DSE DSE331 Operator's Manual

Page 1
DSE331 Operator Manual ISSUE 3
DEEP SEA ELECTRONICS PLC
DSE331 ATS Controller Operators Manual
Document Number 057-146
Author: Allan Jones
Page 2
DSE331 Operators Manual
2
Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND
Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303
Website:
www.deepseaplc.com
DSE 331 ATS controller Operators Manual
© Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above.
The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC.
Any reference to trademarked product names used within this publication is owned by their respective companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.
Amendments List
Issue Comments Minimum
Module version
required
Minimum
Configuration Suite
Version required
1 Initial release 1 5.10.13.0 2 Ammended Gasket part number 1 5.10.13.0 3 Ammended FPE Ac topology List 1 5.10.13.0
Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.
NOTE:
Highlights an essential element of a procedure to ensure correctness.
CAUTION!:
Indicates a procedure or practice which, if not strictly observed, could result in damage or destruction of equipment.
WARNING!:
Indicates a procedure or practice which could result in injury to personnel or loss of life if not followed correctly.
Deep Sea Electronics Plc owns the copyright to this manual, which cannot be copied, reproduced or disclosed to a third party without prior written permission.
SAE Society of Automotive Engineers (USA)
Page 3
DSE331 Operators Manual
3
TABLE OF CONTENTS
1 BIBLIOGRAPHY .............................................................................. 5
2 INTRODUCTION .............................................................................. 5
3 SPECIFICATIONS ........................................................................... 6
3.1 PART NUMBERING ................................................................................... 6
3.1 POWER SUPPLY REQUIREMENTS ......................................................... 7
3.2 TERMINAL SPECIFICATION ..................................................................... 7
3.3 S1/S2 VOLTAGE / FREQUENCY SENSING ............................................. 7
3.4 INPUTS ....................................................................................................... 8
3.4.1 DIGITAL INPUTS .....................................................................................................8
3.5 OUTPUTS................................................................................................... 8
3.5.1 CONFIGURABLE NORMALLY OPEN RELAY OUTPUTS A & B ............................8
3.5.2 CONFIGURABLE CHANGEOVER RELAY OUTPUTS C & D ..................................8
3.5.3 CONFIGURABLE OUTPUTS E - H ..........................................................................8
3.6 COMMUNICATION PORTS ....................................................................... 8
3.7 DIMENSIONS AND MOUNTING ................................................................ 9
3.7.1 DIMENSIONS ...........................................................................................................9
3.7.2 PANEL CUTOUT......................................................................................................9
3.7.3 WEIGHT ...................................................................................................................9
3.7.4 FIXING CLIPS ..........................................................................................................9
3.7.5 OPTIONAL SILICON SEALING GASKET................................................................9
3.8 APPLICABLE STANDARDS .................................................................... 10
3.9 ENCLOSURE CLASSIFICATIONS .......................................................... 11
3.9.1 IP CLASSIFICATIONS ........................................................................................... 11
3.9.2 NEMA CLASSIFICATIONS .................................................................................... 12
4 INSTALLATION ............................................................................. 13
4.1 TERMINAL DESCRIPTION ...................................................................... 13
4.1.1 DC SUPPLY & DC OUTPUTS. ............................................................................... 13
4.1.2 DIGITAL INPUTS. .................................................................................................. 13
4.1.3 VOLT FREE OUTPUTS. ........................................................................................ 13
4.1.4 S1 SENSING .......................................................................................................... 14
4.1.5 S2 SENSING ............................................................................................................ 14
4.1.6 PC CONFIGURATION INTERFACE CONNECTOR ............................................... 14
4.2 TYPICAL WIRING DIAGRAM ................................................................... 15
5 DESCRIPTION OF CONTROLS ................................................... 16
QUICKSTART GUIDE ....................................................................................... 17
5.1.1 MODE SELECTION OPERATION.......................................................................... 17
5.2 GRAPHICAL DISPLAY ............................................................................ 18
5.2.1 DISPLAY PAGES ................................................................................................... 18
5.2.1.1 STATUS ......................................................................................................................... 18
5.2.1.2 INSTRUMENTATION ..................................................................................................... 18
5.2.1.3 ALARMS .......................................................................................................................... 19
5.2.1.4 SCHEDULER. ................................................................................................................... 19
5.2.2 ALARM ICONS....................................................................................................... 19
5.3 CONTROLS .............................................................................................. 20
5.3.1 MODE SELECTION ............................................................................................... 20
5.3.2 DISPLAY ................................................................................................................ 20
5.3.3 LOAD SWITCHING CONTROL .............................................................................. 20
6 OPERATION .................................................................................. 21
6.1 AUTOMATIC MODE OF OPERATION ..................................................... 21
Page 4
DSE331 Operators Manual
4
6.1.1 WAITING IN AUTO MODE ..................................................................................... 21
6.1.2 STARTING SEQUENCE ........................................................................................ 21
6.1.3 S1 / S2 ON LOAD .................................................................................................. 21
6.1.4 STOPPING SEQUENCE ........................................................................................ 21
6.2 MANUAL OPERATION ............................................................................ 22
6.2.1 STARTING SEQUENCE ........................................................................................ 22
6.2.2 S1 OFF LOAD ........................................................................................................ 22
6.2.3 S2 ON LOAD.......................................................................................................... 22
6.2.4 TRANSFER BUTTONS OPERATION .................................................................... 22
6.2.5 STOPPING SEQUENCE ........................................................................................ 22
6.3 TEST ON OPERATION ........................................................................... 23
6.3.1 STARTING SEQUENCE ........................................................................................ 23
6.3.2 S2 ON LOAD.......................................................................................................... 23
6.3.3 STOPPING SEQUENCE ........................................................................................ 23
6.4 LOAD SWITCHING CONTROL ............................................................... 24
