ½” x 16” 384,000 288,000 96,000
9
Page 10
SYSTEM PIPING
Place boiler in the selected location (as near chimney as pos-
1.
sible.) Your boiler is shipped assembled. You need only to install the Relief Valve and a drain line to carry any water or steam to a drain.
Install Relief Valve into the ¾” pipe on the top of the boiler.
2. See Figure 5
the water or steam to a nearby drain. Do not connect directly to a drain but leave an air gap. No shuto of any description shall be placed between the safety relief valve and the boiler, or on discharge pipes between such safety valves and the atmosphere. Installation of the safety relief valve shall conform to the require­ments of the ANSI/ASME Boiler and Pressure Vessel Code, Sec­tion IV. e manufacturer is not responsible for any water dam­age. Install Drain Valve in lower le side of boiler as marked.
Connect Supply and Return Lines to boiler. e connections
3.
may require certain additional ttings and parts, see
and 6)
is boiler is equipped with 1¼” supply and return connections
4.
on the right side of the boiler.
. Use ¾” Pipe and an elbow (not furnished) to carry
(Figures 5
.
Follow the mixing valve manufacturer’s installation instructions.
e minimum design return water temperature to the boiler to
4.
prevent condensation in the boiler and venting is 120ºF. e minimum high limit setting is 140º F.
Figure 5 -Typical Hot Water Piping
Circulator
Cool Water Inlet
Relief Valve
Air Vent
Supply Main
Filtrol
Gauge
In connecting the cold water supply to the water inlet valve, make sure that a clean water supply is available. When the water supply is from a well or pump, a sand strainer should be installed at the pump.
A hot water boiler installed above radiation level must be equipped with a low water cuto device. A periodic inspection is necessary, as is ushing of oat type devices, per manufactures specic instruction. Refer to local codes for low water cut-o requirements.
For Use With Cooling Units
is boiler, when used in connection with chilled water systems,
1.
must be installed so that the chilled water is piped parallel with the heating boiler. Appropriate valves must be used to prevent the chilled water from entering the heating boiler
When this boiler is connected to heating coils located in air
2.
(Figure 6)
.
handling units where they may be exposed to refrigerated air circulation, the piping system shall be equipped with ow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
Low Design Water Temperature Systems (Below 140º)
If the boiler is to be used in a heating system where water tem-
3.
peratures below 140ºF are desired (e.g. radiant oor heating) a 3-way or 4-way mixing valve or suitable alternative is required to prevent low temperature return water from entering the boiler.
Sensor Wire
Return Line
Figure 6 - Chilled Water Piping
Valves A & B - Open For Heating; Closed For Cooling
Valves C & D -Closed For Heating; Open For Cooling
10
Page 11
SYSTEM PIPING
Temperature/Pressure Gauge Installation
To install the temperature/pressure gauge on the boiler:
Remove the box containing the new gauge from the parts bag
1.
and remove the gauge from the box.
Apply pipe sealant to the threads on the sha of the gauge as
2.
shown in
Figure 7 - Apply Pipe Sealant On Shaft of Gauge
Figure 7
.
NOTICE
IMPORTANT: DO NOT TIGHTEN GAUGE BY HAND!! Gauge should be tightened using a crescent wrench or 9/16” open end wrench as shown in
Figure 9 -Tighten Gauge With Crescent Wrench
Figure 9
read the gauge into the supply water tee as shown in
3.
Figure 8
Figure 8 - Thread Gauge Into Supply Water Tee
. To Prevent damage do not overtighten.
4.
Once installation is complete, remove sticker from front of the gauge as shown in
Figure 10 - Remove Sticker From Front of Gauge
Figure 10.
11
Page 12
CHIMNEY AND VENT PIPE OPERATION
Boilers for connection to gas vents or chimneys, vent installations shall be in accordance with Part 7, Venting Equipment, of the Na­tional Fuel Gas Code, ANSI Z2231 - latest revision, and applicable provisions of the local building code.
Check Your Chimney
is is a very important part of your heating system. It must be clean, the right size, properly constructed and in GOOD CON­DITION. No boiler can function properly with a bad chimney.
Table 6
a boiler might be vented to a chimney. Note that the height (HT) is measured from the vent pipe to the top of the chimney.
Chimney Sizing
gives typical chimney size.
Table 6 - Typical Chimney Sizes
Boiler Input
(Btuh)
Up to 100,000 6" x 6" 6" x 5" 5" x 5"
Up to 155,000 6" x 7" 6" x 6" 6" x 5"
Up to 230,000 7" x 8" 7" x 7" 6" x 7"
Up to 350,000 9" x 9" 8" x 9" 8" x 8"
*HT = Top of imble to top of Flue. See
HT 10-15 Ft HT 15-25 Ft HT 25 Ft & up
Fig.11
gives you an idea how
Flue Area in Inches
Figure 11
.
Connecting The Vent Damper And Vent Connector
Refer to the vent (ue opening). Use a 28 gauge (minimum) galvanized pipe to connect to the chimney.
1.
2.
Table 1
IMPORTANT -e damper blade on the furnished vent damper has a 1/2 square inch hole (approximately 3/4” diameter). On boilers equipped with standing pilot, the hole must be le open. On boilers equipped with intermit­tent ignition, the hole should be plugged by using the plug supplied with the vent damper.
Position furnished vent damper on top of ue outlet collar. Fasten damper securely to ue outlet collar with sheet metal screws. Make sure damper blade has clearance to operate inside of diverter.
