Dungs CM 100, CM 101 Installation Instructions Manual

CM 100 & CM 101 Relay Module
Power Equipment Company
2011 Williamsburg Road Richmond, VA 23231 USA
Phone: 804.236.3800 Fax: 804.236.3882 E-Mail: sales@peconet.com
Installation Instructions
DESCRIPTION
The CM100/101 control module contains the relay logic necessary to operate the DUNGS VPS 504 or VDK 200A valve prov­ing systems on a system start-up and during a system shutdown. On startup the valve proving system will interrupt the start­up sequence if it detects an open shutoff valve, thus preventing ignition under potentially dangerous conditions. On shutdown, an open valve detection causes a manual lock-out requiring reset, and an alarm contact will energize; an optional blower terminal can also be energized.
CM 100: Contains enclosure and relay board CM101: Relay board only for panel mounting
NEMA Type 1 Enclosure (IEC 529, IP 30) No Enclosure
SPECIFICATIONS
Electrical Rating
110-120 Vac / 60 Hz When operated at 50Hz, the CM will run a hotter. Therefore, the contact ratings are reduced. In addition, the internal timers will be slower by a factor of 1.2.
Ambient Temperature
+5° F to 140° F
Power Consumption
1 Amp
ATTENTION
• Read these instructions carefully.
• Failure to follow them and/or improper installation may
cause explosion, property damage and injuries.
• Installation must be done with the supervision of a
licensed burner technician.
• Check the ratings in the specications to make sure that
they are suitable for your application.
• Never perform work if gas pressure or power is applied,
or in the presence of an open flame.
• Ensure that the switch is not subject to vibration during
operation.
Approvals
UL Recognized Component: File MH 17004 FM Approved: File J.I. 3004006
Contact Ratings
• Once installed, perform a complete checkout.
• Label all wires prior to disconnection when servicing.
Wiring errors can cause improper and dangerous operation
• Verify proper operation after servicing.
• The system must be installed, used, and maintaned to
meet all applicable national and local code requirements such as but not limited to NFPA 70, NFPA 86, CSD-1, ANSI Z21.13, UL 795, NFPA 85, or CSA B149.3.
Karl Dungs, Inc.
CM 100 & 101 Installation Manual - P/N 80117 - Ed. 01/09
1 … 4
Phone: (651) 792-8912 Fax: (651) 792-8919 E-mail: info@karldungsusa.com
524 Apollo Drive,Suite 10 Lino Lakes, MN 55014 U.S.A.
WIRING
Preparation
•Reference the General Wiring Schematic on page 3.
•Disconnect all power to the valve proving system and the
flame safeguard before wiring to prevent electrical shock and equipment damage.
• All wiring must comply with local electrical codes,
ordinances, and regulations.
• Do not exceed the terminal ratings given in the specications.
• Loosen the screw which secures the cover. (CM 100 only)
• Open the cover.
• Route the wires through the conduit connectors.
• Provide adequate strain relief.
OPERATION
1 Initial Power:
When the main system is rst powered (L1) and there is no
call for heat, J2 gets powered, which allows power to J8. When J8 gets energized. This applies 120Vac to the valve proving system, which will cycle, verifying the automatic shutoff valves position.
2 Valve Proving - Pass on initial system start.
If the valve proving system conrms that both automatic
shutoff valves are closed, it energizes terminal J9, which closes normally open contact C2. If J7 from the flame safeguarge is energzied, then energizing J9 does not close C2.
3 Valve Proving - Pass on call for heat.
When there is a call for heat, terminal J4 is energized, which then breaks relay S1 and then makes relay S2, even if J7 is energized. This restarts the valve proving system. If the valve proven system energizes J9, C2 makesm, and power is then applied to J5. The flame safeguard’s safety interlock terminal is then energized, and the burner continues its igni­tion sequence.
Wiring
• A typical wiring diagram for operating a valve proving
system on burner start-up and after shutdown is shown in the wiring diagram on page 2.
