DSE 335 Operator's Manual

Page 1
057-233 ISSUE: 1
DEEP SEA ELECTRONICS PLC
DSE335 Operator Manual
Document Number: 057-233
Author: Fady Atallah
Page 2
DSE335 Operator Manual
057-233 ISSUE: 1 Page 2 of 90
DEEP SEA ELECTRONICS PLC
Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND
Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303
E-mail: sales@deepseaplc.com Website: www.deepseaplc.com
DSE335 Operator Manual
© Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder’s written permission to reproduce any part of this publication must be addressed to Deep Sea Electronics Plc at the address above.
The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC. Any reference to trademarked product names used within this publication is owned by their respective
companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.
Amendments List
Issue Comments
Minimum Module Version Required
Minimum
Configuration Suite
Version Required
1 Initial release V4.2.22 2014.101 V1.212.3
Typeface: The typeface used in this document is Arial. Care must be taken not to mistake the upper case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.
Clarification of notation used within this publication.
NOTE
Highlights an essential element of a procedure to ensure correctness.
CAUTION!
Indicates a procedure or practice, which, if not strictly observed, results in damage or destruction of equipment.
WARNING!
Indicates a procedure or practice, which results in injury to personnel or loss of life if not followed correctly.
Page 3
DSE335 Operator Manual
Page 3 of 90 057-233 ISSUE: 1
TABLE OF CONTENTS
SECTION
PAGE
1 INTRODUCTION .................................................................................................. 6
1.1 BIBLIOGRAPHY ................................................................................................................. 7
1.1.1 INSTALLATION INSTRUCTIONS ................................................................................. 7
1.1.2 TRAINING GUIDES ...................................................................................................... 7
1.1.3 MANUALS .................................................................................................................... 7
1.1.4 THIRD PARTY DOCUMENTS ...................................................................................... 7
2 SPECIFICATIONS ............................................................................................... 8
2.1 SHORT NAMES .................................................................................................................. 8
2.2 REQUIREMENTS FOR UL CERTIFICATION ...................................................................... 8
2.3 TERMINAL SPECIFICATION .............................................................................................. 9
2.4 POWER SUPPLY REQUIREMENTS................................................................................... 9
2.4.1 MODULE SUPPLY INSTRUMENTATION DISPLAY ..................................................... 9
2.5 S1 & S2 VOLTAGE / FREQUENCY SENSING................................................................. 10
2.6 GENERATOR CURRENT SENSING ................................................................................. 10
2.6.1 V A RATING OF THE CTS ......................................................................................... 11
2.6.2 CT POLARITY ............................................................................................................ 12
2.6.3 CT PHASING ............................................................................................................. 12
2.6.4 CT CLASS.................................................................................................................. 12
2.7 INPUTS ............................................................................................................................. 13
2.7.1 DIGITAL INPUTS ....................................................................................................... 13
2.8 OUTPUTS ......................................................................................................................... 13
2.8.1 CONFIGURABLE OUTPUTS A & E ............................................................................ 13
2.8.2 CONFIGURABLE OUTPUTS B & F ............................................................................ 13
2.8.3 CONFIGURABLE OUTPUTS B & F ............................................................................ 13
2.8.4 CONFIGURABLE OUTPUTS G, H, I, J, K & L............................................................. 13
2.9 COMMUNICATION PORTS .............................................................................................. 14
2.9.1 COMMUNICATION PORT USAGE ............................................................................ 15
2.9.1.1 USB CONNECTION ............................................................................................ 15
2.9.1.2 RS232 ................................................................................................................. 16
2.9.1.3 RECOMMENDED PC RS232 SERIAL PORT ADD-ONS ..................................... 16
2.9.1.4 RECOMMENDED EXTERNAL MODEMS ............................................................ 17
2.9.1.5 RS485 ................................................................................................................. 18
2.9.1.6 RECOMMENDED PC RS485 SERIAL PORT ADD-ONS ..................................... 18
2.9.2 DSENET® FOR EXPANSION MODULES ................................................................. 19
2.10 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION ...................................... 19
2.11 DIMENSIONS AND MOUNTING .................................................................................... 20
2.11.1 DIMENSIONS............................................................................................................. 20
2.11.2 PANEL CUTOUT ........................................................................................................ 20
2.11.3 WEIGHT ..................................................................................................................... 20
2.11.4 FIXING CLIPS ............................................................................................................ 21
2.11.5 CABLE TIE FIXING POINTS ...................................................................................... 22
2.11.6 SILICON SEALING GASKET ...................................................................................... 22
2.11.8 APPLICABLE STANDARDS ....................................................................................... 23
2.11.9 ENCLOSURE CLASSIFICATIONS ............................................................................. 25
2.11.9.1 IP CLASSIFICATIONS......................................................................................... 25
2.11.9.2 NEMA CLASSIFICATIONS .................................................................................. 26
3 INSTALLATION ................................................................................................. 27
3.1 TERMINAL DESCRIPTION ............................................................................................... 27
3.1.1 DC SUPPLY, OUTPUTS G-L ...................................................................................... 28
3.1.2 CONFIGURABLE DIGITAL INPUTS A-I ...................................................................... 28
3.1.3 CONFIGURABLE DIGITAL INPUTS J-L, DSENET ..................................................... 29
3.1.4 CONFIGURABLE VOLT-FREE OUTPUTS E & F........................................................ 29
3.1.5 LOAD SWITCHING AND S2 VOLTAGE SENSING ..................................................... 29
3.1.6 S1 VOLTAGE SENSING ............................................................................................ 30
Page 4
DSE335 Operator Manual
057-233 ISSUE: 1 Page 4 of 90
3.1.7 LOAD CURRENT TRANSFORMERS ......................................................................... 30
3.1.7.1 CONNECTION TO TERMINALS 45 & 46/47 ........................................................ 31
3.1.7.2 CT CONNECTIONS ............................................................................................ 31
3.1.8 CONFIGURABLE VOLT-FREE CHANGEOVER OUTPUTS C & D ............................. 32
3.1.9 PC CONFIGURATION INTERFACE CONNECTOR .................................................... 32
3.1.10 RS485 CONNECTOR ................................................................................................. 33
3.1.11 RS232 CONNECTOR ................................................................................................. 33
3.2 TYPICAL WIRING DIAGRAM ........................................................................................... 34
3.2.1 DSE335 3 PHASE, 4 WIRE WITH RESTRICTED EARTH FAULT PROTECTION ....... 35
3.3 ALTERNATIVE TOPOLOGIES ......................................................................................... 36
3.3.1 3 PHASE, 4 WIRE WITHOUT EARTH FAULT PROTECTION .................................... 36
3.3.2 SINGLE PHASE WITH RESTRICTED EARTH FAULT ............................................... 37
3.3.3 SINGLE PHASE WITHOUT EARTH FAULT ............................................................... 37
3.3.4 2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT .............................. 38
3.3.5 2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT .............................................. 38
3.3.6 2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT .............................. 39
3.3.7 2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING ........................ 40
3.3.8 3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING .................. 41
3.4 EARTH SYSTEMS ............................................................................................................ 42
3.4.1 NEGATIVE EARTH .................................................................................................... 42
3.4.2 POSITIVE EARTH ...................................................................................................... 42
3.4.3 FLOATING EARTH .................................................................................................... 42
3.5 TYPICAL ARRANGEMENT OF DSENET® ....................................................................... 42
4 DESCRIPTION OF CONTROLS ........................................................................ 43
4.1 CONTROL PUSH-BUTTONS ............................................................................................ 45
4.2 VIEWING THE INSTRUMENT PAGES .............................................................................. 47
4.2.1 STATUS ..................................................................................................................... 48
4.2.2 S1 .............................................................................................................................. 49
4.2.3 S2 .............................................................................................................................. 49
4.2.4 MODULE .................................................................................................................... 49
4.2.5 EXPANSION .............................................................................................................. 50
4.2.6 ALARMS .................................................................................................................... 50
4.2.7 EVENT LOG ............................................................................................................... 50
4.2.8 SERIAL PORT ............................................................................................................ 51
4.2.8.1 RS232 SERIAL PORT ......................................................................................... 51
4.2.8.2 RS485 SERIAL PORT ......................................................................................... 55
4.2.9 SCHEDULER ............................................................................................................. 56
4.2.10 ABOUT....................................................................................................................... 56
4.3 VIEWING LATEST TRANSFER INFORMATION PAGE .................................................... 57
4.4 USER CONFIGURABLE INDICATORS ............................................................................ 58
4.5 OPERATION ..................................................................................................................... 59
4.6 QUICKSTART GUIDE ....................................................................................................... 59
4.6.1 STARTING S2 ............................................................................................................ 59
4.6.2 STOPPING S2 ........................................................................................................... 60
4.7 STOP/RESET ................................................................................................................... 61
4.8 MANUAL MODE ............................................................................................................... 62
4.8.1 STARTING SEQUENCE............................................................................................. 62
4.8.2 S2 AVAILABLE ........................................................................................................... 62
4.8.3 STOPPING SEQUENCE ............................................................................................ 63
4.9 AUTOMATIC MODE ......................................................................................................... 64
4.9.1 WAITING IN AUTO MODE ......................................................................................... 64
4.9.2 STARTING SEQUENCE............................................................................................. 64
4.9.3 S2 AVAILABLE ........................................................................................................... 65
4.9.4 STOPPING SEQUENCE ............................................................................................ 65
4.10 MODE SELECTION ....................................................................................................... 66
4.10.1 TEST ON LOAD ......................................................................................................... 66
4.10.1.1 STARTING SEQUENCE ...................................................................................... 66
4.10.1.2 S2 AVAILABLE .................................................................................................... 66
4.10.1.3 STOPPING SEQUENCE ..................................................................................... 66
Page 5
DSE335 Operator Manual
Page 5 of 90 057-233 ISSUE: 1
4.10.2 TEST OFF LOAD ....................................................................................................... 67
4.10.2.1 STARTING SEQUENCE ...................................................................................... 67
4.10.2.2 S2 AVAILABLE .................................................................................................... 67
4.10.2.3 STOPPING SEQUENCE ..................................................................................... 67
4.10.3 PROHIBIT RETURN ................................................................................................... 68
4.10.3.1 WAITING IN PROHIBIT RETURN........................................................................ 68
4.10.3.2 STARTING SEQUENCE ...................................................................................... 68
4.10.3.3 S2 AVAILABLE .................................................................................................... 69
4.10.3.4 STOPPING SEQUENCE ..................................................................................... 69
4.11 SCHEDULER ................................................................................................................ 70
4.11.1 STOP MODE .............................................................................................................. 70
4.11.2 MANUAL MODE ......................................................................................................... 70
4.11.3 AUTO MODE.............................................................................................................. 70
4.12 LOAD SHEDDING CONTROL ....................................................................................... 71
4.12.1 LOAD SHEDDING CONTROL .................................................................................... 71
5 PROTECTIONS.................................................................................................. 72
5.1 INDICATIONS ................................................................................................................... 73
5.2 WARNINGS ...................................................................................................................... 74
5.3 ELECTRICAL TRIPS ........................................................................................................ 75
6 FRONT PANEL CONFIGURATION ................................................................... 76
6.1 ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR ............................. 77
6.1.1 EDITING A PARAMETER ........................................................................................... 78
6.2 ADJUSTABLE PARAMETERS ......................................................................................... 79
7 COMMISSIONING.............................................................................................. 82
8 FAULT FINDING ................................................................................................ 83
8.1 STARTING ........................................................................................................................ 83
8.2 LOADING ......................................................................................................................... 83
8.3 ALARMS ........................................................................................................................... 83
8.4 COMMUNICATIONS ......................................................................................................... 84
8.5 INSTRUMENTS ................................................................................................................ 84
8.6 MISCELLANEOUS ........................................................................................................... 85
9 MAINTENANCE, SPARES, REPAIR AND SERVICING ................................... 86
9.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE .................................... 86
9.1.1 PACK OF PLUGS....................................................................................................... 86
9.1.2 INDIVIDUAL PLUGS .................................................................................................. 86
9.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE ................................................. 86
9.3 PURCHASING ADDITIONAL SEALING GASKET FROM DSE ......................................... 86
9.4 DSENET EXPANSION MODULES .................................................................................... 87
10 WARRANTY ................................................................................................... 88
11 DISPOSAL ...................................................................................................... 88
11.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) ............................... 88
Page 6
Introduction
057-233 ISSUE: 1 Page 6 of 90
1 INTRODUCTION
This document details the installation and operation requirements of the DSE335 module version 4.2 and later, part of the DSEATS® range of products. A separate document covers the DSE335 modules with firmware version prior to version 4.2.
The manual forms part of the product and must be kept for the entire life of the product. If the product is passed or supplied to another party, ensure that this document is passed to them for reference purposes. This is not a controlled document. Updates are not automatically informed. Any future updates of this document are included on the DSE website at www.deepseaplc.com
The module is designed to provide differing levels of functionality across a common platform. This allows the OEM greater flexibility in the choice of controller to use for a specific application.
The module has been designed to allow the operator to control the transfer of the load from Source 1 (S1) to Source 2 (S2), typically the mains supply and a standby generator either manually (via fascia mounted push-buttons) or automatically upon S1 failure. Additionally if configured too, the module automatically starts and stops the generator set (S2) depending upon the status of S1.
The user also has the facility to view the system operating parameters via the LCD display to monitor the supplies and indicating the operational status and fault conditions of the module.
