Dunkirk PWXL Installation, Operation & Maintenance Manual

R
PWXL
Cast Iron Gas Fired
Hot Water Boilers
INSTALLATION, OPERATION &
An ISO 9001-2000 Certified Company
DUNKIRK BOILERS
85 Middle Rd. Dunkirk, NY 14048
www.dunkirk.com
P/N 240007958 REV A [09/09]
H
TABLE OF CONTENTS
Safety Symbols........................................................................................................................................................4
Boiler Ratings and Capacities ................................................................................................................................5
Before You Start ......................................................................................................................................................6
Locating the Boiler .................................................................................................................................................7
Combustion And Ventilation Air ............................................................................................................................8
System Piping ...................................................................................................................................................... 11
Chimney and Vent Pipe Operation ..................................................................................................................... 13
Vent Damper Operation ...................................................................................................................................... 14
Gas Supply Piping ................................................................................................................................................ 16
Electrical Wiring ................................................................................................................................................... 17
Equipment and Optional Accessories ................................................................................................................ 21
Starting the Boiler ............................................................................................................................................... 22
Initial Operational Boiler Test Check-Out Procedure ........................................................................................ 24
Initial Operational Boiler Test Check-Out Certicate & Signed Receipt .......................................................... 25
Operating Your Boiler .......................................................................................................................................... 26
Checking and Adjusting ...................................................................................................................................... 27
Maintaining Your Boiler ...................................................................................................................................... 27
Sequence of Operation ........................................................................................................................................ 28
Troubleshooting .................................................................................................................................................. 29
Hydrolevel Hydrostat Model 3100 ..................................................................................................................... 29
Service Hints......................................................................................................................................................... 30
C.S.A. Certied for
Natural gas or Propane
Tested for 50 LB. ASME
Working Pressure
2
SAFETY SYMBOLS
The following dened symbols are used throughout this manual to notify the reader of potential hazards of varying risk
levels.
DANGER
Indicates an imminently hazardous situation which, if not
!
avoided, WILL result in death, serious injury or substantial property damage.
WARNING
Indicates an imminently hazardous situation which, if not
!
avoided, may result in death, serious injury or substantial property damage.
IMPORTANT: Read the following instructions COMPLETELY before installing!
CAUTION
!
Indicates an imminently hazardous situation which, if not avoided, may result in injury or property damage.
NOTICE
Indicates information which should be followed to ensure proper installation and operation.
NOTICE
ese Instruction must be axed on or adjacent to the boiler. Retain for future reference.
WARNING
All installations of boilers and venting should be done only by a qualied expert and in accordance with the appropri­ate manual. Installing or venting a boiler or any other gas
!
appliance with improper methods or materials may result in serious injury or death due to re or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible.
WARNING
Keep boiler area clear and free from combustible materials, gasoline and other ammable vapors and liquids.
DO NOT obstruct air openings to the boiler room.
Modication, substitution or elimination of factory equipped, supplied or specied components may result in property damage, personal injury or the loss of life.
!
TO THE OWNER - Installation and service of this boiler must be performed by a qualied installer.
TO THE INSTALLER - Leave all instructions with the boiler for future reference.
When this product is installed in the Commonwealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
3
Table 1- Boiler Ratings and Capacities
Number of Boiler
Sections
AGA Input *MBH
BOILER RATINGS AND CAPACITIES
Natural or Propane Gas Dimensions
Heating Capacity
*MBH+
Net I=B=R
Rating *MBH
Flue Diameter Dim. A
3 70 57 50 5" 11-1/4"
4 105 85 74 6" 14-1/2"
5 140 113 98 6" 17-3/4"
6 175 142 123 7" 21"
7 210 170 148 7" 24-1/4"
8 245 198 172 7" 27-1/2"
9 280 226 197 7" 30-3/4"
* MBH = 1,000 BTUH = British ermal Unit Per Hour. Boilers are equipped for altitudes up to 2,000 feet only. For altitudes above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level.
+ Heating Capacity based on D.O.E. (Department of Energy) test procedure.
