Ducane AC10B24 User guide

Page 1
FEATURES
Durable Copeland ®compressors, with internal pressure relief valves and inherent thermal protection
High quality Ducane made condenser coil with copper tubing and enhanced louvered fin for maximum heat transfer capability
Permanently lubricated condenser fan motor
All units run tested
Heavy gauge, textured, pre-painted cabinet provides corrosion and abrasion protection
Easy access to electrical panels, pre-wired for easy hook-up
Hinged control panel allows simple access to internal components
Service valve gauge ports positioned to allow plenty of access room
Warranties: 5 year parts; 5 year compressor
(see warranty certificate for details)
Liquid line filter drier installed in every unit
All units ETL, ETLC approved and ARI listed
Charged for 15 feet of interconnecting tubing
Crankcase heaters standard on all 3-phase models with reciprocating compressors
AC10B
Ducane Air Conditioner
UNIT DIMENSIONS
MODEL SQUARE BASE HEIGHT NUMBER (INCHES) (INCHES)
AC10B18 22 1/2 x 22 1/2 23 1/2 AC10B24 22 1/2 x 22 1/2 23 1/2 AC10B30-A 22 1/2 x 22 1/2 23 1/2 AC10B36-B, 36TA, 36F 22 1/2 x 22 1/2 27 1/2 AC10B42-A 22 1/2 x 22 1/2 31 1/2 AC10B48-A, 48TA, 48FA 22 1/2 x 22 1/2 31 1/2 AC10B60-A, 60T, 60F 30 x 30 27 1/2
T = 208/230V 3 Phase; F = 460V 3 Phase.
OUTDOOR INDOOR AIRFLOW NET CAPACITY SEER UNIT SECTION (SCFM) (BTUH/HR) (BTUH/WATT)
AC10B18 ACC18AA 600 18,200 10.20 AC10B24 ACC24AA 800 23,400 10.00 AC10B30-A ACC30AA 1000 29,200 10.20 AC10B36-B, 36TA ACC36BA 1200 34,600 10.00 AC10B42-A ACC42BA 1400 40,000 10.00 AC10 B48-A, 48TA, 48FA ACC48CA 1500 45,500 10.00 AC10B60-A ACC61CA 1800 58,500 10.00 AC10B60T, 60F ACC61CA + TDR 1800 59,000 10.00
Certified in accordance with the ARI Standard 210/240 certification program, which is based on ARI Standard 210/240.
THE DIFFERENCE IS QUALITY
®
www.ducanehvac.com
R
Page 2
ELECTRICAL DATA
Rated Voltage (Volts) 208-230 460 208-230 460 208-230 460 Phase 1 3 1 3 1 3 Frequency (Hz) 60
Rated Load Amps 9.6 10.9 13.6 16.1 10.0 5. 1 19.0 20.4 14.0 6. 4 30.7 17.2 8.2
Locked Rotor Amps 49 56 76 82 70 33 105 102 91 42 135 124 60
Full Load Amps 0.8 1.4 0.8 1.1 0.8 2.0 0.8 Locked Rotor Amps 1.4 3.0 1.9 3.0 1.9 4.3 1.9 Max. Fuse Size* 20 25 25 30 20 15 40 45 30 15 60 40 15
Min. Circuit Ampacity** 12.8 14.4 16.6 19.8 13.5 7.2 25.0 26.7 18.6 8.8 38.9 22.9 11.1
AC10B
Ducane Air Conditioner
20590101 04/02 20K Replaces 20399201
Printed on recycled paper.
For more information, contact your local Ducane distributor.
Shading means not available or factory installed.
UNIT SPECIFICATIONS
THE DIFFERENCE IS QUALITY
®
ACCESSORIES
* Time delay fuse/HACR Breaker **Refer to national Electrical Code (or Canadian Electrical Code) to determine wire size, fuse and disconnect size requirements ***Field supplied 7/8” to 1-1/8” adapter required. Use of 7/8” vapor line reduces performance approximately 3 - 4%.
DUE TO OUR POLICY OF CONTINOUS IMPROVEMENT, SPECIFICATIONS ARE
SUBJECT TO CHANGE WITHOUT NOTICE.
