Dunham-Bush HRSC - D, HRSC50, HRSC60, HRSC75, HRSC100 Operating & Maintenance Instructions

...
HRSC - D
Remote Condenser Packaged Chiller
Installation, Operation &
Maintenance Instructions
Table of Contents
Description Page No.
Introduction & Product Identification ................................................................................. 1
Inspection, Storage & Rigging............................................................................................. 2
Vibration Isolation .............................................................................................................. 2
Water Piping .............................................................................................................2, 3 & 4
Refrigerant Piping ............................................................................................................... 5
Electrical Connections ......................................................................................................... 5
Operation .....................................................................................................................5 & 6
Maintenance ....................................................................................................................... 6
Slide Valve Unloading System ............................................................................................. 7
Control Settings ............................................................................................................8 & 9
Sequence of Operation ...............................................................................................9 & 10
Optional Microcomputer Controller ..................................................................... 10 thru 16
Electrical Data (60 Hz) ...............................................................................................17 & 18
Typical Power Wiring ......................................................................................................... 19
Typical Control Wiring (Electro-Mechanical ....................................................................... 20
Typical Control Wiring (Optiomal Microcomputer Controller) ................................... 21 & 22
Typical Piping Schematic ................................................................................................... 23
Capacity Control ............................................................................................................... 24
Physical Data..................................................................................................................... 24
Evaporator Pressure Drop ................................................................................................. 25
Rigging (Sizes 50 thru 150) ............................................................................................... 26
Rigging (Sizes 180 thru 300) ............................................................................................. 27
Spring Vibration Isolation Data......................................................................................... 28
Rubber-in-Shear Vibration Isolation Data.......................................................................... 29
Troubleshooting Guide ..................................................................................................... 30
Start-up Check List ............................................................................................................ 31
FORM 5504
INTRODUCTION
This manual is designed to provide all the necessary in­formation for installation, operation and maintenance of the latest generation of the Dunham- Bush small screw compressor remote air-cooled packaged chillers.
Your Dunham-Bush package has been manufactured under a careful quality control system. If the package is installed,
PRODUCT IDENTIFICATION
050 060 075 100 110 120 135 150 180 210 225 240 255 270 300
operated and maintained with care and attention to the instructions contained herein, it will give many years of satisfactory service.
It is assumed the user of this manual and those who install, operate and maintain this equipment are expe­rienced and qualified air conditioning equipment per­sonnel.
VOLTAGE AK = 200 AN = 230 AR = 460 AU = 400 (50 Hz)
1
GENERAL
Packaged chillers are designed to cool water or other non­corrosive liquids. Water is circulated through the direct ex­pansion cooler where it is cooled to the desired temperature then circulated to cooling coils for air conditioning, or to other types of heat exchangers for process cooling.
Care should be taken to see that the equipment is properly installed and adjusted. An installer or operator should first become familiar with the information contained in this manual.
INSPECTION
When the equipment is delivered, it is important that the fol­lowing inspection be completed in the presence of the carrier’s representative.
LOCATION & CLEARANCE
Location of the equipment and the size of the equipment room require careful consideration of the following factors:
1. Route by which the chiller will be moved within the build ing to the equipment room. Make sure there are adequate clearance and floor strength through doors and passage ways.
2. Space required for final connections and for normal equip­ment maintenance. Sufficient clearance should be allowed, between unit and walls, to permit cleaning or repair of cooler tubes.
3. Effect of location on piping sizes and piping layout.
4. Location of service facilities; power supply, water and
approved drainage.
5. Motor starting restrictions of local power company.
1. Check all crates and cartons received against the Bill of Lading/Shipping Papers to be sure they agree.
2. Check the model number and the electrical characteristics on the nameplate to determine if they are correct.
3. Check for freight damage, shortages or other discrepan cies and note them on the delivery receipt before signing.
In the event that any damage is found, a damage claim should immediately be filed by the purchaser against the delivering carrier as all shipments are F.O.B. Factory.
STORAGE
The HRSC unit is designed for indoor use and should be stored indoors and/or protected from the elements.
RIGGING
General - Each unit has been carefully tested and crafted at
the factory where every precaution is taken to assure that the unit reaches you in perfect condition. It is very important that the riggers and movers should use the same care and precaution in moving the equipment into place. Make sure that chains, cables, or other moving equipment are placed so as to avoid damage to the unit or piping. The refrigerant piping must not be used as a ladder or as a hand hold. Do not attach a chain hoist sling to the piping or equipment. Move the unit in an upright position and let it down gently from trucks or rollers.
Another consideration which must be taken into account is that the unit should be mounted away from noise sensitive spaces and must have adequate support to avoid vibration and noise transmission into the building. Units should be mounted over corridors, utility areas, rest rooms or other auxiliary areas where sound levels are not an important fac­tor. Sound and structural consultants should be retained for recommendations on critical installations.
FOUNDATION
A flat concrete foundation or floor, which can support the weight of the equipment, must be provided. The unit must be level for proper operation and functioning of controls.
VIBRATION ISOLATION
Under certain critical conditions, it may be necessary to in­stall vibration isolators under the base of the Packaged Chiller.
Rubber-in-shear or spring vibration isolators are offered as optional items. When spring isolators are used, flexible con­nections must be installed in the water piping system and in the refrigerant lines of split systems. Note: These flexible con­nectors must be suitable for the fluid and pressures involved.
All piping which is external to the packaged chiller must be supported by spring mounted hangers and any piping which goes through the wall, ceiling or floor should be properly sheathed to prevent transmission of piping vibration to the structure.
Rigging and Moving - Any unit mounted on skids may be moved with a forklift, but care must be taken not to damage the unit with forks. The skids should not be removed until the unit is at its final location.
The HRSC units are to be rigged thru the holes in the base side rails. In all cases, spreader bars must be used between rigging lines to prevent damage. The unit must be lifted using All Rigging Points. Refer to Rigging Instructions on pages 29 & 30.
When spring isolators are used, electrical service to the unit must also be flexibly connected, by means of a 36" section of flexible conduit.
PIPING CONNECTIONS
Water Connections, Chilled Water Piping - After the unit
has been leveled, the external water piping may be made up. Be sure water piping is connected to the correct fittings. The water out connection is closest to the expansion valve (R-in) end. A chilled water flow switch must be installed in the external chilled water outlet piping.
2
It must be located in a horizontal section on the pipe where there are at least five (5) pipe diameters on both sides of the flow switch before any other connections. The flow switch paddle must be adjusted to the size pipe in which the paddle is installed. Consult the wiring diagram accompanying the unit for the electrical connections to interlock the flow switch with the control panel.
Water flow through the cooler must remain constant for proper chiller operation. Water pressure gauges are recom­mended to check the water pressure and flow rate in the system, before and after the cooler, and to determine if varia­tions occur in the cooler and system.
Method B. Install units the same as Method A, but add a third thermostat in the return water, as shown in Figure 1 E. This thermostat will be set to cycle off one of the units when the load drops below 40%. When this condition is reached, leaving mixed water temperature will rise, causing the re­turn water temperature to rise and the unit operating will load up. The “off” unit is sequenced to start again before full system load temperature is reached.
This system will not provide as stable an operation as Method A, but in normal air conditioning applications, this is not detrimental. The advantage of Method B is a better part load efficiency.
When installing pressure taps to measure the amount of pressure drop across the water side of the cooler, the taps should be located in the water piping a minimum of twenty­four (24) inches downstream from any connections (flange, elbow, etc.).
There are many piping and control systems which may be used to assure constant water flow through the cooler. A typical system is shown in Figure 1 A. It uses a three way motorized valve which operates in response to the discharge air temperature of the cooling coil.
Another system which is sometimes used consists of a two way modulating control valve, which also responds to the discharge air temperature of the cooling coil, used in con­junction with a spring loaded bypass regulating valve as shown in Figure 1B. The bypass valve must be set to assure the full flow of circulating chilled water when the modulat­ing valve is completely closed.
Other systems are noted in the ASHRAE Handbook and may serve equally well. Whatever system is selected, water flow must be constantly maintained through the chiller.
If the system is arranged for the dual purpose of cooling in the summer and heating in the winter,
THE COOLER MUST BE VALVED OFF DURING THE HEATING SEASON SO THAT HOT WATER WILL NOT PASS THROUGH THE COOLER. THIS MAY BE EITHER A MANUAL OR AUTOMATIC CHANGE-OVER OPERATION. There are also times, such as early spring and
late fall, when both heating and cooling are required. This should also be considered when designing heating and cool­ing systems. For various piping arrangements, consult the ASHRAE Handbook.
Water Connections - Multiple Packaged Chillers - Mul­tiple unit packaged chillers have been successfully applied to parallel and series piping systems for years. Special atten­tion, however, must be given to the particulars involved for each application or serious operational problems can result.