6.4.1 BREAKER SCHEME A .......................................................................................... 24
6.4.2 S1 / S2 LOAD INHIBIT ........................................................................................... 24
6.4.3 LOAD SHEDDING .................................................................................................. 24
6.4.4 TIMING DIAGRAM ................................................................................................. 24
6.4.5 BREAKER SCHEME B .......................................................................................... 25
6.4.5.1 CHECK SYNCHRONISING IS DISABLED ......................................................................25
6.4.5.1.1 TRANSFERRING TO S2........................................................................................................................ 25
6.4.5.1.2 TRANSFERRING TO S1........................................................................................................................ 25
6.4.5.1.3 LOAD SHED INPUT ............................................................................................................................... 25
6.4.5.1.4 TIMING DIAGRAM ................................................................................................................................. 25
6.4.5.2 CHECK SYNCHRONISING IS ENABLED .......................................................................26
6.4.5.2.1 TRANSFER TO S2 ................................................................................................................................. 26
6.4.5.2.2 TRANSFER TO S1 ................................................................................................................................. 26
6.4.5.2.3 LOAD SHED INPUT ............................................................................................................................... 26
6.4.5.2.4 TIMING DIAGRAM ................................................................................................................................. 26
7 PROTECTIONS .............................................................................. 27
7.1 S2 ............................................................................................................. 27
7.2 S1 ............................................................................................................. 27
7.3 PLANT BATTERY ................................................................................... 27
8 FRONT PANEL CONFIGURATION ............................................... 28
8.1 ACCESSING THE FRONT PANEL EDITOR (FPE) ................................. 29
8.1.1 EDITING A PARAMETER ...................................................................................... 29
8.2 ADJUSTABLE PARAMETERS (CONFIGURATION EDITOR) ............... 29
9 MAINTENANCE, SPARES, REPAIR AND SERVICING ............... 34
9.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE ......... 34
9.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE....................... 34
9.3 PURCHASING SEALING GASKET FROM DSE ..................................... 34
10 WARRANTY ................................................................................ 35
11 DISPOSAL ................................................................................... 35
11.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) ..... 35
11.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES) ................. 35
12 APPENDIX ................................................................................... 36
12.1 COMMUNICATIONS OPTION CONNECTIONS ................................... 36
12.1.1 DESCRIPTION ....................................................................................................... 36
12.1.2 PC TO CONTROLLER (DIRECT) CONNECTION .................................................. 36
Page 5
Bibliography / Introduction
5
1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained from the DSE website www.deepseaplc.com
DSE PART DESCRIPTION
053-131 DSE331 installation instructions 057-149 DSE331 Configuration Suite manual
2 INTRODUCTION
This document details the installation and operation requirements of the DSE331 Series modules, part of the DSEAts ® range of products. The manual forms part of the product and should be kept for the entire life of the product. If the product is passed or supplied to another party, ensure that this document is passed to them for reference purposes. This is not a controlled document. You will not be automatically informed of updates. Any future updates of this document will be included on the DSE website at www.deepseaplc.com
The DSE 331 module has been designed to allow the operator to control the transfer of the load from one supply to another, typically the mains supply and a standby generator or two mains supplies. The user also has the facility to view the system operating parameters via the LCD display.
The DSE 331 module monitors the supplies, indicating the operational status and fault conditions, automatically transferring the load to the backup supply in case of mains supply failure. The LCD display indicates the status.
The powerful microprocessor contained within the module allows for incorporation of a range of enhanced features:
• Text & Icon based LCD display (selectable in the software)
• True RMS Voltage monitoring.
• Supply parameter monitoring.
• Fully configurable inputs for use as alarms or a range of different functions.
Using a PC and the DSE Configuration Suite software allows alteration of selected operational sequences, timers and alarm trips.
Additionally, the module’s integral fascia configuration editor allows adjustment of this information. A robust plastic case designed for front panel mounting houses the module. Connections are via locking plug and
sockets.
Page 6
Specifications
6
3 SPECIFICATIONS
3.1 PART NUMBERING
0331 - 001 - 01
At the time of this document production, there have been no revisions to the module hardware.
Product type
Variant
Hardware revision
Revision 1
001
DSE 331 Auto Transfer Switch (ATS) Module
331
Page 7
Specifications
7
3.1 POWER SUPPLY REQUIREMENTS
Minimum supply voltage 8V continuous, 5V for up to one minute. Cranking dropouts
Able to survive 0V for 50mS providing the supply was at least
10V before the dropout and recovers to 5V afterwards. Maximum supply voltage 35V continuous (60V protection for one minute) Reverse polarity protection -35V continuous Maximum operating current Auto mode will all inputs active and all LEDs illuminated
168mA at 12V, 80mA at 24V Maximum standby current
(Stop mode with no active inputs)
39mA at 12V, 20mA at 24V
Plant supply instrumentation display
Range 0V-35V DC (note Maximum continuous operating voltage of 35V
DC) Resolution 0.1V Accuracy 1% of full scale
3.2 TERMINAL SPECIFICATION
Connection type Screw terminal, rising clamp, no internal spring Min cable size 0.5mm² (AWG 24) Max cable size 2.5mm² (AWG 10)
3.3 S1/S2 VOLTAGE / FREQUENCY SENSING
Measurement type True RMS conversion Sample Rate 5KHz or better Harmonics Up to 11th or better Input Impedance
300K Ω ph-N
Phase to Neutral 15V
(minimum required for sensing frequency
)
to 333V AC
(absolute maximum)
Suitable for 110V to 277V nominal
(±20% for under/overvoltage detection)
Phase to Phase 25V
(minimum required for sensing frequency
)
to 576V AC
(absolute maximum)
Suitable for 190V ph-ph to 479V ph-ph nominal
(±20% for under/overvoltage detection)
Common mode offset from Earth
100V AC (max)
Resolution 1V AC phase to neutral
2V AC phase to phase
Accuracy ±1% of full scale phase to neutral
±2% of full scale phase to phase Minimum frequency 3.5Hz Maximum frequency 75.0Hz Frequency resolution 0.1Hz Frequency accuracy ±0.2Hz
Page 8
Specifications
8
3.4 INPUTS
3.4.1 DIGITAL INPUTS
Number 4 Arrangement Contact between input terminal and the module’s plant supply negative terminal Low level threshold 3.0V minimum High level threshold 4.1V maximum Maximum input voltage +60V DC with respect to module’s plant supply negative terminal Minimum input voltage -2V DC with respect to module’s plant supply negative terminal Contact wetting current 6mA ±1mA Open circuit voltage 12V ±1V
3.5 OUTPUTS
3.5.1 CONFIGURABLE NORMALLY OPEN RELAY OUTPUTS A & B
Number 2 (Configurable outputs A & B) Type Volts free normally open contacts Rating 8A @ 35VDC
3.5.2 CONFIGURABLE CHANGEOVER RELAY OUTPUTS C & D
Number 2 (Configurable output C) Type Volts free change over contacts. Rating 8A @ 35VDC
3.5.3 CONFIGURABLE OUTPUTS E - H
Number 4 Type Fully configurable, DC outputs rated at DC voltage Rating 8A @ 35VDC Protection Protected against over current & over temperature. Built in load dump feature.