The powerful ARM microprocessor contained within the module allows for incorporation of a range of complex features:
Text based LCD display (supporting multiple languages)
True RMS Voltage, Current and Power monitoring
Communications capability (RS485 or RS232)
Multiple AC supply monitoring
Fully configurable inputs for use as alarms or a range of different functions.
Using a PC and the DSE Configuration Suite software allows alteration of selected operational sequences, timers, alarms and operational sequences. Additionally, the module’s integral front panel configuration editor allows adjustment of this information.
A robust plastic case designed for front panel mounting houses the module. Connections are via locking plug and sockets.
Access to critical operational sequences and timers for use by qualified engineers, can be protected by a security code. Module access can also be protected by PIN code. Selected parameters can be changed from the module’s front panel.
The module is housed in a robust plastic case suitable for panel mounting. Connections to the module are via locking plug and sockets.
Page 7
Introduction
Page 7 of 90 057-233 ISSUE: 1
1.1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications are obtained from the DSE website: www.deepseaplc.com
1.1.1 INSTALLATION INSTRUCTIONS
Installation instructions are supplied with the product in the box and are intended as a ‘quick start’ guide only.
DSE Part Description
053-135 DSE335 Installation Instructions 053-032 DSE2548 LED Expansion Annunciator Installation Instructions 053-033 DSE2130 Input Expansion Installation Instructions 053-034 DSE2157 Output Expansion Installation Instructions
1.1.2 TRAINING GUIDES
Training Guides are produced to give ‘handout’ sheets on specific subjects during training sessions.
DSE
Part Description
056-005 Using CTs With DSE Products 056-022 Breaker Control 056-024 GSM Modem 056-030 Module PIN Codes
1.1.3 MANUALS
Product manuals are are downloaded from the DSE website: www.deepseaplc.com.
DSE
Part Description
057-237 DSE335 Configuration Suite PC Software Manual 057-082 DSE2130 Input Expansion Manual 057-083 DSE2157 Output Expansion Manual 057-084 DSE2548 Annunciator Expansion Manual 057-158 DSE335 Operators Manual – prior to v4.2
1.1.4 THIRD PARTY DOCUMENTS
The following third party documents are also referred to:
Reference
Description
ISBN 1-55937-879-4
IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device Function Numbers and Contact Designations. Institute of Electrical and
Electronics Engineers Inc ISBN 0-7506-1147-2 Diesel generator handbook. L.L.J.Mahon ISBN 0-9625949-3-8 On-Site Power Generation. EGSA Education Committee.
Page 8
Specifications
057-233 ISSUE: 1 Page 8 of 90
2 SPECIFICATIONS
2.1 SHORT NAMES
Short
N
ame Description
DSE3xx All modules/controllers in the DSEATS range DSE335 DSE335 module/controller
2.2 REQUIREMENTS FOR UL CERTIFICATION
Description
Specification
Screw Terminal Tightening Torque
4.5 lb-in (0.5 Nm)
Conductors
Terminals suitable for connection of conductor size 12 AWG to 26 AWG
(0.5 mm² to 2.0 mm²).
Conductor protection must be provided in accordance with NFPA 70, Article 240
Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated secondary circuit.
The communication, sensor, and/or battery derived circuit conductors shall be separated and secured to maintain at least ¼ ” (6 mm) separation from the generator and mains connected circuit conductors unless all conductors are rated 600 V or greater.
Current Inputs
Must be connected through UL Listed or Recognized isolating current
transformers with the secondary rating of 5 A maximum.
Communication Circuits
Must be connected to communication circuits of UL Listed equipment
Output Pilot Duty
0.5 A
Mounting
Suitable for use in type 1 Enclosure Type rating with surrounding air
temperature -22 ºF to +158 ºF (-30 ºC to +70 ºC)
Suitable for pollution degree 3 environments when voltage sensing inputs do not exceed 300 V. When used to monitor voltages over 300 V, a device is to be installed in an unventilated or filtered ventilation enclosure to maintain a pollution degree 2 environment.
Operating Temperature
-22 ºF to +158 ºF (-30 ºC to +70 ºC)
Storage Temperature
-40 ºF to +176 ºF (-40 ºC to +80 ºC)
Page 9
Specifications
Page 9 of 90 057-233 ISSUE: 1
2.3 TERMINAL SPECIFICATION
NOTE: For purchasing additional connector plugs from DSE, see the section entitled
Maintenance, Spares, Repair and Servicing elsewhere in this document.
Description
Specification
Connection Type
Two part connector.
Male part fitted to module
Female part supplied in module packing case ­Screw terminal, rising clamp, no internal spring.
Example showing cable entry and screw
terminals of a 10 way connector
Minimum Cable Size 0.5 mm² (AWG 24) Maximum Cable Size 2.5 mm² (AWG 10)
2.4 POWER SUPPLY REQUIREMENTS
Description
Specification
Minimum supply voltage 8V continuous Cranking dropouts
Able to survive 0V for 50mS providing the supply was at least 10V
before the dropout and recovers to 5V afterwards. Maximum supply voltage 35V continuous (60V protection) Reverse polarity protection -35V continuous
Maximum operating current
360mA at 24V
480mA at 12V Maximum standby current
96mA at 24V
126mA at 12V
2.4.1 MODULE SUPPLY INSTRUMENTATION DISPLAY
Description
Specification
Range
0 V to 70 V DC
Maximum continuous operating voltage of 35 V DC Resolution 0.1 V Accuracy 1% full scale (±0.7 V)
Page 10
Specifications
057-233 ISSUE: 1 Page 10 of 90
2.5 S1 & S2 VOLTAGE / FREQUENCY SENSING
Description
Specification
Measurement type True RMS conversion Sample Rate 5KHz or better Harmonics Up to 10th or better Input Impedance
300K ph-N Phase to Neutral 15V (minimum required for sensing frequency) to 333V AC (absolute
maximum)
Suitable for 110V to 277V nominal
(±20% for under/overvoltage detection) Phase to Phase 26V (minimum required for sensing frequency) to 576V AC (absolute
maximum)
Suitable for 190V ph-ph to 479V ph-ph nominal
(±20% for under/overvoltage detection) Common mode offset from Earth
100V AC (max) Resolution 1V AC phase to neutral
2V AC phase to phase Accuracy ±1% of full scale phase to neutral
±2% of full scale phase to phase Minimum frequency 3.5Hz Maximum frequency 75.0Hz Frequency resolution 0.1Hz Frequency accuracy ±0.2Hz
2.6 CURRENT SENSING
Description
Specification
Measurement type True RMS conversion Sample Rate 5KHz or better Harmonics Up to 10th or better Nominal CT secondary rating
5A Maximum continuous current 5A
Overload Measurement 15A for 100ms Absolute maximum overload 50A for 1 second Burden
0.5VA (0.02 current shunts) common mode offset ±2V peak plant ground to CT common terminal Resolution 25ma Accuracy ±1% of Nominal (5A) (excluding CT error)
Page 11
Specifications
Page 11 of 90 057-233 ISSUE: 1
2.6.1 V A RATING OF THE CTS
NOTE: Details for 4 mm² cables are shown for reference only. The connectors on the DSE
modules are only suitable for cables up to 2.5 mm².
The V A burden of the module on the CTs is 0.5 V A. However depending upon the type and length of cabling between the CTs and the module, CTs with a greater V A rating than the module are required.
The distance between the CTs and the
measuring module must be calculated and cross-referenced against the chart opposite to find the V A burden of the cable itself.
If the CTs are fitted within the alternator top box, the star point (common) of the CTs must be connected to system ground (earth) as close as possible to the CTs. This minimises the length of cable used to connect the CTs to the DSE module.
Example. If 1.5 mm² cable is used and the distance from the CT to the measuring module is 20 m, then the burden of the cable alone is approximately 15 V A. As the burden of the DSE controller is
0.5 V A, then a CT with a rating of at least 15 + 0.5 V = 15.5 V A must be used. If 2.5 mm² cables are used over the same distance of 20 m, then the burden of the cable on the CT is approximately 7 V A. CT’s required in this instance is at least 7.5 V A (7 + 0.5).
Page 12
Specifications
057-233 ISSUE: 1 Page 12 of 90
2.6.2 CT POLARITY
NOTE: Take care to ensure correct polarity of the CT primary as shown above. If in doubt,
check with the CT supplier.
Take care to ensure the correct polarity of the CTs. Incorrect CT orientation leads to negative kW readings when the set is supplying power. Take note that paper stick-on labels on CTs that show the orientation are often incorrectly placed on the CT (!). It is more reliable to use the labelling in the case moulding as an indicator to orientation (if available).
To test orientation, run the generator in island mode (not in parallel with any other supply) and load the generator to around 10% of the set rating. Ensure the DSE module shows positive kW for all three individual phase readings.
TO GENERATOR
TO LIGHTS
POLARITY OF CT PRIMARY
2.6.3 CT PHASING
Take particular care that the CTs are connected to the correct phases. For instance, ensure that the CT on phase 1 is connected to the terminal on the DSE module intended for connection to the CT for phase 1.
Additionally ensure that the voltage sensing for phase 1 is actually connected to generator phase 1. Incorrect connection of the phases as described above results in incorrect power factor (PF) measurements, which in turn results in incorrect kW measurements.
One way to check for this is to make use of a single-phase load. Place the load on each phase in turn, run the generator and ensure the kW value appears in the correct phase. For instance if the load is connected to phase 3, ensure the kW figure appears in phase 3 display and not in the display for phase 1 or 2.
2.6.4 CT CLASS
Ensure the correct CT type is chosen. For instance if the DSE module is providing overcurrent protection, ensure the CT is capable of measuring the overload level required to be protected against, and at the accuracy level required.
For instance, this may mean fitting a protection class CT (P10 type) to maintain high accuracy while the CT is measuring overload currents.
Conversely, if the DSE module is using the CT for instrumentation only (current protection is disabled or not fitted to the controller) then measurement class CTs can be used. Again, bear in mind the accuracy required. The DSE module is accurate to better than 1% of the full-scale current reading. To maintain this accuracy fit Class 0.5 or Class 1 CTs.
Check with the CT manufacturer for further advice on selecting the CTs.
Labelled as
p1,
k
or K
Labelled as
p2,
l
or L
Page 13
Specifications
Page 13 of 90 057-233 ISSUE: 1
2.7 INPUTS
2.7.1 DIGITAL INPUTS
Description
Specification
Number
12 Configurable negative or positive switching inputs in banks of 3 through PC Software
Arrangement Contact between input terminal and the module’s plant supply
negative or positive terminal. Low level threshold 3.2V minimum High level threshold 8.1V maximum Maximum input voltage +60V DC with respect to module’s plant supply negative terminal Minimum input voltage -2V DC with respect to module’s plant supply negative terminal Contact wetting current 7mA typical Open circuit voltage 12V typical for negative activation.
0V typical for positive activation.
2.8 OUTPUTS
NOTE: Refer to Breaker Control Training Document (DSE part 056-022) for further details
on configuring and control different type of load switching devices.
There are twelve outputs fitted to the controller
2.8.1 CONFIGURABLE OUTPUTS A & E
Description
Specification
Number 2 Type Fully configurable normally closed volt-free contacts. Rating 8A resistive at 250V AC
2.8.2 CONFIGURABLE OUTPUTS B & F
Description
Specification
Number 2 Type Fully configurable normally open volt-free contacts. Rating 8A resistive at 250V AC
2.8.3 CONFIGURABLE OUTPUTS B & F
Description
Specification
Number 2 Type Fully configurable volt-free changeover contacts. Rating 8A resistive at 250V AC
2.8.4 CONFIGURABLE OUTPUTS G, H, I, J, K & L
Description
Specification
Number 6 Type Fully configurable, supplied from DC positive terminal 2 Rating 2 A resistive continuous at 35 V
Page 14
Specifications
057-233 ISSUE: 1 Page 14 of 90
2.9 COMMUNICATION PORTS
Description
Specification
USB Port USB2.0 Device for connection to PC running DSE configuration suite only
Max distance 6m (yards) Serial Communication
RS232 and RS485 are both fitted but provide independent operation RS232 Serial
port
Non – Isolated port
Max Baud rate 115200 baud subject to S/W
TX, RX, RTS, CTS, DSR, DTR, DCD
Male 9 way D type connector
Max distance 15m (50 feet) RS485 Serial port
Isolated
Data connection 2 wire + common
Half Duplex
Data direction control for Transmit (by s/w protocol)
Max Baud Rate 115200
External termination required (120)
Max common mode offset 70V (on board protection transorb)
Max distance 1.2km (¾ mile)
Page 15
Specifications
Page 15 of 90 057-233 ISSUE: 1
2.9.1 COMMUNICATION PORT USAGE
2.9.1.1 USB CONNECTION
NOTE: The DC supply must be connected to the module for configuration by PC.
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Suite PC Software Manual.
The USB port is provided to give a simple means of connection between a PC and the controller. Using the DSE Configuration Suite Software, the operator is then able to control the module, starting or stopping the generator, selecting operating modes, etc.
Additionally, the various operating parameters (such as output volts, oil pressure, etc.) of the remote generator are available to be viewed or changed.
To connect a module to a PC by USB, the following items are required:
DSE335 Controller
DSE Configuration Suite PC Software
(Supplied on configuration suite software CD or available from www.deepseaplc.com).
USB cable Type A to Type B.
(This is the same cable as often used between a PC and a USB printer)
DSE stock this cable: PC Configuration interface lead (USB type A – type B) DSE Part No 016-125
Page 16
Specifications
057-233 ISSUE: 1 Page 16 of 90
2.9.1.2 RS232
The RS232 port on the controller supports the Modbus RTU protocol. The Gencomm register table for the controller is available upon request from the DSE Technical Support Department.