Series Chilled Water Flow Units - Units should be equally sized. The upstream unit will carry a larger load because it cools higher temperature water. The controllers are to sense leaving water temperatures (see Figure 1D). The number 1 unit controller should be set to start the unit at system de­sign leaving water temperature plus 50% of the minimum loading of the number 1 unit times unit number 1 design temperature differential [example: system design supply water temperature is 45°F, design temperature differential is 12°F; Unit #1 minimum loading is 15% and the design temperature difference is 6.5°F: (.5 x 12) + (.15 x 6.5) +45 = 52°F]. The number 1 unit controller should be set to cycle the unit off at system supply water temperature plus num­ber 2 unit design temperature differential times .9 [example: 45°F + (.9 x 5.5) = 50°F]. These settings will ensure enough load on the number 1 unit to prevent short cycling.
The above series flow controller set points are for the elec­tromechanical units. Contact the factory for microcomputer controlled units.
Water Quality - Coolers used in these packages are made of steel, copper and brass and are suitable for operation with well-maintained water systems. However, if the water used in cooler is corrosive, high in mineral content or entrained solids, the water can cause reduced performance and even failure of heat exchangers. Therefore, it may be necessary to obtain the services of a water treatment consultant and to provide and maintain water treatment. This is particularly important with glycol systems.
For information concerning the installation, operation and servicing of Dunham-Bush coolers, consult the latest revision of Form 8110.
The following are guidelines which should be followed for multiple unit application. NOTE: A constant chilled water flow rate is assumed to be maintained through all coolers.
Parallel Chilled Water Flow Units - Method A. Both units operate simultaneously, modulating with load variations. Each packaged chiller operating controller senses leaving water temperature using standard controls (see Figure 1 C). The set point of each controller will be set to maintain the desired unloading.
3
TYPICAL CHILLED WATER PIPING
TYPICAL MULTIPLE PACKAGED CHILLER WATER CONNECTIONS
PARALLEL FLOW
SERIES FLOW
PARALLEL FLOW
4
HRSC SYSTEM REFRIGERANT PIPING
• Horizontal lines must pitch 1/2" per 10 feet in the direction of refrigerant flow.
• Each refrigerant circuit must be piped independently.
• Lines must be sized according to latest edition of ASHRAE Handbook. Liquid lines should be sized based on 100°F liquid subcooling at the condenser.
• Maximum of 50 linear feet of refrigerant line length (contact factory if application requires longer runs).
• All installations require authorized Dunham-Bush start up.
• Factory is to review all field piping.
ELECTRICAL CONNECTIONS
All units are wired as completely as possible at the factory prior to delivery. The connections which must be made by the installer are to the main power source, control power source, remote condenser, and interlocking the satellite equipment. In connecting power wiring to the unit, the fol­lowing precautions should be taken:
¥ All field wiring is to be in accordance with the National Electrical Code and state and local codes.
¥ Due to transport & rigging all wiring is to be checked for damage and all terminal connections tested for tight­ness. Unit terminal blocks are to be connected with cop­per conductors only, sized per ampacity listed on unit data plate.
¥ The power supply should match the unit nameplate in volts, phase and Hertz. Voltage must be within ± 10% of name-
plate value and voltage imbalance between phases must not exceed 2%.
¥ For minimum circuit ampacity and maximum fuse size, see Unit Nameplate.
Refer to the unit nameplate data for the minimum circuit ampacity and maximum allowable dual element fuse size. The factory supplied field power block is sized to accept wires sized per NEC, 75C (3-in-conduit) up to 500MCM as required. When multiple wires per pole are required to stay at or below 500MCM, the power block supplied will have multiple wire per pole capability.
A separate 15 amp 11 5V field power supply is required to power the main control circuit (which includes the com­pressor sump heaters) unless the control transformer op­tion is included.
GENERAL
The unit should be started up only by a refrigeration techni­cian who is familiar with accepted operation practices for re­frigeration systems.
Use small screw unit start-up report, Form NS1157 to record all temperature, pressure, electrical readings and control set-
tings. A copy must be forwarded to Dunham- Bush, Inc., North American Service, Harrisonburg, Virginia before the warranty will be honored.
HRSC REMOTE AIR COOLED CHILLER START-UP
The unit is ready for start-up when the following proce­dures have been completed.
1. Water piping for the cooler is installed and tested. (If cleaning agents are used to clean system, be sure to select an agent that will not harm the chiller or other system components. Do not allow water to stagnate and corrode.
OPERATION - HRSC
2. Electrical connections are made and properly fused.
3. Unit has been leak tested, leaks corrected, and charge com­pleted.
Compressor crankcase heater(s) has been energized for a
4. minimum of 24 hours.
5. Calibrated refrigerant gages have been connected to the suction and discharge.
6. Turn on the chilled water pump, check direction of rotation and adjust the water flow through the cooler to the speci­fied flow rate. Bleed off all entrained air.
7. Manually energize the fan starters and check the fan rota­tion. Fans should pull air through the condenser coil and discharge vertically upwards.
8. Check all refrigerant valves to be sure they are open.
9. Proceed to System Start-up.
SYSTEM START UP
1. Request for Start-Up Representative - Start-up service is an option for these units and is requested when the unit is
5
ordered. If you purchased start-up service, then after the installation has been completed and checked, Form 9180 must be filled out and sent to the local Dunham- Bush representative who sold the unit. Following receipt of this signed form, a representative will be sent to the customer. The purchaser should have competent service and oper­ating personnel in attendance to assist in the work in­volved, and also to be trained in the operation and main­tenance of this unit.
The representative will inspect the installation to deter­mine whether it meets Dunham-Bush, Inc. requirements, perform the initial start-up of the installation, determine whether it is in satisfactory operating condition, and in­struct specified customer personnel in its operation and maintenance for the length of time specified in the pur­chase contract.
NOTE: Sump oil heaters should be energized a minimum of 24 hours and the oil sump temperature must be at a minimum of 100°F (38°C) prior to arrival of start-up rep­resentative. This will ensure that the oil is warm enough to vaporize any dissolved refrigerant and that the oil is within the normal operating temperature range.
3. Start compressor(s), check the gages and note if the pressures are within the prescribed limits.
4. Check the refrigerant sightglass at the TX Valve to be sure it is free of bubbles. If not, charge as required to clean sight glass.
5. Stage unit down until all compressors are off and check
the compressor crankcase sight glass for oil level. It should be 1/2 to 3/4 of the compressor sight glass. If not, see pro­cedure for adding oil on page 7.
6. Restart the compressor. After an hour of operation, the expansion valve superheat setting should be checked, it should be between 9°Fand 12°F at full load design condi­tions. In some instances, it will be necessary to lower the superheat setting to ensure proper distribution. Turn the TX valve adjustment stem clockwise to increase the super­heat setting and counterclockwise to decrease the setting. Be sure and allow ample time between each adjustment for the system to re-balance.
7. The electrical control settings should be checked and, if necessary, reset to those settings indicated on the wiring diagram. Safety controls are factory set and must be main­tained at settings indicated on the wiring diagram.
2. Before starting the compressor(s), check all three phases of supply voltage, of all legs of the motor. They must be within ± 10% of the nameplate voltage. Check to be sure compressor is not running backwards.
MAINTENANCE
COMPRESSOR
1. OIL LEVEL - The oil level in the compressor(s) should be
checked periodically, with the compressor stopped. Stage the unit down until all compressors are off and check the compressor crankcase sight glass for oil level. If the oil level is below one half (1/2) the sight glass, oil must be added.
2. A. RECOMMENDED OIL FOR R-22 MACHINES
Compressor Model Series SSC charged with DB Karlube #10 Oil.
Compressor Model Series SSCB - The compressor is factory charged with DB Karlube #21 Oil.
Do not mix above oils or attempt to operate the screw compressor with any other oil. It is suggested that a gallon or more of the appropriate oil be obtained and kept at the job site.
DB Karlube #10
DB Karlube #21
B. RECOMMENDED OIL FOR 407C MACHINES
DO NOT USE DB Karlube #10.
Compressor Models SSCA use DB Karlube #16 Oil.
Compressor Models SSCB use DB Karlube #21 Oil.
Contact factory for price.
The above-listed oils are synthetic lubricants of the Polyol Ester (POE) type. Due to the complex nature of the POE, great precaution must be taken to prevent any moisture from entering the system when servicing or adding oil. POE oil has a greater solvency for water. Water reacts chemi­cally with the ester to form acids and alcohols in a process called “hydrolysis”. POE molecules attract moisture. Mois­ture removal by evacuation is more difficult because the POE “holds water more tightly” than mineral oil. Moisture causes corrosion and copper plating at an unacceptable, high level. This reaction occurs where temperatures are the highest within the compressor.
To prevent moisture entering the system and contaminating the oil, extra care is necessary. Follow the enclosed proce­dure to add or remove oil from the system.
A - The compressor is factory
8. The temperatures of the chilled water both in and out, should be checked to insure the unit is operating within the desired temperatures.
The holding tank must be clean and free of any mois­ture. (Evacuate tank to 200 microns). The holding tank
can be a receiver or reclaiming tank of a size large enough for the total oil change and must be able to withstand the operating pressure of the system. When adding oil, it should be transferred from the container supplied to a holding tank and then evacuated through the vapor port down to 100 microns with no more than a 50 micron rise per hour. Do not allow the container to vent to the atmo­sphere as the transfer must be done through a closed loop. An oil pump will be required.
