Dunkirk PVSB, PSB, PSB-3D, PSB-4D, PSB-5D Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
These instructions must be affixed on or adjacent to the boiler
Dml'v' ¢
MODEL PVSB
Continuous Pilot
Gas-Fired
Steam
These Gas-Fired Water Boilers are low pressure, sectional
cast iron boilers Designed Certified by C.S.A. (Canadian Standards Association) for use with Natural and Propane Gases. They are constructed and hydrostatically tested for a maximum working pressure of 50 psi (pounds per square inch) in accordance with AS.ME. (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code Section IV Standards for cast iron heating boilers.
MODEL PSB
Electronic
Intermittent
Ignition
Warning: Improper installation, adjustment, alteration, service or maintenance can cause injury or
property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier
Boiler Ratings and Capacities ...................... 2
Before You Start........................................ 3
Locating the Boiler .................................... 3
Fresh Air for Combustion ............................ 4
Installation - System Piping ......................... 5
Chimney and Vent Pipe Connection .............. 8
Vent Damper Operation .............................. 9
Gas Supply Piping .................................... 10
Electrical Wiring ....................................... 11
Controls and Accessories - What They Do ..... 17/
For Your Safety - Read Before Operating ....... 18
Operating Your Boiler ................................ 20
Checking and Adjusting ............................. 21
Cleaning Your Boiler ................................... 22
Maintaining Your Boiler .............................. 23
Service Hints ........................................... 24
Repair Parts ............................................. 25
LI
PRESSURE
GAUGE
r _T /_ "SWITCH I
....... SPILL
I I I_" l
WATER
I I L.E----I---- I [ ]L_\ /
LOW WATER
I _ CUT-OFF
- - -- ± _ -- PRORE
_ SW_TCH
L
GAS
;-.....A __ L,.E
'_'m RE_URE I
oo.TROL|
TRANSFORMER ------
_GAUGE
LOW WATER
_ $8600 CUT-OFF
VALVE
_u
LEFT SIDE FRONT RIGHT SIDE
24"
DESIGN CERTIFIED FOR
NATURAL
AND PROPANE GAS
GAS-FIRED STEAM BOILERS
BOILER MODEL NUMBER tNATURAL GAS tPROPANE GAS
INTERMITTENT STANDING NG OF AGA HEATING NET #£T I=B=R NET
IGNITION PILOT SECTIONS INPUT CAPACITY I=B=R RATING AGA HEATING I=B=R
WITH VENT DAMPER WITH VENT DAMPER *MBH *MBH RATING,MBH PJ_IATIONS0'FT. INPUT,MBH CAPACITY,MBH RATING
*MBH
PSB-3D PSB-4D PSB-5D PSB-6D PSB-7D PSB-8D PSB-9D
PVSB-3D PVSB-4D PVSB-5D PVSB-6D PVSB-7D
PVSB-8D PVSB-9D
3 4
5 6
7 8 9
75 62 47 196 70 58
112 91 68 283 !05 85
!50 122 92 383 !40 114 187 153 115 479 !75 143
225 183 137 571 210 !71 262 2!4 161 671 245 200 299 245 184 767 280 229
DIMENSIONS
_T I=B=R (Inches)
_TI_ _. F_ F_E "A"
PJW_TION D_METER WIDTH
44 !83 5 11% 64 267 6 14½
86 358 6 !7¾
107 446 7 21 !28 533 7 24¼ 150 625 7 27½ 172 717 7 30¾
* MBH = 1,000 Btuh. Btuh = British Thermal Unit Per Hour
**Add 5V_' to height for Vent Damper.
t For altitudes above 2,000 ft. ratingsshould be reduced at the rate of 4% for each 1,O00 ft above sea level.
Heating Capacity is based on DOE {Department of Energy} test procedure
The City of New YorkMEA Number 77-91-E. The Ratingsmarked "Net I=B=RRatings" indicate the amount
of equivalent direct cast iron radiation each boiler will take care of under normal conditions and thermostatic control.
