DSE DSE8610 MKII Installation Instructions Manual

TYPICAL WIRING DIAGRAM
NOTE: A larger version of the Typical Wiring Diagram is available in the product’s operator manual, refer to
DSE Publication: 057-254 DSE8610 MKII Operator Manual available from www.deepseaplc.com for more information.
DEEP SEA ELECTRONICS
053-182
ISSUE 4
DSE8610 MKII Installation Instructions
ACCESSING THE MAIN CONFIGURATION EDITOR
Ensure the engine is at rest and the module is in STOP mode by pressing the (Stop/Reset) button.
Press the (Stop/Reset) and (Tick) buttons simultaneously.
If a module security PIN has been set, the PIN number request is then shown:
The first ‘#’ changes to ‘0’. Press the (Up) or (Down) button to adjust it to the correct value.
Press the (Right) button when the first digit is correctly entered. The digit previously entered now shows ‘#’ for security.
Repeat this process for the other digits of the PIN number. Press the (Left) button to move back to adjust one of the previous
digits.
When the (Tick) button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, the PIN must be re-entered.
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed:
EDITING A PARAMETER
Enter the editor as described above.
Press the (Right) or (Left) buttons to cycle to the section to view/change.
Press the (Up) or (Down) buttons to select the parameter to view/change within the currently selected section.
To edit the parameter, press the (Tick) button to enter edit mode. The parameter begins to flash to indicate editing.
Press the (Up) or (Down) buttons to change the parameter to the required value.
Press the (Tick) button to save the value. The parameter ceases flashing to indicate that it has been saved.
To exit the editor and save the changes, press and hold the (Tick) button.
To exit the editor and not save the changes, press and hold the (Stop/Reset) button
.
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Email: support@deepseaplc.com
Web: www.deepseaplc.com
Deep Sea Electronics Inc.
Tel: +1 (815) 316 8706
Fax: +1 (815) 316 8708
Email: support@deepseausa.com
Web: www.deepseausa.com
NOTE: If the editor is left inactive for the duration of the LCD Page Timer, it is automatically exited to ensure security. NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security. NOTE: Comprehensive module configuration is possible using the DSE Configuration Suite PC Software, refer to DSE
publication 057-239 DSE8610 MKII Configuraiton Suite PC Software Manual available from www.deepseaplc.com.
NOTE: Depending upon module configuration, some parameters in the Main
Section
Parameter As
Shown On Display
Values
Display
Alt Config
Engine
Generator
Section
Parameter As Shown On Display
Values
Generator
(Continued)
0 A
0 A
Timers
Schedule
Parameter
Specification
Section
Parameter As Shown On
Display
Values
Display
)
Engine
Power
Specification
Description
and Running Editors may not be available. For more information refer to DSE publication 057-239 DSE8610 MKII Configuraiton Suite PC Software Manual available from www.deepseaplc.com
MAIN CONFIGURATION EDITOR PARAMETERS
Contrast 0% Language English, Other. Current Date and Time DD:MM:YY, hh:mm:ss Default Config Default Config / Alternative Config Oil Pressure Low Shutdown 0.00 bar Oil Pressure Low Pre Alarm 0.00 bar Coolant Temperature Low Warning 0 ºC Coolant Temp High Pre Alarm 0 ºC Coolant Temp High Shutdown 0 ºC Start Delay Off Load 0 h 0 m 0 s Start Delay On Load 0 h 0 m 0 s Start Delay Telemetry 0 h 0 m 0 s Pre Heat Temp 0 ºC Pre Heat Timer 0 h 0 m 0 s Post Heat Temp 0 ºC Post Heat Timer 0 h 0 m 0 s Cranking 0 m 0 s Cranking Rest 0 m 0 s Safety On Delay 0 m 0 s Smoke Limiting 0 m 0 s Smoke Limiting Off 0 m 0 s Warming 0 h 0 m 0 s Cooling 0 h 0 m 0 s Under Speed Shutdown Active / Inactive Under Speed Shutdown 0 RPM Under Speed Warning Active / Inactive Under Speed Warning 0 RPM Over Speed Warning Active / Inactive Over Speed Warning 0 RPM Over Speed Shutdown 0 RPM Overspeed Overshoot 0 m 0 s Overspeed Overshoot 0 % Fail To Stop Delay 0 m 0 s Battery Under Voltage Warning Active / Inactive Battery Under Voltage Warning Delay 0 h 0 m 0 s Battery Under Voltage Warning 0.0 V Battery Over Voltage Warning Active / Inactive Battery Over Voltage Warning Delay 0 h 0 m 0 s Battery Over Voltage Warning 0.0 V Charge Alternator Failure Warning Active / Inactive Charge Alternator Failure Warning 0.0 V Charge Alternator Warning Delay 0 h 0 m 0 s Charge Alternator Failure Shutdown Active / Inactive Charge Alternator Failure Shutdown 0.0 V Charge Alternator Shutdown Delay 0 h 0 m 0 s Droop Active / Inactive Droop 0 % Fuel Usage Running Rate 0 % Fuel Usage Stopped Rate 0 % DPF Auto Regen Inhibit Active / Inactive Specific Gravity 0.80 to 1.00 CAN Termination Active / Inactive Under Voltage Shutdown 0 V Under Voltage Pre-Alarm 0 V Loading Voltage 0 V Nominal Voltage 0 V Over Voltage Pre-Alarm 0 V Over Voltage Shutdown 0 V Under Frequency Shutdown 0.0 Hz Under Frequency Pre-Alarm 0.0 Hz Loading Frequency 0.0 Hz Nominal frequency 0.0 Hz Over Frequency Pre-Alarm 0.0 Hz