PROCEDURE FOR ADDING OIL
Manually close liquid line service valve. Lower return wa-
ter T-stat (4TAS) setting to start the compressor. Run com­pressor until unit shuts down on low pressure. Place the control circuit on/off switch in the off position. Locate the high pressure port adjacent to solenoid valve UL-3 (see drawing page 8) and remove the cap. Attach oil pump to holding tank high pressure port. Pump oil into this port until the oil level is 1/2 of the sight glass.
Replace the port cap, open the liquid line shut off valve and place the control circuit on/off switch in the on posi­tion. Set the operating T-stat to the normal operating temperature and reset the low pressure switch.
Oil can also be added, through the suction port of the compressor, while running the compressor.
3. COMPRESSOR REPAIRS (internal) - Contact factory or an authorized DB Service Agency if a compressor malfunc­tion is suspected.
4. COMPRESSOR REPAIRS (External) - Proper operation of unloaded start, loading, and unloading is controlled by solenoid valves UL-1, UL-2 and UL-3. Any of these three (3) solenoid valves may be repaired or replaced in the field, as required. Also the compressor crankcase heater may be replaced.
5. Standard oil acid test kit is not compatible with synthetic oil. See DB color chart for oil condition.
6
SLIDE VALVE
UNLOADING SYSTEM
The DB screw compressor capacity control system for infinite modulation consists of a slide valve and hydraulic piston/ cylinder operator internal to the compressor, plus three hy­draulic solenoid valves (UL-1, UL-2, & UL-3) piped externally.
the oil return (low pressure) line. The slide valve will move to the right (unloading) whenever UL-2 opens the oil supply (high pressure) line, since the force of the oil exceeds that of the discharge gas.
The slide valve forms a portion of the chamber wall in which the rotors turn; thus, its position with respect to the rotors determines the effective rotor length and thereby the per­cent of full load capacity.
Upon compressor start-up, UL-3 is opened (energized). This allows oil pressure to act upon the hydraulic piston, holding it in the fully unloaded position. After 30 seconds, during which time full oil flow is established to all bearing surfaces, UL-3 is closed (de-energized). At this point, temperature con­troller is free to open or close UL-1 and UL-2 in response to the supply water temperature.
The slide valve will move to the left (loading) by force of discharge pressure, whenever UL-1 opens to permit flow to
The temperature controller sends a series of electrical “pulses” to the appropriate solenoid to adjust to load conditions. The further the supply water temperature is from the controller set point, the longer is the duration of the pulses. The series of pulses will continue until the controller is satisfied. As the water temperature approaches the set point, the pulses be­come quite brief to prevent overshooting the set point.
This method of compressor unloading, in conjunction with supply water sensing, minimizes action/reaction lag time and overshoot resulting in an exceptionally precise and stable control of supply water temperature.
7
HRSC CONTROL SETTINGS
PRESSURE ACTUATED LEGEND FACTORY SETTING
High Pressure Control HP 1-4 Cut-Out 365 PSIG
(Manual Reset) Low Pressure Control LP 1-4 Cut-In 55 PSIG (Auto Reset) Cut-Out 35 PSIG Low Pressure Freeze Control LPF 1-4 Cut-Out 54 PSIG
PRESSURE ACTUATED LEGEND FACTORY SETTING
Low Chilled Water Temperature Thermostat (Manual Reset) T2 Cut-Out 37°F il Temperature Safety Control (Adjustable) OTS 1-4 Cut-Out 240°F Manual Reset W7100 Controller Settings T1 Control Point Set at 44°F
Note: For special units supplied with the NC25-4 microcomputer controller, refer to the “Operations Guide” Form
6874.
UNIT OPERATING LIMITATIONS
1. Maximum allowable cooler water pressure is 200 PSIG.
2. Maximum allowable operating water temperature to cooler is 85°F.
3. Minimum allowable water temperature from cooler is 42°F. If lower temperatures are required, a glycol solution must be used.
4. Unit should not be installed where it may be subjected to freezing temperatures. Provisions should be made to maintain the ambient air temperature at least 37°F, to avoid possible damage from freezing.
5. Line voltage should not vary more than the voltage tolerances listed for the unit. Refer to the Electrical Data table.
SAFETY CONTROLS
The unit is protected by the following safety controls.
1. High Pressure (HP)
2. Low Pressure (LP)
3. High Discharge Temperature (OS)
4. Compressor Solid State Module (CSTM)
5. Low Water Temperature (T2)
6. Phase Loss Monitor (PLM)
7. Control Circuit Breaker (CB1)
If any of these devices should open due to abnormal conditions, the compressor(s) automatically stop. All controls must be manually reset, except the phase loss monitor (PLM).
8
CONDENSER HEAD PRESSURE CONTROL
General
All units require some means to keep the condensing pres­sure high enough to insure adequate expansion valve feed to the cooler to prevent low side pressure trips, particularly during cold starts.
THE RECOMMENDED SPD-SD REMOTE AIR COOLED CON­DENSER
Standard Factory Installed Fan Cycling
This commonly applied scheme cycles condenser fans “on” and “off “ in response to head pressure to maintain the head pressure within an acceptable range for proper system op­eration. This method will permit starting and sustained run­ning to 30°F ambient.
FAN CYCLING CONTROL SETTINGS
CUT-IN/CUT-OUT)PSIG)
UNIT FCP1 FCP2 FCP3 FCP4
070 260/160 275/175 285/210 295/235
140
FCP1 & 2 FCP3 & 4 FCP5 & 6 FCP7 & 8
260/160 275/175 285/210 295/235
The minimum ambient shown above reflects the performance
of the condenser surface exposed to the operational fan(s) as well as that portion of the surface rejecting heat by natu­ral convection with related fans “off”. To further assist low ambient starts, all fans are held “off” until the head pressure reaches 260 psig. This alone cannot insure sustained opera­tion if the system load is not high enough to produce the minimal pressures required.
Operational Variable Speed Fan Control
This scheme utilizes fan cycling but also adds speed control to the lead fan of each refrigerant circuit. This feature not only serves to stabilize the head pressure between normal fan staging but also allows for virtually “no fan” operation down to 0°F ambient.
SPD-SD
HRSC100-150
SEQUENCE OF OPERATION (TYPICAL) MODELS
The following sequence of operation is typical for all Electro­mechanical HRSC models. Refer to the wiring diagram fur­nished with the unit for specific information.
Important Note!
With all the control circuit switches (SW1-SW3) in the “off” position and the staging thermostat (T1) to its highest tem­perature, there must be a 115 volts supplied to the compres­sor crankcase heaters (CCH1,2) for a minimum of 24 hours.
Preliminary Sequence
Close the main power disconnect switch. Check to see that the red indicating light on the phase loss monitor (PLM1) is lit. (Note: There will be two phase loss monitors, (PLM1) and (PLM2) on dual power block models). This light must be on to indicate proper phase rotation for the compressors. If the light is not on, disconnect the main power and reverse any two phase legs at the Main Incoming Power Terminal Block.
(Warning! DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS, CAUSING SEVERE DAMAGE, AND WILL VOID THE COMPRESSOR WARRANTY!).
The crankcase heater relay contacts are closed and are sup­plying power to the compressor crankcase heaters.
Control power goes through the control panel circuit breaker (CB1) and customer supplied control (if supplied).
Start up the chilled water pump. An auxiliary contact on the chilled water pump closes. The water flow is confirmed when the water flow switch completes the electrical circuit. Set the thermostat (T1) to the desired leaving water tempera­ture (e.g. 44°F.). Set point Adjustment is accomplished di­rectly on the control.
Place the three (3) control circuit switches (SW1-SW3) in the “On” position, thus energizing the balance of the control circuit. The system will be in the “Time-In” mode for five minutes before the first compressor will start.
The low temperature freezestat (T2) must also be satisfied to allow compressor operation.
Stage 1 Loading
Upon demand for cooling, the first step of the staging ther­mostat (T1) will close energizing relays (R1) and time delay (TD1). If all the safety controls and switches are closed, (see “Safety Controls” section for more detail) the control circuit for Compressor No. 1 will energize, allowing the compressor to start. Power is supplied to condenser fan interlock termi­nal CT19 and CT2 to enable the remote condenser fan cir­cuit. Relay (R5) will energize, closing the normally open set of contacts, which energizes the liquid line solenoid valve (SOL1). Another set of normally open contacts on (R5) pro­vide a series interlock with all the safety and operating con­trols, which will lockout the compressor if any safety trips during normal operation. (See Note 6 on Wiring Diagram). The last set of normally closed contacts on (R5) open and de­energizes (CCH1).
Time Delay (TD1) has two (2) sets of contacts: The first set of (TD1) normally closed contacts provides a 30 second jumper around the low pressure control (LP1) to prevent short cy­cling during start-up. The second set of (TD1) normally closed contacts powers the unloader solenoid (UL3-1) which holds the compressor in the full unload position for 30 seconds. After (TD1) times out (30 seconds), the contacts for the unloader solenoid (UL3-1) open and the normally open con­tacts close, which energizes the relay (R3). Upon energizing relay (R3) the normally open contacts of relay (R3) are closed, allowing the thermostat (T1) to energize the load (UL1-1) and the unload solenoid (UL2-1) upon demand.