RS232 is for short distance communication (max 15m) and is typically used to connect the controller to a telephone or GSM modem for more remote communications.
Many PCs are not fitted with an internal RS232 serial port. DSE DOES NOT recommend the use of USB to RS232 convertors but can recommend PC add-ons to provide the computer with an RS232 port.
2.9.1.3 RECOMMENDED PC RS232 SERIAL PORT ADD-ONS
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
Brainboxes PM143 PCMCIA RS232 card (for laptop PCs)
Brainboxes VX-001 Express Card RS232 (for laptops and nettops PCs)
Brainboxes UC246 PCI RS232 card (for desktop PCs)
Brainboxes PX-246 PCI Express 1 Port RS232 1 x 9 Pin (for desktop
PCs)
Supplier:
Brainboxes Tel: +44 (0)151 220 2500 Web: http://www.brainboxes.com Email: Sales: sales@brainboxes.com
NB DSE Have no business tie to Brainboxes. Over many years, our own engineers have used these
products and are happy to recommend them.
Page 17
Specifications
Page 17 of 90 057-233 ISSUE: 1
2.9.1.4 RECOMMENDED EXTERNAL MODEMS
NOTE: For GSM modems a SIM card is required, supplied by your GSM network
provider
Multitech Global Modem – MultiModem ZBA (PSTN) DSE Part Number 020-252 (Contact DSE Sales for details of localisation kits for these modems)
Sierra Fastrak Xtend GSM modem kit (PSU, Antenna and modem)* DSE Part number 0830-001-01
For SMS only, a ‘normal’ voice SIM card is required. This enables the controller to send SMS messages to designated mobile phones upon status and alarm conditions.
For a data connection to a PC running the DSE Configuration Suite software, a ‘special’ CSD (Circuit Switched Data) SIM card is required in order for the modem to answer an incoming data call. Many ‘pay as you go’ services do not provide a CSD (Circuit Switched Data) SIM card.
Page 18
Specifications
057-233 ISSUE: 1 Page 18 of 90
2.9.1.5 RS485
NOTE: For a single module to PC connection and distances up to 6m (8yds) the USB connection method is more suitable and provides for a lower cost alternative to RS485 (which is more suited to longer distance connections).
The RS485 port on the series controller supports the Modbus RTU protocol. The DSE Gencomm register table for the controller is available upon request from the DSE Technical Support Department.
RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices) and allows for connection to PCs, PLCs and Building Management Systems (to name just a few devices).
One advantage of the RS485 interface is the large distance specification (1.2km when using Belden 9841 (or equivalent) cable. This allows for a large distance between the module and a PC running the DSE Configuration Suite software. The operator is then able to control the module, selecting operating modes, etc. The various operating parameters (such as output volts, currents, etc.) of the remote ATS can be viewed or changed.
2.9.1.6 RECOMMENDED PC RS485 SERIAL PORT ADD-ONS
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
Brainboxes PM154 PCMCIA RS485 card (for laptops PCs) Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’
Brainboxes VX-023 ExpressCard 1 Port RS422/485 (for laptops and nettop PCs)
Brainboxes UC320 PCI Velocity RS485 card (for desktop PCs) Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’
Brainboxes PX-324 PCI Express 1 Port RS422/485 (for desktop PCs)
Supplier:
Brainboxes Tel: +44 (0)151 220 2500 Web: http://www.brainboxes.com Email: Sales: sales@brainboxes.com
NB DSE have no business tie to Brainboxes. Over many years,our own engineers have used these products and are happy to recommend them.
Page 19
Specifications
Page 19 of 90 057-233 ISSUE: 1
2.9.2 DSENET® FOR EXPANSION MODULES
NOTE: As a termination resistor is internally fitted to the host controller, the host controller must be the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to the ‘last’ unit on the DSENet®. For connection details, you are referred to the section entitled ‘typical wiring diagram’ elsewhere in this document.
DSENet® is the interconnection cable between the host controller and the expansion module(s) and must not be connect to any device other than DSE equipment designed for connection to the DSENet®
Description
Specification
Cable type Two core screened twisted pair Cable characteristic impedance
120
Recommended cable Belden 9841
Belden 9271
Maximum cable length 1200m (¾ mile) when using Belden 9841 or direct equivalent.
600m (666 yds) when using Belden 9271 or direct equivalent. DSENet® topology “Daisy Chain” Bus with no stubs (spurs) DSENet® termination
120. Fitted internally to host controller. Must be fitted externally to the
‘last’ expansion module by the customer. Maximum expansion modules
Total 6 devices made up of DSE2130 (up to 2), DSE2157 (up to 2),
DSE2548 (up to 2)
This gives the possibility of :
Maximum 16 additional inputs (DSE2130)
Maximum 20 additional relay outputs (DSE2157)
Maximum 20 additional LED indicators (DSE2548)
2.10 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION
When an external alarm or indicator is required, this can be achieved by using the DSE Configuration Suite PC software to configure an auxiliary output for “Audible Alarm”, and by configuring an auxiliary input for “Alarm Mute” (if required). The audible alarm output activates and de-activates at the same time as the module’s internal sounder. The Alarm mute input and internal alarm mute button activate ‘in parallel’ with each other. Either signal mutes both the internal sounder and audible alarm output.
Example of configuration to achieve external sounder with external alarm mute button:
Page 20
Specifications
057-233 ISSUE: 1 Page 20 of 90
2.11 DIMENSIONS AND MOUNTING
2.11.1 DIMENSIONS
240.0 mm x 181.1 mm x 41.7 mm (9.4 ” x 7.1 ” x 1.6 ”)
2.11.2 PANEL CUTOUT
220 mm x 160 mm (8.7 ” x 6.3 ”)
2.11.3 WEIGHT
0.7 kg (1.4 lb)
Page 21
Specifications
Page 21 of 90 057-233 ISSUE: 1
2.11.4 FIXING CLIPS
NOTE: In conditions of excessive vibration, mount the module on suitable anti-vibration
mountings.
The module is held into the panel fascia using the supplied fixing clips.
Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the clip.
Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case.
Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of
the clip are inside their allotted slots.
Turn the fixing clip screws clockwise until they make contact with the panel fascia.
Turn the screws a little more to secure the module into the panel fascia. Care must be taken
not to over tighten the fixing clip screws.
Fixing clip fitted to module
Fixing clip
Page 22
Specifications
057-233 ISSUE: 1 Page 22 of 90
2.11.5 CABLE TIE FIXING POINTS
Integral cable tie fixing points are included on the rear of the module’s case to aid wiring. This additionally provides strain relief to the cable loom by removing the weight of the loom from the screw connectors, thus reducing the chance of future connection failures. Care is to be taken not to over tighten the cable tie (for instance with cable tie tools) to prevent the risk of damage to the module case.
Cable tie fixing point With cable and tie in place
2.11.6 SILICON SEALING GASKET
The supplied silicon gasket provides improved sealing between module and the panel fascia. The gasket is fitted to the module before installation into the panel fascia. Take care to ensure the gasket is correctly fitted to the module to maintain the integrity of the seal.
Gasket fitted
to module
Sealing gasket
Page 23
Specifications
Page 23 of 90 057-233 ISSUE: 1
2.11.8 APPLICABLE STANDARDS
Standard
Description
BS 4884
-1
This document conforms to BS4884-1 1992 Specification for presentation of essential information.
BS 4884
-2
This document conforms to BS4884-2 1993 Guide to content
BS 4884
-3
This document conforms to BS4884-3 1993 Guide to presentation
BS EN 60068
-2-1
(Minimum temperature)
-30 °C (-22 °F)
BS EN 60068
-2-2
(Maximum temperature)
+70 °C (158 °F)
BS EN 60950
Safety of information technology equipment, including electrical business equipment
BS EN 61000
-6-
2
EMC Generic Immunity Standard (Industrial)
BS EN 61000
-6-
4
EMC Generic Emission Standard (Industrial)
BS EN 60529
(Degrees of protection provided by enclosures)
IP65 (front of module when installed into the control panel with the optional sealing gasket) IP42 (front of module when installed into the control panel WITHOUT being sealed to the panel)
UL508
NEMA rating
(Approximate)
12 (Front of module when installed into the control panel with the supplied sealing gasket). 2 (Front of module when installed into the control panel WITHOUT being sealed to the panel)
IEEE C37.2
(Standard Electrical Power System Device Function Numbers and Contact Designations)
Under the scope of IEEE 37.2,
function numbers can also be used to
represent functions in microprocessor devices and software programs.
The controller is device number 11L-8000 (Multifunction device protecting Line (generator) –module).
As the module is configurable by the generator OEM, the functions covered by the module vary. Under the module’s factory configuration, the device numbers included within the module are :
2 – Time Delay Starting Or Closing Relay 3 – Checking Or Interlocking Relay 8 – Control Power Disconnecting Device 11 – Multifunction Device 23 – Temperature control device (USING EXPANSION MODULE) 26 – Apparatus thermal device (USING EXPANSION MODULE) 27AC – AC Undervoltage Relay 27DC – DC Undervoltage Relay 29 – Isolating Contactor Or Switch 30 – Annunciator Relay 37 – Undercurrent Or Underpower Relay (USING INTERNAL PLC EDITOR) 42 – Running Circuit Breaker 44 – Unit sequence relay 48 – Incomplete Sequence Relay
Continued overleaf...
Page 24
Specifications
057-233 ISSUE: 1 Page 24 of 90
Standard
Description
IEEE C37.2
(Standard Electrical Power System Device Function Numbers and Contact Designations)
Continued… 49 – Machine Or Transformer Thermal Relay (USING EXPANSION
MODULE) 50 – Instantaneous Overcurrent Relay 52 – AC Circuit Breaker 55 – Power Factor Relay (USING INTERNAL PLC EDITOR) 59AC – AC Overvoltage Relay 59DC – DC Overvoltage Relay 62 – Time Delay Stopping Or Opening Relay 63 – Pressure Switch 71 – Level Switch 74 – Alarm Relay 78 – Phase-angle measuring relay 79 – Reclosing relay (USING INTERNAL PLC EDITOR) 81 – Frequency Relay 83 – Automatic Selective Control Or Transfer Relay 86 – Lockout Relay
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
Page 25
Specifications
Page 25 of 90 057-233 ISSUE: 1
2.11.9 ENCLOSURE CLASSIFICATIONS
2.11.9.1 IP CLASSIFICATIONS The modules specification under BS EN 60529
Degrees of protection provided by enclosures
IP65
(Front of module when module is installed into the control panel with the optional sealing
gasket).
IP42
(front of module when module is installed into the control panel WITHOUT being sealed to the
panel)
First Digit Second Digit Protection against contact and ingress of
solid objects
Protection against ingress of water
0 No protection 0 No protection 1 Protected against ingress solid objects
with a diameter of more than 50 mm. No protection against deliberate access, e.g. with a hand, but large surfaces of the body are prevented from approach.
1 Protection against dripping water falling
vertically. No harmful effect must be produced (vertically falling drops).
2 Protected against penetration by solid
objects with a diameter of more than 12 mm. Fingers or similar objects prevented from approach.
2 Protection against dripping water falling
vertically. There must be no harmful effect when the equipment (enclosure) is tilted at an angle up to 15° from its normal position (drops falling at an angle).
3 Protected against ingress of solid objects
with a diameter of more than 2.5 mm. Tools, wires etc. with a thickness of more than 2.5 mm are prevented from approach.
3 Protection against water falling at any angle up
to 60° from the vertical. There must be no harmful effect (spray water).
4 Protected against ingress of solid objects
with a diameter of more than 1 mm. Tools, wires etc. with a thickness of more than 1 mm are prevented from approach.
4 Protection against water splashed against the
equipment (enclosure) from any direction. There must be no harmful effect (splashing water).
5 Protected against harmful dust deposits.
Ingress of dust is not totally prevented but the dust must not enter in sufficient quantity to interface with satisfactory operation of the equipment. Complete protection against contact.
5 Protection against water projected from a
nozzle against the equipment (enclosure) from any direction. There must be no harmful effect (water jet).
6 Protection against ingress of dust (dust
tight). Complete protection against contact.
6 Protection against heavy seas or powerful
water jets. Water must not enter the equipment (enclosure) in harmful quantities (splashing over).
Page 26
Specifications
057-233 ISSUE: 1 Page 26 of 90
2.11.9.2 NEMA CLASSIFICATIONS
The modules NEMA Rating (Approximate)
12
(Front of module when module is installed into the control panel with the optional sealing gasket).
2
(front of module when module is installed into the control panel WITHOUT being sealed to the
panel)
NOTE: There is no direct equivalence between IP / NEMA ratings. IP figures shown are
approximate only.
1
IP30
Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt.
2
IP31
Provides a degree of protection against limited amounts of falling water and dirt.
3
IP64
Provides a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure.
3R
IP32
Provides a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure.
4 (X)
IP66
Provides a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the formation of ice on the enclosure. (Resist corrosion).
12/12K
IP65
Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids.
13
IP65
Provides a degree of protection against dust and spraying of water, oil and non corrosive coolants.
Page 27
Installation
Page 27 of 90 057-233 ISSUE: 1
3 INSTALLATION
The module is designed to be mounted on the panel fascia. For dimension and mounting details, see the section entitled Specification, Dimension and mounting elsewhere in this document.
3.1 TERMINAL DESCRIPTION
To aid user connection, icons are used on the rear of the module to help identify terminal functions. An example of this is shown below.
NOTE: Availability of some terminals depends upon module version. Full details are given
in the section entitled Terminal Description elsewhere in this manual.