The Net I=B=R Steam Ratings shown are based on an allowance of 1.333 in accordance with the factors shown
in the t=B=RCode as published by The Hydronics Institute.
Selection of boiler size should be based upon "Net I=B=R Rating" being equal to or greater than installed radiation in square feet. Consult manufacturer before selecting a boiler
for installations having unusual piping and picku!_\ requirements.
Specifications and dimensions are subject to change without notice.
Checktobesureyouhavetherightsizeboilerbeforestartingtheinstallation. _,eeratingandcapacitytableonpreviouspage.Alsobesurethenewboileris _orthetypeofgasyouareusing.Checktheratingplateontherightsideofthe
boiler.
Youmustseethattheboilerissuppliedwiththecorrecttypeofgas,freshair forcombustion,andasuitableelectricalsupply.Also,theboilermustbecon- nededtoasuitableventingsystemandanadequatepipingsystem.Finally,a
thermostat,properlylocated,isneededforcontroloftheheatingsystem.Ifyou haveanydoubtsastothevariousrequirements,checkwithlocalauthorities
andobtainprolessionathelpwhereneeded.Takethetimetocompleteallof
thestepsforSAFEandPROPERoperationoftheheatingsystem. Ifthisboilerisinstalledinabuildingunderconstruction,specialcaremustbe
takentoinsureacleancombustionairsupplyduringtheconstructionprocess. Airborneparticulatessuchasfromdrywalldustandfromfiberglassinsulation canclogtheburnerportsandcauseincompletecombustionandsooting,
Theseboilersaredesignedforuseinclosedheatingsystemswhereallofthe
steamisreturnedtotheboilerascondensateandtheamountofmake-upwater requiredisminimal.Theseboilersarenotdesignedfororintendedforusein opensystemsofprocessapplicationsusing100%make-upwater.Damageto theboilerresultingfromsuchuseshallnotbecoveredunderthewarranty.
Whererequiredbytheauthorityhavingjurisdiction,theinstallationmustcon- formtoAmericanSocietyofMechanicalEngineersSafetyCodeforControls andSafetyDevicesforAulomaticallyFiredBoilers,No.CSD-1.
Theinstallationmustconformtotherequirementsof theauthorityhaving jurisdictionor,intheabsenceofsuchrequirements,totheNationalFuelGas
Code,ANSIZ223.1-1atestrevision. Thefollowingstepsareallnecessaryforproperinstallationandsafeoperation
ofyourboiler.
1. LOCATINGTHEBOILER 5. GASSUPPLYPIPING
2. FRESHAIRFORCOMBUSTION 6. ELECTRICALWIRING
3, INSTALLATION- SYSTEMPIPING 7. CHECKING&ADJUSTING
4. CHIMNEY& VENTPIPECONNECTION
KEEP BOILER AREA CLEAN AND FREE FROM COMBUSTIBLE MATERIALS,
GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS
1.Selectlevellocationascentralizedwithpipingsystem,andasnearchim- neyaspossible.
2.Placecratedboilerat selectedlocation,removecratebypullingcrate sidesfromtopandbottomboards.Combustiblefloors:Whenboileristo
beinstalledonacombustiblefloor,aSpecialBasePlatemustbeused-
1.46-14-031(2-6Section)or146-14-032(7-9Section).Thisboilermust notbeinstalledoncarpeting.
3.I1thisboilerisequippedwithcastironburners,it isalsoequippedwith stainlesssteelwiretiestoholdlhebackendolthecastironburnersin
placeduringshipping.Inorderto removetheburnersforcleaningor inspection,thewiretiesmustbecutandremoved.Thewiretiesare
accessedthroughthecombustionair openingonthebacksideofthe
boileratthebottomoftherearjacketpanel,andmaybecutwithanywire
cuttingpliers.Iftheboilerisinstalledatitsminimumclearancesit may bedifficultto reachthewiretiesaftertheboilerisinstalled,andthewire
tiesshouldbeculnow.Thewireliesareonlyneededduringshipping, anddo notneedtobereplaced.Boilersequippedwilh stainless
steelburnersdonothavewiretiesandthisinformationdoes notapply.