AC10B AC10B AC10B AC10B AC10B AC10B AC10B AC10B AC10B AC10B AC10B
Model Number 18 24 30-A 36-B, 36TA 36FA 42A 48-A, 48TA 48FA 60-A 60T 60F
PHYSICAL DATA
Face Area (ft2) 8.19 9.83 11.51 14.83 Tube / Fin Material (CU/AI)
Smooth Grooved Grooved Smooth Tube Diameter (in.) 3/8 No. of rows 1 Fins per inch 14 20 18 20 18 22 Diameter (in.) 18 22 No. of blades 3 RPM 1100 Motor HP 1/10 1/5 1/4 1/5 1/4
Liquid Line Connection (in.) 3/8 Vapor Line Size Required (in.) 5/8 3/4 7/8 1-1/8*** Vapor Line Connection (in.) 5/8 3/4 7/8 Shipping Weight 124 131 138 146 153 194
CONDENSER
COIL
CONDENSER
FAN
UNIT
COMPRESSOR
FAN
MOTOR
UNIT
Unit Size 18 24 30-A 36-B 36TA, 36FA 42A 48-A,48TA 48FA 60-A 60T, 60F
High Pressure Switch
20442501
(all models)
Low Pressure Switch
20442502
(all models)
Short Cycle Protection
20442601
(all models)
Hard Start Kit
20442701 20442702 20442708 20442704 20442705 20442705
Crankcase Heater
20442801 20442801 20442802
Sound Blanket
20442901 20442905 20442902
Low Ambient Kit
20442504
Page 3
SPLIT SYSTEM AIR CONDITIONER AND HEAT PUMP
INSTALLATION / START-UP INFORMATION
These instructions must be read and understood completely before attempting installation.
These units are designed for use in residential and commercial type buildings with a wide variety of Furnace/Air Handlers and Evaporator Coil combinations. Air-conditioners can be used with conventional forced warm air heating systems and/or straight cooling systems independent of the heating. Heat pumps are sensitive to indoor units and may only be installed with combinations listed in the Air-Conditioning and Refrigeration Institute (ARI) Directory of Certified Products.
After uncrating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation company immediately and file a concealed damage claim.
ISSUE 0144
WARNING
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National
Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian
Electrical Code Part 1 CSA
C22.1.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test equipment.
Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
CAUTION
Improper installation, adjustment, alteration, service or maintenance can void the warranty.
NOTE: These instructions are intended as a general
guide and do not supersede national, state or local codes in any way.
Table
Of Contents:
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . 2
Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Roof Top Installations . . . . . . . . . . . . . . . . . . . 2
Evaporator Piston Selection . . . . . . . . . . . . . . . 2
Refrigeration Line Sets . . . . . . . . . . . . . . . . . . . 2
Installation Of Line Sets . . . . . . . . . . . . . . . . . . 3
Service Valve Type . . . . . . . . . . . . . . . . . . . . . 3
Brazing Connections . . . . . . . . . . . . . . . . . . . . 3
Leak Check . . . . . . . . . . . . . . . . . . . . . . . . . 3
Evacuating & Charging Instructions . . . . . . . . . . 3
Opening Service Valve . . . . . . . . . . . . . . . . . . . 4
Electrical Connections . . . . . . . . . . . . . . . . . . . 4
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 4
Pre-Start Procedure . . . . . . . . . . . . . . . . . . . . . 5
Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . 5
Adjusting Charge . . . . . . . . . . . . . . . . . . . . . . . 5
Piston System Charging . . . . . . . . . . . . . . . . . . 5
TXV System Charging . . . . . . . . . . . . . . . . . . . 5
Defrost System . . . . . . . . . . . . . . . . . . . . . . . . 6
Unit Maintenance . . . . . . . . . . . . . . . . . . . . . . . 6
Home Owner's Information . . . . . . . . . . . . . 7 & 8
20407502 ISSUE 0144 Page 1 of 8
Page 4
Safety Precautions
1. Always wear safety eye wear, work gloves and protective clothing when installing equipment.
2. Never assume electrical power is disconnected. Use a meter to verify power is disconnected.
3. Keep hands out of fan areas when power is connected to equipment.
4. Have a fire extinguisher available.
5. R-22 causes frost-bite burns.
6. R-22 is toxic when burned.
7. The weight of the unit requires caution and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
NOTE TO INSTALLING DEALER: These instructions and warranty are to be given to the owner or prominently displayed near the indoor furnace/air handler unit.