Terminals 1-8 Terminals 9-17
Terminals 18-24
Terminals 30-37 Terminals 38-41 Terminals 42-47 Terminals 48-53
USB PC Configuration
Terminals 25-29
Serial and part number label
Page 28
Installation
057-233 ISSUE: 1 Page 28 of 90
3.1.1 DC SUPPLY, OUTPUTS G-L
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
Pin
No
Description
Cable
Size
Notes
1
DC Plant Supply Input (Negative)
2.5 mm²
AWG 13
2
DC Plant Supply Input (Positive)
2.5 mm²
AWG 13
Supplies the module and DC Outputs A, B, C, D, E & F
3 Output relay G
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
4 Output relay H
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
5 Output relay I
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
6 Output relay J
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
7 Output relay K
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
8 Output relay L
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
3.1.2 CONFIGURABLE DIGITAL INPUTS A-I
Pin
No
Description
Cable
Size
Notes
9 Configurable digital input A
0.5 mm² AWG 20
Switch to negative or positive depending on configuration
10 Configurable digital input B
0.5 mm² AWG 20
Switch to negative or positive depending on configuration
11 Configurable digital input C
0.5 mm² AWG 20
Switch to negative or positive depending on configuration
12 Configurable digital input D
0.5 mm² AWG 20
Switch to negative or positive depending on configuration
13 Configurable digital input E
0.5 mm² AWG 20
Switch to negative or positive depending on configuration
14 Configurable digital input F
0.5 mm² AWG 20
Switch to negative or positive depending on configuration
15 Configurable digital input G
0.5 mm² AWG 20
Switch to negative or positive depending on configuration
16 Configurable digital input H
0.5 mm² AWG 20
Switch to negative or positive depending on configuration
17 Configurable digital input I
0.5 mm² AWG 20
Switch to negative or positive depending on configuration
Page 29
Installation
Page 29 of 90 057-233 ISSUE: 1
3.1.3 CONFIGURABLE DIGITAL INPUTS J-L, DSENET
NOTE: Terminal 24 is not used, do not connect.
Pin
No
Description
Cable
Size
Notes
18 Configurable digital input J
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
19 Configurable digital input K
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
20 Configurable digital input L
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
21 DSENet expansion B (+)
0.5 mm²
AWG 20
Use only 120 RS485 approved cable
22 DSENet expansion A (-)
0.5 mm²
AWG 20
Use only 120 RS485 approved cable
23 DSENet expansion SCR
0.5 mm²
AWG 20
Use only 120 RS485 approved cable
3.1.4 CONFIGURABLE VOLT-FREE OUTPUTS E & F
NOTE: Terminal 27 is not used, do not connect.
Pin
No.
Description
Cable
Size
Notes
25 Output relay E
1.0 mm²
AWG 18
Normally closed volt-free relay user configured (8 A resistive at 250 V AC rated)
26 Output relay E
1.0 mm²
AWG 18
Normally closed volt-free relay user configured (8 A resistive at 250 V AC rated)
28 Output relay F
1.0 mm²
AWG 18
Normally open volt-free relay user configured (8 A resistive at 250 V AC rated)
29 Output relay F
1.0 mm²
AWG 18
Normally open volt-free relay user configured (8 A resistive at 250 V AC rated)
3.1.5 LOAD SWITCHING AND S2 VOLTAGE SENSING
NOTE: The above table describes connections to a three phase, four wire alternator. For alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this manual.
Pin
No.
Description
Cable
Size
Notes
30 Output relay A
1.0 mm² AWG 18
Normally configured to control S1 contactor coil (Recommend 10A fuse)
31 Output relay A
1.0 mm² AWG 18
Normally configured to control S1contactor coil
32 Output relay B
1.0 mm² AWG 18
Normally configured to control S2 contactor coil (Recommend 10A fuse)
33 Output relay B
1.0 mm² AWG 18
Normally configured to control S2 contactor coil
34 S2 L1 (U) voltage monitoring
1.0 mm² AWG 18
Connect to S2 L1 (U) output (AC) (Recommend 2A fuse)
35 S2 L2 (V) voltage monitoring input
1.0 mm² AWG 18
Connect to S2 L2 (V) output (AC) (Recommend 2A fuse)
36 S2 L3 (W) voltage monitoring input
1.0 mm² AWG 18
Connect to S2 L3 (W) output (AC) (Recommend 2A fuse)
37 S2 Neutral (N) input
1.0 mm² AWG 18
Connect to S2 Neutral terminal (AC)
Page 30
Installation
057-233 ISSUE: 1 Page 30 of 90
3.1.6 S1 VOLTAGE SENSING
NOTE: The above table describes connections to a three phase, four wire alternator. For alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this manual.
Pin
No.
Description
Cable
Size
Notes
38 S1 L1 (R) voltage monitoring
1.0 mm²
AWG 18
Connect to S1 L1 (R) incoming supply (AC) (Recommend 2A fuse)
39 S1 L2 (S) voltage monitoring
1.0 mm²
AWG 18
Connect to S1 L1 (S) incoming supply (AC) (Recommend 2A fuse)
40 S1 L3 (T) voltage monitoring
1.0 mm²
AWG 18
Connect to S1 L1 (T) incoming supply (AC) (Recommend 2A fuse)
41 S1 Neutral (N) input
1.0 mm²
AWG 18
Connect to S1 N incoming supply (AC)
3.1.7 LOAD CURRENT TRANSFORMERS
WARNING!: Do not disconnect this plug when the CTs are carrying current. Disconnection does open circuit the secondary of the C.T.’s and dangerous voltages may then develop. Always ensure the CTs are not carrying current and the CTs are short circuit connected before making or breaking connections to the module.
NOTE: The module has a burden of 0.5VA on the CT. Ensure the CT is rated for the burden of the controller, the cable length being used and any other equipment sharing the CT. If in doubt, consult your CT supplier.
Pin
No.
Description
Cable
Size
Notes
42 CT Secondary for Load L1
2.5 mm²
AWG 13
Connect to s1 secondary of L1 monitoring CT
43 CT Secondary for Load L2
2.5 mm² AWG 13
Connect to s1 secondary of L2 monitoring CT
44 CT Secondary for Load L3
2.5 mm² AWG 13
Connect to s1 secondary of L3 monitoring CT
Page 31
Installation
Page 31 of 90 057-233 ISSUE: 1
3.1.7.1 CONNECTION TO TERMINALS 45 & 46/47
The function of terminals 45 & 46/47 change position depending upon wiring topology as follows:
Topology
Pin No.
Description
Cable Size
No earth fault measuring
45 DO NOT CONNECT
46/47
Connect to s2 of the CTs connected to L1,L2,L3,N
2.5 mm² AWG 13
Restricted earth fault measuring
45
Connect to s2 of the CTs connected to L1,L2,L3,N
2.5 mm² AWG 13
46/47
Connect to s1 of the CT on the neutral conductor
2.5 mm² AWG 13
Un-restricted earth fault measuring (Earth fault CT is fitted in the neutral to earth link)
45
Connect to s1 of the CT on the neutral to earth conductor.
2.5 mm² AWG 13
46/47
Connect to s2 of the CT on the neutral to earth link. Also connect to the s2 of CTs connected to L1, L2, L3.
2.5 mm² AWG 13
3.1.7.2 CT CONNECTIONS
p1, k or K is the primary of the CT that ‘points’ towards the SUPPLY p2, l or L is the primary of the CT that ‘points’ towards the LOAD s1 is the secondary of the CT that connects to the DSE Module’s input for the CT measuring s2 is the secondary of the CT that must be commoned with the s2 connections of all the other CTs
and connected to the CT common terminal of the module.
TO SUPPLY
TO LOAD
POLARITY OF CT PRIMARY
Labelled as
p1,
k
or K
Labelled as
p2,
l
or L
Page 32
Installation
057-233 ISSUE: 1 Page 32 of 90
3.1.8 CONFIGURABLE VOLT-FREE CHANGEOVER OUTPUTS C & D
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
Pin
No.
Description
Cable
Size
Notes
48 Output C Normally Open
1.0 mm² AWG 18
Volts free relay change-over relay user configured (8A
resistive
at 250V AC rated)
49 Output C Common
1.0 mm² AWG 18
50 Output C Normally Closed
1.0 mm² AWG 18
51 Output D Normally Open
1.0 mm² AWG 18
Volts free relay change-over relay user configured (8A
resistive
at 250V AC rated)
52 Output D Common
1.0 mm² AWG 18
53 Output D Normally Closed
1.0 mm² AWG 18
3.1.9 PC CONFIGURATION INTERFACE CONNECTOR
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
NOTE: The USB connection cable between the PC and the module must not be extended beyond 6 m (20 feet). For distances over 6 m, it is possible to use a third party USB extender. Typically, they extend USB up to 50 m (55 yards). The supply and support of this type of equipment is outside the scope of Deep Sea Electronics PLC.
CAUTION!: Care must be taken not to overload the PCs USB system by connecting more than the recommended number of USB devices to the PC. For further information, consult the PC supplier.
Description
Cable
Size
Notes
Socket for connection to PC with DSE
Configuration Suite Software
0.5 mm²
AWG 20
This is a standard USB type A to type B connector.
Page 33
Installation
Page 33 of 90 057-233 ISSUE: 1
3.1.10 RS485 CONNECTOR
Pin No.
Notes
A (-)
Two core screened twisted pair cable. 120 impedance suitable for RS485 use. Recommended cable type - Belden 9841 Max distance 1200 m (1.2 km) when using Belden 9841 or direct equivalent.
B (+)
SCR
3.1.11 RS232 CONNECTOR
Pin No.
Notes
1 Received Line Signal Detector (Data Carrier Detect) 2 Received Data 3 Transmit Data 4 Data Terminal Ready 5 Signal Ground 6 Data Set Ready 7 Request To Send 8 Clear To Send 9 Ring Indicator
View looking into the male connector on the module
Location of RS232
connector
Location of RS485 connector
Page 34
Installation
057-233 ISSUE: 1 Page 34 of 90
3.2 TYPICAL WIRING DIAGRAM
As every system has different requirements, these diagrams show only a typical system and do not intend to show a complete system.
Genset manufacturers and panel builders may use these diagrams as a starting point; however, refer to the completed system diagram provided by the system manufacturer for complete wiring detail.
Further wiring suggestions are available in the following DSE publications, available at www.deepseaplc.com.
DSE Part
Description
056-022 Breaker Control (Training guide)
Page 35
Installation
Page 35 of 90 057-233 ISSUE: 1
3.2.1 DSE335 3 PHASE, 4 WIRE WITH RESTRICTED EARTH FAULT PROTECTION
NOTE: Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults ‘after’ the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT only (Restricted to source / upstream of the CT)
Page 36
Installation
057-233 ISSUE: 1 Page 36 of 90
3.3 ALTERNATIVE TOPOLOGIES
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
The controller is factory configured to connect to a 3 phase, 4 wire Star connected alternator. This section details connections for alternative AC topologies. Ensure to configure the controller to suit the required topology.
3.3.1 3 PHASE, 4 WIRE WITHOUT EARTH FAULT PROTECTION
Page 37
Installation
Page 37 of 90 057-233 ISSUE: 1
3.3.2 SINGLE PHASE WITH RESTRICTED EARTH FAULT
NOTE: Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults ‘after’ the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT only (Restricted to source / upstream of the CT)
3.3.3 SINGLE PHASE WITHOUT EARTH FAULT
Page 38
Installation
057-233 ISSUE: 1 Page 38 of 90
3.3.4 2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT
NOTE: Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults ‘after’ the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT only (Restricted to source / upstream of the CT)
3.3.5 2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT
Page 39
Installation
Page 39 of 90 057-233 ISSUE: 1
3.3.6 2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT
NOTE: Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults ‘after’ the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT only (Restricted to source / upstream of the CT)
Page 40
Installation
057-233 ISSUE: 1 Page 40 of 90
3.3.7 2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING
Page 41
Installation
Page 41 of 90 057-233 ISSUE: 1
3.3.8 3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING
NOTE: Unrestricted Earth Fault Protection detects earth faults in the load and in the sources. Be sure to measure the natural earth fault of the site before deciding upon an earth fault alarm trip level.
Page 42
Installation
057-233 ISSUE: 1 Page 42 of 90
3.4 EARTH SYSTEMS
3.4.1 NEGATIVE EARTH
The typical wiring diagrams located within this document show connections for a negative earth system (the battery negative connects to Earth)
3.4.2 POSITIVE EARTH
When using a DSE module with a Positive Earth System (the battery positive connects to Earth), the following points must be followed:
Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
All points shown as Earth on the typical wiring diagram must connect to BATTERY
NEGATIVE (not earth).
3.4.3 FLOATING EARTH
Where neither the battery positive nor battery negative terminals are connected to earth the following points must to be followed
Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
All points shown as Earth on the typical wiring diagram must connect to BATTERY
NEGATIVE (not earth).
3.5 TYPICAL ARRANGEMENT OF DSENET®
Six (6) devices can be connected to the DSENet®, made up of the following devices :
Device
Max Number Supported
DSE2130 Input Expansion 2 DSE2157 Relay Output Expansion 2 DSE2548 LED Expansion 2
For part numbers of the expansion modules and their documentation, see section entitled DSENet Expansion Modules elsewhere in this manual.
Page 43
Description of Controls
057-233 ISSUE: 1 Page 43 of 90
4 DESCRIPTION OF CONTROLS
NOTE: The following descriptions detail the sequences followed by a module containing the standard ‘factory configuration’. Always refer to the configuration source for the exact sequences and timers observed by any particular module in the field.
