DuctlessAire DA-09, DA-12, DA-18, DA-24 Service Manual

Service Manual
1
Service Manual
Mini-Splits
Service Manual
2
1. Applications and features ....................................................................................... 4
1.1 Computer or Data Server Rooms ............................................................................................ 4
1.2 Commercial, Offices, Shops, Churches etc ....................................................................... 6
1.3 Residential .......................................................................................................................................... 7
1.4 Sun Rooms or 4 Season Rooms .............................................................................................. 9
1.5 Low Ambient Cooling ................................................................................................................ 10
1.6 Heat Pump ........................................................................................................................................ 15
1.7 Sleep function ................................................................................................................................. 15
1.8 Anti-mildewing operation function ..................................................................................... 15
1.9 Remember function at the time of power failure ........................................... 15
2. Pre Installation Requirements.............................................................................. 22
2.1 Unit sized correctly and applied correctly ........................................................................ 22
2.2 Electrical Requirements ............................................................................................................ 22
2.3 Breaker Size .................................................................................................................................... 22
2.4 Line Set Lengths and Sizes ...................................................................................................... 20
2.5 Indoor Unit Positioning ............................................................................................................. 21
2.6 Outdoor Unit Positioning .......................................................................................................... 21
3. Installation Tips ..................................................................................................... 21
3.1 R410A Refrigerant ....................................................................................................................... 24
3.2 Electrical Wiring Connections ............................................................................................... 25
Service Manual
3
3.3 Number of Electrical Interconnect Wires ......................................................................... 26
3.4 Service Valves ................................................................................................................................ 27
3.5 Adding Refrigerant Charge ...................................................................................................... 28
3.6 Condensate Piping ........................................................................................................................ 28
4. Common Technical Problems ............................................................................... 29
5. Unit Fault Codes .................................................................................................... 36
6. Maintenance ........................................................................................................... 45
Service Manual
4
1. Applications and Features
1.1 Computer or Data Server Rooms
Mini-splits are designed to primarily keep people comfortable. That means the typical range of temperatures for the zone is 70-72 Deg F.
Mini Splits were not specifically designed for cooling server rooms or other data rooms however due to their size and ease of installation this is a very common application, and also the #1 Technical Service issue.
But FOLLOWING these guidelines can make for a reliable, profitable installation in this application.
Sizing
Sizing of the Mini Split to the room is EXTREMELY IMPORTANT.
DuctlessAire recommends a 12,000 Btu/h capacity per 200 to 250 Sq Ft of room size. Do not exceed this sizing guideline.
Installing large capacity systems in small rooms will lead to short cycling of the compressor as the supply airflow from the unit to “bounces back” into the return air stream of the unit
If using the larger capacity units, Supply air is discharged at a velocity of approximately 6ft per second.
With a small room, where the opposite wall to the unit is less than 10ft away the supply air only circulates for approximately 4 seconds before returning to the unit.
The room temperature sensor is located on the surface of the cooling coil, if the supply air quickly “bounces back” into the unit, it will satisfy the sensor and the compressor will be cycled off.
All DuctlessAire mini splits feature continuous fan operation, maintaining circulation
in the room rapidly picking up the warmer return air from the room, causing the return air
sensor
Service Manual
5
to quickly sense a rise in temperature and call for compressor operation. This leads to short cycling of the unit, poor temperature control and a greatly reduced unit
life span. Due to this scenario we recommend that you DO NOT install any capacity of Mini Split
in rooms of less than 100 Sq Ft in Size
Unit Location
Ensure that no obstacles to the air flow from the Indoor unit are within 10 feet of the unit, be especially aware that Computer server units create an airflow baffle and can have the same effect on airflow to and from the unit as a small room size.
In Computer room application the DuctlessAire Mini Split units must be installed a MINIMUM of 6ft from the floor so that the airflow from the unit is unimpeded.
Sensible Heat and Humidity
DuctlessAire units are designed to provide an approximate SHR of 0.66. Be aware that low humidity conditions will further reduce unit performance, requiring either additional higher fan speeds to be programmed into the unit, or introduction of some latent load into the room, e.g. Use of a humidifier.
Compressor Run Times To ensure compressor longevity it is paramount that the compressor run time be longer
than 5 minutes at all times throughout the year. This will allow oil return to the
compressor, and will ensure that the max number of starts per hour is not exceeded. If the compressor runtime is less than 5 minutes, especially at design ambient temperature
it is very likely that the unit is oversized.
Ambient
The other major issue with Computer or Data rooms is that they are designed to operate
Service Manual
6
365 days 24/7. This means that the Outdoor unit will be exposed to temperature below the minimum design ambient of 65 DegF
Therefore for cooling below 65 DegF, DuctlessAire insists on the following items to be installed on the system.