9
Stage 2 Loading
Subsequent to the start of Compressor No.1 an approximate five minute time delay is incorporated into the microcom­puter. After this time delay, and a further call for cooling, the second step of the staging thermostat (T1) will close. This will energize relay (R2) and time delay (TD2). If all the safety controls and switches are closed, (see “Safety Control’ sec­tion for more details) the control circuit for compressor No.2 will energize, allowing the compressor to start. Power is sup­plied to condenser fan interlock terminal CT20 and CT2 to enable the remote condenser fan circuit. Relay (R6) will ener­gize, allowing the liquid line solenoid valve (SOL2) to ener­gize. Relay (R6) will energize the safety controls the same as compressor No.1 circuit.
SHUTDOWN SEQUENCE
Time delay (TD2) will provide a 30 second jumper around the low pressure control (LP2) and will energize the full un­load solenoid (UL3-2) for 30 seconds then energize relay (R4). Upon energizing relay (R6), the crankcase heater (CCH2) is de-energized and the normally open contacts of relay (R4) are closed, allowing the thermostat (T1) to energize the load solenoid (UL2-1) and the unload solenoid (UL2-2) upon de­mand. Relays (R1) and (R2) will interlock the water pump starters.
Stage 2 Shutdown
After both compressors have unloaded fully and the leaving water temperature is still lower than the set-point, the sec­ond step of the thermostat (T1) will open and de-energize relay (R2), providing an approximate five minute time delay, again integral with the microcomputer to the start of Com­pressor No.2. This will close the liquid line solenoid (SOL2) condenser fan control contactor and turn off Compressor No.2. Compressor No.1 will load and unload as required. Compressor No. 2 will not be able to restart for five minutes due to integral time delays.
STAR-DELTA STARTING
OPEN TRANSITION
Time delay relay (TD1) closes, energizing start contactor (S1) and the five second transition timer (TD9). Contactor (S1) closes, tying the center legs of the motor windings together into the “Star” (wye) configuration. (S1) N.O. auxiliary con­tacts close and energize motor starter (C1), starting the com­pressor motor. This motor starter is then “held in” by (C1) N.O. auxiliary contacts.
MICROCOMPUTER CONTROLLER
1. General Description
Your Dunham-Bush HRSC is controlled by an NC25 micro­computer system. The computer system is composed of a main microcomputer board, several types of input/output (I/ O) boards, and sensors. The I/O boards are connected to the microcomputer by ribbon cables. These hardware compo­nents are controlled by the software program in the micro­computer. The software determines the state of the output relays based on the input values.
There are two types of inputs to the computer system. A digital input indicates whether or not voltage is present at the input. This could be used to determine whether or not a contactor is pulled in, a water flow switch is made, or the status of other on/off devices. Another type of input is an analog input. An analog value is one that varies continu­ously, such as temperature, pressure, current, etc. An ana­log input must be converted to a digital value with an ana­log to digital (A/D) converter board before the computer can process the data.
The computer system outputs are relays that switch the 115 VAC control devices such as contactors and solenoids.
The software for the computer is stored in three different types of computer memory chips. The two EPROM chips
Stage 1 Shutdown
If the leaving water temperature is still lower than the set­point, the first step of the thermostat (T1) will open and de­energize relay (R1). This will close the liquid line solenoid (SOL1) condenser fan control contactor and turn off Com­pressor No.1 as long as it has run for approximately three minutes. Compressor No.1 will not be able to restart for five minutes.
After five seconds (TD9) N.O. contacts close, de-energizing “Star’ contactor (S1) and energizing run contactor C2 through (S1) N.O. auxiliary contacts. The compressor motor now runs in the “Delta” configuration.
There is an instant of time (the “open transition”) between the opening of (S1) power contacts and the closing of (C2) power contacts, in which power across the motor windings is interrupted.
(Electrically Programmable Read Only Memory) store gen­eral operating procedures (algorithms) and are the same for all packages. The EAROM chip (Electrically Alterable Read Only Memory) stores the program that defines the logic for a particular unit. This software is called the data base. Both of these chips retain their content when power is removed. The third type of memory is battery backed RAM (Random Ac­cess Memory) and is used for temporary storage.
Information can be retrieved from the NC25 and displayed on a video display terminal. The RS232 communications port is used. Refer to FORM 6372 for more information.
2. Microcomputer Hardware Precautions
The following precautions must be taken while work­ing with the microcomputer system.
2.1 Do
2.2 Cover the computer components completely when
2.3 Strip wires away from microcomputer to prevent
not lay the solder side of a computer board on a metallic surface. This may damage the battery on the board.
drilling sheet metal near the computer.
strands from falling on components.
10
2.4. Do not allow the component boards to get wet, (direct contact with water or condensation).
2.5 Disconnect power to the NC25 when plugging in or unplugging a ribbon cable connector.
2.6 Disconnect power to the NC25 when changing a chip on the board. Check to make sure that pin 1 of chip is in upper-left corner and that the chip is inserted fully before reconnecting power.
2.7 Route ribbon cable and sensor wires away from control and power wires.
2.8 Handle boards with care.
3. Operation of LCD Display NC25-4
The following instructions are for operation of the NC25- 4 microcomputer with 2 x 40 character LCD display.
To Display data from the menu
3.1
1. Press the MENU key.
2. Use the up or down arrow keys to select the type of information desired. The main menu items are: DATE & TIME SET
ALARMS DIGITAL SENSORS CONTROL POINTS SETPOINTS A & B AUTHORIZATION ANALOG SENSORS
3. Press the ENTER key.
4. Use the up or down arrow keys to select the desired data. For control points, additional data can be viewed with the right and left arrow keys. Press the right arrow key to sequence through the following screens:
A. LAST ON/OFF - RUN T/Y - CYC
TIME TIME TIME TIME COUNT
LAST ON/OFF gives the time of day that the control last turned on or off. The last on time is not updated if a screw compressor is started manually.
RUN T/Y gives the accumulated time that the control point has been on today (T) since mid­night and the accumulated run time during yesterdays(Y) twenty-four hour period.
TOTAL CYCLES gives the number of cycles since a memory clear was performed. This records up to 65,000 cycles.
C. -- CURRENT -- -- TARGET —
VALUE VALUE VALUE VALUE
The values under CURRENT and TARGET give different operating analog input values and setpoints for different types of control points. Screw compressor control points give current and target leaving water temperature and percent full load capacity. Fan type control points give the current analog value and target turn on and turn off setpoints.
NOTE: When displaying analog sensors, the PAGE MODE key can be pressed to display two new analog inputs after each arrow key is pressed. Press PAGE MODE again to return to displaying one new analog input.
To Reset All Control Points to Computer Control
3.2
1. Press the RESET key. The display will show RESET
ALL CPs to COM MODE? N Y
2. Press the right arrow key to select Y.
3. Press the ENTER key. The reset will not be accepted if a lockout control point is active. Resolve the problem and reset again.
3.3
To Display Alarms
.
1. Press the MENU key.
2. Use the up or down arrow to select ALARMS.
3. Press ENTER. The day, time, and alarm code is
displayed.
4. Alarm 1 is the most recent alarm.
5. Press the down arrow to view previous alarms.
6. Check the data label to obtain the name of the alarm. If the data label is not available, display the digital input that corresponds to the alarm number. If the digital input name is SPARE, then display the control point that corresponds to the alarm number. EX: If alarm code 29 has occurred, then display digital input 29 or control point 29 to determine the failure.
CYC gives the number of times that the control point cycled off since midnight. It a feedback digital input is associated with a control point (EX: compressor) the digital input cycles are recorded.
B. TOTAL RUN TIME = COUNT
TOTAL CYCLES = COUNT
TOTAL RUN TIME gives the number of hours the control point has been on since memory clear was performed. This records up to 65,000 hours.
11
To Become Authorized
3.4
1. Select AUTHORIZATION on the main menu. Press ENTER.
2. The current status will show VIEW, press the authorization code (64) on the number keys.
3. Press ENTER. The current status will change to PROG (program) if accepted. If no keys are pressed for five minutes, or if the Authoriza­tion screen is re-displayed, the authorization to change setpoints is removed and the above procedure must be repeated to log in.
To Alter Setpoint Data
3.5
1. You must be authorized and in the PROG
mode. See section 3.4.
2. Select SETPOINTS A & B on the main menu.
Press ENTER.
3. Use the up or down arrow keys to select the setpoint to be changed. Press ENTER. A cursor will flash over the setpoint A value.
4. a) If you want to change setpoint A, press
in the desired new value and press ENTER. If the new value is within limits, it will be stored in memory. The cursor will then move to setpoint B.
b) If you do not want to change setpoint
A, press ENTER.