As an option, the damper may be installed in any hori-• zontal or vertical position, closer to the ue outlet collar preferred. Follow the diagrams -
Install the vent damper to service only the single boiler for which it is intended. e damper position indicator shall be in a visible location following installation. Locate the damper so that it is accessible for servicing.
(page 4) ue diagram for the size and location of
NOTICE
Figures 12, 13 and 14
.
Chimney sizing, and all other aspects of the vent installation must be in accordance with National Fuel Gas Code, ANSI Z223.1 - latest revision, and applicable provisions of the local building codes.
Figure 11 - Typical Masonry Chimney Requirements
2' Min
HT
e damper must be in the open position when appliance main
3.
burners are operating.
e boiler is equipped with a factory wired harness that plugs
4.
into the vent damper.
Vent pipe must be same size as the ue outlet collar.
5.
Slope pipe up from boiler to chimney not less than 1/4” per
6.
foot.
Run pipe as directly as possible with as few elbows as possible.
7.
Do not connect to replace ue.
8.
End of vent pipe must be ush with inside face of chimney ue.
9.
Use a sealed-in thimble for the chimney connection.
Horizontal run should not be longer than 3/4 the chimney
10.
height (HT) for single appliance venting.
e sections of vent pipe should be fastened with sheet metal screws to make the piping rigid. Horizontal portions of the vent system must be supported to prevent sagging. Use stovepipe wires every 5’ to support the pipe from above If the vent pipe must go through a
(see Figure 11)
12
Page 13
CHIMNEY AND VENT PIPE CONNECTION
crawl space, double wall vent pipe should be used Where vent pipe passes through a combustible wall or partition, use a ventilated metal thimble. e thimble should be 4” larger in diameter than the vent pipe.
Minimum Vent Pipe Clearance
Wood and other combustible materials must not be closer than 6” from any surface of single wall metal vent pipe. Listed Type B vent pipe or other listed venting systems shall be installed in accordance with their listing.
REMOVING EXISTING BOILER FROM COMMON VENTING SYSTEM
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper vent­ing of the appliances remaining connected to it.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the com­mon venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Seal any unused openings in the common venting system.
1.
Visually inspect the venting system for proper size and hori-
2.
zontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deciencies which could cause an unsafe condition.
Insofar as is practical, close all building doors and windows and
3.
all doors between the space in which the appliances remaining connected to the common venting system are located and other
spaces of the building. Turn on clothes dryers and any appli­ance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a sum­mer exhaust fan. Close replace dampers.
Place in operation the appliance being inspected. Follow the
4.
lighting instructions. Adjust thermostat so appliance will oper­ate continuously.
Test for spillage at the dra hood relief opening aer 5 minutes
5.
of main burner operation. Use the ame of a match or candle, or smoke from a cigarette, cigar or pipe.
Aer it has been determined that each appliance remaining
6.
connected to the common venting system properly vents when tested as outlined above, return doors windows, exhaust fans, replace dampers and any other gas-burning appliance to their previous conditions of use.
Any improper operation of the common venting system should
7.
be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1-latest revision. When re-sizing any portion of the common venting system, the common venting system should be re-sized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code, ANSI Z223.1-latest revision.
NOTICE
Vent connectors serving appliances vented by natural dra shall not be connected into any portion of mechanical dra systems operating under positive pressure.
Typical Installation For Vent Damper
WARNING
Install the vent damper to service only the single appliance
!
for which it is intended. If improperly installed, a hazard­ous condition, such as an explosion or carbon monoxide poisoning, could result.
Do not install the vent damper on pipe curve.
Do not run wires near high temperature surfaces. Use stando brackets if necessary.
VENT DAMPER OPERATION
For safe, ecient operation, the vent damper and all ue product carrying areas of the appliance must be checked annually by you, with particular attention given to deterioration from corrosion or other sources. If you see corrosion or other deterioration, contact your heating contractor for repairs. Check vent damper operation as follows:
When the boiler is o, check that the vent damper positions
1.
indicator points to the closed position,
Turn the thermostat or controller up to call for heat and check
2.
the vent damper indicator points to the open position,
13
Fig. 14.
Fig. 14
.
Page 14
ROTATION
ROTATION
OPEN
CLOSED
FLUE GAS FLOW
FLUE GAS FLOW
CLOSED
OPEN
DAMPER CLOSED DAMPER OPEN
SHOWING OPEN AND CLOSED POSITION
VENT DAMPER OPERATION
Turn the thermostat or controller down again and check that
3.
the damper position indicator returns to the closed position.
For further information, and for a vent damper troubleshooting guide, refer to the manual that was packaged with the vent damper.
Manual Operation Of The Vent Damper
e vent damper may be placed in the open position to permit burner operation by using the “HOLD DAMPER OPEN” switch, located on the damper controller. e thermostat will control the burner ring as before, while the damper will remain open. DO NOT turn damper open manually or motor damage will result. Set switch to “AUTOMATIC OPERATION” to close vent damper during burner o cycle.
Figure 12 - Damper Installation
e vent damper must be inspected at least once a year by a trained, experienced service technician. e name of the person who origi­nally installed your vent damper is shown on the installation label.
Figure 13 - Damper Installation
Figure 14 - Vent Damper Position Indicator
14
Page 15
Sediment
Trap
Manifold
Floor Line
Automatic
Gas Valve
Ground
Joint
Union
GAS SUPPLY PIPING
Check Gas Supply
e gas pipe to your boiler must be the correct size for the length of the run and for the total Btu per hour input of all gas utilization equipment connected to it. See
Table 7
for the proper size. Be sure your gas line complies with local codes and gas company require­ments.