3.6 COMMUNICATION PORTS
USB Port USB2.0 Device for connection to PC running DSE configuration suite only
Page 9
Specifications
9
3.7 DIMENSIONS AND MOUNTING
3.7.1 DIMENSIONS
180mm x 116mm x 42mm (7.1” x 4.6” x 1.7”)
3.7.2 PANEL CUTOUT
154mm x 98mm (6” x 3.9”)
3.7.3 WEIGHT
400g (0.4kg)
3.7.4 FIXING CLIPS
The module is held into the panel fascia using the supplied fixing clips.
• Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the clip.
• Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case.
• Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the clip are
inside their allotted slots.
• Turn the fixing clip screws clockwise until they make contact with the panel fascia.
• Turn the screws a little more to secure the module into the panel fascia. Care should be taken not to over
tighten the fixing clip screws.
NOTE:- In conditions of excessive vibration, mount the panel on suitable anti-vibration mountings.
3.7.5 OPTIONAL SILICON SEALING GASKET
The optional silicon gasket provides improved sealing between the module and the panel fascia. The gasket is fitted to the module before installation into the panel fascia. Take care to ensure the gasket is correctly fitted to the module to maintain the integrity of the seal.
Fixing clip fitted to module
Fixing clip
Gasket fitted to module
Sealing gasket
Page 10
Specifications
10
3.8 APPLICABLE STANDARDS
BS 4884-1
This document conforms to BS4884-1 1992 Specification for presentation of essential information.
BS 4884-2 This document conforms to BS4884-2 1993 Guide to content BS 4884-3 This document conforms to BS4884-3 1993 Guide to presentation BS EN 60068-2-1
(Minimum temperature)
-30°C (-22°F)
BS EN 60068-2-2
(Maximum temperature)
+70°C (158°F)
BS EN 60950
Safety of information technology equipment, including electrical business equipment
BS EN 61000-6-2
EMC Generic Immunity Standard (Industrial)
BS EN 61000-6-4
EMC Generic Emission Standard (Industrial) BS EN 60529 (Degrees of protection
provided by enclosures)
IP65 (front of module when installed into the control panel with the optional sealing
gasket)
IP42 (front of module when installed into the control panel WITHOUT being sealed
to the panel)
UL508 NEMA rating
(Approximate)
12 (Front of module when installed into the control panel with the optional sealing
gasket).
2 (Front of module when installed into the control panel WITHOUT being sealed to
the panel)
IEEE C37.2
(Standard Electrical Power System Device Function Numbers and Contact Designations)
Under the scope of IEEE 37.2, function numbers can also be used to represent
functions in microprocessor devices and software programs.
The 331 controller is device number 11L-331 (Multifunction device protecting Line
(generator) – 331 series module).
As the module is configurable by the generator OEM, the functions covered by the
module will vary. Under the module’s factory configuration, the device numbers
included within the module are :
2 – Time delay starting or closing relay
30 – annunciator relay
42 – Running circuit breaker
62 – time delay stopping or opening relay
74– alarm relay
81 – frequency relay
86 – lockout relay
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
Page 11
Specifications
11
3.9 ENCLOSURE CLASSIFICATIONS
3.9.1
IP CLASSIFICATIONS
3xx series specification under BS EN 60529 Degrees of protection provided by enclosures IP65 (Front of module when module is installed into the control panel with the supplied sealing gasket).
IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the panel)
First Digit Second Digit
Protection against contact and ingress of solid objects Protection against ingress of water
0 No protection 0 No protection
1 Protected against ingress solid objects with a diameter
of more than 50 mm. No protection against deliberate access, e.g. with a hand, but large surfaces of the body are prevented from approach.
1 Protection against dripping water falling vertically. No
harmful effect must be produced (vertically falling drops).
2 Protected against penetration by solid objects with a
diameter of more than 12 mm. Fingers or similar objects prevented from approach.
2 Protection against dripping water falling vertically. There
must be no harmful effect when the equipment (enclosure) is tilted at an angle up to 15° from its normal position (drops falling at an angle).
3 Protected against ingress of solid objects with a
diameter of more than 2.5 mm. Tools, wires etc. with a thickness of more than 2.5 mm are prevented from approach.
3 Protection against water falling at any angle up to 60°
from the vertical. There must be no harmful effect (spray water).
4 Protected against ingress of solid objects with a
diameter of more than 1 mm. Tools, wires etc. with a thickness of more than 1 mm are prevented from approach.
4 Protection against water splashed against the equipment
(enclosure) from any direction. There must be no harmful effect (splashing water).
5 Protected against harmful dust deposits. Ingress of
dust is not totally prevented but the dust must not enter in sufficient quantity to interface with satisfactory operation of the equipment. Complete protection against contact.
5 Protection against water projected from a nozzle against
the equipment (enclosure) from any direction. There must be no harmful effect (water jet).
6 Protection against ingress of dust (dust tight).
Complete protection against contact.
6 Protection against heavy seas or powerful water jets.
Water must not enter the equipment (enclosure) in harmful quantities (splashing over).
Page 12
Specifications
12
3.9.2 NEMA CLASSIFICATIONS
3xx series NEMA Rating (Approximate) 12 (Front of module when module is installed into the control panel with the optional sealing gasket). 2 (front of module when module is installed into the control panel WITHOUT being sealed to the panel)
NOTE: - There is no direct equivalence between IP / NEMA ratings. IP figures shown are approximate
only.
1
IP30
Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt.
2
IP31
Provides a degree of protection against limited amounts of falling water and dirt.
3
IP64
Provides a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure.
3R
IP32
Provides a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure.
4 (X)
IP66
Provides a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the formation of ice on the enclosure. (Resist corrosion).
12/12K
IP65
Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids.
13
IP65
Provides a degree of protection against dust and spraying of water, oil and non corrosive coolants.
Page 13
Installation
13
4 INSTALLATION
4.1 TERMINAL DESCRIPTION
4.1.1 DC SUPPLY & DC OUTPUTS.
PIN No DESCRIPTION CABLE SIZE NOTES
1
DC Plant Supply Input (Negative)
2.5mm²
AWG 13
2
DC Plant Supply Input
(Positive)
2.5 mm²
AWG 13
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and all output
relays
3 Output A
1.0mm²
AWG 18
Volts free relay (8A rated)
4 Output A
1.0mm²
AWG 18
Volts free relay (8A rated)
5 Output B
1.0mm²
AWG 18
Volts free relay (8A rated)
6 Output B
1.0mm²
AWG 18
Volts free relay (8A rated)
7 Output E
1.0mm²
AWG 18
Plant Supply Positive from terminal 7. 2 Amp rated.