Unit
Location
The remote condensing unit is to be installed on a solid foundation. This foundation should extend a minimum of 2" (inches) beyond the sides of the condensing unit and must be level. To reduce the possibility of noise transmission, the foundation slab should NOT be in contact with or be an integral part of the building foundation.
The "top discharge" condenser air is taken in through the condenser coil and is discharged out the top. For quiet operation and maximum efficiency, eliminate any obstructions which might interfere with air discharge.
DO NOT LOCATE THE UNIT:
• on brick, concrete blocks or unstable surfaces.
• near clothes dryer exhaust vents.
• near sleeping area or near windows.
• under eaves where water, snow or ice can fall directly on the unit.
Top Installations
Roof
If necessary to install units on a roof structure, be sure to elevate and level the units. The unit must be installed at least 6" (inches) above the roof surface. Ensure the roof structure and anchoring method is adequate for unit location. Isolate unit and tubing from building structure. Consult local codes regarding rooftop mounting.
Evaporator
Piston Selection
The condensing unit must be matched to an approved evaporator. Refer to the unit specification sheet furnished with the unit or unit rating plate for proper size piston. If the evaporator coil does not have a piston already installed or if the piston installed is not the one indicated, a replacement piston is required. The correct number piston is included with unit or may be purchased from a wholesale distributor. See the evaporator coil (indoor unit) instructions for details of changing the piston.
The evaporator coil may also use a thermal expansion valve (TXV) in place of a piston.
NOTE: The proper piston or thermostatic expansion
valve MUST be installed in the indoor coil prior to installation of refrigerant lines.
Zoning ordinances may govern the minimum distance the condensing unit can be installed from the property line. Check before proceeding.
Refrigeration
Fully annealed refrigeration lines should be used when
installing the system. DO NOT use copper water pipe.
Line Sets
Refer to unit specification sheet for proper line set sizes.
Locate the outdoor unit as close to the indoor unit as possible to avoid any long refrigeration line runs. Allow a minimum of 36" (inches) on the service panel side of the unit for service. Ensure there is a minimum of 24" (inches) clearance on two of the sides and 12" (inches) on the other side. A minimum vertical clearance of 60" (inches) is required to overhang. Allow at least 24" (inches) between multiple units.
DO LOCATE THE UNIT:
• with proper clearances on sides and top of unit.
• on a solid, level foundation or pad
• to minimize refrigerant line lengths.
• to allow for drainage of defrost water and prevent ice build-up (heat pump only)
• above expected snowfall levels (heat pump only).
20407502 ISSUE 0144 Page 2 of 8
Table 1 lists line set sizes if specification sheet is not
available. Split systems may be installed with up to 50 feet of line set (no more than 20 feet vertical) without special consideration. For other lengths, contact your distributor technical service.
Table 1 Line set sizes
Unit Size Liquid Line Vapor Line
18 3/8" * 5/8"
24 3/8" * 5/8"
30 3/8" 3/4"
36 3/8" 3/4"
42 3/8" 7/8"
48 3/8" 7/8"
60 3/8" 1-1/8" **
* Up to 25 feet of 1/4" line is permissible ** 7/8" permissible, resulting in 3-4% capacity reduction
Page 5
It is important that no tubing be cut or seals broken until you are ready to actually make connections to the evaporator and to the condenser section. DO NOT remove rubber plugs or copper caps from the tube ends until ready to make connections at evaporator and condenser. Under no circumstances leave the lines open to the atmosphere for any period of time.
Be extra careful with sharp bends. Tubing can "kink" very easily, and if this occurs, the entire tube length will have to be replaced. Extra care at this time will eliminate future service problems.
It is recommended that vertical suction risers not be up­sized. Proper oil return to the compressor should be maintained with suction gas velocity. Contact your distributor technical service for line sets longer than 50 feet or with more than 20 feet vertically between the indoor and outdoor unit.
On applications where liquid floodback to the compressor may occur, a suction line accumulator is recommended. Please note accumulators are factory installed in heat pumps, if required. Contact your distributor technical service for further information.