Testing pressures in excess of 1/2psig:
e boiler and its individual shuto valve must be discon-• nected from the gas supply piping system when testing pressures in excess of 1/2 psig (3.5 kPa) during any pres­sure testing of that system.
Testing pressures equal to or less than 1/2 psig:
e boiler must be isolated from the gas supply piping • system by closing its individual manual shuto valve when testing pressures equal to or less than 1/2 psig (3.5kPa) dur­ing any pressure testing of the gas supply piping system.
Connecting The Gas Piping
Refer to
Fig. 15
for the general layout at the boiler. It shows the basic ttings you will need. e gas line enters the boiler from the right side.
e following rules apply:
Use only those piping materials and joining methods listed
1.
as acceptable by the authority having jurisdiction, or in the absence of such requirements, by the National Fuel Gas Code, ANSI Z223.1-latest revision.
Use pipe joint compound suitable for LP gas on male threads
2.
only.
Use ground joint unions.
3.
Checking The Gas Piping
Upon completion of piping, check immediately for gas leaks. Open the manual shut-o valve. Test for leaks by applying soap suds (or a liquid detergent) to each joint. Bubbles forming indicate a leak.
CORRECT EVEN THE SMALLEST LEAK AT ONCE.
WARNING
!
NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS.
TABLE 7  GAS SUPPLY PIPE SIZES
Pipe
Length ()
20 92 190 350 625
Natural Gas
40 63 130 245 445
60 50 105 195 365
Pipe
Length ()
Propane Gas
20 131 216 189 393
40 90 145 129 267
60 72 121 103 217
* Dimension is outside diameter. e length of pipe or tubing should be measured from the gas meter or propane second stage regulator.
Figure 15 - Gas Piping At Boiler
Pipe Capacity - KBtuh Input
(includes Fittings)
1/2" 3/4" 1" 1 1/4"
Pipe Capacity - KBtuh Input
(includes Fittings)
Copper Tube* Iron Pipe
5/8" 3/4" 1/2" 3/4"
Install a sediment trap upstream of gas controls.
4.
Use two pipe wrenches when making the connection to the gas
5.
valve to keep it from turning.
Install a manual shut-o valve in vertical pipe about 5 feet
6.
above oor.
Tighten all joints securely.
7.
Propane gas connections should only be made by a licensed
8.
propane installer.
Two-stage regulation should be used by the propane installer.
9.
Propane gas piping should be checked out by the propane
10.
installer.
15
Page 16
El E c t r i c a l Wi r i n g
WARNING
!
Turn o electrical power at fuse box before making any line voltage connections. Follow local electrical codes
All electrical work must conform to local codes as well as the Na­tional Electrical Code, ANSI/NFPA-70, latest revision.
Electric Power Supply
Prior to making any line voltage connections, service switch at boiler should be in the o position and the power turned o at the fuse box.
Run a separate 120 Volt circuit from a separate over current protec­tive device in the electrical service entrance panel. is should be a 15 ampere circuit. A service switch has been provided and should be mounted to the Junction box located on the exterior boiler jacket. see
Fig. 16-1
e boiler, when installed, must be electrically grounded in accor­dance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA - 70, latest revision.
Run a 14 gauge or heavier copper wire from the boiler to a grounded connection in the service panel or a properly driven and electrically grounded ground rod.
Install Your Thermostat
for diagram showing power supply connection points.
Connect 24 Volt thermostat leads to the white (TW) and red (TR) wires located in service switch junction box, located on outer jacket of boiler see
Fig.16-1
for service switch junction box and thermo-
stat eld wiring connections.
Vent Damper Wiring
e boiler is equipped with a factory wired harness with 4 pin Molex plug, that plugs into a 4 pin Molex receptacle inside the vent damper operator. e vent damper must be connected for the boiler to operate. Follow the wiring diagram follow for the various dierent models.
CAUTION
Label all wires prior to disconnection when servicing
!
controls. Wiring errors can cause improper and dangerous operation. Verify proper operation aer servicing.
Connect Circulator Pump Wiring
See
Fig. 16 -1
for line voltage, thermostat and circulator pump eld wiring connections. A ve (5) foot wiring harness with exible metal conduit is supplied to connect the circulator pump to the service switch junction box. If the two 120 Volt circulator wire terminals in­side the junction box are not used, do not remove the two wire nuts to prevent a short circuit.
NOTICE
All low volt interconnect wiring must be at least 18 AWG.
e thermostat location has an important eect on the operation of your boiler system. BE SURE TO FOLLOW THE INSTRUCTIONS INCLUDED WITH YOUR THERMOSTAT. Locate the thermo­stat about ve feet (5') above the oor on an inside wall. It may be mounted directly on the wall or on a vertically mounted outlet box. It should be sensing average room temperature.
THERMOSTAT LOCATIONS TO AVOID
DEAD SPOTS HOT SPOTS COLD SPOTS
Behind doors
Corners &
alcoves
Concealed pipes
Fireplace
TV sets Stairwells - dras
Radios Doors - dras
Lamps
Direct sunlight
Kitchens
Concealed pipes
or ducts
Unheated room on
other side of wall
16
Page 17
El E c t r i c a l Wi r i n g
Figure 16-1 - Field Wiring Connections -Circulator Pump Wiring
Ve n t Da m p e r Ha r n e s s
ermostat TW & TR Referenced on Page 15
No t e s :
Ve N t Da m p e r s h i p p e D l o o s e i N c r a t e .