5. Repeat Step 4 for Setpoint B.
To Calibrate Temperature and Pressure Sensors
3.6 NOTE: Pressure calibration should only be
done by a qualified refrigeration technician. Calibrate amps with potentiometer on filter board.
NOTE: For units with SI display option, the
critical temperature and pressure calibration values are stored in the setpoints corresonding to the sensor names or numbers.
1. You must be authorized and in the PROG
mode. See Section 3.4.
2. Display the analog sensor to be calibrated on
the top line of the display.
3. Press ENTER to show ZERO CALIBRATION
value.
4. Use an accurate gauge to measure the
analog value when it is stable and near design conditions.
5. Determine the revised zero calibration
required as follows: Meter Reading - Al Display + Zero Calibration = New Zero Calibration. The new zero calibration must be rounded to the nearest whole number.
6. Press ENTER to place the cursor on the zero
calibration value.
7. Enter the new value from Step 5. Negative
values are entered by pressing LOWER FUNCTION +/- before the number.
8. Press ENTER to store the revised zero calibra-
tion.
For example, if a suction pressure gauge shows 58 psig and the computer displays
60.3 psig with a zero calibration of -1, then new calibration would be 58 - 60.3 + (-1) =
-3.3 (-3). So the zero calibration should be changed to -3.
3.7
To Set Date and Time 1 . You must be authorized. See Section 3.4.
2. Select DATE & TIME SET on the main menu.
Press ENTER to display current date and time.
3. Press ENTER key to move cursor to each date/
time item.
4. As each item flashes, use the number keys to
enterrevised data if necessary. The day of week, SUNday through SATurday, is selected by number keys 1 through 7, respectively.
5. Press ENTER to continue. The last ENTER will
store the new date and time.
12
WARNING: Setting the clock will cause a system reset. The entire unit will shut down and start over again. If the change was started inadvertently, press MENU key before completing the change.
3.8
To Display Data without Accessing Menu
1. Press LOWER FUNCTION.
2. Press function desired (blue sub-script)
3. Press item number to be displayed.
4. Press ENTER. EX- To display analog input #5, press LOWER FUNCTION, ANALOG INPUT, 5, ENTER.
3.9
To Revise Unit Schedule of Operation (Optional) If a seven day time schedule of unit operation is desired, the internal real time clock of the microcomputer can be used. When the SCHEDULE control point is ON, the unit is allowed to operate. The following procedure is used to modify the operating schedule.
1. Perform the authorization procedure (See 3.4).
2. Press MENU key.
3. Use Up and Down to select CONTROL POINTS.
4. Press ENTER.
5. Use Up and Down to select SCHEDULE control point.
6. Use --> to display the first schedule. The standard display screen would show: CP 17 SCHEDULE GRP:1 SCH:1 0000 2400 DAYS: *** ALL DAYS *** This indicates that control point 17 named SCHEDULE is controlled by schedule group (GRP) #1. The first schedule (SCH:1) turns on at 0000 hours and off at 2400 hours (military time) every day of the week. Thus it is on all the time.
7. To change this schedule, press ENTER. The cursor will flash over the turn-on time. To move to the next schedule, press the right arrow key.
8. Use the number keys (0-9) to enter the revised turn-on time using military format.
9. Press ENTER. The cursor will move over to the turn-off time.
10. Use the number keys to enter the turn-off time in military format.
11. Press ENTER. The cursor will move to DAYS during which this schedule is active.
12. To change the days for this schedule, press one or more of the following number keys: 0 ­Clear all current days; 1 - Sunday(S); 2 ­Monday(M); 3 - Tuesday(T); 4 - Wednesday(W); 5 - Thursday(R); 6 - Friday(F); 7 - Saturday(A);
8 - *** ALL DAYS’**.
13. Press ENTER. The revised schedule number is now stored.
14. To add another schedule, press the right arrow key and repeat steps 7-13.
15. To delete a schedule, clear all of the days by pressing 0 at Step 12.
The schedule group turns on when any of the indi­vidual schedules turns on. The turn-on time does
not have to be earlier than the turn off time. Schedules turn on by time and day, but turn off by time alone. For example, a schedule from 1900 to 0700 Saturdays would turn on at 7:00 PM Saturday (time and day) and turn off at 7:00 AM Sunday (time only).
Example: If a unit is to operate at all times except between the hours of 1:00 AM and 6:00 AM, the following schedule would be entered:
CP 17 SCHEDULE GRP:1 SCH:1 0600 0100 DAYS: *** ALL DAYS ***
Another example: A typical building may require cooling from 6:00 AM to 7:00 PM Monday - Friday and from 7:00 AM - 3:00 PM on Saturdays. The schedules would be entered as follows:
CP 17 SCHEDULE GRP:1 SCH:1 0600 1900 DAYS: MTWRF CP 17 SCHEDULE GRP:1 SCH:2 0700 1500 DAYS: A
4. HRSC Package Control
In order to start a unit, the following conditions must be met:
-- chilled water pump running
-- chilled water flow switch made
-- customer control contact closed
-- control switch and compressor switch on
-- main unit power on
-- all safety conditions satisfied
-- reset pressed on microcomputer keypad
-- the compressor has not started within the last 15 minutes
-- leaving chilled water temperature 20°F or more above set point
The NC25 computer system performs the following functions on small screw compressor packages:
1. Capacity control of compressors
2. Staging of compressors
3. Compressor current limiting
4. Ramp control
5. Manual lead/lag
6. Compressor start delay
7. Power loss reset
8. Anti-recycle timing
9. Low pressure safety
10. High pressure safety
11. Freeze safety
12. High Oil Temp Safety
13. Alarm output
14. Fan control
15. Customer control interlock
16. Hot Gas Bypass option control
17. Compressor power control (No-stop alarm)
18. Sensor alarm shutdown
19. External shutdown indication (No-run alarm)
20. Fast Unload Solenoid Control (HRSC 50 thru 225)
21. Low suction / discharge differential pressure alarm
22. High Motor temperature safety
23. Low chiller flow alarm
A description of each of the functions follows:
4.1.
Capacity Control of Screw Compressors The capacity of a compressor can be controlled manually or automatically.
The status of a compressor can be observed by displaying the compressor control point (1/CP, 4/CP, 7/CP or 10/CP). One of the following messages will be displayed where # is 1, 4, 7 or 10 for compres­sors 1, 2, 3 or 4:
CP# COMP LOAD COM Computer load CP# COMP CURRENT STATUS: LOAD Manual load CP# COMP HOLD COM Computer hold CP# COMP CURRENT STATUS: HOLD Manual hold CP# COMP UNLD COM Computer
CP# COMP CURRENT STATUS: UNLD Manual unload CP# COMP OFF COM Off on a normal
CP# COMP COFF COM Off on timer
CP# COMP LOFF MAN Manual off or
Automatic Control
4.1.1 The computer calculates the operating per­cent capacity of a compressor by measuring discharge pressure and amps. This operating percent capacity is then compared to a tar­get percent capacity. If the operating capacity is outside of a
+ 3% deadband, the load or unload solenoids are pulsed to match the operating and target percent capacities. Since all compressors have the same target, their percent capacities are balanced.
The target percent capacity is given a fixed value when a compressor starts or stops. This value is then increased or decreased based on how far the leaving water tem­perature (TLW) is from setpoint and also on how fast the TLW is approaching setpoint. The target percent capacity will not change if the temperature is within a temperature deadband around the setpoint.
Some packages may have logic that prevents loading if the leaving water temperature is falling (negative derivative) at a certain rate.
The desired leaving water temperature is typically stored in setpoint 1 A.
Calibrations of Amps Calculation at Full Load The amps calculation is calibrated at the factory and does not normally need to be altered. If a compressor is replaced or improper operation is observed, the amps values can be calibrated as follows:
1. Check calibration of discharge pressure,
and amps. NOTE: Calibrate amps with
13
potentiometer on filter board.
unload
control shutdown
(clock off)
safety shutdown
2. Manually load the compressor(s) to full load. This can be done one compressor at a time if necessary.
3. Locate the amps and full load amps (FLA) analog locations from the analog input menu for the compressor being calibrated.
4. When the compressor(s) are at full load and conditions are close to design, record the amps and FLA analog values.
5. If the values do not match within 2-3 amps, do the following calculation: AMPS - FLA
6. Locate the amps calculation A setpoint for the compressor from the setpoint menu. The setpoint is labeled FLA # CON, where is 1 through 4 for each compressor number. 7.
7. Add the value obtained in step 5 to the amps calculation A setpoint value from step 6.
8. Change the amps calculation setpoint to the new value.
9. Verify that amps and FLA now match closely.
10. Manually unload the compressor all the way.
11. Locate the percent full load capacity (%FLCP) for the compressor from the analog input menu and record the value.
12. If the value is 25% ±3%, no change is re­quired. If the value is less than 22% or greater than 28%, locate the %FLA # CON setpoint B. If the setpoint is equal to 25.0, change it to the value observed in step 11 and proceed to step 13. If the setpoint is not equal to 25.0, change it to 25.0 and repeat steps 11 and 12.