Installation
DO NOT fasten liquid or suction lines in direct contact with the floor or ceiling joist. Use an insulated or suspension type of hanger. Keep both lines separate, and always insulate the suction line. Long liquid line runs (30 feet or more) in an attic will require insulation. Route refrigeration line sets to minimize length.
DO NOT let refrigerant lines come in direct contact with foundation. When running refrigerant lines through the foundation or wall, openings should allow for a sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap between foundation or wall and refrigerant lines should be filled with a pliable silicon-based caulk, RTV or a vibration damping material.
Of Line Sets
Brazing
Connections
WARNING
FIRE H AZARD !
Refrigerant and oil mixture under pressure could ignite as it escapes and contacts brazing torch resulting in FIRE. M ake sure the refrigerant charge is properly removed from both the high and low sides of the system before brazing any component or lines.
FAILURE TO DO SO COULD RESULT IN BOD ILY INJURY O R DEATH.
Before making braze connections, be sure all joints are clean. Before heat is applied for brazing, dry nitrogen should be flowing through the tubing to prevent oxidation and scale formation on the inside of the tubing.
The following is the recommended method for making braze connections at the refrigerant line connections:
1. Debur and clean refrigerant tube end with emery cloth or steel brush.
2. Insert tubing into swage fitting connection.
3. Apply heat absorbing paste or heat sink product to prevent damage to the service valve.
4. Braze joint, using a suitable brazing alloy for copper to copper joints.
5. Quench the joint and tubing with water using a wet rag. Leave rag on fitting body and re—wet with water to help cool area.
Leak Check
Refrigeration lines and indoor coil must be checked for leaks after brazing and before evacuation. The recommended procedure is to apply a trace amount of vapor refrigerant (approximately two ounces or 3 psig) into the line set and indoor coil, then pressurize with 150 psig of dry nitrogen. Use a refrigerant leak detector to check all joints. The system may also be checked for leaks using a halide torch or pressure and soapy solution. After completion of leak check, relieve all pressure from system before evacuation.
Service
service valves with copper stubs. All service valves are positioned to seal refrigerant in the unit with gauge ports open to connecting lines. Gauge ports have Schraeder valve core installed and require use of charging hoses with depressors. DO NOT heat valve body above 250 degrees F. Service valves must be wrapped with wet rags or otherwise protected from heat during brazing. Use care to ensure no moisture enters valves or Schraeder valve cores if wet rags are used.
20407502 ISSUE 0144 Page 3 of 8
Valve Type
The outdoor condensing unit is supplied with sweat brass
Evacuating
NOTE: Intentional release of CFC or HCFC
These condensing units are pre-charged at the factory with adequate refrigerant to handle 15 feet of refrigerant tubing.
And Charging Instructions
refrigerant to the atmosphere violates Federal Law. It may also violate State and Local Codes. Check all Federal, State and Local Codes before proceeding.
Page 6
NOTE: DO NOT use any portion of the charge for
purging or leak testing. It is mandatory that a thorough evacuation of the refrigeration lines and indoor coil be performed.
The liquid line and suction line service valves have been
closed after final testing at the factory. DO NOT disturb
these valves until the lines have been leak checked and evacuated or the charge in the unit may be lost.
1. Connect the vacuum pump to the center hose of the manifold gauge set, the low-pressure manifold gauge to the vapor service valve and the high pressure manifold gauge to the liquid service valve.
NOTE: Unnecessary switching of hoses can be
avoided and complete evacuation of all lines can be achieved by also connecting a branch hose from the manifold gauge center port to a cylinder of R-22. Provide a separate shut-off valve to vacuum pump to avoid contaminating vacuum pump oil with refrigerant.
2. The valves should be kept in the "front seated" (closed) position. This will allow evacuation of the refrigeration lines and the indoor coil, without disturbing the factory charge in the outdoor unit.
3. Follow the vacuum pump manufacturer's instructions. Allow the pump to operate until the system has been evacuated down to 300 microns. Allow the pump to continue running for an additional 15 minutes. Turn OFF the pump and leave the connections secured to the two (2) service valves. After 5 minutes, if the system fails to hold 500 microns or less, check all connections for tight fit and repeat the evacuation procedure.