4.Boileristobelevel.Metalshimsmaybeusedunderbaselegsforfinal leveling.
5.Equipmentshallbeinstalledina Iocalioninwhichthefacilitiesforven- tilationpermitsatisfactorycombustionofgas,properventing,andmain-
tenanceofambienttemperatureatsalelimitsundernormalconditionsof use,Equipmentshallbelocatedsoasnottointerferewithpropercircu- lationofair.Whennormalinfiltrationdoesnotprovidethenecessaryair,
outsideair shall be introduced(See Page4 - "FreshAir for Combustion").
6.Adviseownerto keepairpassagesfreeofobstructions.Ventilatingand combustionairmustenterboilerroomwithoutrestrictions.
7. Theboilershallbeinstalledsuchthattheautomaticgasignitionsystem componentsareprotectedfromwater(dripping,spraying,rain,etc.)dur- ingapplianceoperationandservice(condensatetrap,controlreplace- ment,etc.).
Top
Rear Control Side
Opposite Side Front
Flue/Vent Connectol Near Boiler Piping
BoilerVolume
BoilerSize (Cu.Ft.)
3 sect. 6.3 4 sect. 8,1 5 sect, 9.9 6 sect. 11,7 7 sect. 13.5 8 sect. 15.3 9 sect. 17.2
* FOBROOMWITHSINGLEBOILERONLY
Alcove,orRoomNotLarge
InComparisonWith6oiler
6" 6"
6" 6'
7" 6" 6" 6'
18" 18'
6" 6' 1' 1"
MinimumRoomVolumeRequiredToBe
LargeRoom(Cu.Ft.)*
100.4
129.4 !58.4 187,4
216,4
245,4
274,5
RoomLargeIn
ComparisonWithBoiler
THIS UNIT MUST BESET ON A CONCRETEOR OTHER
NON-COMBUSTIBLEMATERIALBASEOR FLOOR.
?4_oaA
Provisionfor combustionandventilationair mustbe in accordancewithSection5.3, Air for CombustionandVentilation,of I
the National Fuel Gas Code, ANSIZ223.1-1atest revision, or applicable provisions of the local building codes.
i
WARNING
Be sure to provide enough fresh air for combustion. Enough air insures proper combustion and assures that
no hazard will develop due to the lack of oxygen.
NOTE
if you use a fireplace or a kitchen or bathroom exhaust
fan, you should install an outside air intake. These
devices will rob the boiler and water heater of combus- tion air.
Youmustprovideforenoughfreshairtoassurepropercombustion.Thefire in theboilerusesoxygen.It musthavea continuoussupply.Theairin a housecontainsonlyenoughoxygentosupplytheburnerfor ashorttime. Outsideair mustenterthehouseto replacethatusedbytheburner.Study followingexamples1and2todetermineyourfreshairrequirements.
EXAMPLE1: BoilerLocatedin UnconfinedSpace Anunconfinedspaceis definedasa spacewhosevolumeisnotlessthan 50cubicfeetper1,000Btuperhourofthetotalinputratingofallappliances
installedinthatspace. Ifyourboilerisinanopenarea(unpartitionedbasement)in aconventional house,theairthatleaksthroughthecracksarounddoorsandwindowswin usuallybeadequatetoprovideairforcombustion.Thedoorsshouldnotfit tightly.Donotcaulkthecracksaroundthewindows. Equipmentlocatedinbuildingsofunusuallytightconstructionshallbepro- videdwithairforcombustion,ventilation,anddilutionoffluegasesusing themethodsdescribedinexample2Borshallbespeciallyengineered.The authorityhavingjurisdictionmustapprovespeciallyengineeredinstalla-
tions.