New York City MEA Number 484-84 E Vol. IV.
e Ratings marked “Net I=B=R Ratings” indicate the amount of remaining heat input that can be used to heat the radiation units. e net I=B=R Ratings shown are based on an allowance of 1.15 in accordance with the factors shown on the I=B=R Standard as published by the Hydronics Institute. Selection of boiler size should be based upon “Net I=B=R Rating” being equal to or greater than the calculated heat loss of the building. e Manufacturer should be consulted before selecting a boiler for installations having unusual piping and pickup requirements.
Boilers For Use At High Altitude
is boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level. For use at altitudes above sea level, the input ratings are reduced by a change in main orice size.
For altitudes above 2,000 feet above sea level, input ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. Consult the latest edition of the National Fuel Gas Code (NFPA54/ANSI Z223.1) for correct orice sizing information. High altitude orices are available from the boiler manufacturer.
4
BEFORE YOU START
Check to be sure you have the right size boiler before starting the installation. See rating and capacity table on previous page. Also be sure the new boiler is for the type of gas you are using. Check the rating plate on the right side of the boiler.
You must see that the boiler is supplied with the correct type of gas, fresh air for combustion, and a suitable electrical supply. e boiler must be connected to a suitable venting system and an adequate pip­ing system. A thermostat, properly located, is needed for control of the heating system. If you have any doubts as to the various require­ments, check with local authorities. Take the time to complete all of the steps for SAFE and PROPER operation of the heating system.
If this boiler is installed in a building under construction, special care must be taken to insure a clean combustion air supply during the construction process. Airborne particulates such as from dry­wall dust and from berglass insulation can clog the burner ports, ueway passages and cause incomplete combustion and sooting.
Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boil­ers, No. CSD-1.
e installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest revision.
Installers - Follow local regulations with respect to installation of CO detectors. Follow maintenance recommendations in this instruction manual.
WARNING
Keep boiler area clean and free from combustible materi-
!
als, gasoline and other ammable vapors and liquids. Fail­ure to keep boiler area clean may result in death, serious injury, or substantial property damage.
5
LOCATING THE BOILER
Select level location as centralized with piping system, and as
1.
near chimney as possible.
Place crated boiler at selected location, remove crate by pulling
2.
crate sides from top and bottom boards.
is boiler must be set on non-combustible oor or optional
3.
non-combustible Base Plate placed over the top of a combusti­ble oor. Refer to Repair Parts and Optional Kits for additional detals (3-6 section Boiler Base Plate Part #14614031; or 7-9 Section Boiler base Plate Part #14614032). A combustible oor is dened as materials made of or surfaced with wood, com­pressed paper, plant bers, or other materials that are capable of being ignited and burned. Such material shall be considered combustible even thought ame-proofed, re-retardant treated, or plastered. is boiler must not be installed on carpeting.
Boiler is to be level. Metal shims may be used under base legs
4.
for nal leveling.
Additional clearance for service may exceed clearance for re
5.
protection. Always comply with the minimum re protection clearance shown on the boiler. An 18 inch clearance should be maintained on any side where passage is required to access another side for cleaning, servicing, inspection or replacement of any part that may need attention.
To determine minimum clearances to combustibles refer to Ta-
6.
ble 2b, for rooms with a single boiler only. Rooms that are large in comparison with the size of the boiler are dened as rooms having a volume equal to or greater than 16 times the volume of the boiler. Where the actual ceiling height of a room is greater that 8’ the volume of a room shall be gured on the basis of a ceiling height of 8’. Determination of room size should be based on the total volume of all gas red equipment install in the room. Consult the latest revision of the National Fuel Gas Code for further information.
Equipment shall be installed in a location in which the facilities
7.
for ventilation permit satisfactory combustion of gas, proper venting, and maintenance of ambient temperature at safe limits under normal conditions of use. Equipment shall be located so as not to interfere with proper circulation of air. When normal inltration does not provide the necessary air, outside air shall be introduced.
Advise owner to keep air passages free of obstructions. Ven-
8.
(See “Combustion and Ventilation Air”)
tilating and combustion air must enter boiler room without restrictions.
e boiler shall be installed such that the automatic gas ignition
9.
system components are protected from water (dripping, spray­ing, rain, etc.) during appliance operation and service (conden­sate trap, control replacement, etc.).
Table 2a - Determination of Room Size
If room does not contain mimimum volume shown to be considered a
Large Room, use "Small Room or Alcove" values.
