WARNING: This manual contains information on limitations regarding product use
and function and information on the limitations as to liability of the manufacturer.
Read the entire manual carefully.
CL3050
Page 2
Location
Test Time & Day
Additional Notes
For Your Records
CONNECT 24
Note: Only authorized dealers can enroll a wireless system to Connect 24.
Dealer application forms and additional information on the Connect 24 Voice
Response Unit can be found at the Connect 24 web site.
The information required for activation is listed below. Ensure that all information
is available before calling the Connect 24 Voice Response Unit.
TM
Enrollment Information
http://www.connect24.com/dealer.htm
USA 1-888-251-7458CAN 1-888-955-5583
Profile Number ...................................................5 digits I___I___I___I___I___I
The profile number provides Central Station Receiver information.
Installer ID Number............... 8-9 digits I___I___I___I___I___I___I___I___I___I
An Installer ID number was provided for each installer listed on the Dealer
Enrollment Form. This number can be found on the authorized Installer Card
sent with the Dealer Confirmation Form.
The Skyroute Mobile Identification Number identifies the Skyroute transmitter.
The 10-digit MIN is located on the label affixed to your Skyroute Transmitter.
System ID Number (SID)................................ 5 digits I___I___I___I___I___I
The System ID Number informs Connect 24 and the cellular network the home
area that your transmitter is installed in. When this number is programmed into
an alarm panel it is entered in HEX format. When entering this number into the
Connect 24 Voice Response Unit, it is entered in Decimal Format.
The Skyroute CL3050 is a standalone wireless communicator that sends alarm system information to Connect 24. Connect 24 then forwards this information to the central station.
The Skyroute CL3050 has four modes of operation. It can operate in one of three operational modes or; if it is connected to a keypad, in the programming mode. The Skyroute
CL3050 is pre-programmed with the most commonly used settings for quick installation. If
required the default options can be custom programmed.
NOTE: For UL Installations, use mode 2 or 3 ONLY.
Mode 1: Bell Follower
In Mode 1, the Skyroute CL3050 monitors the Bell Output of the control panel.
The system identifies the Bell Output cadence and transmits the corresponding
Fire or Burglar alarm reporting code to Connect 24.
Refer to the appropriate control panel Installation Manual.
NOTE: Not for UL Listed installations.
Mode 2: 2-ZonePanel
In Mode 2, the system will configure itself for 2 zone, stand alone operation.
NOTE: UL Listed for residential burglary installations ONLY.
Mode 3: 8-Zone Panel
If the Skyroute CL3050 detects a PC5108 expander card on power up it will automatically configure itself for 8-zone standalone operation with normally closed
loops.
NOTE: Standalone operation is intended for household fire and burglary and it is
considered ancillary operation for commercial fire and burglary installations.
Programming Mode
If the Skyroute CL3050 detects a keypad on power up it will go into the programming mode. Programming mode allows the installer to custom program system
options. Refer to Section 5, Programming Descriptions; and Section 6, Programming Worksheets for programming options and default settings.
Figure 1
CL3050
1
Page 6
1.1 Specifications
•Power Supply Ratings
Voltage: 10.6-14 V
Current: 500 mA (Max)
Low DC Trouble: 8.8 V
Low DC Restore: 9.0 VDC
Low AC Trouble: 7.5 V
Low AC Restore: 8.0 V
•Current Drain
Standby: 100 mA
Receiving: 150 mA
Transmitting: 850 mA (350 mA from external power supply)
•RF Power Output: 600 mW
•Antenna Gain: 0 db
•Battery
Charging Voltage: 6.87 V
Low Battery Restore: 5.87 V
Low Battery Trouble: 5.72 VDC
Critical Shutdown: 5.0 VDC
•Operating Modes
Bell Follower
2-24Hr Zones
8-24Hr zones (with PC5108)
•Programmable by all PowerSeries Keypads
PC5508/KP5508Z: 8 Zone LED keypad
PC5516Z/KP5516Z: 16 Zone LED keypad
PC5532Z/KP5532Z: 32 Zone LED keypad
LCD5500Z/KPL5500Z: Programmable Message LCD Keypad
LCD5501Z/KP5501Z: Fixed Message LCD Keypad
AC or VDC
DC
AC
AC
DC
DC
Introduction
1.2 Unpacking
Verify that the following items have been included.
Skyroute CL3050 (rechargeable battery included)
1
Installation & Programming Guide
1
Antenna
1
Mounting screws
4
5.6KΩ resistors
4
Enclosure screw
1
Remove antenna from protective bubble pack and install in unit.
CAUTION: Install antenna before connecting battery or power leads to this unit. Transmission without an antenna can cause permanent damage.