4. Isolate the vacuum pump from the system by closing the shutoff valves on the gauge-set. Disconnect the vacuum pump.
Opening
After evacuation of the connecting lines, remove the service valve cap and fully insert the hex wrench into the stem. A back-up wrench is required on the valve body to open the valve stem. Back-out counterclockwise until the valve stem just touches the retaining ring.
Service Valves
Replace service valve cap and torque to 8-11 ft-lb on 1/4" and 3/8" valves; 12-15 ft-lb on 5/8" and 3/4" valves; 15-20 ft-lb on 7/8" valves.
NOTE: The cap is the primary seal and must be tightened to prevent leaks.
Torque gauge port caps hand tight after adjusting charge per "Adjusting Charge" section.
Electrical
Connections
WARNING
ELECTRICAL SHOCK HAZARD!
Turn OFF electric power before connecting unit, performing any maintenance or removing panels or doors.
FAILURE TO DO SO COULD RESULT IN BODILY INJURY OR DEATH.
Be sure to check all local codes to determine that the unit is installed accordance with local requirements. Consult the National Electric Code for wire size requirements. Use 60° C wire or higher. Always provide ground connections to the outdoor unit. Power supply must agree with rating on unit nameplate.
Provide line voltage power supply to unit from a properly sized disconnect switch. Route power and ground wires from disconnect switch to unit. Line voltage connections are made at the line side of the contactor in the electrical box of the condensing unit. Follow the appropriate wiring diagram attached to inside of the access door of the unit.
Proper fusing recommendations are also indicated on Unit Rating Plate. In general, the best fuse for any unit is the smallest fuse that will hold equipment on line under normal use and service without nuisance tripping breakers or blowing of fuses. Time delay fuses are recommended to prevent blowing due to starting current (the current in rush when equipment starts is referred to as the Locked Rotor Amps or (LRA). A fuse of this kind properly sized will give maximum equipment protection.
CAUTION
BODILY INJURY HAZARD!
Control
This is not a backseating valve. Care must be taken to prevent dislodging retainer ring when opening valve.
FAILURE TO DO SO COULD RESULT IN BODILY INJURY.
20407502 ISSUE 0144 Page 4 of 8
AWG is recommended for control wiring. Table 2 provides a guideline for wire size and distance. For lengths longer than 150 feet, contact your local distributor for technical service.
Wiring
The control voltage is 24 Vac. High quality insulated 18
Page 7
Table 2 - Control Wiring Size
For length of wire up to: Use minimum wire size of:
30 feet 22 AWG* 100 feet 20 AWG 150 feet 18 AWG
* Use only high
quality 22 AW G w ire
Ensure room thermostat is properly installed per instructions shipped with room thermostat. Generally, thermostat should not be exposed to sunlight, drafts or vibration and should not be mounted on exterior walls.
Low voltage control wire connections should be made as noted on the wiring diagram on the inside cover of the outdoor unit. Generally, the connections from room thermostat to indoor unit and
indoor unit to outdoor unit are connected point to point (Y to Y, C to C, etc.), with points as follows:
"Y" (compressor) - yellow "C" (common) - black or brown "G" (indoor fan) - green "R" (24 Vac) - red "O" (reversing valve) - orange (heat pump only) "W" (first stage heat) - white (furnace only) "W1" / "W2" (supplemental heat) - white (heat pump only)
Pre-Start
Procedure
1. Check to ensure:
• service valve caps are installed and tightened
• voltage supply at unit agrees with nameplate rating
• all factory and field wiring connections are tight
• indoor fan motor is on correct speed tap
2. Close electrical disconnects to energize system.
3. Energize crankcase heater, on units so equipped, for
8 hours before operating the units.
lengths other than 15 feet. For line sets shorter than 15 feet in length, remove charge per Table 3. For line sets longer than 15 feet, add charge per Table 3. Oil charge is sufficient for all line lengths.
Final charge adjustments must be in the cooling mode by subcooling / superheat check, only when outdoor ambient is above 60°F. If the outdoor ambient is below 60°F, adjust charge only by weight and recheck later when ambient is above 60°F.
Heat pumps should also have performance checked in heating mode. The only acceptable method to charge a heat pump in the heating mode is by weight.