8 Output F
1.0mm²
AWG 18
Plant Supply Positive from terminal 8. 2 Amp rated.
9 Output G
1.0mm²
AWG 18
Plant Supply Positive from terminal 9. 2 Amp rated.
10 Output H
1.0mm²
AWG 18
Plant Supply Positive from terminal 10 2 Amp rated.
4.1.2 DIGITAL INPUTS.
4.1.3 VOLT FREE OUTPUTS.
PIN No DESCRIPTION CABLE SIZE NOTES
23 Output C
1.0mm²
AWG 18
User configured volt free output (N/O)
24 Output C
1.0mm²
AWG 18
User configured volt free output (Common)
25 Output C
1.0mm²
AWG 18
User configured volt free output (N/C)
26 Output D
1.0mm²
AWG 18
User configured volt free output (N/O)
27 Output D
1.0mm²
AWG 18
User configured volt free output (Common)
28 Output D
1.0mm²
AWG 18
User configured volt free output (N/C)
PIN No
DESCRIPTION CABLE SIZE NOTES
11 Input A
1.0mm²
AWG 18
Configurable input. Connects to plant supply negative
12 Input B
1.0mm²
AWG 18
Configurable input. Connects to plant supply negative
13 Input C
1.0mm²
AWG 18
Configurable input. Connects to plant supply negative
14 Input D
1.0mm²
AWG 18
Configurable input. Connects to plant supply negative
Page 14
Installation
14
4.1.4 S1 SENSING
PIN No DESCRIPTION
CABLE
SIZE
NOTES
19 S1 L1 (R) voltage monitoring
1.0mm²
AWG 18
Connect to S1 L1 (R) output (AC) (Recommend 2A fuse)
20 S1 L2 (S) voltage monitoring
1.0mm²
AWG 18
Connect to S1 L2 (S) output (AC) (Recommend 2A fuse)
21 S1 31 (T) voltage monitoring
1.0mm²
AWG 18
Connect to S1 L3 (T) output (AC) (Recommend 2A fuse)
22 S1 Neutral (N) input
1.0mm²
AWG 18
Connect to S1 Neutral terminal (AC)
4.1.5 S2 SENSING
PIN No DESCRIPTION
CABLE
SIZE
NOTES
15 S2 L1 (R) voltage monitoring
1.0mm²
AWG 18
Connect to S2 L1 (R) output (AC) (Recommend 2A fuse)
16 S2 L2 (S) voltage monitoring
1.0mm²
AWG 18
Connect to S2 L2 (S) output (AC) (Recommend 2A fuse)
17 S2 31 (T) voltage monitoring
1.0mm²
AWG 18
Connect to S2 L3 (T) output (AC) (Recommend 2A fuse)
18 S2 Neutral (N) input
1.0mm²
AWG 18
Connect to S2 Neutral terminal (AC)
4.1.6 PC CONFIGURATION INTERFACE CONNECTOR
DESCRIPTION CABLE
SIZE
NOTES
Socket for connection to PC with DSE Configuration Suite PC software.
0.5mm²
AWG 20
This is a standard USB type A to
type B cable.
NOTE:- The USB connection cable between the PC and the DSE331 module must not be extended beyond 5m (5yds). For distances over 5m, it is possible to use a third party USB extender. Typically, they extend USB up to 50m (yds). The supply and support of this type of equipment is outside the scope of Deep Sea Electronics PLC.
CAUTION!: Care must be taken not to overload the PCs USB system by connecting more than the recommended number of USB devices to the PC. For further information, consult your PC supplier.
CAUTION!: This socket must not be used for any other purpose.
This configuration cable is the same as normally used between a PC and a USB printer.
Page 15
Installation
15
4.2 TYPICAL WIRING DIAGRAM
As every system has different requirements, these diagrams show only a TYPICAL system and do not intend to show a complete system.
Genset manufacturers and panel builders may use these diagrams as a starting point, however you are referred to the completed system diagram provided by your system manufacturer for complete wiring detail.
Further wiring suggestions are available in the following DSE publication, available at www.deepseaplc.com.
DSE PART DESCRIPTION
056-022 Breaker Control (Training guide)
Page 16
Description of Controls
16
5 DESCRIPTION OF CONTROLS
The following section details the function and meaning of the various controls on the module.
Display Scroll button
Common Alarm Indicator
S1 breaker control
Main status display
Select Mode
S2 breaker control
Info button
Page 17
Description of Controls
17
QUICKSTART GUIDE
This section provides a quick start guide to the module’s operation.
5.1.1 MODE SELECTION OPERATION
NOTE:- For further details, see the section entitled ‘MODE SELECTION’ elsewhere in this manual.
Press button until preferred mode is
Press button to confirm selected
Page 18
Description of Controls
18
5.2 GRAPHICAL DISPLAY
- 4- line, 64 x 132 small Graphic Display with LED Backlight
- Icon and numeric display. Switch to select ‘Icon’ or ‘English’ display
- Software controlled contrast
- Mimic of Text insert / 4x indicators via LCD
5.2.1 DISPLAY PAGES
It is possible to scroll to display the different pages of information by repeatedly operating the scroll button
Once selected the page will remain on the LCD display until the user selects a different page or after an extended period of inactivity, the module will revert to the status display.
When scrolling manually, the display will automatically return to the Status page if no buttons are pressed for the duration of the configurable LCD Page Timer.
If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw the operator’s attention to the alarm condition.
At power up, the display will show the software version, and then display the default display screen, which will display Mains instrumentation.
5.2.1.1 STATUS
Displays voltage operational status information Example :
5.2.1.2 INSTRUMENTATION
The instrumentation page contains the following information S1 Voltage L-N
S1 Voltage L-L S1 Frequency S2 Voltage L-N S2 Voltage L-L S2 Frequency Battery Voltage Scheduler
Example::
Page 19
Description of Controls
19
5.2.1.3 ALARMS
Lists any current alarms Example (English) (Icon)
5.2.1.4 SCHEDULER.
Shows the settings of the exercise scheduler Example:
5.2.2 ALARM ICONS
In instances where more than one alarm is present the icon area will transition between icons to display all active alarm conditions. For information alarm conditions see section
Alarm Icon Reason
Switch fail alarm
The Switching device has failed to operate.
Failed to start
The engine has not fired after the preset number of start attempts.
Failed to stop
The module has detected a condition that indicates that the engine is running when it has been instructed to stop.
Over Voltage
S1 or S2 voltage has risen above the pre-set pre-alarm setting.
Under voltage
S1 or S2 voltage has fallen below the pre-set pre-alarm setting.