Boiler Size Volume (Ft3)
3 Section 5.4 86.6 4 Section 7.0 111.6 5 Section 8.5 136.6 6 Section 10.1 161.7 7 Section 11.7 186.7 8 Section 13.2 211.7
9 Section 14.8 236.7
Minimum Room Volume To Be
Considered a Large Room (Ft3)
Table 2b - Minimum Clearances
Minimum
Clearances
To p
Rear
Right Side
Le Side
Front
Flue/Vent
Near Boiler Piping
Small Room or Alcove Large Room
3-5 section 6-9 section 3-9 section
6" 6" 6"
6" 6" 6"
8" 24" 6"
6" 24" 6"
18" 18" 18"
6" 6" 6"
1" 1" 1"
6
COMBUSTION AND VENTILATION AIR
Provision for combustion and ventilation air must be in accordance with the latest revision of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes. You must provide for enough fresh air to assure proper combustion. e re in the boiler uses oxygen. It must have a continuous supply. Outside air must enter the house to replace that used by the burner.
EXAMPLE 1: Boiler Located In Unconned Space An unconned space is dened as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour of the total input rating of all appliances installed in that space.
If your boiler is in an open area (non-partitioned basement) in a conventional house, the air that leaks through the cracks around doors and windows will usually be adequate to provide air for combustion. e doors should not t tightly. Do not caulk the cracks around the win­dows.
NOTICE
Equipment located in buildings of tight construction shall be provided with air for combustion, ventilation, and dilution of ue gases using the methods described in example 2 (below) or shall be specially engineered. e authority having jurisdiction must approve specially engineered installations. A building of tight construction is dened as: 1) walls exposed to the outdoor atmo­sphere have a continous water vapor retarder with a rating of one perm or less with openings gasketed or sealed; and 2) openable windows and doors which meet the air leakage requirements of the International Energy Conservation Code, Section 502.1.4; and
3) caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, and at other openings.
EXAMPLE 2: Boiler Located in Conned Space
All Air from Inside the Building:1.
an additional room(s) of sucient volume so that the combined volume of all spaces meets the criteria for an unconned space. e total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each open­ing shall have a minimum free area of one square inch per 1,000 Btu per hour of the total input rating of all gas utilization equipment in the conned space, but not less that 100 square inches. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure. e minimum dimension of air openings shall not be less than 3 inches (see
Figure 1 - Boiler Located in Conned Space
e conned space shall be provided with two permanent openings communicating directly with
Figure 1
WARNING
Be sure to provide enough fresh air for combustion. Enough air insures proper combustion and assures that no hazard will develop due to lack of oxygen.
!
If you use a replace or a kitchen or bathroom exhaust fan, you should install an outside air intake. Otherwise exhaust fans will rob the boiler and water heater of com­bustion air.
).
7
COMBUSTION AND VENTILATION AIR
All Air from Outdoors:2.
e conned space shall communicate with the outdoors in accordance with methods A or B. e minimum dimension of air openings shall not be less than 3 in. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
Two permanent openings, one commencing within 12 inches of the top, and one commencing within 12 inches of the bottom, of A. the enclosure shall be provided. e openings shall communicate directly, or by the ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Where directly communicating with the outdoorsI. ducts
(see Figure 3)
, each opening shall have a minimum free area of 1 sq. in, per 4000 Btu per hour of total input rating of all
(see Figure 2)
or where communicating to the outdoors through vertical
equipment in the enclosure.
Figure 2 - Directly Communicating to the Outdoors
Figure 3 - Vertical Ducts Communicating to the Outdoors
FRESH AIR DUCT CAPACITIES (1 Square inch per 4,000 Btuh)
Fresh Air Duct Size
3” x 12” 144,000 108,000 36,000
8” x 8” 256,000 192,000 64,000
8” x 12” 384,000 288,000 96,000
8 ½” x 16” 512,000 384,000 128,000
see Figures - 2 and 3
100% Free Area
1/4” Wire Mesh
Table 3
75% Free Area Metal Louvers
8
25% Free Area Wood Louvers
COMBUSTION AND VENTILATION AIR
Where communicating with the outdoors through horizontal ducts (see II. of 1 area of sq. in. per 2000 Btu per hour of total rating of all equipment in the enclosure.