EXAMPLE2: BoilerLocatedin ConfinedSpace
A.All Air fromInsidethe Building:Theconfinedspaceshallbepro-
videdwithtwopermanentopeningscommunicatingdirectlywithanaddi-
tionalroom(s)of sufficientvolumeso thatthecombinedvolumeof al! spacesmeetsthecriteriaforanunconfinedspace.Thetotalinputofall gasutilizationequipmentinstalledinthecombinedspaceshallbecon- sideredin makingthisdetermination.Eachopeningshallhavea mini- mumfreeareaofonesquareinchper1,000Btuperhourofthetotalinput
ratingofal!gasutilizationequipmentintheconfinedspace,butnotless that100squareinches.Oneopeningshallbewithin12inchesofthetop
andonewithin12inchesofthebottomoftheenclosure.Theminimum dimensionofairopeningsshallnotbetessthan3 inches.
B.AllAirfromOutdoors:Theconfinedspaceshallcommunicatewiththe
outdoorsinaccordancewithmethods1or2.Theminimumdimensionof airopeningsshallnotbelessthan3 in.Whereductsareused,theyshall
beofthesamecross-sectionalareaasthefreeareaoftheopeningsto
whichtheyconnect.
1.Twopermanentopenings,onecommencingwithin12 inchesofthe top,andonecommencingwithin12inchesofthebottom,oftheenclo- sureshallbeprovided.Theopeningsshallcommunicatedirectly,orby theducts,withtheoutdoorsorspaces(crawlorattic)thatfreelycom-
municatewiththeoutdoors. a)Wheredirectlycommunicatingwiththeoutdoorsorwherecommu-
nicatingtotheoutdoorsthroughverticalducts,eachopeningshall haveaminimumfreeareaof1sq.in.per4000Btuperhouroftotal
inputratingof allequipmentintheenclosure.(SeeFigure3A.)
b)Wherecommunicatingwiththeoutdoorsthroughhorizontalducts,
eachopeningshallhaveaminimumfreeareaof 1sq.in. per2000 Btuperhouroftotalinputratingofallequipmentintheenclosure.
(SeeFigure3B.)
2.Onepermanentopeningcommencingwith12inchesof thetopofthe
enclosure,shallbepermittedwheretheequipmenthasclearanceofat
least1inchfromthesidesandbackand6inchesfromthefrontofthe
appliance.Theopeningshalldirectlycommunicatewiththeoutdoors
orshaltcommunicatethroughaverticalorhorizontalducttotheout- doorsorspaces(crawlorattic)thatfreelycommunicatewiththeout-
doors,andshallhaveaminimumfreeareaof: a)1sq.inchper3000Btuperhourofthetotalinputofallequipment
locatedintheenclosure(SeeFigure4),and
b)Notlessthanthesumoftheareasofallventconnectorsinthecon-
finedspace.
1
Figure 3A - FRESH AIR DUCT CAPACITIES (Btuh) I
FreshAir Duct Size
3"x 12" 8"x 8" 8"x 12"
= 1 tt
18Y2 x 16"
1 Square Inch per 4,000 Btuh
100% Free 75% Free
Area Area
1/4"Wire Metal Mesh Louvers
144,000 108,000
256,000 192,000 384,000 288,000
5t2,000 384,000
25% Free
Area
Wood Louvers
36,000 64,000
96,000
128,000
Figure 3B- FRESH AIR DUCT
1SquareInchper2,000Btuh
Fresh Air Duct Size
3" x 12"
8" x 8" 8" x 12" 81/2"x 16"
100% Free
Area
1/4"Wire Mesh
72,000
128,000
192,000
256,000
CAPACITIES (Btuh) I
75% Free Area
Metal Louvers
54,000
96,000 144,000 192,000
25%Free Area
Wood
Louvers
18,000 32,000 48,O0O
64,000
Figure 4 - FRESH AIR DUCT CAPACITIES (Btuh)
1Squaretnch per3,000 Btuh
100%Free 75% Free 25% Free
Area Area Area
FreshAir 1/4"Wire Metal Wood Duct Size Mesh Louvers Louvers
3"x !2" 108,000 81,000 27,000 8"x8" 192,000 144,000 48,000 8"x 12" 288,000 216,000 72,000 8½"x 16" 384,000 288,000 96,000
I
7,_8 4
The near boiler piping, that is the piping around the boiler,
must be considered as part of the boiler for proper water level control, and to produce dry steam. Correct near boiler piping is crucial to the proper operation of the boiler and
the heating system. Followthese recommendations carefully.