Over frequency
S1 or S2 frequency has risen above the pre-set pre-alarm setting.
Under frequency
S1 or S2 frequency has fallen below the pre-set pre-alarm
setting.
Page 20
Description of Controls
20
5.3 CONTROLS
5.3.1 MODE SELECTION
NOTE:- Icons only apply when display mode in the software programme is set to `icons`
5.3.2 DISPLAY
This button changes between the various pages About, Status, Instrumentation, Alarms, Event Log, LCD Indicators
This buttons scrolls through the items in the currently displayed page.
5.3.3 LOAD SWITCHING CONTROL
Two fascia mounted buttons are provided for load switching operation when in manual mode. These buttons are enabled/disabled in the modules PC configuration Suite so refer to your configuration file to ensure the configuration has enabled the buttons.
Pressing this button when the S1 is on load will open the S1 load switch. Pressing this button when S2 is on load and S1 is healthy, will open S2 load switch, wait for the duration of the transfer delay, then close the S1 load switch.
Pressing this button when S2 is on load will open the S2 load switch. Pressing this button when the S1 is on load and S2 is available, will open the S1 load switch, wait for the duration of the transfer delay, then close S2 load switch.
This button selects the preferred mode of operation. to complete the selection press the button. Automatic mode. This mode allows the module to control the function of the load switching completely
automatically. The module will monitor the remote start input and mains supply status and once a start request is made, the set will be placed on load. Upon removal of the starting signal (or S1supply returns), the module will automatically transfer the load from the generator to the mains and remove the genset starting instruction.
Manual mode. This mode allows manual control of the ATS functions. Once in this mode the module will send a start request to the generator. Breakers can be opened and close using the transfer buttons detailed below.
Test mode. Once in Test mode the module will send a start request to the generator and place the set on load or off load depending what is set in the software. The set will remain on load or off load when in this mode.
Start inhibit mode.
This mode is used to provide an over-ride function to prevent the controller from starting the
generator in the event of a remote start/S1 out of limits condition occurring.
Prohibit return.
This mode is used to prevent the module from loading S1 even though S1 has returned.
Page 21
Operation
21
6 OPERATION
6.1 AUTOMATIC MODE OF OPERATION
NOTE:- If a digital input configured to external panel lock is active, changing module modes will not
be possible. Viewing the instruments is NOT affected by panel lock.
Activate auto mode by pressing the mode button until Auto is selected and then press the button to confirm. Auto mode will allow the transfer system to operate fully automatically, switching between S1 and S2 as required with no user intervention.
6.1.1 WAITING IN AUTO MODE
If a starting request is made and there is no input present for Auto Start Inhibit, the starting sequence will begin. Starting requests can be from the following sources :
• S1 failure
• Activation of an auxiliary input that has been configured to remote start
• Activation of the inbuilt exercise scheduler.
6.1.2 STARTING SEQUENCE
To allow for ‘false’ start requests, the start delay timer begins. Should all start requests be removed during the start delay timer, the unit will return to a stand-by state. When S2 is configured for a generator If a start request is still present at the end of the start delay timer the Start
and Run S2 output will be energised. After the generator has started, it will enter the warming up timer. If S2 fails to become available before the S2 Fail Delay timer expires the module will alarm. This is indicated on
the LCD display but the starting signal remains active.
6.1.3 S1 / S2 ON LOAD
Once S2 is measured as being within limits S1 is removed from the load, and after the transfer timer has expired, S2 is placed on load.
If all start requests are removed and there is no input present for Auto Restore Inhibit, the stopping sequence will begin.
6.1.4 STOPPING SEQUENCE
The return delay timer operates to ensure that the starting request has been permanently removed and isn’t just a short term removal.
After the return delay timer, the generator load switch is opened, then after the transfer timers, the mains is placed back on load. Should another start request be made during the cooling down period, the generator will be placed on load.
The cooling timer allows the set to run off load and cool sufficiently before being stopped. This is particularly important where turbo chargers are fitted to the engine.
After the cooling timer has expired, the set is stopped.
Page 22
Operation
22
6.2 MANUAL OPERATION
NOTE:- If a digital input configured to panel lock is active, changing module modes will not be possible. Viewing the instruments and event logs is NOT affected by panel lock.
Manual mode allows the operator to change the state of the load switching devices.
6.2.1 STARTING SEQUENCE
NOTE:- There is no start delay in this mode of operation.
The start request is sent to the generator via a digital output configured to Start and Run S2. If S2 fails to become available before the S2 failure timer expires. This is indicated on the LCD display, but the
starting signal remains active.
6.2.2 S1 OFF LOAD
The generator will continue run OFF LOAD in this mode unless :
• S1 supply fails
• An input is given for Auxiliary S1 fail
• An input is given for Transfer to S2
• The fascia mounted transfer buttons are pressed (when configured)
6.2.3 S2 ON LOAD
Once on load, the generator will remain on load unless:
• An input is given for Transfer to S1
• The fascia mounted transfer buttons are pressed (when configured)
• The module mode is changed to AUTO mode. The system may then transfer back to mains supply
automatically if conditions are suitable.
6.2.4 TRANSFER BUTTONS OPERATION
Two fascia mounted buttons are provided for load switching operation when in manual mode. These buttons are enabled/disabled in the modules PC configuration Suite so refer to your configuration file to ensure the configuration has enabled the buttons. Pressing this button when S1 is on load will open S1 load switch. Pressing this button when S2 is on load and S1 is healhty, will open S2 load switch, wait for the duration of the transfer delay, then close the S1 load switch. Pressing this button when S2 is on load will open S2 load switch. Pressing this button when S1 is on load and S2 is available, will open S1 load switch, wait for the duration of the transfer delay, then close S2 load switch.
6.2.5 STOPPING SEQUENCE
The set will not be stopped in this mode of operation.
To begin the stopping sequence, the module should be placed in the AUTO or START INHIBIT mode.
Page 23
Operation
23
6.3 TEST ON OPERATION
NOTE:- If a digital input configured to panel lock is active, changing module modes will not be
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Test mode allows the operator to start and stop the set manually, and if required change the state of the load switching devices. Test on load and Test off load is selectable in the software.
6.3.1 STARTING SEQUENCE
NOTE:- There is no start delay in this mode of operation.
The start request is sent to the generator via a digital output configured to Start and Run S2. If S2 fails to become available before S2 fail delay timer expires. This is indicated on the LCD display, but the
starting signal remains active.
6.3.2 S2 ON LOAD
S2 will continue run ON LOAD in this mode unless :
• S2 supply fails – S2 supply is placed back on load if available.