1. ICM 326H Fan Speed controller
2. Crankcase Heater on ALL units
If winter temperature fall below 32 DegF a Wind Baffle on the Coil Inlet and the Exhaust of the condenser fan is required.
This will isolate the unit from any wind that could cause the unit to over condense, slugging liquid refrigerant back to the Compressor, which can damage the valve plate, wash oil from the bearing services and eventually cause the Compressor to fail.
A Wind Baffle will provide cooling operation down to an Ambient of 0 DegF Wind Baffles are field fabricated, drawings are available on request from DuctlessAire.
1.2 Commercial, Offices, Shops, Churches etc
Sizing Again Sizing and Location of the Mini Split to the room is EXTREMELY
IMPORTANT. DuctlessAire recommends a 12,000 Btu/h capacity for each 350 to 450 Sq Ft of the
Room Do not exceed this sizing guideline for the same reason as the computer room
application information Again DO NOT install DuctlessAire Mini Splits in rooms of less than 100 Sq Ft
Ambient
Check as to the lowest ambient temperature that will be required for cooling, the minimum
Service Manual
7
design temperature for the Outdoor unit is 65 DegF, if cooling is required below that, down to 32 DegF, DuctlessAire insists on an ICM 326H Fan Speed controller being installed on the Outdoor unit. On ALL units, a Crankcase Heater should also be installed.
For cooling down to 0 DegF, the use of Wind Baffles is required, per the computer room application information.
Filters
DuctlessAire Mini Splits, because of the constant operation of the fan require much more frequent filter cleanings or replacements than the standard “ducted US style” units which are generally used for commercial buildings. DuctlessAire recommends that the filters are cleaned every 4 weeks of operation, more frequently in areas subject to dirtier conditions e.g. Warehouse offices etc.
Condensers located inside the Building
Especially with Warehouse or additional office space the condensers can be installed inside the building, this provides two specific issues to address:
1. Lower ambient, these units are rated at 95 DegF ambient, if the ambient in the building does not rise above 80 DegF, we can downsize the unit as it will produce more capacity and operate more efficiently.
2. Cleaning the condenser coil, use soapy water and keep the condenser coil clean, put it on the same schedule as the indoor unit filter cleaning.
1.3 Residential
Sizing
Sizing and Location of the Mini Split to the room is still EXTREMELY IMPORTANT. DuctlessAire recommends a 12,000 Btu/h capacity for each 500 to 600 Sq Ft of the Room for most applications inside the house.
Service Manual
8
The throw of the 9 or 12,000 Btu/h units is approximately 15 feet, and the 18 or 24,000 Btu/h units have a throw of approximately 25 feet.
Therefore when applying these units in a residential application make sure that the units are not mounted at the top of the stairs blowing directly onto a wall or inside a niche or cut out in a room.
Again the temperature sensor is designed to sense the returning air after it has been supplied to the room, extracted the heat and humidity and then returned to the unit, not when it has been bounced directly back off a wall or other obstacle.
Ambient
As standard the units are capable of cooling down to an ambient of 65 DegF, which is sufficient for the majority of residential applications.
Indoor unit Location
For optimum unit operation the High Wall Indoor unit should be mounted a minimum of 6 feet from the floor. A minimum height of 4 feet must be maintained for correct unit operation. Ensure air flow is never directly straight onto areas where people may sit or congregate, as the temperature difference between Supply and Return air will be approximately 35 DegF.
Outdoor unit location
The Outdoor units are designed to operate with extremely low noise levels compared to the standard US condensing unit, this allows the outdoor units to located in areas closer to property lines, however when locating the DuctlessAire Outdoor unit, ensure that the spacing detailed in the Installation manual are observed, and that the maximum line length and lift restrictions are adhered to.
Garages or FROG’s/Bonus Rooms
DuctlessAire Mini Splits are perfect for adding conditioning to Garages and Bonus Rooms Use a 400 sq per 12,000 Btu/h sizing guide and as always follow the location
Service Manual
9
guidelines provided for the Indoor and Outdoor unit.
1.4 Sun Rooms or 4 Season Rooms
Sizing
Sizing and Location of the Mini Split to the room is still EXTREMELY IMPORTANT. DuctlessAire recommends a 12,000 Btu/h capacity for each 325 to 350 Sq Ft of the Room.
The throw of the 9 or 12,000 Btu/h units is approximately 15 feet, and the 18 or 24,000 Btu/h units have a throw of approximately 25 feet.
Sun Rooms are a great application for DuctlessAire Mini Split units however there are several items that must be addressed to make the installation a success.
