DSC WS4916 Series Installation And Operation Instructions Manual

WS4916 Series Wireless Smoke Detector
Installation and Operating Instructions
Read this instruction sheet thoroughly before installation and use of the WS4916 Wireless Smoke Detector

Introduction

The WS4916 is a wireless photoelectric smoke detector with a fixed temperature and rate of rise heat detector, and an internal piezo­electric alarm. Four versions are available: US version (UL), Canadian version (ULC), International version (EU), and Australian version (AUS).
NOTE: Heat detection based on rate of rise has not been investi­gated by UL/ULC.
NOTE: Australian version does not include the heat detector.
LED/Test Button
Piezo Siren
'*
Alignment Marks

Operation

Approximately every 7 to 8 seconds the unit tests for a smoke or heat alarm condition. During this sequence the unit also performs self diagnostics, and checks for tampers and faults. During normal operation the LED will flash every 50 seconds and the sounder will not sound.

Smoke Alarm

The smoke detector will go into alarm when the signal level exceeds the “alarm” threshold and automatically restore when the signal level falls below the alarm “restore” threshold. During an alarm the LED will flash 1/second and the sounder will sound the evacuation temporal pattern (UL, EU) or continuous beeps (ULC). The smoke detector has a preset warning threshold at 75% of the alarm threshold. If the signal level stays above this threshold, but below the alarm threshold, for more than 120 seconds, the detec­tor will go into the “warning” state. If the signal level falls below the early warning “restore” threshold, the detector will restore to its normal state automatically. If the signal level rises above the alarm threshold, the detector will go into alarm. The LED will flash and the sounder will chirp every 50 seconds when in the warning state.
NOTE: This feature is intended to provide a warning if the envi­ronment is persistently close to the alarm threshold and provide more time to investigate and either escape or correct the situa­tion.

Smoke - Drift Compensation

The detector automatically compensates for long-term environmen­tally induced changes to maintain a constant smoke sensitivity. When the drift compensation has reached its high or low limit of adjustment, the detector will go into the trouble state.

Heat Alarm

The heat detector will go into alarm when the heat signal level exceeds the heat alarm threshold (135ºF/57ºC); and will automati­cally restore when the heat signal level falls below the heat alarm threshold (restore). The detector will also go into heat alarm if there is a rapid increase in the temperature over a short period of time. During an alarm the LED will flash 1/second and the sounder will sound the evacuation temporal pattern (UL, EU) or continuous beeps (ULC).

Tamper

The removal of the detector from the mounting plate initiates a “tamper” transmission. The tamper condition is restored after the detector is mounted on the plate.

Wireless Transmissions

A supervisory message is transmitted at 64 minute intervals (12 minutes in EU model) to the control panel. If the signal is not received the control panel determines that the detector is missing. The detector transmits the following:
Alarm / Alarm Restore - (heat or smoke alarm). Transmitted at time of occurrence.
Tamper / Tamper Restore - (tamper switch activated) 10 second maximum delay on restore before transmission.
Low Battery - (battery voltage falls below threshold). The bat- teries are tested & transmitted at the time of a supervisory or other transmissions.
Trouble - (detector fault or sensor compensation limit reached). Troubles are transmitted at the time of occurrence (one trouble per supervisory interval).

Batteries

The WS4916 is powered by two, 3VDC lithium batteries.
Do NOT use batteries other than those listed.
The low battery threshold is set so the batteries will provide not less than 14 days of operation and at that point the detector will send a “low battery” signal. If the battery is still low 7 days after falling through the low battery threshold, the horn will “chirp” once every 48 seconds until battery failure. During the first 7 days after low battery detection, (non-chirp period), if the detector is tested or goes into alarm, the horn will “chirp” once the test or alarm is restored and remain “chirping” until battery failure. Replacement batteries can be purchased from the distributor, the installation company, hardware stores or supermarkets etc.
Installation Instructions Installation
The WS4916 Series wireless smoke detector shall be installed and used within an environment that provides the pollution degree max 2 and overvoltages category II in NON HAZARDOUS LOCATIONS, indoor only. The equipment is designed to be installed by SERVICE PERSONS only; (SERVICE PERSON is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task and of measures to minimize the risks to that person or other persons.)
1. Smoke Detector Placement
On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart as a guide. Other spacing may be required depending on ceiling height, air movement, the presence of joists, uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72 Chapter 11, CAN/ ULC-S553-02 or other appropriate national standards for installa­tion recommendations.
•DoNOT locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these locations may prevent the unit from detecting smoke. Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector may prevent smoke from entering the unit.
•DoNOT locate detectors in areas of high humidity.
•DoNOT locate detectors in areas where the temperature rises above 38ºC (100ºF) or falls below 5ºC (41ºF).
Install Smoke detectors in accordance with NFPA 72, Chapter 11.
“Smoke detectors shall be installed outside of each sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family living unit, including basements and excluding crawl spaces and unfinished attics. In new construction, a smoke detector also shall be installed in each sleeping room.”
2. Mount Smoke Detector Backplate
Secure backplate to the mounting sur­face using the screws
Locking
Ta b
provided.
CAUTION: The dust cover protects the unit when not in service. Remove the dust cover before use.
Mounting Holes
3. Install Batteries
If batteries are not installed, install bat­teries in the sequence indicated. Use only approved Panasonic CR123A,
Insert Last
3V CR123A
3V CR123A
Insert First
Sanyo CR123A or Duracell DL123A batteries. If batteries are installed, remove the “Pull” tab to activate.
CAUTION: Without batteries the unit cannot be mounted onto the base plate prop­erly! (WS4916 Aus­tralian version only).
4. Mounting
• Detector Installation
Position the detector on to the base plate using the detector and base plate alignment marks.
Mounting
Surface
Alignment
Marks
Detector
PULL DOWN Tab
Backplate
Tabs
Press the detector gently in place while rotating the
CLOSE
detector clockwise until the detector snaps into place. Remove the side tab from the locking tab to lock in place (optional).
• Removal
OPEN
Depress tab with a small slotted screwdriver. Rotate detector counter-clockwise until the alignment marks line up. Remove detector.

