DSE 7560 Installation Instructions Manual

DEEP SEA ELECTRONICS
7560 INST AL LA T IO N IN ST R UC TI ON S
053-054
ISSUE 4
.
Press the Stop/Reset and Info buttons simultaneously.
If a module security PIN has been set, the PIN number request is then
shown :
Press
(up) or
(down) to adjust it to the correct value.
Press (right) when the first digit is correctly entered. The digit you have just entered will now show ‘#’ for security.
Repeat this process for the other digits of the PIN number. You can press
(left) if you need to
move back to adjust one of the previous digits.
When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, you must re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed :
EDITING A PARAMETER
Enter the editor as described above.
Press the left or right buttons to cycle to the section you wish to view/change.
To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that
you are editing the value.
Press the up or down buttons to change the parameter to the required value.
Press to save the value. The parameter ceases flashing to indicate that it has been saved.
To exit the editor at any time, press the button.
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
LO CALL (from UK BT landlines) :
Telephone 0845 260 8933
Email: support@deepseaplc.com
Web:
www.deepseaplc.com
Deep Sea Electronics inc.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) : Tel: 1 866 636 9703
Email: dsesales@deepseausa.com
Web: www.deepseausa.com
Deep Sea Electronics Plc.
(Far East)
Tel:+66 (0) 2191 8052
Fax: +66 (0) 81805 5625
Email: support@deepseaplc.com
Web: www.deepseaplc.com
NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure security. NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security. NOTE: More comprehensive module configuration is possible using the 75xx series PC configuration software. Please contact us for further details NOTE: The contents of the tables overleaf may differ depending on the actual module configuration.
TYPICAL WIRING DIAGRAM
ADJUSTABLE PARAMETERS.
Front Panel Configuration Editor
(Factory default settings are shown in bold italicised text)
Section
Parameter
as shown on
Values
Timers
Mains Transient Delay
0 -10s (2s)
Start Delay
0– 60m (5s)
Transfer Delay
0– 10s (0.7s)
Return Delay
0– 60m (30sa0
Low battery Delay
0– 10m (1m)
High battery Delay
0– 10m (1m)`
Mains
Mains Under Voltage Alarm 50V-360V ph-N (184V)
(184V)(184V)
(184V)
Mains Over Voltage Alarm 50V-360V ph-N (276V)
(276V)(276V)
(276V)
Mains Under Frequency 0Hz-75Hz (45Hz)
(45Hz)(45Hz)
(45Hz)
Mains Over Frequency 0Hz-75Hz (55Hz)
(55Hz)(55Hz)
(55Hz)
System
Plant Battery Under Volt Alarm 0-40V (10V)
(10V)(10V)
(10V)
Plant Battery Over Alarm 0-40V (30V)
(30V)(30V)
(30V)
Misc
Language English, Other
Alternative Frequency Enable Disable
DisableDisable
Disable
Alternative Voltage Enable Disable
DisableDisable
Disable
AC System
3 phase 4 wire
3 phase 4 wire3 phase 4 wire
3 phase 4 wire
Single phase 2 Wire 3 phase 3 wire 2 phase 3 wire L1 & L2 3 phase 4 wire ED 2 phase 3 wire L1 & L3
Contrast
l
Date and Time dd mmm yyyy hh:mm
Auto Scroll Time 0-10s (2s)
(2s)(2s)
(2s)
Mains CT Primary Rating 5A- 6000A (600A)
(600A)(600A)
(600A)
Mains CT Secondary Rating 1A, 5A (5A)
(5A)(5A)
(5A)
Load Ramp Rate
0.1%-100% (
2.0%)
2.0%)2.0%)
2.0%)
(% per sec)
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
The ‘running’ editor can be entered while the engine is running. All protections remain active if the engine is running while the running editor is entered.
Press and hold the button to enter the running editor.
EDITING A PARAMETER
Enter the editor as described above.
Press the left or right buttons to cycle to the section you wish to view/change.
Press the up
or down
buttons to change the parameter to the required value.
To save paremeters scroll to `save changes and exit followed by the down buttton
To cancel changes scroll to `Abandon changes and exit followed by the down
button
ADJUSTABLE PARAMETERS (Running editor)
Running Editor
Section Parameter as shown on display
Factory Settings
DISPLAY Contrast
l
Language
English
Load power factor
%
Load parallel power
%
Enable commissioning screens
No
Voltage adjust
(manual mode only engine running bus breaker open )
Raise Steady Lower
Frequency adjust
(manual mode only engine running bus breaker open )
Raise Steady Lower
Enable mains decoupling
No
Abandon changes and exit
Save changes and exit
DIMENSIONS
240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”)
PANEL CUTOUT
:
220mm x 160mm (8.7” x 6.3”)