CAUTION: The module may instruct an engine start event due to external influences. Therefore, it is possible for the engine to start at any time without warning. Prior to performing any maintenance on the system, it is recommended that steps are taken to remove the battery and isolate supplies.
Control of the module is via push buttons mounted on the front of the module with Start Inhibit/Reset , Manual , Auto , Mode , Alarm Mute
,
Latest Transfer
Information
,
Close/Open S1 and Close/Open S2 functions. For normal operation, these
are the only controls which need to be operated. Details of their operation are provided later in this document.
Page 44
Description of Controls
057-233 ISSUE: 1 Page 44 of 90
Menu navigation buttons
Four configurable LEDs
Select Stop
mode
Select
Manual mode
Select mode: Test On Load, Test Off Load &
Prohibit Return
Alarm Mute /
Lamp Test
Latest Transfer Information (Info)
Open/Close S2 (manual mode only)
Open/Close S1 (manual mode only)
Main status and instrumentation display
Select
Auto mode
S2 status LED. Illuminated when S2 is supplying the load.
S2 Available LED. Illuminated when the S2 is within limits and able to take load.
S2 Available LED. Illuminated when the S2 is within limits and able to take load.
S1 status LED. Illuminated when S1 is supplying the load.
Page 45
Description of Controls
Page 45 of 90 057-233 ISSUE: 1
4.1 CONTROL PUSH-BUTTONS
Icon Description
Stop
/ Reset
This button places the module into its Stop / Reset mode. This clears any alarm conditions for which the triggering criteria have been removed. If S2 is on load and the module is placed into Stop mode, the module automatically instructs the changeover device to unload the S2 source (Close S2 Output becomes inactive (if used)). If S2 is configured for a generator, the start signal given to the generator controller is also removed. If a Remote Start signal is present while operating in this mode, the remote start does not occur.
Manual
This button places the module into its Manual mode to allow manual control of the ATS functions. This starts S2 when configured as a generator, and runs it off load.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere in this document.
Auto
This button places the module into its Auto mode. This mode allows the module to control the function of S1 and S2 automatically. The module monitors the remote start input and S1 supply status and once a start request is made, a start request is given to S2 if configured to a generator and once available, placed on load. Upon removal of the starting signal, the module automatically transfers the load from S2 and remove the start signal to the generator observing the return delay timer and cooling timer as necessary. The module then awaits for the next start event. For further details, please see the more detailed description of ‘Auto operation’ elsewhere in this manual.
Mode
This button allows the user to cycle through different operating Mode and press the Tick
to accept the mode change.
The modes available are:
Test On Load: This mode allows the module to start and load S2 for test purposes. Test Off Load: This mode allows the module to start S2 and leave off load for test
purposes. Prohibit Return: This mode is used to prevent the module from returning load the
S1 until instructed. For further details, please see the more detailed description of ‘Mode operation’
elsewhere in this manual.
Page 46
Description of Controls
057-233 ISSUE: 1 Page 46 of 90
Icon Description
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the LEDs as a lamp test feature.
Latest Transfer
Information
Whilst pressing this button, the module displays the reason, time, date and duration for the latest transfer that occurred, holding this button cycles between the last S1 transfer and the last S2 transfer.
For further details, please see the more detailed description of ‘Viewing Latest Transfer Information Page’ elsewhere in this manual.
Close / Open
to S1
NOTE: This button only operates in manual mode.
Pressing the Close / Open S1 button when S1 is on load, opens the S1 load switch.
Pressing the Close / Open S1 button when S2 is on load and S1 is healthy, the S2 load switch opens, wait for the duration of the transfer delay, then closes the S1 load switch.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere in this document.
Close/Open
to S2
NOTE: This button only operates in manual mode.
Pressing the Close / Open S2 button when S2 is on load, opens the S2 load switch.
Pressing the Close / Open S2 button when S1 is on load and S2 is healthy, the S1 load switch opens, wait for the duration of the transfer delay, then closes the S2 load switch.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere in this document.
Menu navigation
Used for navigating the instrumentation, event log and configuration screens. For further details, please see the more detailed description of these items elsewhere in this manual.
Page 47
Description of Controls
Page 47 of 90 057-233 ISSUE: 1
4.2 VIEWING THE INSTRUMENT PAGES
It is possible to scroll to display the different pages of information by repeatedly operating the Next /
Previous page buttons .
Example
Status
S1
S2
Further presses of the Next Page Button returns the display to the Status page.
The complete order and contents of each information page are given in the following sections Once selected the page remains on the LCD display until the user selects a different page, or after an
extended period of inactivity (LCD Page Timer), the module reverts to the status display. If no buttons are pressed upon entering an instrumentation page, the instruments are displayed
automatically subject to the setting of the LCD Scroll Timer. The LCD Page and LCD Scroll timers are configurable using the DSE Configuration Suite Software or
by using the Front Panel Editor.
The screenshot shows the factory settings for the timers, taken from the DSE Configuration Suite Software.
Alternatively, to scroll manually through all instruments on the currently selected page, press the scroll
buttons. The ‘autoscroll’ is disabled.
To re-enable ‘autoscroll’ press the scroll buttons to scroll to the ‘title’ of the instrumentation page (ie S1). A short time later (the duration of the LCD Scroll Timer), the instrumentation display begins to autoscroll.
When scrolling manually, the display automatically returns to the Status page if no buttons are pressed for the duration of the configurable LCD Page Timer.
If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw the operator’s attention to the alarm condition.
If you want to view one of the
instruments towards the end of the list,
it may be quicker to scroll up through
the instruments rather than down!
If you want to view one of the instrument pages towards the
end of the list, it may be quicker
to scroll left through the pages
rather than right!
Page 48
Description of Controls
057-233 ISSUE: 1 Page 48 of 90
4.2.1 STATUS
This is the ‘home’ page, which is displayed when no other page has been selected, and the page that is automatically displayed after a period of inactivity (LCD Page Timer) of the module control buttons.
Contains summary information of both supplies along with different module status display.
Main Summary (Backup source)
Main Summary (Primary source)
Source supply summary
Supervisors summary
Monitors summary
This page changes with the action of the controller, when S1 is on load, S1 parameters are seen and when changing to S2 on load, the S2 parameters are shown.
No Start Request
Example of the first status screen showing no start request to S2 and S1 closed supplying the load…
S1 Closed L-N 230V 40A L-L 400V 50.0Hz
S2 Available
… and showing S2 on load.
S2 Closed L-N 229V 40A L-L 399V 50.1Hz
Press to access more status information about two supplies.
Page 49
Description of Controls
Page 49 of 90 057-233 ISSUE: 1
4.2.2 S1
Contains electrical values of S1 measured or derived from the module’s voltage and current inputs.
S1 Configuration
S1 State
S1 Summary
S1 Voltage (ph-N)
S1 Voltage (ph-ph)
S1 Frequency
S1 Current
S1 Earth Current
S1 Load (ph-N kW)
S1 Load (Total kW)
S1 Load (ph-N kV A)
S1 Load (Total kV A)
S1 Power Factor
S1 Power Factor Average
S1 Load (ph-N kvar)
S1 Load (Total kvar)
S1 Load (kW h, kV A h, kvar h)
4.2.3 S2
Contains electrical values of S2 measured or derived from the module’s voltage and current inputs.
S2 Configuration
S2 State
S2 Summary
S2 Voltage (ph-N)
S2 Voltage (ph-ph)
S2 Frequency
S2 Current
S2 Earth Current
S2 Load (ph-N kW)
S2 Load (Total kW)
S2 Load (ph-N kV A)
S2 Load (Total kV A)
S2 Power Factor
S2 Power Factor Average
S2 Load (ph-N kvar)
S2 Load (Total kvar)
S2 Load (kW h, kV A h, kvar h)
Load Control
4.2.4 MODULE
Contains information on the module configuration.
S1 Configuration
S2 Configuration
Date and Time
Battery Voltage
Page 50
Description of Controls
057-233 ISSUE: 1 Page 50 of 90
4.2.5 EXPANSION
Contains the measured value of the expansion module’s analogue inputs, this is pressure, percentage or temperature for example ‘Bulk Fuel Level’.
4.2.6 ALARMS
Contains the alarms currently active on the module. For more information please see the section entitled ‘Protections’ else where in this manual.
4.2.7 EVENT LOG
The module maintains a log of past alarms and/or selected status changes. At the time of writing, the modules log is capable of storing the last 250 log entries.
Under default factory settings, the event log only includes electrical trip alarms (The event log does not contain Warning alarms); however, this is configurable by the system designer using the DSE Configuration Suite software.
Once the log is full, any subsequent shutdown alarms overwrites the oldest entry in the log. Hence, the log always contains the most recent alarms. The module logs the alarm, along with the date and time of the event (or engine running hours if configured to do so). If the module is configured and connected to send SMS text
To view the event log, repeatedly press the next page button until the LCD screen displays the Event log :
1 Event log
S1 Failure
Warning
23 Mar 2014, 08:25:46
Press down
to view the next most recent shutdown alarm:
Continuing to press down
cycles through the past alarms after which the display shows the
most recent alarm and the cycle begins again.
To exit the event log and return to viewing the instruments, press the next page button to select the next instrumentation page.
Example showing the possible configuration of the modules event log (DSE Configuration Suite Software) This also shows the factory settings of the module.
This is event 1.
Page 51
Description of Controls
Page 51 of 90 057-233 ISSUE: 1
4.2.8 SERIAL PORT
4.2.8.1 RS232 SERIAL PORT
NOTE: Factory Default settings are for the RS232 port to be enabled with no modem connected, operating at 19200 baud, Modbus slave address 10.
This section is included to give information about the RS232 serial port and external modem (if connected).
The items displayed on this page change depending upon configuration of the module. Refer to the system supplier for further details.
Module Connected To an RS232 Telephone Modem
NOTE: Not all alarms generate a dial out command; this is dependant upon module configuration of the event log. Any event configured to be recorded in the event log causes the modem to dial out to a PC.
When the module is powered up, it sends ‘initialisation strings’ to the connected modem. It is important therefore that the modem is already powered, or is powered up at the same time as the module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the modem does not ‘hang up’.
If the module does not correctly communicate with the modem, “Modem initialising’ appears on the Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, once the modem is dialled, it answers after two rings (using the factory setting ‘initialisation strings). Once the call is established, all data is passed between the dialling PC and the module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module dials out whenever an alarm is generated.
Press the Scroll Down button view the modem
status....
Indicates that the RS232 port is
configured for modem use. It displays
‘RS232’ if no modem is configured.
Page 52
Description of Controls
057-233 ISSUE: 1 Page 52 of 90
Module Connected To an RS232 GSM Modem
NOTE: Not all alarms generate a dial out command; this is dependant upon module configuration of the event log. Any event configured to be recorded in the event log causes the modem to dial out to a PC.
NOTE: In the case of GSM modems, it is important that a DATA ENABLED SIM is used. This is often a different number than the ‘voice number’ and is often called Circuit Switched Data (CSD) by the SIM provider.
When the module is powered up, it sends ‘initialisation strings’ to the connected modem. It is important therefore that the modem is already powered, or is powered up at the same time as the module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the modem does not ‘hang up’.
If the module does not correctly communicate with the modem, “Modem initialising’ appears on the Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, once the modem is dialled, it answers after two rings (using the factory setting ‘initialisation strings). Once the call is established, all data is passed between the dialling PC and the module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module dials out whenever an alarm is generated.
Many GSM modems are fitted with a status LED to show operator cell status and ringing indicator. These are a useful troubleshooting tool.
In the case of GSM connection problems, try calling the DATA number of the SIMCARD with an ordinary telephone. After two rings, the modem answers the call and then starts ‘squealing’. If this does not happen, check all modem connections and double check with the SIM provider that it is a DATA SIM and can operate as a data modem. DATA is NOT the same as FAX or GPRS and is often called Circuit Switched Data (CSD) by the SIM provider.
Press the Scroll Down button view the modem GSM
status....
If the GSM modem is not purchased from DSE, ensure that it has been correctly set to operate at 9600 baud.
Currently connected GSM
operator and signal strength.
Page 53
Description of Controls
Page 53 of 90 057-233 ISSUE: 1
Modem Initialisation Sequence
1) The modem attempts to communicate to the module
2) If the Modem and module communicate successfully:
3) In case of communication failure between the modem and module, the modem is automatically
reset and initialisation is attempted once more:
In the case of a module that is unable to communicate with the modem, the display continuously cycles between ‘Modem Reset’ and ‘Modem Initialising’ as the module resets the modem and attempts to communicate with it again, this continues until correct communication is established with the modem. In this instance, check connections and verify the modem operation.
Module Modem Diagnostics
Modem diagnostic screens are included; press the Scroll Down button when viewing the RS232 Serial Port instruments to cycle to the available screens. If modem communication problems are experiencied, this information aids troubleshooting.
Serial Port
RTS
CTS
DSR
DTR
DCD
Line Description
RTS Request to Send Flow Control CTS Clear to Send Flow Control DSR Data Set Ready Ready to Communicate DTR Data Terminal Ready Ready to Communicate DCD Data Carrier Detect Modem is Connected
Modem Commands
Rx: OK
Tx: AT+IPR=9600 Rx: OK
Shows the state of the modem communication lines. These can
help diagnose connection problems.
Example:
RTS A dark background shows the line is active. RTS A grey background shows that the line is toggling high and low
RTS No background indicates that the line is inactive
Shows the last command sent to the
modem and the result of the command.