Ve N t Da m p e r ha r N e s s m u s t b e c o N N e c t e D t o V e N t
w h e N m o u N t e D
17
Page 18
ELECTRICAL WIRING
Figure 16-2 - Wiring Diagram - Electronic Ignition
If any of the original wire as supplied with this appliance must be replaced, It must be replaced with type 105°C thermoplastic wire or it’s equivalent
NOTICE
18
Page 19
Figure 16-3 - Wiring Diagram - Standing Pilot
ELECTRICAL WIRING
If any of the original wire as supplied with this appliance must be replaced, It must be replaced with type 105°C thermoplastic wire or it’s equivalent
NOTICE
19
Page 20
EQUIPMENT AND OPTIONAL ACCESSORIES
Relief Valve
You must have a relief valve on your boiler. Water expands as it is heated. If there is no place for the water to expand into, water pres­sure will build up inside the boiler and system. Should this happen, the relief valve will automatically open at a predetermined pressure. is will relieve the strain on the boiler and system. Run a pipe from the relief valve outlet (pipe must be same size as outlet and the open end must not be threaded) to an open drain, tub or sink, or other suitable drainage point not subject to freezing. Failure to do so may cause water damage or injury should relief valve release.
Expansion Tank
In a properly assembled system, the expanding water ows into a expansion tank. is tank should be of the correct size. e tank is partially lled with air. As the water expands it compresses the air in the tank to form an air pressure cushion. is “spring-like” cushion serves to maintain correct operating water pressure regardless of water temperature. is assures a “full measure” of a water, even in the highest radiation unit of the system. It also prevents blowing o of the relief valve. e air in the tank in the beginning (with system lled with cold water) is sucient for proper operation. e tank also serves as a trap for excess air in the system. e air would cause gurgling in the pipes and inecient circulation in the radiators if le in the system . It is possible for a tank to become “waterlogged” (lled with water). It can also become overlled with air. is can happen aer lling the system with new water. Fittings provided on the tank and in the line to the tank are for bleeding o excess water or air. When installing this tank, it is important:
at the tank be higher than the boiler top.
1.
Main Air Vent For Down Flow Systems Or Diaphragm Type Expansion Tank
Before a system is lled with water, there is air in the pipes and radiation units. Some of it will be trapped as the system is lled . It is possible to eliminate most of this air through the air vent on the radiation units. A main air vent will speed and simplify this. It should be installed on the highest point in the supply main when all radiation is below top of boiler.
Automatic Fill Valve
For safe, ecient operation, a hot water system must be completely lled with water. Adding new water, when needed can be done manually (by use of a hand valve in the water supply line). is re­quires regular attention to the system’s needs. An automatic ll valve accomplishes this without attention. It is installed in the supply line on hot water boilers only. e valve operates through water pressure dierentials. It does not require an electrical connection.
Drain Valve
is manual valve provides a means of draining all water from the boiler and system. It is oen installed in the 3/4” tapping at the bot­tom of the end boiler section. Or it can be installed in a tee where the return line enters the boiler.
Circulating Pump
Every forced hot-water system requires a circulating pump. is pump must have the capacity to provide the circulation required by your system. e pump is connected into the return main just ahead of the boiler. It is also wired to the electrical system.
at the pipe to the tank continuously rises up to the tank (so
2.
that air can “bubble” up to it).
Diaphragm Type Expansion Tank
e diaphragm type expansion tank (EXTROL) takes the place of the conventional expansion tank. Carefully read the instructions packed with your EXTROL tank assembly.
e EXTROL tank comes to you with a 10-12 pounds per square inch air charge. is is the same as the pressure produced in the system by the automatic ll valve. When the system is rst lled, the EXTROL tank will contain little or no water.
As the water is heated its pressure increases. It expands into the EXTROL tank, compressing the air in the tank. is compressed air cushion permits the water in the system to expand as the tempera­ture changes. e diaphragm type tank can be mounted on the air purger tting or at any convenient place in the supply or return line.
Air Eliminating Fitting (Air Purger)
An air purger is used to remove excess air from the system. It is installed in the supply line. It will eliminate air from the water before it reaches the radiators and bleed o this air.
Vent Damper
is product is an automatic, motorized stack damper that has been developed to increase the eciency of heating systems by reducing standby losses from the heating apparatus and the conditioned air space. e damper closes the chimney vent when the burner is o and fully opens it when combustion is required.
Rollout Switch (Flame Rollout Safety Shuto󱐯)
e rollout switch is a temperature-sensitive fuse link device. It is lo­cated on the boiler base just outside the re box. In the event of heat exchanger ueway blockage causing ame to roll out of the re box, the fuse does not change in appearance when blown. If the rollout switch blows, it must be replaced with an exact replacement. Check heat exchanger ueways for blockage when restoring system to oper­ating condition. DO NOT operate system without a rollout switch.
20
Page 21
EQUIPMENT AND OPTIONAL ACCESSORIES
Blocked Vent Safety Shuto󱐯
e blocked vent switch is a manual reset disc thermostat with a xed setpoint (340° F), and normally closed contacts. It is located at the relief opening of the integral dra diverter. In the event of chim­ney or venting system blockage causing products of combustion to spill out of the relief opening, the blocked vent switch disc heats up and the blocked vent switch contacts open, shutting down the ow
STARTING THE BOILER
How A Hot-Water System Operates
Your entire heating system (boiler, piping and radiation units) is lled with water. As the water in the boiler is heated, it is pumped from the top of the boiler through the supply main to the radia­tion units. e cooler water in them ows back through the return main to the boiler. is provides positive and rapid response to the thermostat.
