The DUNGS double solenoid valve DMV
integrates two solenoid valves in one
compact tting.
-
Automatic shut-o valves as per DIN EN 161
Class A Group 2.
- Two A valves in one housing
- Double seat valves
- High ow rates
- Max. operating pressure up to 0.5 bar
(50 kPa)
- Fast closing
- Fast opening
(DMV/11 eco, DMV-D/11 eco)
- Adjustable main volume (DMV-D/11 eco,
DMV-DLE/11 eco)
- DC solenoid
- Low electric power consumption through
power switching
-
Mountable closed position signal contact
- Compact, light-weight
Application
Double solenoid valves are used where two
single valves were mounted previously. In
connection with DUNGS gas regulators and
additional components, a wide variety of
regulating tasks can be performed.
It does not contain any non-ferrous metals,
suitable for gases of up to max. 0.1 vol.%
H2S, dry. Suitable for gases of families 1, 2,
3 and other neutral gaseous media.
Approvals
EC type testing certicate as per:
• EC-Gas Appliances Regulation
• EC-Pressure Equipment Directive
Approvals in other important gas consum-
ing countries.
Specications
Nominal diameters
Flange
Nominal diameters
Flange with pipe thread as
per ISO 7-1
Max. operating pressure
Solenoid valve V1
Solenoid valve V2
Closing time
Opening time
Main valve restrictor
Materials of gas conveying parts
DN 65 80 100 125
Connection ange as per DIN 2501 Part 1, to t preweld anges as per DIN 2633
(PN 16) DN 65 to DN 125, ISO 7005 - 1 (PN 16), ISO 7005 - 2 (PN 16)
Construction length as per DIN 3202 Part 1, row F1 for DN 65 to DN 125
DMV 525/11 eco
Rp 2
500 mbar (50 kPa)
Automatic shut-o valve as per EN 161: Class A, Group 2
Automatic shut-o valve as per EN 161: Class A, Group 2
< 1 s
DMV.../11 eco, DMV-D…/11 eco: < 1 s
Adjustable (DMV-D.../11 eco, DMV-DLE.../11 eco)
Housing: aluminium, steel, no non-ferrous metals
Seals at valve seat:
NBR basis, suitable for gases as per G260/l
FKM basis, suitable for gases as per G260/l (Viton version)
Ambient temperature
Installation position
Dirt trap
Measuring gas connection
Ignition gas connection
Voltage/frequency
Rating / power consumption
at 230 V AC, + 20°C
all indications are eective values
NBR: -15 °C to +60 °C
Viton: 0 °C to +60 °C
Solenoid vertically upright to lying horizontally
Sieve installed. To protect the complete gas train we recommend you to install
a suitable gas lter (refer to Datasheet 11.02)
G 1/4 DIN ISO 228 centrally upstream of V1 and downstream of V2 (not 525/11 eco)
G 1/8 DIN ISO 228 on both sides upstream of V1, between V1 and V2, downstream of V2
G 3/4 ignition gas ange as per ISO 228, possible on both sides between V1 and V2
50 - 60 Hz, 230 V AC, -15% +10%, further voltages on request
Other preferred voltages: 110 V AC, 24 V DC
Important: Always order, plug
connection and system
accessories separately.
3 … 6
256 151
256 296
256 357
253 459
253 461
256 172
256 297
256 358
256 458
256 459
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Rp 2 (DN 50)
DN 65
DN 80
DN 100
DN 125
Rp 2 (DN 50)
DN 65
DN 80
DN 100
DN 125
162
290
310
350
400
162
290
310
350
400
88
88
104
119
142
88
88
104
119
142
275
179
275
179
370
246
450
292
500
329
275
179
275
179
370
265
450
346
500
387
1)
Switching rate of DMV-DLE.../11 eco depends on opening time setting
125
185
200
220
255
125
185
200
220
255
97
97
109
116
125
97
97
109
116
125
1411/2P
1511/2P
1611/2P
1711/2P
1411/2PL
1411/2PL
1511/2PL
1611/2PL
1711/2PL
1411/2P
60
60
60
60
60
20
20
20
20
20
7.2
10.0
16.3
24.2
31.7
7.2
10.0
16.5
24.5
32.0
DMV/11 eco Two single stage solenoid valves, de-energised in absence of current, fast-opening, fast-clo-
sing.
DMV-D/11 eco Two single stage solenoid valves, de-energised in absence of current, fast-opening, fast-closing.
Manual limitation of gas ow is possible with main load adjustment (D) at valve 1 (V1).
DMV-DLE/11 eco Two single stage solenoid valves, de-energised in absence of current, slow-opening (L), fast-
closing. Adjustment of opening time (E) with fast stroke range at valve 2 (V2). Manual limitation
of gas ow is possible with main load adjustment (D) at valve 1 (V1).
Variants
Double solenoid valve DMV-…/11 eco
single stage operating mode
DMV
DMV-D
DMV-DLE
Filter
Gas pressure switch can be mounted:
ontheange
afterthelter,beforeV1
between V1 and V2
after valve 2
valve V1, double seat
valve V2, double seat
DMV/11 eco Rp 2 (DN 50)
◆
◆
◆
◆
◆
◆
◆
◆
◆
◆
DMV/11 eco DN 65 - DN 125
◆
◆
◆
◆
(◆)
◆
◆
◆
◆
◆
Valves open separately
IgnitiongasangeG3/4
◆ = standard
(◆) = on request
-- = not possible
◆
◆
◆
◆
4 … 6
Double solenoid valve modular system
Leakage gas valve
Ignition gas ange
External bypass valve
Internal bypass valve
p
= 500 mbar
e,max.
Min. gas pressure switch
System accessories
The double solenoid valve is prepared
for direct mounting of DUNGS system
accessories and additional equipment.
V1
Closed
position
signal
contact
Valve proving system
Closed position signal contact
V2
Max. gas pressure switch
Compact pressure switch for multiple actuators GW…A5
Datasheet 5.02
If a system accessory is
added, it may not be possible
to mount further devices.
Information on system accessories
VPS 504 valve proving system
Datasheet 8.10
Pressure limiter ÜB, NB...A2 for
multiple actuators
Datasheet 5.08
5 … 6
K01/1 closed position signal contact
to monitor closed position of valves