Page 54
Description of Controls
057-233 ISSUE: 1 Page 54 of 90
Module RS232 Port Configured For Connection to A Modbus Master
The modules operate as a modbus RTU slave device. In a modbus system, there is only one Master, typically a PLC, HMI system or PC SCADA system.
This master requests for information from the modbus slave (The module) and may (in control systems) also send request to change operating modes etc. Unless the Master makes a request, the slave is ‘quiet’ on the data link.
The factory settings are for the module to communicate at 19200 baud, modbus slave address 10.
To use the RS232 port, ensure that ‘port usage’ is correctly set using the DSE Configuration Suite Software.
‘Master inactivity timeout’ must be set to at least twice the value of the system scan time. For example if a modbus master PLC requests data from the module once per second, the timeout must be set to at least 2 seconds
The DSE MODBUS document containing register mappings inside the DSE module is available upon request from support@deepseaplc.com. Email the request along with the serial number of the DSE module to ensure the correct information is sent.
Page 55
Description of Controls
Page 55 of 90 057-233 ISSUE: 1
4.2.8.2 RS485 SERIAL PORT
NOTE: Factory Default settings are for the RS485 port to operate at 19200 baud, modbus slave address 10.
This section is included to give information about the currently selected serial port The items displayed on this pagel change depending upon configuration of the module. Refer to the
system supplier for further details.
Module RS485 Port Configured For Connection to A Modbus Master
The modules operate as a modbus RTU slave device. In a modbus system, there is only one Master, typically a PLC, HMI system or PC SCADA system.
This master requests for information from the modbus slave (The module) and may (in control systems) also send request to change operating modes etc. Unless the Master makes a request, the slave is ‘quiet’ on the data link.
The factory settings are for the module to communicate at 19200 baud, modbus slave address 10.
‘Master inactivity timeout’ must be set to at least twice the value of the system scan time. For example if a modbus master PLC requests data from the module once per second, the timeout must be set to at least 2 seconds.
The DSE MODBUS document containing register mappings inside the DSE module is available upon request from support@deepseaplc.com. Email the request along with the serial number of the DSE module to ensure the correct information is sent.
Typical Requests (Using Pseudo Code)
BatteryVoltage=ReadRegister(10,0405,1): reads register (hex) 0405 as a single register (battery volts) from slave address 10.
WriteRegister(10,1008,2,35701, 65535-35701): Puts the module into AUTO mode by writing to (hex) register 1008, the values 35701 (auto mode) and register 1009 the value 65535-35701 (the bitwise opposite of auto mode)
Shutdown=(ReadRegister(10,0306,1) >> 12) & 1): reads (hex) 0306 and looks at bit 13 (shutdown alarm present)
Warning=(ReadRegister(10,0306,1) >> 11) & 1): reads (hex) 0306 and looks at bit 12 (Warning alarm present)
ControlledShutdown=(ReadRegister(10,0306,1) >> 10) & 1): reads (hex) 0306 and looks at bit 11 (Controlled Shutdown alarm present)
ControlMode=ReadRegister(10,0304,2): reads (hex) register 0304 (control mode).
Page 56
Description of Controls
057-233 ISSUE: 1 Page 56 of 90
4.2.9 SCHEDULER
Contains the current schedule plan for S2 configured in module.
2/3 Schedule 10:39
Example of the 3
rd
scheduled operation in bank 2 for S2.
Off Load Week 3 On 12:00 Run Time 00:30
MMMM T W T F S S
T W T F S ST W T F S S
T W T F S S
4.2.10 ABOUT
Contains important information about the module and the firmware versions. This information may be asked for when contacting DSE Technical Support Department for advice.
About
Variant
335 Application
V3.0.20
USB ID
BC614E
Press to access more information about the module.
About
Bootloader V1.3.4 Analogue V2.0.0
Variant – 335
Application Version – The version of the module’s main firmware file (Updatable using the Firmware Update Wizard in the DSE Configuration Suite Software).
USB ID – Unique identifier for PC USB connection
Bootloader - Firmware Update bootloader software
version
Page 57
Description of Controls
Page 57 of 90 057-233 ISSUE: 1
4.3 VIEWING LATEST TRANSFER INFORMATION PAGE
It is possible to view the reason, time, date and duration of the latest transfer by pressing and holding the Latest Transfer Information . Holding this button cycles between the last S1 transfer and the
last S2 transfer.
S1
S1 S1
S1 Latest Transfer
Latest TransferLatest Transfer
Latest Transfer 16:53
16:5316:53
16:53
Example of the Latest Transfer page which shows that there
was a transfer cause by an S1 Under Voltage failure which lasted for 27 minutes and 13 seconds.
S2
S2S2
S2 Under Voltage
Under VoltageUnder Voltage
Under Voltage
22
22 22
22 Oct
OctOct
Oct 201
201201
2014444, 12:59:47
, 12:59:47, 12:59:47
, 12:59:47
00:27:13
00:27:1300:27:13
00:27:13
Page 58
Description of Controls
057-233 ISSUE: 1 Page 58 of 90
4.4 USER CONFIGURABLE INDICATORS
These LEDs can be configured by the user to indicate any one of
100+ different functions
based
around the following:
Indications - Monitoring of a digital input and indicating associated functioning user’s equipment - Such as Battery Charger On or Louvres Open, etc.
Warning & Electrical Trips - Specific indication of a particular warning or electrical trip condition, backed up by LCD indication - Such as S2 Under Voltage Trip, Transformer Over Temperature, etc.
Status Indications - Indication of specific functions or sequences derived from the modules operating state - Such as, Panel Locked, S2 Available, etc.
User configurable LEDs
Page 59
Description of Controls
Page 59 of 90 057-233 ISSUE: 1
4.5 OPERATION
NOTE: The following descriptions detail the sequences followed by a module containing the standard ‘factory configuration’. Always refer to the configuration source for the exact sequences and timers observed by any particular module in the field.
4.6 QUICKSTART GUIDE
This section provides a quick start guide to the module’s operation.
4.6.1 STARTING S2
NOTE: This only applies when S2 is configured as a generator supply.
First, select manual mode, this gives the start request to the external generator control…
…when S2 becomes available, press the S2 Breaker button to
transfer the load.
Page 60
Description of Controls
057-233 ISSUE: 1 Page 60 of 90
4.6.2 STOPPING S2
NOTE: This only applies when S2 is configured as a generator supply.
Select Stop/Reset mode. S2 breaker is opened and the start request is removed.
Page 61
Description of Controls
Page 61 of 90 057-233 ISSUE: 1
4.7 STOP/RESET
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not possible. Viewing the instruments and event logs is NOT affected by panel lock.
Stop mode is activated by pressing the button.
In Stop mode , the module removes S2 from load (if necessary) and removes the start signal given to the generator controller (if S2 is configured as a generator and it is running).
If S2 is configured as a generator and it does not stop after the cooling down time, the Fail To Stop alarm is activated (subject to if the Fail To Stop timer is enabled and its duration). To detect the generator (S2) is at rest the following must occur:
S2 Frequency must be zero
S2 Voltage must be zero
Any latched alarms that have been cleared are reset when Stop mode is entered.
S2 is not placed on load (or started if configured as a generator) when in Stop mode . If remote start signals are given, the input is ignored until Auto mode is entered.
Page 62
Description of Controls
057-233 ISSUE: 1 Page 62 of 90
4.8 MANUAL MODE
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not possible. Viewing the instruments and event logs is NOT affected by panel lock.
Manual mode is activated by pressing the button.
In Manual mode, the module actives an output to give a start signal to an external generator controller (if S2 is configured as a generator supply), and if required, change the state of the load switching devices. An LED indicator beside the button confirms this action.
4.8.1 STARTING SEQUENCE
NOTE: There is no start delay in this mode of operation.
As soon as the Manual mode button is pressed, the output to give a start signal to an external generator controller is activated (if S2 is configured as a generator)
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains supply) or had achieved loading voltage and frequency (if configured as a generator).
4.8.2 S2 AVAILABLE
NOTE: The load transfer signal remains inactive until S2 is seen as available. This prevents loading to a supply that has failed or is not yet available.
In Manual mode, the load is not transferred to S2 unless a ‘loading request’ is made and the S2 supply is within limits (if configured as a mains supply) or achieve Loading Voltage and Loading Frequency (if configured as a generator). A loading request can come from a number of sources.
Pressing the Close/Open S2 button
S1 supply out of limits
Activation of an auxiliary input that has been configured to remote start on load
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
As the load increases and decreases, the module may (depending upon configuration) remove non­essential loads. This is configured as part of the Load Shedding control settings in the DSE Configuration Suite Software. See section entitled Load Shedding elsewhere in this document for further details.
Page 63
Description of Controls
Page 63 of 90 057-233 ISSUE: 1
Once the load has been transferred to S2, it is not automatically transferred back to the S1 supply. To manually transfer the load back to the mains either:
Pressing the Close/Open S1 button
Pressing the Auto button to return to automatic mode.
Pressing the Start Inhibit button to return to start inhibit mode.
For further details of breaker control, see the section entitled “controls and indications” elsewhere in this manual.
4.8.3 STOPPING SEQUENCE
In manual mode, S2 continues to run until either:
Pressing the Start Inhibit button to return to start inhibit mode.
Pressing the Auto button to return to automatic mode.
Page 64
Description of Controls
057-233 ISSUE: 1 Page 64 of 90
4.9 AUTOMATIC MODE
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not possible. Viewing the instruments and event logs is NOT affected by panel lock.
Auto mode is activated by pressing the button.
In Auto mode, the module operates fully automatically, changing between the two supplies in case of failure without user intervention. An LED indicator beside the button confirms this action.
4.9.1 WAITING IN AUTO MODE
If a starting/loading request is made, the starting sequence begins. Starting/loading requests can be from the following sources:
S1 supply out of limits
Activation of an auxiliary input that has been configured to remote start on load or remote
start off load.
Activation of the inbuilt exercise scheduler.
Instruction from external remote telemetry devices using the RS232 or RS485 interface
4.9.2 STARTING SEQUENCE
To allow for ‘false’ start/load requests such as S1 brownouts, the Start Delay timer begins. There are individual start delay timers for each of the different start/load request types.
When all start/load requests are removed during the Start Delay timer, the unit returns to a stand-by state.
If a start/load request is still present at the end of the Start Delay timer, an output to give a start signal to an external generator controller is activated (if S2 is configured as a generator).
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
If a start/load request is present but the starting sequence has not begun, an input configured to ‘Auto Start Inhibit’ could be active.
Page 65
Description of Controls
Page 65 of 90 057-233 ISSUE: 1
4.9.3 S2 AVAILABLE
In Auto mode, the load is automatically transferred to S2 when it is within limits (if configured as a mains supply) or achieve loading voltage and frequency (if configured as a generator).
If a start/load request is present but S2 does not go on load, an input configured to ‘S2 Load Inhibit’ could be active.
A loading request can come from a number of sources.
S1 supply out of limits
Activation of an auxiliary input that has been configured to remote start on load
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non­essential loads. This is configured as part of the Load Shedding control settings in the DSE Configuration Suite Software. See section entitled Load Shedding elsewhere in this document for further details.
If all start/load requests are removed, the stopping sequence begins.
4.9.4 STOPPING SEQUENCE
The Return Delay timer operates to ensure that the start/load request has been permanently removed and isn’t just a short term removal. In case another start request is made during the Return Delay (or cooling down period when S2 is configured as a generator), the set returns on load.
If there are no starting requests at the end of the Return Delay timer, the load is transferred back from the S2 to the S1 supply and the Cooling timer is initiated (when S2 is configured as a generator).
The Cooling timer allows S2 (when configured as a generator) to run off load and cool sufficiently before the start signal to the external generator control unit is removed. This is particularly important where turbo chargers are fitted to the engine.
After the Cooling timer has expired, the start signal given to the external generator controller is removed..
Page 66
Description of Controls
057-233 ISSUE: 1 Page 66 of 90
4.10 MODE SELECTION
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not possible. Viewing the instruments and event logs is NOT affected by panel lock.
Pressing the Mode button sets which of the three modes below to leave the controller in.
4.10.1 TEST ON LOAD
Activate by pressing the Mode button repeatedly until Test on Load is shown on the display, then press the Tick button to confirm the change. An LED indicator beside the button confirms this
action. The Test on Load mode starts S2 (if configured as a generator) and transfers the load to S2.
4.10.1.1 STARTING SEQUENCE
As soon as the Mode is selected and confirmed by pressing the Tick button is pressed, the output to give a start signal to an external generator controller is activated (if S2 is configured as a generator)
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
4.10.1.2 S2 AVAILABLE
In Test on Load mode, the load is automatically transferred to S2 when it is within limits (if configured as a mains supply) or had achieved loading voltage and frequency (if configured as a generator).
If a start/load request is present but S2 does not go on load, an input configured to ‘S2 Load Inhibit’ could be active.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non­essential loads. This is configured as part of the Load Shedding control settings in the DSE Configuration Suite Software. See section entitled Load Shedding elsewhere in this document for further details.
4.10.1.3 STOPPING SEQUENCE
In Test on Load mode, S2 continues to run on load until either:
Pressing the Start Inhibit button to return to start inhibit mode.
Pressing the Auto button to return to automatic mode.
Page 67
Description of Controls
Page 67 of 90 057-233 ISSUE: 1
4.10.2 TEST OFF LOAD
Activate by pressing the Mode button repeatedly until Test off Load is shown on the display, then press the Tick button to confirm the change. An LED indicator beside the button confirms this
action. The Test off Load mode only starts S2 (if configured as a generator) and leave it off load.