1. Place boiler in selected location, as near chimney as possible.
2. Install the pop safety valve, using the furnished 3/4" coupling, intothe 3/4" pipe nipple on the top of the boiler. Make a discharge pipe, using 3/4' pipe (not furnished} to carry the water or steam to a nearby drain. Do not connect the discharge pipe directly to a drain but leave an air gap. The downstream end of the discharge pipe must be unthreaded. No shutoff of any description shall
be placed between the pop safety valve and the boiler,
,
,
or on discharge pipes between such safety valves and the atmosphere. Installation of the pop safety valve shall
conform to the requirements ofthe ANSltASME Boiler and Pressure Vessel Code, Section IV The manufacturer is not
responsible for any water damage. This boiler is equipped with two 21/2"supply connections
and two 21/2"return connections, one each on both the left and right sides ofthe boiler. Unused connections must
be plugged with the 21/2_ plugs (furnished}. Recommended near boiler piping for gravity return
systems is shown in Figure 5. This configuration uses one supply and one return tapping. This setup can be used on any size boiler in this series. The supply and return
connections may be piped both into the same side (either
left or right} or one into each side ofthe boiler.
POPSAFETYVALVE
FLUE
PIPEFULLSIZESAME
AS BOILERTAPPING
(2ii2")_ MIN'
2 1/2" TEEWiTH PLUGFOR
24"
FEED
STEAMMAINS
REDUCINGELL POINTING DOWN
6" TO 10"
MAINVENT
1 1/2" MtN. PIPESiZE
NIPPLE
15' MIN,
28' MIN.- DIMENSIONA
I
-- HARTFORD LOOP
WET RETURN
GATEVALVE(NOTFURNISHED)
_"'--DRAiN VALVE(FURNISHED)
FORFLUSHINGSYSTEM
I t/2" FULLPORTBALLVALVE
FORBOTTOMSLOWDOWN ANDDRAININGBOILER & SYSTEM(NOT FURNISHED}
DRYRETURN MAIN
Z4OCBF
5. For installerschoosing to use both supply tappings, Figure 6A shows the correct way to pipe this system. Figure 6B showsthe wrong way to pipe a header with two risers.
Headers mustbefittedwithheaderoffsetsorswing joints,
or be equipped with expansion joints, so that thermal expansion and contraction of the header wilt notdamage
the boiler. Headers shall not be welded.
System takeoffs from the header must be between the
equalizer and the riser to the header nearest the equalizer. System takeoffs must never be between two
risers.
6. System takeoffs from the header must never be bul- lheaded. If the steam main goes in two directions, there
must betwo takeoffsfrom the header, one for each main.
,
8.
All boilers in gravity return systems must be equipped with a Hartford Loop as shown in Figures 5 and 6A.
When piping the vertical risers from the boiler to the
header, the bottom of the header must be a minimum of 24 inches above the water level line on the right side
ofthe boiler.
9. Steam riser(s) and header shall be 21/2"pipe size.
!0. Equalizerline shall be minimum 11/2"pipe size.
11. The near boiler piping shall include a 21/2"tee with a plug located on the supply line as shown for skimming
(i.e.surface blowdown).
