ACCESSING THE FRONT PANEL CONFIGURATION EDITOR
• Press the Stop/Reset and Info buttons simultaneously.
• If a module security PIN has been set, the PIN number request is then
shown :
• Press
(up) or
(down) to adjust it to the correct value.
• Press (right) when the first digit is correctly entered. The digit you have just entered will now
show ‘#’ for security.
•
Repeat this process for the other digits of the PIN number. You can press
(left) if you need to
move back to adjust one of the previous digits.
•
When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is
not correct, you must re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :
• Enter the editor as described above.
• Press the left or right buttons to cycle to the section you wish to view/change.
• To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that
you are editing the value.
• Press the up or down buttons to change the parameter to the required value.
• Press to save the value. The parameter ceases flashing to indicate that it has been saved.
• To exit the editor at any time, press the button.
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
LO CALL (from UK BT landlines) :
Telephone 0845 260 8933
Email: support@deepseaplc.com
Deep Sea Electronics inc.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) : Tel: 1 866 636 9703
Email: dsesales@deepseausa.com
Web: www.deepseausa.com
Deep Sea Electronics Plc.
(Far East)
Tel:+66 (0) 2191 8052
Fax: +66 (0) 81805 5625
Email: support@deepseaplc.com
Web: www.deepseaplc.com
NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to
ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or
automatically) to ensure security.
NOTE: More comprehensive module configuration is possible using the 75xx series PC
configuration software. Please contact us for further details
NOTE: The contents of the tables overleaf may differ depending on the actual module
configuration.
![](/html/17/17d3/17d386915ec0c34b3ddf5829b0c37fd7d5382e78d82302145f8c2246d907804c/bg2.png)
Front Panel Configuration Editor
(Factory default settings are shown in bold italicised text)
Mains Transient Delay
0 -10s (2s)
Start Delay
0– 60m (5s)
Transfer Delay
0– 10s (0.7s)
Return Delay
0– 60m (30sa0
Low battery Delay
0– 10m (1m)
High battery Delay
0– 10m (1m)`
Mains Under Voltage Alarm 50V-360V ph-N (184V)
(184V)(184V)
(184V)
Mains Over Voltage Alarm 50V-360V ph-N (276V)
(276V)(276V)
(276V)
Mains Under Frequency 0Hz-75Hz (45Hz)
(45Hz)(45Hz)
(45Hz)
Mains Over Frequency 0Hz-75Hz (55Hz)
(55Hz)(55Hz)
(55Hz)
Plant Battery Under Volt Alarm 0-40V (10V)
(10V)(10V)
(10V)
Plant Battery Over Alarm 0-40V (30V)
(30V)(30V)
(30V)
Language English, Other
Alternative Frequency Enable Disable
DisableDisable
Disable
Alternative Voltage Enable Disable
DisableDisable
Disable
3 phase 4 wire
3 phase 4 wire3 phase 4 wire
3 phase 4 wire
Single phase 2 Wire
3 phase 3 wire
2 phase 3 wire L1 & L2
3 phase 4 wire ED
2 phase 3 wire L1 & L3
Contrast
l
Date and Time dd mmm yyyy hh:mm
Auto Scroll Time 0-10s (2s)
(2s)(2s)
(2s)
Mains CT Primary Rating 5A- 6000A (600A)
(600A)(600A)
(600A)
Mains CT Secondary Rating 1A, 5A (5A)
(5A)(5A)
(5A)
Load Ramp Rate
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
• The ‘running’ editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
• Press and hold the button to enter the running editor.
• Enter the editor as described above.
• Press the left or right buttons to cycle to the section you wish to view/change.
• Press the up
or down
buttons to change the parameter to the required value.
• To save paremeters scroll to `save changes and exit followed by the down buttton
• To cancel changes scroll to `Abandon changes and exit followed by the down
button
ADJUSTABLE PARAMETERS (Running editor)
Running Editor
Section Parameter as shown on display
Factory Settings
DISPLAY Contrast
l
Enable commissioning screens
No
(manual mode only engine running bus breaker open )
(manual mode only engine running bus breaker open )
Enable mains decoupling
No
240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”)
:
220mm x 160mm (8.7” x 6.3”)