4.10.2.1 STARTING SEQUENCE
As soon as the Mode is selected and confirmed by pressing the Tick button is pressed, the output to give a start signal to an external generator controller is activated (if S2 is configured as a generator)
If the generator fails to start during the S2 Fail Delay timer, an alarm appears on the display which shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
4.10.2.2 S2 AVAILABLE
In Test Off Load mode, the load is not transferred to S2 unless a ‘loading request’ is made and the S2 supply is within limits (if configured as a mains supply) or has achieved loading voltage and frequency (if configured as a generator). A loading request can come from a number of sources.
S1 supply out of limits
Activation of an auxiliary input that has been configured to remote start on load
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non­essential loads. This is configured as part of the Load Shedding control settings in the DSE Configuration Suite Software. See section entitled Load Shedding elsewhere in this document for further details.
4.10.2.3 STOPPING SEQUENCE
In Test off Load mode, S2 continues to run on load until either:
Pressing the Start Inhibit button to return to Start Inhibit mode.
Pressing the Auto button to return to Automatic mode.
Page 68
Description of Controls
057-233 ISSUE: 1 Page 68 of 90
4.10.3 PROHIBIT RETURN
Activate by pressing the Mode button repeatedly until Prohibit Return is shown on the display, then press the Tick button to confirm the change. An LED indicator beside the button confirms
this action. The Prohibit Return mode prevents the load being transfer back to the S1 from the S2 supply until the
module is instructed to do so.
4.10.3.1 WAITING IN PROHIBIT RETURN
If a starting/loading request is made, the starting sequence begins. Starting/loading requests can be from the following sources:
S1 supply out of limits
Activation of an auxiliary input that has been configured to Remote Start On Load or Remote
Start Off Load.
Activation of the inbuilt exercise scheduler.
Instruction from external remote telemetry devices using the RS232 or RS485 interface
4.10.3.2 STARTING SEQUENCE
To allow for ‘false’ start/load requests such as S1 brownouts, the Start Delay timer begins. There are individual Start Delay timers for each of the different start/load request types.
When all start/load requests are removed during the Start Delay timer, the unit returns to a stand-by state.
If a start/load request is still present at the end of the Start Delay timer, an output to give a start signal to an external generator controller is activated (if S2 is configured as a generator).
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
If a start/load request is present but the starting sequence has not begun, an input configured to ‘Auto Start Inhibit’ could be active.
Page 69
Description of Controls
Page 69 of 90 057-233 ISSUE: 1
4.10.3.3 S2 AVAILABLE
In Prohibit Return mode, the load is automatically transferred to S2 when it is within limits (if configured as a mains supply) or has achieved Loading Voltage and Loading Frequency (if configured as a generator).
If a start/load request is present but S2 does not go on load, an input configured to ‘S2 Load Inhibit’ could be active.
A loading request can come from a number of sources.
S1 supply out of limits
Activation of an auxiliary input that has been configured to Remote Start On Load
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non­essential loads. This is configured as part of the Load Shedding control settings in the DSE Configuration Suite Software. See section entitled Load Shedding elsewhere in this document for further details.
If all start/load requests are removed, the Stopping sequence begins.
4.10.3.4 STOPPING SEQUENCE
In Return Inhibit mode, S2 continues to run on load even if S1 has return until either:
Pressing the Start Inhibit button to return to start inhibit mode.
Pressing the Auto button to return to automatic mode.
Page 70
Description of Controls
057-233 ISSUE: 1 Page 70 of 90
4.11 SCHEDULER
The controller contains an inbuilt exercise run scheduler, capable of automatically starting and stopping the set. Up to 16 scheduled start/stop sequences can be configured in banks of 8 to either repeat on a 7-day or 28-day cycle. Scheduled runs may be on load or off load depending upon module configuration.
Example Screen capture from DSE
Configuration Suite Software showing the configuration of the Exercise Scheduler.
In this example the set starts at 09:00 on the first Monday of each month and run for 5 hours, then start at 13:30 on every Tuesday and run for 30 minutes.
4.11.1 STOP MODE
Scheduled runs do not occur when the module is in Stop mode.
4.11.2 MANUAL MODE
Scheduled runs do not occur when the module is in Manual mode.
Activation of a Scheduled Run ‘On Load’ when the module is operating Off Load in Manual
mode has no effect, the set continues to run Off Load
4.11.3 AUTO MODE
Scheduled runs operate ONLY if the module is in Auto mode with no Electrical Trip alarm present.
If the module is in Stop or Manual mode when a scheduled run begins, S2 is not started (if configured as generator). However, if the module is moved into Auto mode
during a scheduled run, S2 is called to start.
Depending upon configuration by the system designer, an external input can be used to inhibit a scheduled run.
If S2 is Off Load in Auto mode and a scheduled run configured to ‘Transfer to S2’ begins, S2 is placed On Load for the duration of the Schedule.
Page 71
Description of Controls
Page 71 of 90 057-233 ISSUE: 1
4.12 LOAD SHEDDING CONTROL
This feature may be enabled by the system designer to ensure the loading on S2 is kept to a nominal amount. Conversely as the load increases towards the maximum rating of the set, non-essential loads can be shed to prevent overload of S2.
4.12.1 LOAD SHEDDING CONTROL
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
The Load Shedding Control feature (if enabled) allows for a maximum of five load shedding steps. When S2 is about to take load, the configured number of Load Shedding Control Outputs at Startup energises. This configurable setting allows (for instance) certain loads to be removed from S2 prior to the set’s load switch being closed. This can be used to ensure the initial loading of the set is kept to a minimum, below the Load Acceptance specification of S2.
S2 is then placed on load. The Load Shedding Control scheme begins. When the load reaches the Load Shedding Trip level the Trip Delay timer starts. If S2 loading is still high when the timer expires, the first Load shedding Control output energises. When the load has been above the trip level for the duration of the timer the ‘next’ Load shedding Control output energises and so on until all Load Shedding Control outputs are energised.
If at any time the load falls back below the Load Shedding Return level, the Return Time starts. If the load remains below the return level when the timer has expired the ‘highest’ Load Shedding Control output that has been energised is de-energised. This process continues until all outputs have been de-energised. When the set enters a stopping sequence for any reason the Load Shedding control’ outputs are de- energised at the same time as the S2 load switch is signalled to open.
Page 72
Protections
057-233 ISSUE: 1 Page 72 of 90
5 PROTECTIONS
When an alarm is present, the Audible Alarm sounds and the Common alarm LED if configured illuminates.
The audible alarm can be silenced by pressing the Alarm Mute The LCD display jumps from the ‘Information page’ to display the Alarm Page
1/2 Alarm S1 Failure
Latched Warning
The LCD displays multiple alarms E.g. “S1 Failure Warning”, “Fail to Stop Warning” and “Digital Input A Electrical Trip”. These automatically scroll in the order that they occurred.
In the event of a warning alarm, the LCD displays the appropriate text. If an electrical trip then occurs, the module again displays the appropriate text. Example:-
Alarm 1/2
Fail to Stop Unlatched Warning
Alarm 2/2
Digital Input A Unlatched Electrical Trip
The nature of alarm, e.g. S1 Failure
The type of alarm. E.g. Electrical Trip or warning
Number of present alarms. This is alarm 1 of a total of 2 present alarms
If the alarm automatically resets (unlatched) or
needs to be manually reset (latched).
Page 73
Protections
Page 73 of 90 057-233 ISSUE: 1
5.1 INDICATIONS
Indications are non-critical and often status conditions. They do not appear on the LCD of the module as a text message. However, an output or LED indicator can be configured to draw the operator’s attention to the event.
Example
Input configured for indication.
The LCD text does not appear on the module display but can be added in the configuration to remind the system designer what the input is used for.
As the input is configured to Indication there is no alarm generated.
LED Indicator to make LED1 illuminate when Digital Input A is active.
The Insert Card Text allows the system designer to print an insert card detailing the LED function.
Sample showing operation of the LED.
Page 74
Protections
057-233 ISSUE: 1 Page 74 of 90
5.2 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the system, they serve to draw the operators attention to an undesirable condition.
Example 1/2 Alarm S1 Failure
Latched Warning
In the event of an alarm the LCD jumps to the alarms page, and scroll through all active warnings and shutdowns.
By default, warning alarms are self-resetting when the fault condition is removed. However some warning alarms are latched and need to be reset manually.
Display
Reason
Auxiliary Inputs If an auxiliary input has been configured as a warning the appropriate
LCD message is displayed and the COMMON ALARM LED illuminates.
Battery Under Voltage The DC supply has fallen below the low volts setting level for the
duration of the low battery volts timer
Battery Over Voltage The DC supply has risen above the high volts setting level for the
duration of the high battery volts timer
Calibration Lost The module has lost its calibration settings and must be sent back to
DSE to be re-calibrated.
Expansion Inputs If an expansion input has been configured as a warning the appropriate
LCD message is displayed and the COMMON ALARM LED illuminates.
Fail To Start S2 has not reached the configured limits or loading voltage and
frequency before the S2 Fail Delay timer has expired.
Fail To Stop The module has detected a condition that indicates that S2 is present
when it has been instructed to stop. Loading Voltage Not Reached
Indicates that the S2 voltage is not above the configured
loading
voltage. S2 does not take load when the alarm is present after the
safety timer.
NOTE: Only applicable when S2 is configured as a generator
supply.
Loading Frequency Not Reached
Indicates that the S2 frequency is not above the configured
loading
frequency. S2 does not take load when the alarm is present after the
safety timer.
NOTE: Only applicable when S2 is configured as a generator
supply.
Page 75
Protections
Page 75 of 90 057-233 ISSUE: 1
Display
Reason
PLC Functions If a PLC Function has been configured as a warning the appropriate
LCD message is displayed and the COMMON ALARM LED illuminates. S1 Breaker Auxiliary Fail
Indicates that the
S1 Closed Auxiliary
input has not activated along with
the Close S1 Output or Open S1 Output, or the input has activated
when the output was not energised. S1 Failure Unlatched The module has detected that S1 has failed for either an under/over
voltage/frequency condition. The unlatched alarm is automatically
cleared upon S1 returning to an available state. S1 Phase Rotation The module has detected a wrong phase sequence for S1. S2 Breaker Auxiliary Fail
Indicates that the
S2
Closed Auxiliary
input has not activated along with
the Close S2 Output or Open S2 Output, or the input has activated
when the output was not energised. S2 Failure Unlatched The module has detected that S2 has failed for either an under/over
voltage/frequency condition. The unlatched alarm is automatically
cleared upon S2 returning to an available state. S2 Phase Rotation The module has detected a wrong phase sequence for S2.
5.3 ELECTRICAL TRIPS
Electrical trips are latching unload and stop S2 (if configured as a generator) but in a controlled manner. On initiation of the electrical trip condition the module de-energises the ‘Close S2 Output’ to remove the load from S2. Once this has occurred the module starts the Cooling timer and allow the generator to cool down and shut off. The alarm must be accepted and cleared, and the fault removed to reset the module.
Example 1/2 Alarm Digital Input A
Latched Electrical Trip
Electrical trips are latching alarms and unload and stop S2 (if configured as a generator). To clear these alarms the STOP button is pressed
Display
Reason
Auxiliary Inputs If an auxiliary input has been configured as an electrical trip, the
appropriate LCD message is displayed and the COMMON ALARM LED
illuminates. Expansion Inputs If an expansion input has been configured as an electrical trip, the
appropriate LCD message is displayed and the COMMON ALARM LED
illuminates. PLC Functions If a PLC Function has been configured as an electrical trip, the
appropriate LCD message is displayed and the COMMON ALARM LED
illuminates. S1 Breaker Auxiliary Fail
Indicates that the
S1
Closed Auxiliary
input has not activated along with
the Close S1 Output or Open S1 Output, or the input has activated
when the output was not energised. S1 Phase Rotation The module has detected a wrong phase sequence for S1. S2 Failure Unlatched The module has detected that S2 has failed for either an under/over
voltage/frequency condition. The unlatched alarm is automatically
cleared upon S2 returning to an available state. S2 Phase Rotation The module has detected a wrong phase sequence for S2.
Page 76
Front Panel Configuration
057-233 ISSUE: 1 Page 76 of 90
6 FRONT PANEL CONFIGURATION
This configuration mode allows the operator limited customising of the way the module operates. Use the module’s navigation buttons to traverse the menu and make value changes to the
parameters:
Previous page
Increase value / next item
Decrease value / next item
Page 77
Front Panel Configuration
Page 77 of 90 057-233 ISSUE: 1
6.1 ACCESSING THE
MAIN
FRONT PANEL CONFIGUR
ATION EDITOR
Press and hold the Stop and Tick buttons simultaneously to enter the editor. If a module security PIN has been set, the PIN number request is then shown :
Editor
# # # #
Press the Tick button, the first ‘#’ changes to ‘0’. Press (up or down) to adjust it to the correct value.
Press (right) when the first digit is correctly entered. The digit entered is now shown as ‘#’ for security.
Repeat this process for the other digits of the PIN number. Press (left) to move back and adjust one of the previous digits.
When the Tick button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed :
Editor - Display
Contrast
54 %
NOTE: The PIN number is not set by DSE when the module leaves the factory. If the module has a PIN code set, this has been affected by the ATS supplier who must be contacted if the code is required. If the code has been ‘lost’ or ‘forgotten’, the module must be returned to the DSE factory to have the module’s code removed. A charge is applied for this procedure. NB - This procedure cannot be performed away from the DSE factory.
Page 78
Front Panel Configuration
057-233 ISSUE: 1 Page 78 of 90
6.1.1 EDITING A PARAMETER
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security.