13. Repeat this procedure for each compressor.
4.1.2
Manual Control Screw compresors can be controlled manually with the key pad. A compressor can be turned on, off, or placed in computer control. When a compressor is controlled manually, it can be com­manded to load, hold, or unload. If current limit is active, it will not accept a load command.
To place a compressor in manual control, which turns it on, use the following proce­dure:
1 . Log in for authorization.
2. Address desired compressor (1, 4, 7, or 10 control point).
3. Press ENTER to modify status.
4. Use up or down arrow keys to select ON MAN.
5. Press ENTER. The compressor will start or continue to run in hold state.
6. Press 0 to return to computer control, 1 to hold, 2 to load, 3 to unload. Note: Compressors will not load past amp limits.
7. Use menu key or arrows to access other data.
If a safety condition is exceeded while oper­ating manually, the compressor will shutdown. To put all compressors back into computer control from a locked off state, press RESET.
14
CAUTION: Anti-recycle timer is bypassed by manual control. DO NOT start a compressor more
than once every 15 minutes. NOTE: All compressors will revert back to auto-
matic control if the computer is not given a load, unload or hold command at least once every 15 minutes. A command can be repeated to meet the 15 minute requirement for manual control.
4.2.
Staging of Compressors The staging of compressors is based on leaving water temperature and the capacity calculations mentioned in section 4.1. When the percent capacity target gets up to full load and tempera­ture is above deadband, a time delay of one or two minutes is initiated before starting the next compressor. When the capacity target falls below a stored setpoint and temperature is below the deadband, a compressor is turned off.
The percent capacity values that the computer is calculating can be displayed by addressing the analog input menu.
Compressor Current Limiting
4.3. The amp limit B setpoint on the unit control data sheet is the amp value at which the compressor will be prevented from loading. The amp limit A setpoint is the amp value at which the compres­sor will be given an unload command until the current drops below the A setpoint.
If the values are changed, the difference be­tween the hold and unload points should not be decreased below 10% of compressor RLA so that oscillations will not occur.
4.4.
Ramp Control Ramp control can be implemented with the microcomputer. Whenever the unit starts with leaving water temperature greater than 5°F above setpoint, a ramp up is generated. The ramp start B setpoint specifies the percent capacity target at which the ramp begins on the first compressor. This can be set between 25 & 100 percent. The ramp rate A setpoint specifies the maximum amount that can be added to the target at each compressor control interval. Thus a ramp rate of 0.1 produces the longest ramp rate. Table 1 gives sample ramp times for various ramp rate setpoints and start points for a two-compressor machine.
TABLE 1 Sample Ramp Times (Minutes) For a Two­Compressor Unit with a 2 Second Compressor Control Interval
Ramp 25% 50% 75% Rate Start Pt. Start Pt. Start Pt. Setpoint Setpoint Setpoint Setpoint
.1 38 50 42 .2 29 25 21 .3 19 17 14 .4 15 12 10
A formula for calculating ramp time in minutes is T = [(# compressors x 100) - start pt.] x Compressor Control Interval/(Ramp rate x 60)]
The compressor control interval can be determined by timing the frequency of load/unload pulses given to a compressor. It is typically 2 seconds.
4.5.
Manual Lead/Lag Selection The lead compressor can be selected by the lead B setpoint. The number stored in this setpoint should be one less than the desired compressor number. So a 0.0 in the setpoint specifies com­pressor 1 as the lead, a 1.0 puts compressor 2 as lead, etc. It is preferable to have compressor 1 as the lead. If a compressor is locked off, the next compressor will automatically take its place in the lead/lag sequence.
Compressor Start Delay
4.6. A compressor start delay of one or two minutes is incorporated into the computer to prevent two compressors from starting at the same time and insure that the system load requires another com­pressor. The compressor control point will display COFF (“clock off”) during this timing.
4.7
Power Loss Reset This function allows the customer the option of automatic or manual reset of the computer after a power loss to the computer. The power loss could be from the UVR or control switch. For au­tomatic reset, a 0.0 is stored in the power in the power loss B setpoint. For manual reset after power failure, a 1.0 is stored in the set- point. A power loss alarm is also recorded by the computer.
Anti-Recycle Timing
4.8. At the start of a compressor, a 15 minute timer is initiated during which the compressor cannot start. If cooling is called for during this time, a COFF is displayed in the compressor control point.
CAUTION: This timer is bypassed by manual control of compressors. DO NOT manually start a compressor more than once every 15 minutes.
4.9. Low
Pressure Safety When the evaporator pressure of a given refrig­eration circuit drops below the low pressure B setpoint, a time delay is initiated. If the pressure stays below the setpoint during the time period, all compressors on the circuit will be locked off and the low pressure alarm will be recorded by the computer.
For an air-cooled unit, the time delay is two min­utes when ambient temperature is above 40°F. If ambient temperature drops below 40°F, the delay on compressor start up is extended to 4 minutes. After start-up, the low pressure delay is 2 min­utes.
4.10
High Pressure Safety
If the condensing pressure of a refrigeration circuit exceeds the high pressure A setpoint, all compres-
15
sors on the circuit are locked off. The high pressure alarm will be recorded by the computer. Typical setpoint value is 360 psig.
Freeze Safety
4.11 If the leaving water temperature of a chiller drops
below the freeze B setpoint, all of the compressors will be locked off. The freeze alarm will be recorded by the computer. Press RESET to clear the lockout.
4.12
High Oil Temp Safety If the oil temperature switch of a compressor opens,
the oil temperature digital input turns ON. If the compressor is operating, the compressor will be locked off. The high oil temperature alarm will be recorded by the computer and RESET must be pressed after the problem is resolved.
4.13
Alarm Output The alarm control point closes the digital output
relay on all safety alarms. This relay is used to turn an alarm light on. After the problem is resolved, press RESET to reset the system and turn the alarm output off.
4.14
Fan Control The fans are controlled by the microcomputer out put relays. The computer switches fans on or off basel on the discharge pressure and the fan pressure setpoints. The high (A) setpoints are where the fans turn on and the low (B) setpoints
are where the fans turn off.
Chilled Water Reset (Optional) and Customer Con-
4.15
trol Interlock
If an analog input is available, the chilled water tem-
perature setpoint can be raised automatically by a 0-5 VDC signal provided by an external controller. The reset signal must be between 0VDC and 5VDC, with 0VDC being no reset and 5VDC being maxi­mum reset. The maximum temperature reset (in­crease) desired must be stored in CWR max B setpoint. For example, to raise the chilled water setpoint from 44°F to 50°F (6.0°F) with a 5VDC in­put, a 6.0 is stored in CWR max setpoint.
CAUTION: The voltage input must never exceed
5.0VDC.
Control contacts from an external controller are used to enable or disable operation of compres­sors. The wiring diagram specifies the terminals to which the contacts must be wired. To enable the compressors, the contacts must be closed. To place the unit in stand-by mode, open the control contact.
Note: This control must be used for automatic control of the package. Do not use the flow switch to control the package.
4.16 Hot Gas Bypass Control (option) When hot gas bypass has been supplied with the package, an output from the computer controls the solenoid. The solenoid is turned on if only one compressor is operating and the target percent capacity of the compressor drops below the hot gas bypass B setpoint. If the target percent capacity then climbs above the hot gas bypass A setpoint, the solenoid is turned off. Typical setpoints are 45% for the B setpoint and 80% for the A setpoint.
4.17
Compressor Power Control (No-Stop Alarm) and Unit Schedule
The control power/schedule feeds power to the compressor safety and control circuit and closes the chilled water pump contacts. (See Field Control Wiring). After power-up, the relay is held open for 15 seconds to allow for reset of the high temperature safety switch. The relay is then closed to allow normal compressor control if the unit schedule is calling for unit operation.
The computer will open this relay if it detects that a compressor auxiliary contact digital input stays ON for 15 seconds when the computer is commanding the compressor to be off. A No­Stop alarm would then be stored in the alarm history. This would indicate that either a hard­ware problem is forcing the compressor to run when it should not or that the digital input is staying on when the compressor is actually off. When the problem is resolved, press the RESET button to allow the machine to start.
During normal operation, this output turns ON/ OFF based on the unit schedule of operation (see Section 3.9).
Sensor Alarm Shutdown
4.18 If the computer measures an analog sensor value that is outside of a given boundary, the associated compressors are shutdown. The computer then stores the alarm code corres­ponding to the sensor alarm. The boundary values are as follows:
Low High
1. Water temp sensor - 190°F
2. Air temp. sensor 25°F 180°F
3. Suction pressure -20 psig See below
4. Discharge pressure 5 psig -
The high setpoint for the suction pressure sensor will be triggered if the leaving water temperature is less than 60°F and suction pressure is greater than 150 psig.
not operating if the associated digital input from the compressor contactor does not indicate that the contactor is pulled in (digital input stays OFF), or if the amps of the com­pressor are less than about 12 amps. If a faulty No-run alarm occurs, monitor the digital input and amps to see which is producing the fault.