• If the blower is to be operated every time the valve
proving system detects an open valve, connect the blower to J1, and the blower terminal of the flame safeguard to J6. (The connection from the flame safeguard blower terminal to J6 is required to provide proper operation of the blower during a normal start-up procedure.) If the above is not required, connect the blower directly to the flame safeguard terminal and do not make the connection from the flame safeguard blower terminal to J6. Terminal J1 can be used to energize an alarm.
NOTE: Frequency converters with insufcient
shielding can cause faults in the VPS 504/VDK 200A as the result of transients. Verify that the equipment
is provided with sufcient shielding.
5 Safety Shutdown:
During a safety shutdown, the flame safeguard control en­ergizes J7, which closes (if open) normally closed relay C2, overrides the input to J4, and forces relay S2 to break and then relay S1 to make. This resets the valve proving system. If the valves are proved closed, J9 is energized and closes C2 (or remains closed. If the valve proving fails, J10 will be energized and C2 opens (or remains open).
6 Normal Shutdown:
On normal shutdown, J4 and subsequently J5 are deener­gized when the “burner start” switch is opened. When J4 is de-energized, relay S2 breaks and then relay S1 makes, which causes the valve proving system to reset and veri-
es the position of the two automatic shutoff valves. If the
valves are proved closed, J9 is energized and closes C2. If the valve proving fails, J10 will be energized and C2 remains open.
4 Valve Proving - Failure
If at anytime the valve proving system fails to prove the automatic shutoff valve are closed, it energizes terminal J10, which closes normally open relay C1. The blower turns on if it is wired to J1 as shown in the wiring diagram. The internal contact C2 remains opened, and J5 cannot be energized even if J4 is energized; this prevents the burner system from continuing with the ignition sequence.
2 … 4
CM 100 or CM 101
(Shown in the de-energized state)
VDK or VPS Valve Proving system
N
L1
J4: When energized, S1
brakes, and then S2 makes, which will start a valve proving sequence. If J7 is energized, it will override J4 and force S2 to brake and then S1 to make, which will start a valve proving sequence.
When de-energized, S2 brakes, and then S1 makes, which will start a valve proving sequence.
S1
J7: When energized, C2 will close
(or remains closed), and J7 will override J4, force S2 to brake, and then force S1 to make, which will start a valve proving sequence.
When de-energized and if J4 is powered (i.e. resetting of FSG and Burner Start is still on), C2 will open, S1 will
brake, and then S2 will make, which will start a valve proving sequence.
When de-energized and if only J2 is powered (i.e. resetting of FSG and Burner Start is off), S1 remains in the
closed position and S2 remains in the opened position. C2 will open. If J9 is powered, then C2 will immediately close, but there is no valve proving sequence.
Neutral
Normally opened relay
Normally opened relay
J9: When energized,
closes C2. If J7 is
already energized,
having J9 powered
does nothing.
J10: When energized,
closes C1
S2
C2
J6: When
energized,
closes C1
Interlock Limits
Blower
Blower
Alarm
Flame Safeguard Control (FSG)
Alarm
High Gas
Burner Start
Low Gas
Run
L1
N
Valves are Proved Closed
To PLC, additional alarm, light, or horn, if desired.
Do not connect to J7!
GENERAL WIRING SCHEMATIC AND INTERNAL LOGIC
3 … 4
A manual reset on the valve proving system can be performed at anytime by pressing the red reset
button on the valve proving system. Resetting the valve proving system will initiate a new test run. Refer to the valve proving system installation manual for specica­tions and for operational details.
DIMENSIONS
CM 100 CM 101
PART NUMBERS
Type
CM 100
CM101
Description
Contains enclosure and relay board NEMA Type 1 Enclosure (IEC 529, IP 30)
Relay board only for panel mounting No Enclosure
Part Number
46022
46023
4 … 4
Loading...