PiPEFULL SIZESAME
AS BOILERTAPPING
(2
POPSAFE_ VALVE
CONNECTRISERTO BOILERWITH
2 I/2" ELBOWANDNIPPLE (NOTSHOWN)
FLUE
COLLAR
MIN,
....{"2112" W TN
PLUGFORS
24"
W_AT_RFEED
STEAMMAINS
REDUCINGELL POINTING DOWN
6" TO t0"
I1/2" MIN. PiPEStZE
15" MIN,
28" MIN - DIMENSION A
I i
NIPPLE
HARTFORDLOOP
RETURN
-GATEVALVE(NOTFURNISHED)
_-- DRAINVALVE(FURNISHED)
FORFLUSHINGSYSTEM
I ;/2" FULLPORTBALLVALVE
FORBOTTOMBLOWDOWN ANDDRAINING BOILER
& SYSTEM(NOT FURNISHED)
MAINVENT
ORYRETURN MAiN
_4106A 6
WRONG WAY
DONOTBULLHEAD,USE TWOTAKEOFFS
THIS PIPING CONFIGURATION
tS INCORRECTTO SHOW
COMMONMISTAKES
WAY
TAKEOFFSMUSTBEBETWEENRISER&EQUALIZER
WRONG WAY
SWINGJOINTSAREMISSING
WRONG WAY
MiSSiNGTEE FORSKIMMING
12. The near boiler piping shall include a 11h"ball valve in the return piping as shown for bottom blowdown and
draining.
13. Forgravity returnsystems,the bottom ofthe lowest steam carrying pipe, be it a dry return, or the end of the steam
main, must be at least 28" above the normal water level
line on the right side of the boiler. This is known as "Dimension A."
14. For pumped returnsystems,follow the condensate pump or boiler feed pump manufacturer's instructionsfor proper installation and hookup.
15. In connecting the cold water supply to the water inlet valve, make sure that a clean water supply is available. When the water supply is from a welt or pump, a sand strainer should be installed at the pump.
FOR USE WITH COOLING UNITS
A. This boiler, when used in connection with chilled water
, systems,mustbe installed sothat thechilled water ispiped
in parallel with the heating boiler. Appropriate valves must be used to prevent the chilled water from entering the heating boiler (Fig.7).
B When this boiler is connected to heating coils located
in air handling units where they may be exposed to
refrigerated air circulation, the piping system shall be equipped with flowcontrol valvesor otherautomaticmeans to prevent gravity circulation of the boiler water during the cooling cycle.
VALVES A & B
OPEN FOR HEATING; CLOSE FOR COOLING
VALVES C & O CLOSE FOR HEATING:
OPEN FOR COOLING
WATER
CHILLER
TO SYSTEM t
74_o7
For boilers for connection to gas vents or chimneys, vent installations shall be I
in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code,
I
ANSI Z223.1-1atest revision and applicable provisions of the local building codes.
CHECK YOUR CHIMNEY
This is a very important part of your heating system. It must
be clean, the right size, properly constructed and in GOOD CONDITION.Noboilercan function properly with a bad chim- ney.Inspect the chimney and verify that the construction and size of the chimney meets all applicable provisions of the National Fuel Gas Code and local building codes. Fig. 8 gives you an idea how a boiler might be vented to a chimney.
Note that the height (HT} is measured from the vent pipe
to the top.
CHIMNEY SIZING
Chimney sizing and all other aspects of the vent installation
must be in accordance with Part 7 of the National Fuel Gas
Code, ANSI Z223.1-latest revision, and applicable provisions
ofthe local building codes.
CONNECTING THE VENT DAMPER AND VENT CONNECTOR
Refer to Fig. 1 flue diagram for the size and location of the vent (flue opening). Use a 28 gauge (minimum) galvanized pipe to connect to the chimney.
IMPORTANT - The damper blade on the furnished vent damper has a 1/2square inch hole (approximately 3/4"diame-
ter). On boilers equipped with standing pilot, the hole must
be left open. On boilers equipped with intermittent ignition,
the hole should be plugged by using the plug supplied with
the ventdamper.
1. Positionfurnished vent damper on top offlue outletcollar. Fasten damper securely to flue outlet collar with sheet
metal screws, Make sure damper blade has clearance to operate inside ofdiverter.
As An Option
The damper maybe installed in any horizontal or vertical position, closer to the flue outlet collar preferred. Follow the diagrams - Figures 9, 10 and 11.