4.20
Fast Unload Solenoid Control
When a compressor starts, it’s fast unload solenoid is energized for 30 seconds to ensure that the compressor unloads fully. The load and unload, solenoids are de-energized during this time delay. After the time delay, normal control of the load/unload solenoids is re­stored.
4.21
Low Suction/Discharge Differential Alarm If the difference between suction and dis charge pressure is less than minimum differen­tial pressure for 3 minutes while a compressor is operating, all the compressors on the affected refrigerant circuit are locked off. A low differential pressure alarm will be recorded by the computer and the alarm output will be turned on. Press RESET to clear the lockout.
4.22
High Motor Temperature Safety If the high motor temperature switch of a compressor opens, the motor temperature digital input turns ON. If the compressor is operating, the ‘compressor will be locked off. The high motor temperature alarm will be recorded by the computer and RESET must be pressed after the problem is resolved.
Low Chiller Flow Alarm
4.23 A low flow alarm will be generated if a com­pressor control point is ON and the flow switch digital input is OFF. All compressors will be locked off and the alarm light turned on. After resolving the problem, press RESET.
High Discharge Pressure Unload
4.24 This function unloads the compressor if discharge pressure is approaching the high pressure limit. If discharge pressure of an operating compressor reaches the high pressure setpoint minus 10 psi, the compressor will be prevented from loading (HOLD state). If the discharge pressure reaches the high pressure setpoint minus 5 psi, the compressor will begin unloading.
If one of these sensor alarms occurs, it usually indi­cates a loose wire, blown fuse, defective sensor, or faulty analog board.
External Shutdown Indication (No-Run Alarm)
4.19 A No-Run control point error is generated if the computer tries to start (or run) a compressor but the compressor is held off by an external control. The computer determines that the compressor is
16
60 Hz HRSC ELECTRICAL DATA (50 - 150)
COMPRESSORS
Model HRSC
50 208/230 Y-D 179 - 347 - 224 400
60 208/230 XL 205 - 409 - 257 450
75 208/230 XL 209 - 472 - 262 450
100 208/230 XL 179 179 347 347 403 500
110 208/230 Y-D 205 179 409 347 436 600
120 208/230 Y-D 205 205 409 409 462 600
135 208/230 XL 209 205 472 409 467 600
150 208/230 XL 209 209 472 472 471 600
Volts 60 Hz 3 Ph.
208/230 XL 179 - 1040 - 224 400
460 XL 74 422 93 150 460 Y-D 74 - 141 - 93 150
208/230 XL 205 - 1228 - 257 450
460 Y-D 91 - 485 - 114 200 460 XL 91 - 162 - 114 200
208/230 Y-D 209 - 1415 - 262 450
460 Y-D 98 - 539 - 123 200 460 XL 98 180 - 123 200
208/230 Y-D 179 1040 1040 403 500
460 XL 74 74 422 422 167 200 460 Y-D 74 74 141 141 167 200
208/230 XL 205 179 1228 1040 436 600
460 XL 91 74 485 422 188 250 460 Y-D 91 74 162 141 188 250
208/230 XL 205 205 1228 1228 462 600
460 XL 91 91 485 485 205 250 460 XL 91 91 162 162 205 250
208/230 Y-D 209 205 1415 1228 467 600
460 Y-D 98 91 539 485 213 300 460 XL 98 91 180 162 213 300
208/230 Y-D 209 209 1415 1415 471 600
460 Y-D 98 98 539 539 221 300 460 XL 98 98 180 180 221 300
Type of Start
RATED LOAD AMPS MOTOR NO.
1
LOCKED ROTOR AMPS MOTOR NO.
2
12
Minimum Circuit Ampacity
Max Fuse Size
17
60 Hz HRSC ELECTRICAL DATA (50 - 150)
Model HRSC
180
210
225
240
255
270
300
Volts 60 Hz. 3 PH.
COMPRESSORS
Type of
1 2 3 4 1 2 3 4 Cir. 1 Cir. 2 Cir. 1 Cir. 2
Unit
RATED LOAD AMPS MOTOR NO.
LOCKED ROTOR AMPS MOTOR NO.
Minimum Circuit Ampacity
Maximum Fuse Size
208/230 XL 205 205 205 - 1228 1228 1228 - 667 - 800 ­208/230 XL 205 205 205 - 409 409 409 - 667 - 800 -
460 Y-D 91 91 91 - 485 485 485 - 296 - 350 -
460 XL 91 91 91 - 162 162 162 - 296 - 350 ­208/230 Y-D 209 209 209 - 1415 1415 1415 - 471 262 600 450 208/230 XL 209 209 209 - 472 472 472 - 471 262 600 450
460 Y-D 98 98 98 - 539 539 539 - 312 - 400 -
460 XL 98 98 98 - 180 180 180 - 312 - 400 ­208/230 Y-D 209 209 209 - 1415 1415 1415 - 471 262 600 450 208/230 XL 209 209 209 179 472 472 472 - 471 262 600 450
460 XL 98 98 98 74 539 539 539 - 319 - 400 -
460 Y-D 98 98 98 74 180 180 180 - 319 - 400 ­208/230 XL 205 205 205 205 1228 1228 1228 1228 462 462 600 600 208/230 Y-D 205 205 205 205 409 409 409 409 462 462 600 600
460 XL 91 91 91 91 485 485 485 485 387 - 450 -
460 Y-D 91 91 91 91 162 162 162 162 387 - 450 ­208/230 XL 209 209 209 209 1415 1415 1415 1415 467 462 600 600 208/230 Y-D 209 209 209 209 472 472 472 472 467 462 600 600
460 XL 98 98 98 98 539 539 539 539 396 - 450 -
460 XL 98 98 98 98 180 180 180 180 396 - 450 ­208/230 Y-D 209 209 209 209 1415 1415 1415 1415 471 462 600 600 208/230 XL 209 209 209 209 472 472 472 472 471 462 600 600
460 Y-D 98 98 98 98 539 539 539 539 403 - 500 -
460 XL 98 98 98 98 180 180 180 180 403 - 500 ­208/230 Y-D 209 209 209 209 1415 1415 1415 1415 471 471 600 600 208/230 XL 209 209 209 209 472 472 472 472 471 471 600 600
460 Y-D 98 98 98 98 539 539 539 539 417 - 500 -
460 XL 98 98 98 98 180 180 180 180 417 - 500 -
NOTES:
1. XL: Across the line; Y-D: Star-Delta
2. RLA (Rated Load Amps) rated in accordance with ARI Standard 590.
3. Starting current for normal Y-D start is shown. In certain compressor failure modes, Y-D inrush can be as high as XL inrush.
4. Wire Size Amps (ampacity) equal 125% of the rated load amps for the largest motor in the circuit plus 100% of the rated load amps for all other motors in the circuit, per N.E.C.
5. Maximum fuse size is based on 225% of the rated load amps for the largest motor in the circuit plus 100% of the rated load amps for all other motors in the circuit. This is the largest fuse allowed per N.E.C. A smaller fuse is often recom­mended based on unit application and ambient temperature.
VOLTAGE TOLERANCES:
1) 208 volt: min. 187, max. 229
2) 230 volt: min. 207, max. 253
3) 460 volt: min. 414, max. 506
18
TYPICAL HRSC 150 POWER WIRING (460/3/60)
COMPRESSOR MOTORS 1-2 SEE NOTE 5
19
TYPICAL HRSC 150 CONTROL WIRING
(Electrical Mechanical)
20
TYPICAL HRSC 150 CONTROL WIRING
(Optional Micro-Computer Controller)
21
HRSC 050 TO 300 PIPING SCHEMATIC
Shown Typical for
Each Separate Refrigerant Circuit
1 CIRG - 050. 060, 075
2 CIRC - 100, 110. 120, 135, 150 3 CIRC ­180, 210, 225 4 CIRC - 240. 255, 270, 300
CAP
t
~
~
HOT GAS
REGULATO
R
SOLENOID
VALVE
HOT GAS BYPASS OPTION
(CIRC. #1 ONLY)
TACCESS
VALVE COUPL ING
ACCESS VALVE CHECK
COUPLING VALVE
DISCHA@RG@E
,RFW Sum
comp
- SCREW
CAP
LIQUID
VALVt
FILTER DRIER AND CORES
~
'All
THERMAL (STD)
/- COUPLING
SIGHT SOLENOID GLASS VALVE
ACCESS VALVE
WATER
OUT
WATE
R
IN
23
CAPACITY CONTROL
Each compressor can modulate from 100% to 30% of full load by slide valve operation. This provides reduction down to 7.5% on four-compressor units.
Model Number HRSC 50-75 HRSC 100-150 HRSC 180-225 HRSC 240 300
Circuits 1 2 3 4
Further reduction is possible on all units through use of the hot gas bypass option which reduces compressor capac­ity to 10%. Minimum capacities are tabulated below.
Standard Min.