Ambient
Sun Rooms are different in their application as they by definition have a large solar gain and therefore can require cooling in cold ambient temperatures. Therefore as per Computer room and Commercial applications it is mandatory to install the ICM 326H low ambient control and a crankcase heater on the system.
Indoor unit Location
For optimum unit operation the High Wall Indoor unit should be mounted a minimum of 6 feet from the floor. A minimum height of 4 feet must be maintained for correct unit operation.
Ensure air flow is never directly straight onto areas where people may sit or congregate, as the temperature difference between Supply and Return air will be approximately 35 DegF.
Heat Pumps
In order to use the Sun Room year round Heat Pumps are the recommended system,
Service Manual
10
however it may be advisable to install some additional source of heat, such as electric baseboard if the Sun Room is to be used in temperatures below 24 DegF.
Below 24 DegF the air temperature delivered from the unit will be close to body temperature making it feel uncomfortable, as when the Outdoor temperature falls the unit capacity and efficiency reduces, together with the unit requiring more frequent defrost cycles.
This will assist in truly making the Sun Room a room to be enjoyed in comfort all year round.
1.5 Low Ambient Cooling
As stated in the Computer Room, Commercial and Sun Room application pages - ALL DuctlessAire models are capable of providing COOLING operation down to an ambient temperature of 65 DegF.
Therefore to operate in Cooling down to an ambient temperature of 32 DegF, both an ICM326H Fan Speed Controller, plus a Crankcase Heater, either a Mars #32342 or Raychem #CCH-1 or 2 bellyband types MUST be installed.
For cooling operation below 32 DegF, and down to a minimum of 0 DegF, DuctlessAire recommends that Wind Baffles be installed on both the Coil Inlet and Fan Outlet of the Outdoor unit. Please contact DuctlessAire directly for details of the design requirements for the Wind Baffles.
We also recommend using these Wind Baffles in applications where the units may be exposed to prevailing winds blowing though the condenser coils. These winds may cause the unit to over condense and freeze the indoor unit, or allow liquid refrigerant to be inadvertently slugged back into the compressor.
Installing the ICM326H Fan Speed Controller
The controller should be located per the instructions provided, it is not weatherproof, therefore should be mounted inside the compressor compartment of the Outdoor unit.
DuctlessAire Units have Ball Bearing Condenser Fan motors, set both the Hard Start and cut out speed setting dials to 1/3 off the MINIMUM position.
Service Manual
11
The Temperature sensing probe should be securely attached on or adjacent to a return bend on the condenser coil that measures 100 DegF in normal operation. In practice this works out to be the 3rd Return bend down from the top of the coil. Securely strap the probe to the bend or tube and insulate to ensure accurate temperature sensing.
Wiring
Wiring should be in accordance with the diagrams on the following pages, DO NOT deviate from the wiring shown, if in doubt please call Technical Support for assistance.
Please note on Heat Pump units the bypass connection must be wired from the Reversing Valve to the ICM controller to ensure that the Outdoor fan operates at full speed in the Heat Pump Heating mode.
Service Manual
12
Low Ambient Wiring Cs-26C1A / CS-35C1A
Low Ambient Wiring Cs-51C2A / KF-70GW/GX1a
Service Manual
13
Service Manual
14
Low Ambient Wiring Cs-51H2A / KFR-70GW/GX1a
Service Manual
15
1.6 Heat Pump
DuctlessAire Heat Pump units are NOT fitted with any type of auxiliary heating for back up heat during periods of time when the outdoor ambient is too cold to allow for full capacity operation. Basically the colder the air outside, the lower the capacity and supply air temperature provided by your DuctlessAire Heat Pump.
If the Outdoor Coil temperature is below 14 DegF, Heat Pump operation is stopped and the unit will shut down, until the coil temperature increases.
Therefore we recommend that the DuctlessAire heat pump should NOT be used as the primary source of heating where Outdoor temperatures are regularly below 24 DegF for sustained periods of time.
If a Heat Pump is used in these applications ensure that an additional source of heat (baseboard electric or hydronic, or other type) be used when the temperature falls below 24 DegF.
Warm Start
In Heat Pump operation the Indoor fan motor will only start operating, when the indoor coil temperature has reached 86 DegF. Then the fan will start operating in an ultra low speed mode, increasing in fan speed back to the selected speed on the remote control as the Indoor coil temperature increases.
When the unit completes Defrost, the warm start feature will be used to allow the coil to warm up before restarting the Indoor fan. Warm start operation is indicated by a the run light on the display blinking once.
Heat Pump Heating on the Remote Control
The symbol on the Remote Control for Heat Pump Heating is a little confusing The symbol that is a SUN is the correct symbol for Heat Pump Heating Press the mode
button until the SUN is displayed, and then selects the desired temperature and fan speed and the unit will operate in Heat Pump mode.