• An input is given for Open/Close S1
6.3.3 STOPPING SEQUENCE
The set will not be stopped in this mode of operation. To begin the stopping sequence, the module should be placed in the AUTO or START INHIBIT mode.
Page 24
Operation
24
6.4 LOAD SWITCHING CONTROL
The following timing diagrams detail the differences between the load switching control options.
6.4.1 BREAKER SCHEME A
NOTE : S2 Closed Auxiliary and S1 Closed Auxiliary inputs do not affect the operation of the load switching in Breaker Scheme A
6.4.2 S1 / S2 LOAD INHIBIT
Activation of an input configured to S1 load inhibit or S2 load inhibit inputs cause the corresponding breaker to be opened immediately. No other change in function will occur. When the input is deactivated the breaker is closed again if appropriate.
6.4.3 LOAD SHEDDING
If an input configured to Load Shed is activated, outputs set to Open S1 and Open S2 will energise, and inputs configured to Open/CloseS1 and Open/CloseS2 will de-energise. Open S1 Ouput Pulse and Open S1 Ouput Pulse will only energise if the corresponding supply was on load before application of the Load Shed input. When the Load Shed input is deactivated, the load will be transferred back to the supply that was disconnected before application of the input.
6.4.4 TIMING DIAGRAM
Open S1
Close S2
Close S1
Open S2
Open S1 Pulse
Close S2 Pulse
Close S1 Pulse
Open S2 Pulse
Transfer time Transfer Time
Page 25
Operation
25
6.4.5 BREAKER SCHEME B
Breaker Scheme B is intended only for use with certain designs of transfer switch. If you are using contactors, you MUST select Breaker Scheme A.
6.4.5.1 CHECK SYNCHRONISING IS DISABLED
6.4.5.1.1 TRANSFERRING TO S2
To open S2 breaker the Open S1 output energises, it then de-energises when the S1 Closed Auxiliary indicates it has successfully opened, or after 1s whichever occurs first. When the ‘S1 Closed Auxiliary’ indicates the mains breaker has opened, the transfer timer begins. When the transfer timer expires, the module attempts to close S2 breaker by energising the Open S1 and Close S2 outputs simultaneously, it then de-energises these outputs when the S2 Closed Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.
6.4.5.1.2 TRANSFERRING TO S1
To open S1 breaker the Open S2 output energises, it then de-energises when the S2 Closed Auxiliary indicates it has successfully opened, or after 1s whichever occurs first. When the ‘S2 Closed Auxiliary’ indicates S2 breaker has opened, the transfer timer begins. When the transfer timer expires, the module attempts to close S1 breaker by energising the Open S2 and Close S2 outputs simultaneously, it then de-energises these outputs when S1 Closed Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first
6.4.5.1.3 LOAD SHED INPUT
When the Load Shed input is activated while the generator is closed the Open S2 output energises, it then de­energises when the S2 Closed Auxiliary input indicates that it has successfully opened, or after 1s whichever occurs first.
When the Load Shed input is activated while the mains is closed the Open S1 output energises, it then de­energises when the S1 Closed Auxiliary input indicates that it has successfully opened, or after 1s whichever occurs first.
When the Load shed input is de-energised the load will be returned to the supply that was disconnected, providing that supply is healthy.
6.4.5.1.4 TIMING DIAGRAM
Open S1
Close S2
Close S1
Open S2
Non-Sync Transfer Time Non-Sync Transfer
S2 has closed
S1 has closed
S1 has opened
S2 has opened
Page 26
Operation
26
6.4.5.2 CHECK SYNCHRONISING IS ENABLED
NOTE : The module waits indefinitely for synchronisation unless the ‘Return to programmed transition’ function is active in which case after 2 minutes it performs a non-sync transfer as described in the previous section.
NOTE : The transfer time is ignored during a check-sync but is used if the transfer fails and it performs a non-sync transfer.
6.4.5.2.1 TRANSFER TO S2
When the module is about to transfer from S1 to S2 it activates the check sync function. When the S1 and S2 are within the phase and frequency window the module energises the Open S1 and Close S2 outputs simultaneously. These outputs are de-energised when the S2 Closed Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.
6.4.5.2.2 TRANSFER TO S1
When the module is about to transfer from S2 to S1 it activates the check sync function. When S1 and S1 are within the phase and frequency window the module energises the Open S2 and Close S1 outputs simultaneously. These outputs are de-energised when the S2 Closed Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.
6.4.5.2.3 LOAD SHED INPUT
When the Load Shed input is activated while the S2 is closed the Open S2 output energises, it then de-energises when the S2 Closed Auxiliary input indicates that it has successfully opened, or after 1s whichever occurs first.
When the Load Shed input is activated while the mains is closed the Open S1 output energises, it then de­energises when the S1 Closed Auxiliary input indicates that it has successfully opened, or after 1s whichever occurs first.
When the Load shed input is de-energised the load will be returned to the supply that was disconnected, providing that supply is healthy.
6.4.5.2.4 TIMING DIAGRAM
Open S1
Close S2
Close S1
Open S2
S2 has closed
S1 has closed
In Sync
In Sync
Page 27
Protections
27
7 PROTECTIONS
7.1 S2
The 331 ATS module monitors the S2 supply to ensure that it remains within configured levels. If the S2 supply fails, it is taken off load and the start/run signal is be removed.
S2 failure
S2 has not become available after the period of the S2 Failure timer has expired.
S2 Under Voltage shutdown
The S2 supply is below the configured under voltage trip level
S2 Under Frequency shutdown
The S2 supply is below the configured under frequency trip level
Failed to reach loading voltage
S2 is running and within under / over voltage trip points, but has failed to reach the configured Loading Voltage, hence it is unfit to take load.
Failed to reach loading frequency
S2 is running and within under / over frequency trip points, but has failed to reach the configured Loading Frequency, hence it is unfit to take load.
7.2 S1
S1 alarms signal that the mains supply is out of limits. In AUTO mode, the generator is called to start (if not already running) and will be placed on load when available. If the S1 supply fails while the S2 is running in MANUAL mode, the 331 ATS module transfers load to S2 supply. Should an input configured to Simulate S1 Available be active, the mains failure detection is inhibited.
S1 failure
Combined message to indicate the failure of the mains supply or activation of an input configured to Auxiliary S1 Failure.
S1 Under Frequency trip
The S1 supply is below the configured Under Frequency trip level.
S1 Under Voltage trip
The S1 supply is below the configured Under Voltage trip level.