Unloading
30% 15% 10%
7.5%
Optional Hot Gas Bypass 15%
7.5% 5% 4%
PHYSICAL DATA
MODELS HRSC-50 THRU 150
Model HRSC 50 60 75 100 110 120 135 150 Nominal Capacity - Tons 40 50 60 80 85 95 110 120
SEMI-HERMETIC SCREW TYPE COMPRESSORS
No. of Compressors 1112 2 2 2 2 Nominal Size (HP) 50 60 75 (2)50 50-60 (2)60 60-75 (2)75 Oil Charge (Oz./Compr) 202 236 236 (2)202 (1)202(1)236 (2)236 (2)236 (2)236 Crankcase Heater (Watts) 200 200 200 (2)200 (2)200 (2)200 (2)200 (2)200
COOLER
Storage Capacity (Gal.) 6.25 9.4 11.1 17.6 25.4 25.4 29.4 29.4 Diameter x Length 860 1060 1160 1360 12102 12102 4102 14102
REMOTE CONDENSER
No. of SPD-SD Condensers 1111 1 1 1 1 SPD-SD Condenser Size 70 70 70 140 140 140 140 140
UNIT
Refrigerant Charge - R22 (lbs.)(1) 96 130 156 208 228 247 280 312 HRSC Operating Weight (lbs.)(2) 1700 2100 2325 3240 3555 4590 5415 5910
MODELS HRSC-180 THRU 300
Model HRSC 180 210 225 240 255 270 300 Nominal Capacity - Tons 145 165 175 190 205 210 230
SEMI-HERMETIC SCREW TYPE COMPRESSORS
No. of Compressors 33 3 4 4 4 4 Nominal Size (HP) (3)60 (1)60(2)75 (3)75 (4)60 (3)60(1)75 (2)60(2)75 (4)75 Oil Charge (Oz./Compr) (3)236 (3)236 (3)236 (4)236 (4)236 (4)236 (4)236 Crankcase Heater (Watts) (3)200 (3)200 (3)200 (4)200 (4)200 (4)200 (4)200
COOLER
Storage Capacity (Gal.) 60.5 60.5 60.5 67.7 67.7 67.7 67.7 Diameter x Length 18122 18122 18122 20122 20122 20122 20122
REMOTE CONDENSER
No. of SPD-SD Condensers 1/1 1/1 1/1 2 2 2 2 SPD-SD Condenser Size 70/140 70/140 70/140 140 140 140 140
UNIT
Refrigerant Charge - R22 (lbs.)(1) 390 442 481 546 575 611 663 HRSC Operating Weight (lbs.)(2) 8710 8860 8950 10460 10560 10650 10800
NOTES: 1. Refrigerant charge includes condenser but does not include refrigerant piping.
2. HRSC operating weight does not include remote condenser. See page 12 for condenser weights.
24
EVAPORATOR WATER PRESSURE DROP
MODEL HRSC-D CHILLER MODEL CURVE NO. MIN. GPM MAX. GPM
50 CHS008601B* 1 70 242 60 CHS010601B* 2 78 316 75 CHS011601B* 3 85 316
100 CHD013601B* 4 100 420 1 10, 120 EXD12102J07DVTO 5 160 444 135, 150 EXD14102J07DVTO 6 175 553
180, 220, 225 EXT18122J07DFRO 7 270 1060
240, 255, 270, 300 EXT20122J07DFRO 8 300 11 40
*These chillers have welded heads. All other chillers have removable heads.
NOTE: Constant water flow through the evaporator is required with a minimum of three gallons per
ton of system water loop volume. System volume should increase
up to ten gallons per ton for process loads, low load applications with small temperature ranges, or systems with widely fluctuating loads.
25
POWER
KNOCKOUT
HRSC 50-150 RIGGING INSTRUCTIONS
SPREADER BAR ASSEMBLY
(SUPPLIED BY OTHERS)
13 3/8
18
2 1/2" DIA. LIFTING HOLES
3/4" DIA MOUNTING HOLES (9)
HRSC 50-150 ISOLATOR INSTRUCTIONS
6
1
3 3
2
1
1
ISOLATOR CROSS RAIL
ISOLATOR ASSEMBLY (FRONT VIEW)
(SHIPPED LOOSE WITH IS OLATOR OPTION ONLY)
*
MIDPOINT
3
2
1
FRONT
(CONTROL BOX)
UNIT FRAME RAIL
UNIT ISOLATOR (OPTIONAL)
*
(9) 3/4 DIA. HOLES SUPPLIED
SPREADER BAR
6
2
1
26
HRSC 180-300 RIGGING INSTRUCTIONS
2 1/2 DIA. LIFTING HOLES (4)
3/4 DIA HOLES
ISOLATOR MOUNTING
HOLES-6 SUPPLIED
SPREADER BAR ASSEMBLY
(SUPPLIED BY OTHERS)
SPREADER BARS
BY OTHERS
HRSC 180-300 ISOLATOR INSTRUCTIONS
CONDENSER BUMPER RAIL
D N
E X
O B
L O
R T
N O C
1
R O
S S E R P
M O
1
C
2
2
7512 1/2
(6) 3/4 DIA. HOLES SUPPLIED
3
R O
S S E R P
M O C
R E
M
I
R
R
O
D
F
R
T
E
A
T
L
L
P
I F
3
75
3 1/2
27
TROUBLESHOOTING GUIDE
POSSIBLE CAUSE REMEDY
CHILLER UNIT WILL NOT START
1. Power off 1. Check main disconnect switch
2. Main line open 2. Check main fuses
3. Incorrect wiring 3. Check the wiring diagram
4. Loose terminals 4. Tighten all terminals
5. Control circuit open 5. Check phase loss monitor, flow switch, circuit
breakers, temperature control, low ambient thermostat, low temperature, thermostat, remote switch, etc.
6. T ime delay 6. Wait
COMPRESSOR HUMS BUT DOES NOT START
1. Low Voltage 1a. Check at service and unit for loss b. Consult power company
COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL
1. Refrigerant shortage 1. Check for leaks -- add refrigerant
2. Restriction in liquid line 2a. Plugged strainer -- clean or replace b. Liquid line valve partially closed — open valves fully
c. Expansion valve clogged or inoperative — clean or
replace as required
d. Solenoid valve partially open — clean or replace as
required
3. Low water flow thru cooler 3. Check water flow thru cooler and correct as required
COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL
1. Compressor discharge valve partially closed 1. Open valve fully
2. Non-condensible gases in system 2. Operate condenser fans with compressors off.
If condenser pressure exceeds saturated pressure corresponding to condenser entering air temperature, then reclaim air from the top of hot gas vertical header coil.
3. Overcharge of R-22 3. Reclaim refrigerant from system while in oper-
ation until head pressure reaches a normal level.
4. Clean the condenser
5. Replace if necessary
6. Check pressure control setting
CAUSES AND PREVENTION OF FREEZE-UP
CAUSES PREVENTION
1. Improper charging 1. Charge per manufacturer’s recommendation
2. Improperly set safety time delay 2. Check the safety time delay low pressure control for
proper setting at the beginning of each season.
3. Improper chilled water circulation 3. Use an ample sized cleanable strainer in the chilled
water circuit. Make certain the strainer is clean to insure full flow and velocity of chilled water. It may sometimes be necessary to treat the water to prevent formation of deposits.
30
ST ART-UP CHECK LIST Date ______________
YES NO
Unit Model No. _________________________
Setting Unit:a. Vibration isolator used _________ _________
b. Spring isolator adjusted for equal heiqht _________ _________ c. If rubber-in-shear isolators are used, is unit leveled by shimming _________ _________
Wiring: a. Power wiring complete _________ _________
b. Control wiring complete _________ _________ c. Electric service adequate for load _________ _________ d. Power source voltage correct for motor(s) used _________ _________ e. Motor circuit has proper size fusetrons _________ _________ f. System wired per diagram _________ _________ g. All wire connections tight _________ _________ h. Wiring complies with local codes _________ _________ i. Flow switch operation _________ _________
j. Microcomputer (if supplied) components dry _________ _________
Piping: a. Piping complies with applicable codes _________ _________
b. External piping independently supported _________ _________ c. Chilled water lines insulated _________ _________
d. All systems refrigerant and water piping leak tested and corrected as _________ _________ necessary
Before Start-Up:
a. Open compressor discharge service valve (if supplied) _________ _________
b.
Open liquid valve(s) _________ _________ c. Open suction, and discharge valves to pressure gauges (if supplied) _________ _________ d. Check rotation of all fan motors _________ _________ e. Start auxiliary equipment (pump s, fans, etc.) _________ _________ f. Is crankcase heater operating? Operate 24 hours prior to
unit start-up. _________ _________
g. Check the compressor oil level through the crankcase sight glass. _________ _________ The oil level should be 1/2 of the glass. If the level is low , add _________ _________ oil in accordance with the directions in the maintenance instructions _________ _________ h. Check all control settings as specified on unit wiring diagram _________ _________ i. Air purged from chilled water system _________ _________
After St art-up:
a. Check high pressure control _________ _________ b. Check oil temperature safety switch _________ _________ c. Check and adjust low temperature freeze control _________ _________ d. Check and adjust unit controller _________ _________ e. Check and adjust low pressure control _________ _________
f. Check and adjust expansion valve superheat _________ _________
31
Loading...