WARNING
!
Never run water into a hot empty boiler.
Filling System With Water
Close the air vents on all radiation units. Open the valves to these units. Make sure the boiler and expansion tank drain cocks are
of gas to the main burners by removing power to the gas valve. In the event that the blocked vent switch contacts open, the reset button on the back of the switch will pop up. e blocked vent switch must be reset manually, aer the switch has cooled o, by pushing the reset button down. Check the venting system and chimney for blockage when restoring the system to operating condition. DO NOT operate the boiler without a blocked vent switch.
closed. e air bleed screw on the expansion tank drain tting should be closed. Open the valve in the line from the boiler to the expansion tank. Open the water inlet to your boiler and leave it open. Start with the lowest radiation unit. Open the air vent on this unit. When all the air has escaped and water starts to ow from the vent, close it. Go to the next radiation unit, and repeat this process. Repeat until you have covered every radiation unit in the system (ending up at the highest unit in the system). If your units have auto­matic vents, this manual venting is unnecessary but it will speed up the proper lling of your system. If your system is a closed expansion tank system, you may leave it open to rell the system automatically as needed. Check the temperature pressure gauge, of the hand indicating the pressure. is should be between 10 and 15 lbs. any lowering of this movable hand below 10 lbs. will indicate loss of water due to leakage. e automatic ll valve should compen­sate for this. Instructions are packaged with the valve.
NOT
the position
FOR YOUR SAFETY READ BEFORE OPERATING
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
Some boilers are equipped with an intermittent igni-
1.
tion device which automatically lights the pilot. Do
!
not try to light the pilot by hand.
Some boilers are equipped with a continuous pilot
2.
and must be manually lighted. (See lighting instruc­tions.)
BEFORE OPERATING smell all around the appli-
3.
ance area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
WARNING
Use only your hand to push in or turn the gas control knob.
4.
Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualied service technician. Force or attempted repair may result in a re or explosion.
Do not use this appliance if any part has been under water.
5.
Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. •
Do not touch any electric switch; do not use any phone in • your building.
Immediately call your gas supplier from a neighbor’s • phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the re depart-• ment.
21
Page 22
OFF
ON
INL ET
GAS CONTROL KNOB
SHOWN IN "ON" POSITION
OFF
ON
INLET
GAS CONTROL
KNOB
PILOT ADJUSTMENT
(UNDER CAP SCREW)
PILOT OUTLET
OUTLET
WIRING TERMINALS (2)
INLET
PRESSURE
TA P
TERMINALS (2)
GROUND
PRESSURE TA P
PRESSURE REGULATOR
ADJUSTMENT
(UNDER CAP SCREW)
OUTLET
STARTING THE BOILER
Intermittent Ignition Boiler - VR8204A/VR8304M Gas Valve Operating Instructions
STOP1.
! Read the
Set the thermostat to lowest setting.
2.
Turn o all electric power to the appliance.
3.
is appliance is equipped with an ignition device which auto-
4.
WARNING
on the previous page.
matically lights the pilot. Do not try to light the pilot by hand.
Remove lower front panel.
5.
Rotate the gas control knob clockwise to “OFF”
6.
Wait ve (5) minutes to clear out any gas. en smell for gas,
7.
including near the oor. If you smell gas,
STOP
! Follow the safety information the previous page. If you don’t smell gas, go to next step.
Rotate the gas control knob counterclockwise to “ON.”
8.
Replace lower front panel.
9.
Turn on all electric power to the appliance.
10.
Set thermostat to desired setting.
11.
If the appliance will not operate, follow the instructions “To
12.
Turn O Gas To Appliance” and call your service technician or gas supplier.
To Turn O󱐯 Gas To Appliance
1. Set the thermostat to lowest setting.
2. Turn o all electric power to the appliance if service is to be performed.
3. Push in gas control knob slightly and turn clockwise to “OFF” Do not force.
Continuous Pilot Boiler - VR8200A/VR8300A Gas Valve Operating Instructions
STOP1.
! Read the
Set the thermostat to lowest setting.
2.
Turn o all electric power to the appliance.
3.
Remove lower front panel.
4.
Rotate the gas control knob clockwise to “OFF”
5.
Wait ve (5) minutes to clear out any gas. en smell for gas,
6.
including near the oor. If you smell gas,
WARNING
on the previous page.
STOP
! Follow the safety information the previous page. If you don’t smell gas, go to next step.
Find pilot - follow metal tube from gas control. e pilot is
7.
between two burner tubes as shown in
Turn knob on gas control counterclockwise to “PILOT”
8.
Push down and hold the red reset button while you light pilot
9.
Fig. 18
.
burner with a match. Do not release reset button.
Aer about one minute, release reset button. Pilot should re-
10.
main lit. If it goes out, turn gas control knob clockwise to OFF. To relight, repeat steps 5-9.
If button does not pop up when released, stop and immedi-• ately call your service technician or gas supplier.
If the pilot will not stay lit aer several tries, turn the gas • control knob to “OFF” and call your service technician or gas supplier.
Aer pilot remains lit when red reset button is released, turn
11.
gas control knob counterclockwise to “ON.”
Replace lower front panel.
12.
Turn on all electric power to the appliance.
13.
22
Set thermostat to desired setting.
14.