S1 Over Frequency trip
The S1 supply is above the configured Over Frequency trip level.
S1 Over Voltage trip
The S1 supply is above the configured Over Voltage trip level.
7.3 PLANT BATTERY
Plant battery alarms are Warning alarms only. The module displays the fault but no further action is taken.
Under Voltage warning
The battery supply is below the configured Under Voltage warning level.
Under Voltage warning
The battery supply is above the configured Over Voltage warning level.
Page 28
Front Panel Configuration
28
8 FRONT PANEL CONFIGURATION
This configuration mode allows the operator limited customising of the way the module operates.
Use the module’s navigation buttons to traverse the menu and make value changes to the parameters:
Increase value / next item
Edit /Accept value. Press and hold to exit editor.
Decrease value / next item
Next page
Page 29
Front Panel Configuration
29
8.1 ACCESSING THE FRONT PANEL EDITOR (FPE)
To enter the ‘configuration mode’ press Press and hold the button
NOTE:- To exit the front panel configuration editor and activate your changes, press and hold the
button. Ensure you have saved any changes you have made by pressing the  button first.
NOTE:- When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
security.
8.1.1 EDITING A PARAMETER
Press (+) to select the next parameter or (-) to select the previous parameter When viewing the parameter to be changed, press the button. The value begins to flash.
Press (+) or (-) to adjust the value to the required setting.
Press the save the current value, the value ceases flashing.
Press and hold the button to exit the editor, the configuration icon will be removed from the display.
:
8.2 ADJUSTABLE PARAMETERS (CONFIGURATION EDITOR)
When viewing the configuration editor, Press to select the required ‘page’ as listed below.
Front Panel Configuration Editor (Factory default settings are shown in bold italicised text)
CONFIGURATION PARAMETERS – MODULE (Page 1)
101 Contrast 000 (%) 102 Display mode Icon only (1), English (0)n 103 S1 Option Generator (1), Mains (0) 104 S1 Summary screen phase display 1-3 105 S2 Option Generator (1), Mains (0) 106 S2 Summary screen phase display 1-3 107 Lamp test at power up On (1), Off (0) 108 Power up in auto On (1), Off (0) 109 Enable transfer by buttons On (1), Off (0) 110 Test mode On Load (1), Off Load (0)
CONFIGURATION PARAMETERS – APPLICATION (Page 2)
201 Breaker Type Scheme B (1), Scheme A(0) 202 Check Sync On (1), Off (0) 203 Return to Programmed Transition On (1), Off (0) 204 Display mode Icon only (1), English (0)
Page 30
Front Panel Configuration
30
CONFIGURATION PARAMETERS – INPUTS (Page 3)
301 Digital Input A Source 0 (Input Source List) 302 Digital Input A Polarity 0 (Input Polarity List) 303 Digital Input B Source 0 (Input Source List) 304 Digital Input B Polarity 0 (Input Polarity List) 305 Digital Input C Source 0 (Input Source List) 306 Digital Input C Polarity 0 (Input Polarity List) 307 Digital Input D Source 0 (Input Source List) 308 Digital Input D Polarity 0 (Input Polarity List)
CONFIGURATION PARAMETERS – OUTPUTS (Page 4)
401 Digital Output A Source 0 (Output Source List) 402 Digital Output A Polarity 0 (Output Source Polarity) 403 Digital Output B Source 0 (Output Source List) 404 Digital Output B Polarity 0 (Output Source Polarity) 405 Digital Output C Source 0 (Output Source List) 406 Digital Output C Polarity 0 (Output Source Polarity) 407 Digital Output D Source 0 (Output Source List) 408 Digital Output D Polarity 0 (Output Source Polarity) 409 Digital Output E Source 0 (Output Source List) 410 Digital Output E Polarity 0 (Output Source Polarity) 411 Digital Output F Source 0 (Output Source List) 412 Digital Output F Polarity 0 (Output Source Polarity) 413 Digital Output G Source 0 (Output Source List) 414 Digital Output GPolarity 0 (Output Source Polarity) 415 Digital Output H Source 0 (Output Source List) 416 Digital Output H Polarity 0 (Output Source Polarity)
CONFIGURATION PARAMETERS – TIMERS (Page 5)
501 S1 Transient Delay 509 Breaker trip pulse 502 Start Delay 510 Return delay 503 Warming time 511 Cooling time 504 S2 Fail delay 512 S2 transient delay 505 Elevator Delay 513 Fail to stop enable 506 Non-sync transfer time 514 Fai to stop delay 507 Check sync transfer time 515 LCD Page timer 508 Breaker close pulse 516 LCD Scroll timer
CONFIGURATION PARAMETERS – S1 (Page 6)
601 Immediate S1 dropout On (1), Off (0) 602 AC system 0 (AC System) 603 Under voltage enable On (1), Off (0) 604 Under voltage trip 0 V 605 Under voltage return 0 V 606 Over voltage enable On (1), Off (0) 607 Over voltage return 0 V 608 Over voltage trip 0 V 609 Under frequency enable On (1), Off (0) 610 Under frequency trip 0.0 Hz 611 Under frequency return 0.0 Hz 612 Over frequency enable On (1), Off (0) 613 Over frequency return 0.0 Hz 614 Over frequency trip 0.0 Hz
Page 31
Front Panel Configuration
31
CONFIGURATION PARAMETERS – S2 (Page 7)
701 Immediate S2 dropout On (1), Off (0) 702 Under voltage enable (Generator Option) On (1), Off (0) 703 Under voltage trip (Generator Option) 0 V 704 Loading voltage (Generator Option) 0 V 705 Over voltage enable (Generator Option) On (1), Off (0) 706 Over voltage trip (Generator Option) 0 V 707 Under frequency enable (Generator Option) On (1), Off (0) 708 Under frequency trip (Generator Option) 0.0 Hz 709 Loading frequency (Generator Option) 0.0 Hz 710 Over frequency enable (Generator Option) On (1), Off (0) 711 Over frequency trip (Generator Option) 0.0 Hz 712 Under voltage enable (Mains Option) On (1), Off (0) 713 Under voltage (Mains Option) 0 V 714 Under voltage return (Mains Option) 0 V 715 Over voltage enable (Mains Option) On (1), Off (0) 716 Over voltage return (Mains Option) 0 V 717 Over voltage trip (Mains Option) 0 V 718 Under frequency enable (Mains Option) On (1), Off (0) 719 Under frequency (Mains Option) 0.0 Hz 720 Under frequency return (Mains Option) 0.0 Hz 721 Over frequency enable (Mains Option) On (1), Off (0) 722 Over frequency return (Mains Option) 0.0 Hz 723 Over frequency trip (Mains Option) 0.0 Hz