Installer Compensation Reset

Cleaning or replacement of the smoke sensor chamber changes the background signal/noise of the detector; this requires the drift com­pensation be reset. Compensation trouble is one of the faults indi­cated when the LED indicator is OFF while the sounder is chirping.
1. Remove batteries, then short the detector battery contacts for
5 seconds to power down unit.
2.Replace batteries to power up unit while pressing the test
button.
3.The tamper switch must not be pressed.
4.The LED will flash when 5 seconds has elapsed. Release the
test button within 2 seconds of the LED flash.
5.The LED will flash every 2 seconds for 1 minute. During this
period, the detector must be mounted.
Allow an additional 2 minutes for the detector to make back­ground level checks.
6.Test the detector to verify normal operation.
5. Test Unit
NOTE: The central monitoring station (if used) should be notified
prior to the test being generated. This will prevent a false alarm and an unnecessary response from the central monitoring station.
Initiate test by pressing the test button for 5 seconds minimum. Alarm activation is indicated by the flashing LED, the sounder, and transmission of the alarm signal to the control panel. The detector restores to normal when the test button is released.
NOTE: Allow a minimum of 20 seconds after power up and , after test, alarm or tamper restore activations. Do not use test but­ton when smoke is present.
NOTE: If the detector is in one of the following states when a test is initiated; it will not enter an alarm state.
• Tamper, (detector not installed on mounting plate)
• Compensation Trouble
• Other internal faults that could prevent a smoke or heat alarm
NOTE: Smoke sensitivity of installed detectors can be measured without removal or an alarm being generated using the FSD-100 Smoke Detector Test Meter.
To test the unit using the FSD-100, set the test meter up to read devices as per the instructions supplied. Depress the test button on the smoke detector for 1 second and release.
NOTE: If the test button is held for 5 seconds or longer, an alarm will be generated.
Move the test meter over the center of the detector, wait until you hear the test meter beep, remove the unit and the information can be immediately reviewed. Please see the instructions supplied with the FSD-100 Smoke Detector Test Meter for more information.
6. Device Enrollment
The 6-digit serial number located on the back of the smoke detec­tor housing must be enrolled into the alarm control panel with Installer programming. Refer to the receiver Installation Manual for details. For placement tests remove detector from backplate for one second (tamper) then reattach. Wait at least 30 seconds for test result before activating again.

Owner’s Instructions

Fire Safety In The Home

Most fires occur in the home, and to minimize this danger, it is rec­ommended that a household fire safety audit be conducted and a family escape plan be developed.

Household Fire Safety Audit

1. Are all electrical appliances and outlets in safe condition? Check for frayed cords, overloaded lighting circuits, etc. If you are uncertain about the condition of your electrical appliances or household service, have a professional evaluation.
2.Are all flammable liquids safely stored in closed containers,
and in a cool and well ventilated area? Cleaning the unit with flammable liquids should be avoided.
3.Are hazardous materials (i.e., matches) out of the reach of
children?
4.Are furnaces and wood burning appliances properly installed,
clean, and in good working order? If in doubt, have a profes­sional evaluation.

Family Escape Planning

There is often very little time between the detection of a fire and the time it becomes deadly. Because of this, it is very important that a family escape plan be developed and rehearsed.
• Every family member should participate in the escape plan.
• Study the possible escape routes from each location within the
house. Since many fires occur at night, special attention should be given to the escape routes from sleeping quarters.
• It is essential that escape from a bedroom be possible without
opening the interior door. Consider the following when making your escape plans:
• Ensure that doors and windows that open to the outside are eas-
ily opened. Ensure that they are not painted shut and that the locking mechanisms operate smoothly.
• If opening or using the exit is too difficult for children, the elderly
or handicapped, plans for their rescue should be developed. This plan includes making sure that those who are to perform the res­cue can promptly hear the fire warning signal.
• If the exit is above the ground level, an approved fire ladder or
rope should be provided, as well as training in its use.
• Exits on the ground level should be kept clear. Be sure to remove
snow from exterior patio doors in the winter and that outdoor furniture or equipment does not block exits.
• The family should have a predetermined assembly point where
everyone can be accounted for; for example, across the street or at a neighbor’s house.
• Once everyone is out of the house, call the Fire Department.
• A good plan emphasizes a quick escape. Do not investigate first
or attempt to fight the fire, and do not attempt to rescue belong­ings or valuables as this takes up time. Once outside, do not re­enter the house; wait for the Fire Department.
• Write the plan down and rehearse it frequently so that should
an emergency ever arise, everyone will know what to do. Revise the plan as conditions change; for example, when there are more or fewer family members in the home or if there are changes to the house.
• Make sure your fire warning system is operational by conducting
weekly tests. If you are unsure about system operation, contact your smoke detector installer or dealer.
• DSC recommends that you contact your local Fire Department
and request further information on home fire safety and escape planning. If available, have your local fire prevention officer con­duct an in-house fire safety inspection.