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details on configuring, monitoring and control.
Enter the editor as described above.
Press the (left) or (right) buttons to cycle to the section to view/change.
Press the (up or down) buttons to select the parameter to view/change within the currently selected section.
To edit the parameter, press the Tick
button to enter edit mode. The parameter begins to flash to
indicate that value is being edited.
Press the (up or down) buttons to change the parameter to the required value.
Press the Tick button to save the value. The parameter ceases flashing to indicate that it has been saved.
To exit the editor at any time, press and hold the Tick
button.
Page 79
Front Panel Configuration
Page 79 of 90 057-233 ISSUE: 1
6.2 ADJUSTABLE PARAMETERS
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details on configuring, monitoring and control.
Section Parameter As Shown On Display Values
Display
LCD Contrast 0% Language English LCD Page Timer hh:mm:ss Scroll Delay hh:mm:ss Date and Time dd-mm-yyyy, hh:mm:ss
S1
S1 Option Generator, Mains Immediate S1 Dropout Inactive, Active Under Voltage Trip 0 V Over Voltage Trip 0 V Under Frequency Trip 0 Hz Over Frequency Trip 0 Hz
S2
S2 Option Generator, Mains Immediate S2 Dropout Inactive, Active Under Voltage Trip (Generator Option) 0 V Over Voltage Trip (Generator Option) 0 V Under Frequency Trip (Generator Option) 0.0 Hz Over Frequency Trip (Generator Option) 0.0 Hz Under Voltage Trip (Mains Option) 0 V Over Voltage Trip (Mains Option) 0 V Under Frequency Trip (Mains Option) 0.0 Hz Over Frequency Trip (Mains Option) 0.0 Hz
Timers
S1 Transient Delay mm:ss Start Delay hh:mm:ss Warming Up Time hh:mm:ss S2 Fail Delay mm:ss Elevator Delay mm:ss Non-sync Transfer Time mm:ss.s Check-Sync Transfer time mm:ss.s Return Delay hh:mm:ss Cooling Time hh:mm:ss Fail to Stop Enable Inactive, Active Fail to Stop Delay mm:ss S2 Transient Delay s.s
Parameters continue overleaf...
Page 80
Front Panel Configuration
057-233 ISSUE: 1 Page 80 of 90
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details on configuring, monitoring and control.
Section Parameter As Shown On Display Values
Scheduler
Bank 1
Scheduler Enable Inactive, Active
Bank 1 Run Mode
Do Not Transfer Transfer to S1 Transfer to S2 S1 Off Load (When S1 = Gen)
S2 Off Load (When S2 = Gen) Bank 1 Period Weekly, Monthly Bank 1 Event 1 Week 1-4 Bank 1 Event 1 Day Monday to Sunday Bank 1 Event 1 Start Time hh:mm Bank 1 Event 1 Duration hh:mm Bank 1 Event 2 Week 1-4 Bank 1 Event 2 Day Monday to Sunday Bank 1 Event 2 Start Time hh:mm Bank 1 Event 2 Duration hh:mm Bank 1 Event 3 Week 1-4 Bank 1 Event 3 Day Monday to Sunday Bank 1 Event 3 Start Time hh:mm Bank 1 Event 3 Duration hh:mm Bank 1 Event 4 Week 1-4 Bank 1 Event 4 Day Monday to Sunday Bank 1 Event 4 Start Time hh:mm Bank 1 Event 4 Duration hh:mm Bank 1 Event 5 Week 1-4 Bank 1 Event 5 Day Monday to Sunday Bank 1 Event 5 Start Time hh:mm Bank 1 Event 5 Duration hh:mm Bank 1 Event 6 Week 1-4 Bank 1 Event 6 Day Monday to Sunday Bank 1 Event 6 Start Time hh:mm Bank 1 Event 6 Duration hh:mm Bank 1 Event 7 Week 1-4 Bank 1 Event 7 Day Monday to Sunday Bank 1 Event 7 Start Time hh:mm Bank 1 Event 7 Duration hh:mm Bank 1 Event 8 Week 1-4 Bank 1 Event 8 Day Monday to Sunday Bank 1 Event 8 Start Time hh:mm Bank 1 Event 8 Duration hh:mm
Parameters continue overleaf...
Page 81
Front Panel Configuration
Page 81 of 90 057-233 ISSUE: 1
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
Section
Parameter As Shown On Display
Values
Scheduler Bank 2
Bank 2 Run Mode
Do Not Transfer
Transfer to S1
Transfer to S2
S1 Off Load (When S1 = Gen)
S2 Off Load (When S2 = Gen) Bank 2 Period Weekly, Monthly Bank 2 Event 1 Week 1-4 Bank 2 Event 1 Day Monday to Sunday Bank 2 Event 1 Start Time hh:mm Bank 2 Event 1 Duration hh:mm Bank 2 Event 2 Week 1-4 Bank 2 Event 2 Day Monday to Sunday Bank 2 Event 2 Start Time hh:mm Bank 2 Event 2 Duration hh:mm Bank 2 Event 3 Week 1-4 Bank 2 Event 3 Day Monday to Sunday Bank 2 Event 3 Start Time hh:mm Bank 2 Event 3 Duration hh:mm Bank 2 Event 4 Week 1-4 Bank 2 Event 4 Day Monday to Sunday Bank 2 Event 4 Start Time hh:mm Bank 2 Event 4 Duration hh:mm Bank 2 Event 5 Week 1-4 Bank 2 Event 5 Day Monday to Sunday Bank 2 Event 5 Start Time hh:mm Bank 2 Event 5 Duration hh:mm Bank 2 Event 6 Week 1-4 Bank 2 Event 6 Day Monday to Sunday Bank 2 Event 6 Start Time hh:mm Bank 2 Event 6 Duration hh:mm Bank 2 Event 7 Week 1-4 Bank 2 Event 7 Day Monday to Sunday Bank 2 Event 7 Start Time hh:mm Bank 2 Event 7 Duration hh:mm Bank 2 Event 8 Week 1-4 Bank 2 Event 8 Day Monday to Sunday Bank 2 Event 8 Start Time hh:mm Bank 2 Event 8 Duration hh:mm
Page 82
Commissioning
057-233 ISSUE: 1 Page 82 of 90
7 COMMISSIONING
Before the system is started, it is recommended that the following checks are made:-
The unit is adequately cooled and all the wiring to the module is of a standard and rating compatible with the system. Check all mechanical parts are fitted correctly and that all electrical connections (including earths) are sound.
The unit DC supply is fused and connected to the battery and that it is of the correct polarity.
To check the start cycle operation, take appropriate measures to prevent S2 from starting (if
configured as a generator by disconnecting the start output) and press the Manual
mode
button. Check to see if the start signal energises.
Set the modules internal clock/calendar to ensure correct operation of the scheduler and event logging functions. For details of this procedure see section entitled Front Panel Configuration – Editing the date and time.
If, despite repeated checking of the connections between the controller and the customer’s system, satisfactory operation cannot be achieved, then the customer is requested to contact the DSE Technical Support Department for further advice.
Page 83
Fault Finding
057-233 ISSUE: 1 Page 83 of 90
8 FAULT FINDING
8.1 STARTING
Symptom
Possible Remedy
Unit is inoperative Read/Write configuration
does not operate
Check the battery and wiring to the unit. Check the DC supply. Check the DC fuse.
Unit shuts down Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70 °C. Check the DC fuse.
Fail to Start is activated Check wiring of the S2 sensing cables. Check the start output is
correctly wired into the generator controller.
Continuous starting of S2 when in Auto mode.
Check that there is no signal present on the “Remote Start” input. Check configured polarity is correct.
Check the S2 supply available and within configured limits S2 fails to start or go on load on receipt of Remote Start signal.
Check S2 Fail Delay timer has timed out.
Check signal is on “Remote Start” input. Confirm correct configuration
of input is configured to be used as “Remote Start”.
8.2 LOADING
Symptom
Possible Remedy
S2 supply present runs but does not take load
Ensure S2 is available and within configured limits and a load inhibit
signal is not present on the module inputs. Check connections to the
switching device.
Note that S2 does not take load in manual mode unless there is an
active remote start on load signal.
8.3 ALARMS
Symptom
Possible Remedy
Electrical Trip fault operates Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input. Warning fault operates Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.
Page 84
Fault Finding
057-233 ISSUE: 1 Page 84 of 90
8.4 COMMUNICATIONS
Symptom
Possible Remedy
RS485 inoperative Check :
Connection cable – Belden 9841 or equivalent
120 termination resistors are correctly fitted
Baud rate of controller and of master device are the same
Slave ID of the controller is the same as configured in the
master device RS232 connection to PC inoperative
Check :
RS232 maximum of 15 m is not exceeded
Direct to PC connection requires a Crossover (NULL modem)
RS232 cable
Baud rate of controller and of master device are the same
Slave ID of the controller is the same as configured in the
master device RS232 connection to GSM modem inoperative
Check :
RS232 maximum of 15 m is not exceeded
Modem Initialisation strings in the DSE configuration is correct
for the connected modem type
Modem is configured to 9600 baud
SIM card is CSD (circuit switched data) compatible
SIM card is not PIN locked
SIM card is correctly inserted
Antenna is correctly installed and is not inside an earthed
metal cabinet / control panel
A good signal is available in the locality RS232 connection to landline modem inoperative
Check :
RS232 maximum of 15 m is not exceeded
Modem Initialisation strings in the DSE configuration is correct
for the connected modem type
Modem is configured to 9600 baud
8.5 INSTRUMENTS
Symptom
Possible Remedy
Inaccurate S1 & S2 measurements on controller display
Check that the CT primary, CT secondary and VT ratio settings are correct for the application.
Check that the CTs are wired correctly with regards to the direction of current flow (p1,p2 and s1,s2) and additionally ensure that CTs are connected to the correct phase (errors occur if CT1 is connected to phase 2).
Remember to consider the power factor. Ie (kW = kV A x powerfactor) The controller is true RMS measuring so gives more accurate display
when compared with an ‘averaging’ meter such as an analogue panel meter or some lower specified digital multimeters.
Accuracy of the controller is better than 1% of full scale. Ie S1 volts full scale is 333 V ph-n so accuracy is ±3.33 V (1% of 333 V).
Page 85
Fault Finding
Page 85 of 90 057-233 ISSUE: 1
8.6 MISCELLANEOUS
NOTE: The above fault finding is provided as a guide check-list only. As the module can be configured to provide a wide range of different features, always refer to the source of the module configuration if in doubt.
Symptom
Possible
Remedy
Module appears to ‘revert’ to an earlier configuration
When editing a configuration using the PC software it is vital that the configuration is first ‘read’ from the controller before editing it. This edited configuration must then be “written” back to the controller for the changes to take effect.
When editing a configuration using the fascia editor, be sure to press the Tick button to save the change before moving to another item
or exiting the fascia editor
Page 86
Maintenance, Spares, Repairs and Servicing
86
9 MAINTENANCE, SPARES, REPAIR AND SERVICING
The controller is Fit and Forget. As such, there are no user serviceable parts within the controller. In the case of malfunction, contact the original equipment manufacturer (OEM).
9.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE
If additional plugs are required from DSE, please contact our sales department using the part numbers below.
9.1.1 PACK OF PLUGS
Module type Plug Pack Part Number
DSE335 100-400-35
9.1.2 INDIVIDUAL PLUGS
Module Terminal Designation Plug Description Part No.
1-8
8 way 5.08 mm 007-164
9-17
9 way 5.08 mm 007-167
18-24
7 way 5.08 mm 007-447
25-29
5 way 7.62 mm 007-473
30-37
S2
8 way 7.62 mm 007-454
38-41
S1
4 way 7.62 mm 007-171
42-47
6 way 5.08 mm 007-446
48-53
6 way 7.62 mm 007-162
RS485
3 way 5.08 mm 007-174
NOTE: Terminals 24 and 27 are fitted to controllers but must not be connected.
9.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE
Item Description Part No.
Module fixing clips (packet of 4) 020-294
9.3 PURCHASING ADDITIONAL SEALING GASKET FROM DSE
Item Description Part No.
Module silicon sealing gasket 020-507
Page 87
Maintenance, Spares, Repairs and Servicing
057-233 ISSUE: 1 Page 87 of 90
9.4 DSENET EXPANSION MODULES
NOTE: A maximum of six (6) expansion modules can be connected to the DSENet®.
NOTE: DSENet® utilises an RS485 connection. Using Belden 9841 (or equivalent) cable allows for the expansion cable to be extended to a maximum of 1.2 km. DSE Stock and supply Belden 9841 cable. DSE Part Number 016-030.
Item
Description
DSE Part Numbers
Max No.
supported
Model
order
number
Sales
literature
Operator
manual
Installation
Instructions
2
Model DSE2130 input module provides additional analogue and digital inputs for use with the controller.
2130-001-00 055-060 057-082 053-033
2
Model DSE2157 expansion relay module provides eight additional voltage free relays for use with the controller
2157-001-00 055-061 057-083 053-034
2
Model DSE2548 expansion LED module provides additional LED indications, internal sounder and remote lamp test/alarm mute for use with the controller.
2548-001-00 055-062 057-084 053-032
Page 88
Warranty and Disposal
057-233 ISSUE: 1 Page 88 of 90
10 WARRANTY
DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any applicable warranty, refer to the original equipment supplier (OEM).
11 DISPOSAL
11.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
If you use electrical and electronic equipment you must store, collect, treat, recycle and dispose of WEEE separately from your other waste.
Page 89
This Page is Intentionally Blank
Page 90
This Page is Intentionally Blank