CONFIGURATION PARAMETERS – PLANT BATTERY (Page 8)
801 Under voltage enable On (1), Off (0) 802 Under voltage 0.0 V 803 Under voltage return 0.0 V 804 Under voltage delay 0.00.00 805 Over voltage enable On (1), Off (0) 806 Over voltage return 0.0 V 807 Over voltage trip 0.0 V 808 Over voltage delay 0.00.00
CONFIGURATION PARAMETERS – SCHEDULER (Page 9)
901 Enable scheduler On (1), Off (0) 902 On or off load On (1), Off (0) 903 Start time 0:00 904 Day 1-7 (Day, 1=Monday) 905 Duration 0:00
CONFIGURATION PARAMETERS – TIME (Page 10)
1001 Time of day 0:00 1002 Day of week 1-7 (Day, 1=Monday) 1003 Start time 0:00
Page 32
Front Panel Configuration
32
Parameters with multiple choices use the following identification tables for the parameter values:
INPUT SOURCE LIST
0 Not used 1 Alarm Reset 2 Alarm Mute 3 Auto Restore Inhibit 4 Auto Start Inhibit 5 Auxiliary S2 Available 6 Auxiliary S1 Fail 7 S2 Load Inhibit 8 S2 Closed Auxiliary
9 Inhibit Scheduled Run 10 Lamp Test 11 Load Shedding 12 S1 Closed Auxiliary 13 S1 Load Inhibit 14 Open / Close S2 15 Open / Close S1 16 Panel Lock 17 Remote Start off-load 18 Remote Start on-load 19 Simulated S1 available 20 Simulated S2 available
INPUT POLARITY LIST INPUT ARMING LIST
Index Action Index Arming
0 Close to Activate 0 Always
1 Open to Activate 1 From Safety On
2 From Starting
OUTPUT POLARITY LIST
3 Never
Index Arming
0 Energise
INPUT ACTION LIST
1 De-energise
Index Action
0 Electrical Trip
AC SYSTEM
1 Shutdown
Index Type
2 Warning 0 3 phase 4 wire 1 Single phase 2 wire 2 3 phase 3 wire 3 2 phase 3 wire (L1-L2) 4 2 phase 3 wire (L1-L3) 5 3 phase 4 wire (Delta)
Page 33
Front Panel Configuration
33
OUTPUT SOURCE LIST
0 Not Used 1 Audible Alarm 2 Battery High Voltage 3 Battery Low Voltage 4 Close S2 Output 5 Close S2 Output Pulse 6 Close S1 Output 7 Close S1 Output Pulse 8 Close to N Output
9 Close to N Output Pulse 10 Common Warning 11 Cooling Down 12 Digital Input A 13 Digital Input B 14 Digital Input C 15 Digital Input D 16 Elevator Control 17 Fail to start 18 Fail to stop 19 Fail to reach loading voltage 20 Fail to reach loading frequency 21 S2 Available 22 S2 Failure Latched 23 S2 Failure Unlatched 24 S2 In Limits 25 S2 Load Inhibited 26 S2 ready 27 S1 Failure unlatched 28 S1 Failure latched 29 S1 High Frequency 30 S1 High Voltage 31 S1 In Limits 32 S1 Load Inhibited 33 S1 Low Frequency 34 S1 Low Voltage 35 Return Delay 36 Open S2 Output 37 Open S2 Output Pulse 38 Open S1 Output 39 Open S1 Output Pulse 40 Scheduled Run 41 Start And Run S2 42 Start Delay 43 Waiting For S2 44 Waiting For Manual Restore 45 Warming Up
Page 34
Maintenance, Spares, Repairs, Servicing, Warranty, Disposal
34
9 MAINTENANCE, SPARES, REPAIR AND SERVICING
The DSE331 Series controller is designed to be Fit and Forget. As such, there are no user serviceable parts within the controller. In the case of malfunction, you should contact your original equipment supplier (OEM).
9.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE
If you require additional plugs from DSE, please contact our Sales department using the part numbers below.
Module terminal designation Plug description Part No.
1-10
10 way 5.08mm 007-450
11-14
4 way 5.08mm 007-444
15-22
S2 S1
8 way 7.62mm 007-454
23-28
6 way 5.08mm 007-446
9.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE
Item Description Part No.
DSE331 / DSE3xx series fixing clips (packet of 2) 020-294
9.3 PURCHASING SEALING GASKET FROM DSE
The optional sealing gasket is not supplied with the controller but can be purchased separately.
Item Description Part No.
DSE331 silicon sealing gasket 020-313
Page 35
Maintenance, Spares, Repairs, Servicing, Warranty, Disposal
35
10 WARRANTY
DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any applicable warranty, you are referred to your original equipment supplier (OEM).
11 DISPOSAL
11.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
Directive 2002/96/EC If you use electrical and electronic equipment you must store, collect, treat, recycle and dispose of WEEE separately from your other waste.
11.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES)
Directive 2002/95/EC:2006 To remove specified hazardous substances (Lead, Mercury, Hexavalent Chromium, Cadmium, PBB & PBDE´s)
Exemption Note: Category 9. (Monitoring & Control Instruments) as defined in Annex 1B of the WEEE directive will be exempt from the RoHS legislation. This was confirmed in the August 2005 UK´s Department of Trade and Industry RoHS REGULATIONS Guide (Para 11).
Despite this exemption DSE has been carefully removing all non RoHS compliant components from our supply chain and products. When this is completed a Lead Free & RoHS compatible manufacturing process will be phased into DSE production.
This is a process that is almost complete and is being phased through different product groups.
Page 36
Appendix
36
12 APPENDIX
12.1 COMMUNICATIONS OPTION CONNECTIONS
12.1.1 DESCRIPTION
The DSE Configuration Suite software allows the controller to communicate with a PC. The computer connects to the module as shown below and allows easy adjustment of the operating parameters and firmware update of the controller.
12.1.2 PC TO CONTROLLER (DIRECT) CONNECTION
To connect a 331 ATS module to a PC the following items are required: -
• DSE331 series module
• Configuration Suite software (Supplied on configuration suite
software CD or available from www.deepseaplc.com).
• USB cable Type A to Type B.
NOTE:- The DC supply must be connected to the module for configuration by PC.
NOTE:- Refer to DSE Configuration Suite software Manual (057-149) for further details on configuring
the module by PC.
Page 37
This Page is Intentionally blank
37
Page 38
This Page is Intentionally blank
38
Loading...