Table 3 — Refrigeration Charge Adjustment
Liquid Line Diameter Oz. Per Linear Foot *
1/4"
5/16"
3/8" 1/2"
.25 .45 .60
1.20
* Factory charge for series is for 15' (ft.) line sets
and evaporator coil.
Before final adjustment is made to the refrigerant charge, it is imperative proper indoor airflow be established. Airflow will be higher across a dry coil versus a wet coil. Blower charts are usually calculated with a dry coil. Recommended airflow is 350-450 CFM per ton (12,000 Btuh) through a wet coil. Refer to indoor unit instructions for methods of determining air flow and blower performance.
With outdoor ambient above 60°F, the refrigerant charge should be adjusted first by weight, then final adjustment by super heat (for piston systems) or subcool (for TXV systems).
Start-Up
Procedure
1. Set thermostat selector switch to OFF.
2. Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature.
3. Set the system switch of the thermostat on COOL and fan switch for continuous operation or AUTO, as desired. Operate unit for 15-20 minutes, then check the system refrigerant charge.
4. Adjust refrigerant charge per "Adjusting Charge" section.
Piston
1. Operate unit for minimum of 10 minutes.
2. Measure pressure and temperature at vapor valve
3. Subtract saturation temperature (of measured
System Charging
service port. Use a good thermistor or electronic thermometer.
pressure) from temperature measured to obtain superheat. Refer to Table 4 for saturation temperatures of R-22.
4. Measure outdoor dry bulb using a good thermometer
Adjusting
All split system units are factory charged for 15 feet of connecting line set and matched evaporator coil. Refrigerant charge should initially be adjusted for line set
20407502 ISSUE 0144 Page 5 of 8
Charge
and indoor wet bulb using a sling psychrometer.
5. Using measured temperatures, find closest outdoor dry bulb and indoor wet bulb temperatures in the chart inside control cover and locate required superheat.
Page 8
6. If measured superheat is:
• more than required, slowly add refrigerant to obtain required superheat.
• Less than required, slowly recover refrigerant to obtain required superheat.
outdoor unit when required. The defrost function is initiated and terminated based on time and temperature. During frosting conditions, the compressor will operate for 30, 60 or 90 minutes (field adjustable, factory set for 90 minutes) before switching to the defrost mode.
NOTE: Each time charge is added to or removed
from the system, allow the system to run approximately 15 minutes before pressure/temperature readings are re-taken and superheat calculations made.
TXV
System Charging
1. Operate unit for minimum of 10 minutes.
2. Measure pressure and temperature at liquid valve service port. Use a good thermistor or electronic thermometer.
3. Subtract measured temperature from saturation temperature (of measured pressure) measured to obtain subcooling. Refer to Table 4 for saturation temperature of R-22.
4. The subcooling level should be as specified on the unit specification sheet. In the absence of the specification sheet, use 12-14°F subcooling.
5. If measured subcooling is:
• more than required, slowly recover refrigerant to
obtain required subcooling.
• less than required, slowly add refrigerant to obtain
required subcooling.
Defrost
System (Heat Pumps Only)
A defrost system consisting of a defrost thermostat (mounted to the outdoor coil) and a defrost control board (in the control box) provides automatic defrosting of the
In geographical areas where heavy snowfall, freezing rain, or extensive operation in 20°F-40°F range is expected, the setting should be changed to 30 or 60 minutes. This is performed by relocating the "RUN TIME" jumper on the defrost board from the pins labelled "90" to either the "30" or "60" pins.
The defrost board provides a five (5) minute time delay for compressor short cycle protection. To bypass this delay, short the two "TEST" terminals together for 2 seconds.
For defrost system checkout, with the system running in the heating mode, short the two "TEST" terminals together. The heat pump will go into the defrost mode for as long as the "TEST" terminals are shorted together.
Maintenance
Unit
The unit should be inspected and cleaned on an annual basis by a qualified technician. This should include checking for adequate clearances, electrical connections, duct connections/blockages, air filters, airflow, lubrication, and operational performance of system. Coils may
require cleaning. The coil should always be cold when cleaning. Use an alkaline-based cleaner only. Cleaning a hot coil or using an acid based cleaner will remove the paint from the fins and may clog the coil.