Figure 4 - Horizontal Ducts Communicating to the Outdoors
Figure 4
), each opening shall have a minimum free area
Table 4
FRESH AIR DUCT CAPACITIES (1 Square inch per 2,000 Btuh)
see Figure 3D
Fresh Air Duct Size
3” x 12” 72,000 54,000 18,000
8” x 8” 128,000 96,000 32,000
8” x 12” 192,000 144,000 48,000
8 ½” x 16” 256,000 192,000 64,000
100% Free Area
1/4” Wire Mesh
75% Free Area
Metal Louvers
25% Free Area Wood Louvers
One permanent opening commencing within 12 inches of the top of the enclosure shall be permitted where the equipment has B. clearance of at least 1 inch from the sides and back and 6 inches from the front of the appliance. e opening shall directly commu­nicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or to a crawl space or attic that freely communicate with the out doors, and shall have a minimum free area of:
1 sq. inch per 3000 Btu per hour of the total input of all equipment located in the enclosure (see chart below).I.
Not less than the sum of the areas of all vent connectors in the conned space.II.
Table 5
FRESH AIR DUCT CAPACITIES (1 Square inch per 3,000 Btuh)
Fresh Air Duct Size
100% Free Area
1/4” Wire Mesh
75% Free Area Metal Louvers
25% Free Area
Wood Louvers
3” x 12” 108,000 81,000 27,000
8” x 8” 192,000 144,000 48,000
8” x 12” 288,000 216,000 72,000
8 ½” x 16” 384,000 288,000 96,000
9
SYSTEM PIPING
Place boiler in the selected location (as near chimney as pos-
1.
sible.) Your boiler is shipped assembled. You need only to install the Relief Valve and a drain line to carry any water or steam to a drain.
Install Relief Valve into the ¾” pipe on the top of the boiler.
2. See Figure 5
the water or steam to a nearby drain. Do not connect directly to a drain but leave an air gap. No shuto of any description shall be placed between the safety relief valve and the boiler, or on discharge pipes between such safety valves and the atmosphere. Installation of the safety relief valve shall conform to the require­ments of the ANSI/ASME Boiler and Pressure Vessel Code, Sec­tion IV. e manufacturer is not responsible for any water dam­age. Install Drain Valve in lower le side of boiler as marked.
Connect Supply and Return Lines to boiler. e connections
3.
may require certain additional ttings and parts, see
and 6)
is boiler is equipped with 1¼” supply and return connections
4.
on the right side of the boiler.
. Use ¾” Pipe and an elbow (not furnished) to carry
(Figures 5
.
Follow the mixing valve manufacturer’s installation instructions.
e minimum design return water temperature to the boiler to
4.
prevent condensation in the boiler and venting is 120ºF. e minimum high limit setting is 140º F.
Figure 5 -Typical Hot Water Piping
Circulator
Cool Water Inlet
Relief Valve
Air Vent
Supply Main
Filtrol
Gauge
In connecting the cold water supply to the water inlet valve, make sure that a clean water supply is available. When the water supply is from a well or pump, a sand strainer should be installed at the pump.
A hot water boiler installed above radiation level must be equipped with a low water cuto device. A periodic inspection is necessary, as is ushing of oat type devices, per manufactures specic instruction. Refer to local codes for low water cut-o requirements.
For Use With Cooling Units
is boiler, when used in connection with chilled water systems,
1.
must be installed so that the chilled water is piped parallel with the heating boiler. Appropriate valves must be used to prevent the chilled water from entering the heating boiler
When this boiler is connected to heating coils located in air
2.
(Figure 6)
.
handling units where they may be exposed to refrigerated air circulation, the piping system shall be equipped with ow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
Low Design Water Temperature Systems (Below 140º)
If the boiler is to be used in a heating system where water tem-
3.
peratures below 140ºF are desired (e.g. radiant oor heating) a 3-way or 4-way mixing valve or suitable alternative is required to prevent low temperature return water from entering the boiler.
Sensor Wire
Return Line
Figure 6 - Chilled Water Piping
Valves A & B - Open For Heating; Closed For Cooling
Valves C & D -Closed For Heating; Open For Cooling
10
Loading...
+ 22 hidden pages