2. Install the vent damper to service only the single boiler for which it is intended. The damper position indicator shall be in avisible location following installation. Locate the damper so thatit is accessible for servicing.
3. Thedamper mustbeintheopen position whenappliance main burners are operating.
4. The boiler is equipped with a factory wired harness that
plugs into the vent damper. The thermostat must be connected to the black wires marked 24 volt thermostat
on the boiler.
5. Vent pipe must be same size as the flue outlet collar.
6. Slope pipe up from boiler to chimney not less than 1/4' per foot.
7. Run pipe as directly as possible with as few elbows as possible.
8. Do not connect tofireplace flue.
9. Endofvent pipe must be flush with insideface ofchimney flue. Usea sealed-in thimblefor the chimney connection.
10. Horizontal run should not be longer than 3/4the chimney height (HT}(Fig.8}.
The sectionsofventpipeshould be fastenedwith sheet metal
screws to make the piping rigid. Horizontal portions of the
vent system must be supported to prevent sagging. Use
stovepipe wires every 5' to support the pipe from above. If the vent pipe must go through a crawl space, double wall vent pipe should be used. Where vent pipe passes through a combustible wall or partition, use a ventilatedmetal thimble. The thimble should be 4 inches larger in diameter than the vent pipe.
MINIMUM VENT PIPE CLEARANCE
Wood and other combustible materials must not be closer than 6" from anysurfaceof single wall metal vent pipe. Listed
Type B vent pipe or other listed venting systems shall be
installed in accordance with their listing.
REMOVING EXISTING BOILER FROM COMMON VENTING SYSTEM
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large
for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining connectedto the commonventingsystemplaced inoperation, while the other appliances remaining connected to the common venting systemare not in operation.
1. Sealany unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction,leakage,corrosionand otherdeficiencies which
could cause an unsafecondition.
3. Insofaras is practical,close all building doors and windows and atl doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turnon clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
7_ 8
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance
will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutesofmain burner operation. Usetheflameofamatch
or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remain- ing connected to the common venting system properly
vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other
gas-burning appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the
National FuelGasCode,ANSIZ223.1-latestrevision. When resizing any portion of the common venting system, the
common venting system should be resized to approach the minimum size as determined using the appropriate
tables in Part 1! in the National Fuel Gas Code, ANSI Z223.1 -latestrevision.
For boilers for connection to gas vents or chimneys, vent installations shall be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1-1atest revision and applicable provisions of the local building codes.
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mech- anical draft systems operating under positive pressure.
ROOF RIDGE
3t4 HT MAXIMUM
J
MUST SLOPE UP
AT LEAST 1/4 INCH PER FOOT OF HORIZONTAL RUN
HORIZONTAL INSTALLATION
YES YES
TO FURNACE VENT TO CHIMNEY
OR BOILER DAMPER INSTALL VENT DAMPER WITH
ACTUATOR TO SIDES OF
VENT ONLY, DO NOT MOUNT
ABOVE OR BELOW VENT,
VERTICAL INSTALLATION
TO CHIMNEY
_ VENT
FLOW uDAMPE R
TO FURNACE N
OR BOILER U
ACTUATOR MAY BE
INSTALLED IN ANY POSITION
CAUTION: DO NOT INSTALL
THE VENT DAMPER
WITHIN 6 In. (152 ram) OF
COMBUSTIBLE MATERIAL.
INSTALL DAMPER
NOT
HERE
_'HtMNEY
BOILER WATER HEATER
TYPICAL INSTALLATION FOR VENT DAMPER
NOTE CAUTION AND FOOTNOTES
1. Install the vent damper to service only the singleappliance for which it is intended.Ifimproperly installed,a hazardous condition,
such as an explosion or carbon monoxidepoisoning,could result.
2. Do not installthevent damper on vent pipecurve.
3. Do not run wires near high temperature surfaces. Use stand-off brackets ifnecessary.
7_c090
Loading...
+ 19 hidden pages