Table 4 - R-22 Saturation Temperature / Pressure Chart
Pressure
(psig)
Temp.
(°F)
Pressure
(psig)
Temp.
(°F)
Pressure
(psig)
Temp.
(°F)
Pressure
(psig)
Temp.
(°F)
Pressure
(psig)
Temp.
(°F)
Pressure
(psig)
Temp.
(°F)
19.3 -6 31.8 9 44.1 21 58.8 33 76.0 45 155.7 85
20.8 -4 32.8 10 45.3 22 60.1 34 77.6 46 168.4 90
22.4 -2 33.7 11 46.4 23 61.5 35 79.2 47 181.8 95
24.0 0 34.7 12 47.6 24 62.8 36 80.8 48 195.9 100
24.8 1 35.7 13 48.8 25 64.2 37 82.4 49 210.8 105
25.6 2 36.7 14 49.9 26 65.6 38 84.0 50 226.4 110
26.4 3 37.7 15 51.2 27 67.1 39 92.6 55 242.7 115
27.3 4 38.7 16 52.4 28 68.5 40 101.6 60 259.8 120
28.2 5 39.8 17 53.6 29 70.0 41 111.2 65 277.8 125
29.1 6 40.8 18 54.9 30 71.4 42 121.4 70 296.7 130
30.0 7 41.9 19 56.2 31 73.0 43 132.2 75 316.5 135
30.9 8 43.0 20 57.5 32 74.5 44 143.6 80 337.4 140
20407502 ISSUE 0144 Page 6 of 8
Page 9
Home Owner's Information — Air Conditioners and Heat Pumps
Room Thermostat
The wall-mounted thermostat controls your air conditioner. The thermostat is available in various configurations from different manufacturers. The information below is typical for most thermostats. Ask your dealer for specific information regarding the model of thermostat installed.
For Cooling Cycle switch the room thermostat system lever to "Cool". The thermostat will turn the air conditioner or heat pump on in the cooling mode until the selected room temperature is achieved and then shut off automatically.
For Heating Cycle switch the room thermostat system lever to "Heat". The thermostat will turn the heat pump (or furnace) on in the heating mode until the selected room temperature is achieved and then shut off automatically. On heat pumps systems only, sometimes an emergency heat setting "EM HT" is available on the thermostat, which will automatically cycle supplemental electric heat only to heat your home.
Some room thermostats have a setting on the system lever marked "AUTO" which will automatically change between heating and cooling modes.
NOTE: Some heating and cooling units have a reset
feature which will allow you to reset the unit at the thermostat after some abnormal condition has caused safety switches to cut the unit off. If your unit has this feature, switch the system lever to OFF and back to COOL or HEAT. If you are in doubt which model you have, please consult your Dealer.
For Fan Control your thermostat may have a Fan Selection Switch that allows you to run the fan continuously or cycle it automatically with the heating or cooling system. Switch the lever to ON for continuous operation and to AUTO for automatic cycling.
For maximum comfort satisfaction and continual air cleaning/filtering, constant fan operation is recommended.
On models without a Fan Selection Switch, the fan will always cycle with the outdoor unit.
Important
• Your system should never be operated without a clean
• Return air and supply air registers should be free from
• On heat pump systems, increasing your thermostat
• Air conditioners and heat pumps (in the cooling mode)
• During the heating cycle of heat pumps, air from the
• Outdoor heat pump sections may accumulate frost
• Defrost cycles typically occur every 90 minutes of unit
System Information
air filter properly installed.
restrictions or obstructions to allow full flow of air.
setting by more than 2 degrees may cause supplemental heaters to turn on, reducing potential energy savings.
remove humidity from your home. Depending on the amount of moisture in the air inside your home, water will trickle from the condensate drain of the cooling coil.
registers may seem cool as the air being supplied moves faster and at a more constant flow than a conventional furnace. Additionally the air from a heat pump is typically less than 95°F (instead of sudden bursts of hot air), which may feel cool to your skin since it is slightly less than your body temperature. The air is sufficiently warm to maintain the temperature setting of your thermostat.
during certain operating conditions. It is not abnormal for the coil to become completely white with frost before the unit will defrost. Heat pumps are designed to maintain energy savings by defrosting only at optimum times when frost accumulation starts to significantly increase energy consumption.
run time, but can be adjusted to 30 or 60 minutes. Defrost cycles will run until all frost is melted or for up to 10 minutes before switching back into the heating cycle automatically. Do not be alarmed if steam or fog appears to be coming from the outdoor unit during the defrost cycle. It is simply water vapor condensing into a mist in the cold outside air.