Figure 18 - Manual Gas ValveFigure 17- Automatic Gas Valve
Page 23
INITIAL OPERATIONAL BOILER TEST CHECKOUT PROCEDURE
Cast Iron Gas-Fired Cast Iron Boilers
Check o each step as completed.
o Verify base insulation is securely fastened to base panels.
o Verify air purged from hydronic heating system.
o Purge air from gas piping; check gas piping for leaks.
o Verify proper orices have been installed.
o Follow Lighting Instructions in Installation, Operation and Maintenance Manual furnished with boiler.
o Visually check the main burner ame and verify it has a well dened inner blue mantel with a lighter blue outer mantel.
o Inspect vent system to verify it is functional, unobstructed, and not leaking.
o Test the temperature limit control: With burner operating, adjust indicator on limit control below actual boiler water temperature. Verify burners turn o. Verify the circulator continues to operate. Adjust the indicator on limit control above actual boiler water temperature and verify burners reignite.
o Test any additional eld-installed controls. If boiler has a low water cut-o or additional high limit, test for operation as outlined by the controls manufacturer. Burners should be operating and should go o when controls are tested. When controls are reset, burn ers should reignite.
o Test safety control circuit: With main burner operating, disconnect the ignition cable from the intermittent pilot control box. Verify that the main gas control closes, shutting o the gas to the main burner. Aer verifying safety control circuit, turn o electric power and reconnect ignition cable. Once ignition cable securely reset to intermittent pilot control box, turn electric power on.
o For multiple heating system zones, balance ow through each zone so that it is about equal per zone.
o Verify several operating cycles of proper operation.
o Measure Gas Input:
Natural Gas Procedure
o Operate boiler for 10 minutes.
o Turn o all other gas appliances piped with the boiler.
o At the gas meter, measure the cubic feet of gas used in 10 seconds (CF10).
o Calculate input: BTUh = CF10 x 360,000
o Verify the BTUh is approximate to the input rating on the boiler rating plate.
LP Gas Procedure
o LP gas input rate is determined by measuring gases produced during combustion. Refer to Boiler Manual for combustion guidelines and corresponding BTUh input
o Verify the BTUh is approximate to the input rating on the boiler rating plate.
o Record the BTUh input on the OPERATIONAL BOILER TEST CERTIFICATE & SIGNED RECEIPT form.
o Set operating control (thermostat(s)) to the desired design requirement.
o Forward boiler manuals, instructions, wiring diagrams, piping diagrams, and supporting information shipped with this boiler to owner and/or maintenance personnel.
o Complete and sign the INITIAL OPERATIONAL BOILER TEST CERTIFICATE & SIGNED RECEIPT form.
23
Page 24
INITIAL OPERATIONAL BOILER TEST CHECKOUT CERTIFICATE & SIGNED RECEIPT
Boiler Manufacturer: Boiler Identication:
Model #: _______________________________________________
Serial #: ________________________________________________
Measured BTUh input: _____________________ Operational Test Date: ________ /________ /_________
Installation Instructions in the Installation, Operation and Maintenance Manual have been followed.•
Initial Operational Boiler Test Check-Out Procedure has been performed.•
Information on this form is certied to be correct.•
All boiler instructions, wiring diagrams, piping diagrams, and supporting information shipped with this boiler forwarded to owner/• maintenance personnel.
Installation Location:
Customer Name: __________________________________________________________________________
Address: _________________________________________________________________________________
City: ________________________________________________ State: ________ Zip: ___________________
Installer Information
Company/Contractor: ______________________________________________________________________
Address: _________________________________________________________________________________
City: ________________________________________________ State: ________ Zip: ___________________
Telephone #: _____________________________________________________________________________
Installer’s Signature ___________________________________ Date: ________ /________ /_________
Installer’s Printed Name: ___________________________________________
24
Page 25
OPERATING YOUR BOILER
Automatic Gas Valve
e Automatic Gas Valve opens or closes according to the heat requirements of the thermostat and temperature limit control. It closes if the pilot goes out. Each individual control must be operat­ing correctly before any gas can pass to the burners. Any one control can hold the gas supply from burner regardless of the demand of any other control.
Safety Pilot
Safety Pilot prevents the ow of gas to burner if the pilot goes out, or will not ignite.
Gas Valve Safety Shutdown Test
1. For boilers equipped with continuous pilot, with main burners ring, disconnect the thermocouple from the gas valve. e gas valve should immediately shut o the main burners and the pilot.
2. For boilers equipped with intermittent ignition, with main burn­ers ring, disconnect the ignition cable from the intermittent pilot control box. e gas valve should shut o the main burners.
TURN OFF ELECTRIC POWER to boiler before reconnecting igni­tion cable, to prevent electric shock.
Figure 19- Lighting the Pilot
Figure 20- Burner Flame
Relight
e electric and gas shall be o for 5 minutes before relighting.
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the boiler underwent tests specied in ANSI Z21.13 - latest revision.
Thermostat
Keep it set at a desired room temperature. If windows are to be opened or heat is not needed, move thermostat pointer to a lower setting.
NOTICE
In the event of failure of any component, the system will not operate or will go into safety lockout. e system is completely self-checking. On every call for heat, each com­ponent must be functioning properly to permit operation. On safety lockout the system has to be reset by turning the thermostat to the lowest setting for one minute, then back to the normal setting.
25
Page 26
CHECKING AND ADJUSTING
Adjust Pilot Burner
Pilot ame should surround 3/8” to 1/2” of the pilot sensor,
to Fig. 21)
1.
2.
3.