Testing Your Smoke Detector

Follow the test procedure described here or contact your smoke detector dealer or installer for testing instructions. DSC recommends that you test the entire alarm system at least once a week to verify the operation of all system functions.

Smoke Detector Unit Test

Initiate test by pressing the test button for 5 seconds (min.), the sounder makes clicking noises during this time. Press the button until the unit alarm sounds, an alarm should be sent to the control panel. When the button is released, the alarm should cease. If this does not occur, ensure batteries are the correct type, in good condi­tion and are installed correctly (see 3. Install Batteries in the Installation Instructions section). Upon completing the functional testing of the smoke detector, check the unit’s sensing chamber to ensure proper operation. To test the sensing chamber, wave a lit cotton wick or punk stick around the outside of the unit until a generous amount of smoke enters the sensing chamber or the unit alarms. If the smoke detec­tor does not function properly, call your smoke detector installer or dealer for service.

Owner’s Maintenance

The smoke detector is designed to require minimum maintenance. If the case becomes dusty, vacuum with a small brush attachment. If the case is greasy, wipe the case gently with a soft cloth slightly dampened with soapy water.
Never disassemble the smoke detector; there are no user serviceable parts inside the unit. You may only remove detector from backplate to replace batteries if not serviced by installer. When replacing the batteries, follow the instructions specified within the Installation Instructions, Item 3 Install Batteries.
CAUTION: This product uses lithium batteries, improper handling may result in a HEAT, EXPLOSION or FIRE causing personal injury. DO NOT recharge batteries. Follow the battery manufacturer’s safety instructions. Dispose of used batteries in accordance with the regulations in your area.
Never paint the unit. Paint may prevent smoke from entering the unit. If you are planning renovations or repainting, contact your installer and ask that the unit be temporarily removed until work is complete.
If the unit is located in an area where it is exposed to high levels of dust or insects and causes false alarms, it may require service; con­tact your smoke detector installer or dealer. Testing and maintenance procedures shall be in accordance with CAN/ULC-S552-02.

Specifications

• Diameter (base): 5.8in (147mm)
• Height (including base): 2.077in (528mm)
• Alarm Sensitivity (threshold) UL: 3.0±0.8%/ft obscuration, ULC:
2.0±0.5 %/ft obscuration
• Alarm Sensitivity (threshold) EU: complies with EN54-7
• Warning threshold: 75% of alarm threshold for 120 seconds
• Heat Alarm: 135ºF (57ºC)
• Supervisory Transmission Frequency UL, ULC: 64 min. intervals
• Supervisory Transmission Frequency EU: 12 minute intervals
• Sounder Alarm Pattern UL, EU: evacuation temporal pattern
• Sounder Alarm Pattern ULC: continuous beeps
• Operating Temperature with Heat Detector: 32º-100ºF (0º-37.8ºC)
• Operating Temperature for Smoke Alarm (Australian version): 41º-113ºF (5º-45ºC)
• Humidity: 5%-95% RH, non-condensing
• Batteries (2) CR123A
• Low Battery Detection Low battery 14 days remaining
• Approved Batteries: Panasonic CR123A, Sanyo CR123A and Duracell DL123A

Alarm Indications

Condition LED Sounder Transmission
Normal Flash 1/50s OFF Supervisory
Alarm Smoke Flash 1/1s
Alarm Heat Flash 1/1s
Early Warning
Smoke
Compensation
Trouble High
Compensation
Trouble Low
Sensor/
Internal Fault
Low Battery
0 - 7 days
Low Battery
0 - 7 days & Test or
Alarm
Low Battery After
7 days
Tamper Flash 1/50s OFF Tamper
Flash 1/50s CHIRP None
OFF CHIRP Trouble
OFF CHIRP Trouble
OFF CHIRP Trouble
Flash 1/50s
Flash 1/50s
Flash 1/50s
This product has been approved by the California State Fire Marshal (CSFM) pursuant to section 13144.1 of the California Health and Safety Code. See CSFM Listing No. 7272-1273:125 for allowable values and/or conditions for use concerning mate­rial presented in this document. The approval is subject to reex­amination, revision and possible cancellation.
Temporal or
Steady
Temporal or
Steady
OFF Low Battery
CHIRP
CHIRP
Low Battery
Low Battery
Alarm
Alarm
Loading...
+ 5 hidden pages