20407502 ISSUE 0144 Page 7 of 8
Page 10
Regular Maintenance Requirements
Your system should be regularly inspected by a qualified service technician. These regular visits may include (among other things) checks for:
• motor operation
• ductwork air leaks
• coil & drainpan cleanliness (indoor & outdoor)
• electrical component operation & wiring check
• proper refrigerant level & refrigerant leaks
• proper airflow
• drainage of condensate
• air filter(s) performance
• blower wheel alignment, balance & cleaning
• primary & secondary drain line cleanliness
• proper defrost operation (heat pumps)
There is some routine maintenance procedures you can do to help keep your system operating at peak performance between visits.
Filter
Air
Inspect air filters at least monthly and replace or clean as required. Disposable filters should be replaced. Washable filters may be cleaned by soaking in mild detergent and rinsing with cold water. Replace filters with the arrows pointing in the direction of airflow. Dirty filters are the most common cause of poor heating / cooling performance and compressor failures.
Use a soft bristle brush with light pressure only. DO NOT damage or bend condenser coil fins. Damaged or bent fins may affect unit operation.
Painted
of automobile wax should be applied every year. In geographical areas where water has a high concentration of minerals (calcium, iron, sulfur, ect.). It is recommended that lawn sprinklers not be allowed to spray the unit. In such applications, the sprinklers should be directed away from the unit. Failure to follow this precaution may result in premature deterioration of the unit finish and metal components.
due to the corrosive atmosphere provided by the high salt concentration in ocean mists and the air. Periodic washing of all exposed surfaces and coil will add additional life to your unit. Please consult your installing dealer for proper procedures in your geographic area.
Surfaces
For maximum protection of the unit's finish, a good grade
In sea coastal areas, special maintenance is required
IF YOUR SYSTEM DOES NOT WORK, BEFORE
REQUESTING A SERVICE CALL:
Indoor
place, it should require minimal cleaning. Use a vacuum cleaner and soft brush attachment to remove any accumulation of dust from the top and underside of the finned coil surface. However, perform this maintenance only when the coil is completely dry.
dealer for service. It may need a detergent solution and rinsing with water for cleaning, which may require coil removal. You should not attempt this yourself.
Condensate
flow of drainage and clean if necessary.
Condenser
and fall off from trees can be drawn into coils by movement of the air. Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser. Periodically, debris should be brushed from the condenser coils.
Coil
If the system has been operated with a clean filter in
If the coil cannot be cleaned by this method, call your
Drain
During cooling season check at least monthly for free
Coils
Grass cuttings, leaves, dirt, dust, lint from clothes dryers,
WARNING
SHARP OBJECT HAZARD!
Condenser coils have sharp edges. Wear adequate body protection on body extremities (e.g. gloves). Failure to follow this warning could result in bodily injury.
1. Ensure thermostat is set below (cooling) or above
(heating) room temperature and that the system lever is in the "COOL", "HEAT" or "AUTO" position.
2. Inspect your return air filter: If it is dirty your air
conditioner may not function properly.
WARNING
ELECTRICAL SHOCK HAZARD!
Turn OFF electric power to unit before performing any maintenance or removing panels or doors.
FAILURE TO DO SO COULD RESULT IN BODILY INJURY OR DEATH.
3. Check indoor and outdoor disconnect switches.
Confirm circuit breakers are ON or that fuses have not blown. Reset breakers/replace fuses as necessary.
4. Inspect the outdoor unit for clogged condenser coils,
(grass cuttings, leaves, dirt, dust or lint). Ensure that branches, twigs or other debris are not obstructing the condenser fan.
IF YOUR SYSTEM STILL DOES NOT OPERATE, CONTACT YOU SERVICING DEALER.
Be sure to describe the problem, and have the model and serial numbers of the equipment available.
20407502 ISSUE 0144 Page 8 of 8
Loading...