Main Burner(S)
e main burners do not require primary air adjustment and are not equipped with primary air shutters. Main burner ames should form sharp blue inner cones in a soer blue outer mantel, with no yellow
(Refer to Figure 20).
stamping on the oor will cause the ames to turn orange momen­tarily. is is not unusual. Remain still when observing the main burner ames. If the ame appearance is not correct, check main burner orices and the burner throat and ame ports for dust and lint obstruction. It may be necessary to remove the rollout shield to observe the main burner ames. Replace rollout shield aer observa­tion.
Adjust Limit Controls
. If ame needs adjusting, do it as follows:
Remove screw cover over pilot adjusting screw on gas valve.
Insert small screwdriver and adjust ame as needed. Turn screw counterclockwise to increase ame, clockwise to decrease.
Replace screw cover over pilot adjusting screw.
Pus of air from blowing on the ame or
(Refer
boiler gauge to check your settings. Make the adjustments according to its readings.
Check thermostat operation. When set above temperature indicated on the thermometer, boiler should ignite. Make certain the thermo­stat turns o the boiler when room temperature reaches the selected setting and starts the boiler operating when room temperature falls a few degrees.
Aer setting limit control to limit setting, check to see if it shuts o the gas supply to the burners. Turn your thermostat up to call for heat and let your boiler run until the temperature of the water reaches the limit setting. e gas valve should shut o and the circu­lator keep running until the thermostat is satised, or the water cools enough to restart the burners through the limit control.
Finally, set the thermostat for the desired temperature. Special con­ditions in your home and the location of the thermostat will govern this setting.
Figure 21 - Pilot Flame Adjustment
Flame
on
Sensor
Instructions for each control are included with the controls. ese settings can be changed aer you have had some idea how the sys­tem works. Example: If your system does not give quite enough heat in very cold weather, you can raise the limit setting to 220° F Use the
MAINTAINING YOUR BOILER
Burners
A visual check of the pilot end main burner ames should be made at least once each year, preferably at the beginning of the heating season.
Relief Valve
is valve should open automatically if the system pressure exceeds the pressure rating (usually 30 psi) of the relief valve. Should it ever fail to open under this condition, shut down your system. Drain the system until system pressure is reduced below the relief valve pressure rating. If valve discharge occurs, or if valve fails to open as described above, contact an authorized contractor or qualied service technician to replace the relief valve and inspect the heating system to determine the cause, as this may indicate an equipment malfunction.
is valve should be tested every month during periods of boiler operation, and at the beginning and end of any extended non-service period. Prior to testing, make certain discharge pipe is properly connected to valve outlet and arranged so as to contain and safely dispose of boiler discharge. Test at
normal system operating pressure. Hold the trip lever fully open for at least ve seconds in order to ush free any sediment that may lodge on the valve seat. en permit the valve to snap shut.
Expansion Tank
As previously noted, this tank may become waterlogged, or may receive an excess of air. Frequent automatic opening of the relief valve indicates water logging. A high boiler temperature accompanied by unusually low radiation unit temperature (and “knocking”) indicates excess air in tank.
To correct either condition, close the valve between the boiler and the tank. Drain the tank until it is empty. Check all the tank plugs and ttings. Tighten as necessary. Open the valve between the boiler and tank. Water will rise to the normal height in the tank if you have an automatic ll valve (otherwise, manually rell the system).
Boiler Flue Passages
Under normal operating conditions, with the burners properly adjusted, it should not be necessary to clean the boiler ue gas passages. However, to as-
26
Page 27
MAINTAINING YOUR BOILER
sure trouble-free operation, we recommend that you have the ue passages, burner adjustment, and operation of the controls checked once each year by a competent Service Technician.
Before the start of each season (or whenever system has been shut down for some time) recheck the whole system for leaks and recheck the boiler and vent pipe for leaks. Replace or patch any boiler seals that are faulty.
Vent Pipe
e venting of this unit is very important and the piping should be checked at least once a season. If the vent piping shows any sign of leaking, replace it immediately.
Water System
If system is to remain out of service during freezing weather, always drain it completely (water le in to freeze will crack the pipes and/or boiler).
SEQUENCE OF OPERATION
e Boiler uses an electronic control to maintain water temperature and to monitor the critical water level. ere are four (4) LED indi­cators that will display the mode of operation of the unit.
LOW WATER RED Low water condition
TSTAT GREEN ermostat call for heat
HIGH LIMIT YELLOW
ACTIVE GREEN Active, power to unit is on
Water temperature at high limit
Cleaning Your Boiler And Burners
Flue passages between sections should be examined yearly and cleaned if necessary. To clean, remove burners, pilot, and vent pipe, Remove top and front jacket panels. Remove the two screws attaching the intermediate front panel to the le and right side jacket panels. Remove the dra diverter and intermediate front panel as a unit. Carefully remove the cerafelt gasket strips. Clean passageways between sections with a exible handle wire brush. Remove dirt from bottom of boiler and from between sections by vacuum­ing. Make sure all ame ports in burners are open and clear. Shake out or blow out all loose dirt in burners. Reseal seams between adjacent sections as necessary with 400° F RTV silicone sealant. Reassemble all parts. Be sure to check tightness of pilot connections and condition of burner ames aer reassembly ( chimney are secure and no obstructions are present.
PWXL with Electronic Ignition
Upon a call for heat the room thermostat will close the Green ermostat LED will illuminate. Power will be applied to the pump circuit enabling the ow of water to the heating space. e automat­ic vent damper will then begin to open. When the vent damper is completely open the ignition module will start the ignition sequence.