MAIN CONFIGURATION EDITOR PARAMETERS (CONTINUED)
Over Frequency Pre-Alarm 0.0 Hz Over Frequency Shutdown 0.0 Hz Full Load Rating 0 A kW Overload Trip 0 % Delayed Over Current Active / Inactive Gen Over Current Trip 0 % AC System 3 Phase, 4 Wire CT Primary CT Secondary Short Circuit Trip 0 % Earth CT Primary 0 A Earth Fault Trip Active / Inactive Earth Fault Trip 0 % Transient Delay 0.0 s Gen Reverse Power Delay 0.0 s Full kW Rating 0 kW Full kVAr Rating 0 kvar Ramp Up Rate 0 % Ramp Down Rate 0 % Load Level For More Sets 0 % Load Level For Less Sets 0 % Load Demand Priority 1 Gen Reverse Power Trip 0 kW Insufficient Capacity Delay 0 m 0 s
Insufficient Capacity Action Reactive Load CTL Mode
Load Parallel Power 0 kW In Mains Parallel Mode Load Power Factor 0 % In Mains Parallel Mode Enable MSC Compatibility Active / Inactive LCD Page Timer 0 h 0 m 0 s Scroll Delay 0 h 0 m 0 s Engine Pre Heat Timer 0 h 0 m 0 s Engine Post Heat Timer 0 h 0 m 0 s Engine Cranking 0 m 0 s Engine Cranking Rest 0 m 0 s Engine Safety On Delay 0 m 0 s Engine Smoke Limiting 0 m 0 s Engine Smoke Limiting Off 0 m 0 s Engine Warming 0 h 0 m 0 s Engine Cooling 0 h 0 m 0 s Engine Overspeed Overshoot 0 m 0 s Engine Fail To Stop Delay 0 m 0 s Battery Under Voltage Warning Delay 0 h 0 m 0 s Battery Over Voltage Warning Delay 0 h 0 m 0 s Return Delay 0 h 0 m 0 s Generator Transient Delay 0 s Schedule Active / Inactive Schedule Bank 1 Period Weekly / Monthly,
On Load / Off Load / Auto Start Inhibit, Week, Start Time, Run Time and Day. Selection (1 to 8)
Schedule Bank 2 Period Weekly / Monthly, On Load / Off Load / Auto Start
Inhibit, Week, Start Time, Run Time and Day. Selection (1 to 8)
Power Cycle After Exit Power Cycle After Exit
None / Indication / Warning / Shutdown / Electrical Trip None / VAr Share / VAr Fixed Export
Press to begin editing then up or down when selecting the different parameters.
Press to begin editing then up or down when selecting the different parameters.
DIMENSIONS AND MOUNTING
Dimensions 245 mm X 184 mm X 51 mm (9.6” X 7.2” X 2.0”) Panel Cutout 220 mm X 160 mm (8.7” X 6.3”) Weight 0.98 kg (2.16 lb) Operating Temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF) Storage Temperature -40 ºC to +80 ºC (-40 ºF to +176 ºF)
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
The ‘Running’ Configuration Editor is enterable without stopping the engine. All protections remain active whilst using the ‘Running’ Configuration Editor.
Press and hold the (Tick) button to enter and exit the running editor.
RUNNING CONFIGURATION EDITOR PARAMETERS
Contrast 0 % Language English, Other Load Demand Priority 1 Commissioning Screens Active / Inactive Override Starting Alarms Active / Inactive
Levels
REQUIREMENTS FOR UL CERTIFICATION
information.
Screw Terminal Tightening Torque Conductors
Current Inputs Communication
Circuits DC Output Pilot Duty Mounting
Operating Temperature
Voltage Adjust (manual mode only, breaker open) Frequency Adjust (manual mode only, breaker open) Mains Decoupling Test Mode Active / Inactive Governor Gain 0.0 Frequency Adjust Offset 0.0 Hz DPF Auto Regen Inhibit Active / Inactive DPF Manual Regen Active / Inactive
Power Control Mode
kVAr Control Mode Load Parallel Power 0 %
Load Parallel kVAr 0 % Load Parallel PF 0.00 pf
WARNING!: More than one live circuit exists, see diagram overleaf for further
4.5 lb-in (0.5 Nm) Terminals suitable for connection of conductor size 13 AWG
to 20 AWG (0.5 mm² to 2.5 mm²).
Conductor protection must be provided in accordance with
NFPA 70, Article 240
Low voltage circuits (35 V or less) must be supplied from the
engine starting battery or an isolated secondary circuit.
The communication, sensor, and/or battery derived circuit
conductors shall be separated and secured to maintain at least ¼” (6 mm) separation from the generator and mains connected circuit conductors unless all conductors are rated 600 V or greater.
Must be connected through UL Listed or Recognized isolating
current transformers with the secondary rating of 5 A max.
Must be connected to communication circuits of UL Listed
equipment
0.5 A Suitable for flat surface mounting in Type 1 Enclosure Type
rating with surrounding air temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC)
Suitable for pollution degree 3 environments when voltage
sensing inputs do not exceed 300 V. When used to monitor voltages over 300 V device to be installed in an unventilated or filtered ventilation enclosure to maintain a pollution degree 2 environment.
-22 ºF to +122 ºF (-30 ºC to +50 ºC)
0 % 0 %
Const Power / Frequency-Power / Voltage-Power Const Power Factor / Voltage­Reactive Power / Power-Power Factor / Const Reactive Power