At the start of the ignition sequence the pilot valve will open and the spark controller will light the pilot burner. Upon a successful proven pilot light the main gas valve will open allowing the main burners to light. e burners will continue to re until the call for heat is satis­ed and the thermostat opens or the water temperature in the boiler reaches the High Temperature Limit setting.
see Figures 20 and 21
). Be sure vent pipe connections to
ere are four adjustable settings on the control. ese can be adjusted using a small screw driver or by turning the adjusting post. When power is applied to the unit all LED's will illuminate for a brief moment. e Active LED will remain lit indicating that the control is powered and that the temperature function is active. e display will then cycle through the settings of the control.
CONTROL SETTINGS
Setting Range (oF)
HIGH TEMPERATURE
LIMIT (HL)
HIGH TEMPERATURE
DIFFERENTIAL (H df)
LOW TEMPERATURE
DIFFERENTIAL (LL)
LOW TEMPERATURE
LIMIT (L df)
130°-220° 180°
10°-30° 10°
10°-30° 10°
OFF or
110°-200°
Factory
setting
OFF
When the water temperature reaches the High Temperature Limit setting, while the thermostat is not satised, the Yellow LED will illuminate and the circulator pump circuit will remain energized. e gas valve will close, shutting o the main burners. While the thermostat is calling, if the water temperature falls below the High Temperature Limit setting (minus) the High Temperature dierential setting, the ignition sequence will start again to maintain the boiler water temperature.
If the Low Temperature Limit is active (not set to OFF) the control will maintain a minimum water temperature allowing for warm start operation enabling the boiler to readily satisfy the heat load.
While the thermostat is NOT calling, the control will allow the burner to re until the boiler water temperature reaches the Low Temperature Limit setting (minus the Low Limit Dierential).
27
Page 28
SEQUENCE OF OPERATION
CAUTION
Do not set the Low Temperature Limit setting above the High Temperature Limit setting. For example if the High Temperature Limit is set at 1900 F with the High Tem-
!
perature Dierential at 200 F then the Low Temperature Limit needs to be set at 1700 F or lower. If the settings are overlapped then the control will not operate properly and the burner will switch o at the lower setting.
Low Water Condition
If the water level in the boiler falls below the level of the sensing well,
TROUBLESHOOTING
Initial Service Checks
Before troubleshooting:
1.
Make sure that circuit breaker is on or fuse is ok at electri-A. cal panel.
Make sure that service switch is on.B.
Make sure that gas is on at the gas meter, and that all ap-C. propriate manual shuto valves and gas control valve are open.
Make sure that the thermostat is calling for heat.D.
Check that wire connectors at the Temperature Limit Con-E. trol and Transformer are securely plugged in or connected.
the control will close the main gas valve within three seconds, shut­ting o the main burners. e a low water condition. Once the water level has been restored the
RED
LED will go dark and the control will resume normal opera-
tion.
PWXL with Standing Pilot
Units with a standing pilot do not use an ignition module or a sepa­rate pilot valve. Upon a call for heat the control will open the main gas valve and the standing pilot will then light the main burners.
RED
LED will illuminate indication
Troubleshooting tools:
2.
Voltmeter to check 120Vac and 24Vac.A.
Continuity tester.B.
U-tube manometer or dierential pressure gauge with C. 0-14” range (0.1” Scale) for measuring inlet and manifold gas pressures.
What is the system status?
3.
For troubleshooting information refer to Hydrolevel A. Hydrostat Model 3100 ECR Temperature Limit Control Instructions.
HYDROLEVEL HYDROSTAT MODEL 3100
Hydrolevel Model 3100 ECR Temperature Limit Control Instructions and Troubleshooting :
SEE HYDROLEVEL INSTRUCTIONS AND TROUBLESHOOTING GUIDE SUPPLIED IN LITERATURE PACKAGE
RECEIVED WITH YOUR BOILER
28
Page 29
SERVICE HINTS
You may avoid inconvenience and service calls by checking these points before you call for service.
IF YOUR SYSTEM IS NOT HEATING OR NOT GIVING ENOUGH HEAT . . .
Possible Cause What to do
ermostat is not set correctly Reset thermostat above room temperature
Burner is not operating properly Check ame. If it is yellow, the burner is not getting enough air. Or, if ame is blue and noisy and seems
to li o the burner, the burner is getting too much air. Contact your service technician.
No electric power to boiler Check over current protection. Check to be sure electric power supply circuit is “ON”.
Controls out of adjustment Reset according to instructions.
Radiators not heating Open radiator vents to excess air. Check ow control valve (if used). It may be in closed position.
Circulating pump not running Check over current protection. Check relay operation
Poor electrical contact Check all control terminals and wire joints.
Rollout switch blown Have your service technician check heat exchanged for blockage. Replace rollout switch with exact
replacement.
Spill switch blown Have your service technician check venting system and chimney for blockage, or down dra condition.
Reset spill switch.
Vent damper not operating Consult troubleshooting guide in Ekal manual, packaged with vent damper.
If Burner is Noisy...
Gas input amount is incorrect Contact your service Technician.
Relief Valve is Leaking...
Dirt on valve Seat Open valve manually. Allow water to run and clear valve seat.
Water-logged expansion tank Drain tank, see instructions.
!
Do not try to light any appliance. •
Do not touch any electric switch; do not use any phone in your building. •
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.•
If you cannot reach your gas supplier, call the re department.•
WARNING
WHAT TO DO IF YOU SMELL GAS
29
Page 30
30
Page 31
31
Page 32
85 Middle Rd.
Dunkirk, NY 14048
Loading...