When removing cover of this unit DO NOT touch or handle exposed electrical devices and
components. Electrostatic discharge (ESD) can permanently damage this unit or reduce the
reliability and life expectancy of components.
2
Page 7
Skyroute CL3050 Universal Wireless Communicator
Section 2: Quick Start
2.1 Installation
1Determine The Operating mode required
The operating mode (modes 1, 2, or 3) will determine how the unit is to be wired
up. Refer to section 6, Programming Descriptions, section [10] for available
options and for programming defaults. See section 4, Power up Sequence for
selection of Operating and Programming modes.
NOTE: For UL Installations, use only mode 2 or 3.
2Determine the Mounting Location
Select a mounting location in a dry, protected area. The mounting location
should be positioned so that it is at least 30 cm. away from physical contact with
any person.
NOTE: Do Not exceed the following recommendations for wire run distances
•Keybus and zone wiring should be run using minimum 22 gauge quad
(0.5mm). Two pair twisted is preferred.
•a keypad, PC5108, or zone wiring can not exceed 1,000'/305m (in wire
length) from the Skyroute CL3050.
•Shielded wire is not necessary unless wires are run in an area that may present
excessive RF noise or interference.
•Refer to section 6, Programming Descriptions, section [10] for zone wir-
ing details.
NOTE: Generally, the higher the location and the closer that the Skyroute CL3050
is to an outside wall, the better the signal strength will be.
3Checking Signal Strength
•Remove front cover
•Connect Battery to the RED and BLK flying leads.
•Connect AC Power source or 12 V
•Allow unit to power up
NOTE: The unit does not need to be enrolled with Connect 24 to check signal
strength.
•When the green LED stops flashing, press and release the enroll button.
•Ensure that Radio Signal Strength Indication (RSSI) is greater than the mini-
mum acceptable level as indicated below. If the signal level is not acceptable, reposition and retest the Skyroute CL3050 until an acceptable signal
strength is found.
Red LEDYellow LEDGreen LEDSignal Strength
On
On
On
On
On
Flash
On
On
On
Flash
Off
Off
DC
to RED & BLK terminals.
On
Flash
Off
Off
Off
Off
>87%
69-87%
*52-68%
34-51%
16-33%
0-15%
*Minimum recommended signal strength for enrollment
4Route Wiring to Mounting Location
Route wiring from the hardwired zones or control panel as required.
NOTE: Route wiring through conduit to a junction box if possible. Mount the
Skyroute Panel.
3
Page 8
5Mount Unit
•Remove the front cover if required
•Disconnect flying leads from battery and power leads from the RED and BLK
•Remove two screws securing battery clamp. Remove battery
•Mount backplate of unit to wall or over electrical junction box using the
NOTE: DO NOT connect the battery to the flying leads and AC or DC power to
the terminal strip until all other wiring connections are completed.
•Route wiring through the access holes provided and connect to terminal
•Power up unit by connecting battery and power source.
•Front cover is to be securely fastened with screw provided.
6Enroll Unit
Call Connect 24 and Enroll the Skyroute CL3050. Refer to back of Front Cover
for contact information and a list of information required to complete the enrollment with the Connect 24 Voice Response Unit.
2.2 Testing
Quick Start
terminals (if connected).
four screws provided.
strip.
Program Mode: If you have wired the unit to power up in the programming
mode. Follow the steps outlined in Section 6, Programming Descriptions and
record the program settings in Section 7, Programming Worksheets.
Test Transmission - Pressing and holding the enroll button for 2 seconds will
send a test transmission to the central station via Connect 24. Refer to Enroll Button in Section 3, Controls and indicators for test transmission details.
Mode 1: Disable the telephone line connected to the control panel. Simulate
Burglar and Fire Zone violation. Verify that the Skyroute CL3050 transmits the
events to the central station.
Mode 2 & 3: Simulate Faults, Tampers, and Zone violations in accordance with
the settings outlined in Sections 6, Programming Descriptions. Verify that the
Skyroute CL3050 transmits the events to the central station.
2.3 Resetting to Factory Defaults
NOTE: Resetting to factory defaults is required to change mode of operation.
•Remove Power from the Skyroute CL3050; disconnect battery and control
panel if applicable (mode 1).
•Disconnect all wiring from the YEL and GRN terminals.
•Connect a jumper wire between the YEL and GRN terminals.
•Apply power to the system.
NOTE: When the hardware default has been completed; the yellow, green and
red LEDs will flash on and off continuously.
•Remove power from the system.
NOTE: To resume communications with Connect 24, Section [11], Option 6
must be set to ON. To do this; the system must be powered up in programming
mode. Refer to Section 5 System Programming.
•Reconnect all original wiring and reapply power to the system.
•Test System - Refer to Section 2.2
4
Page 9
Skyroute CL3050 Universal Wireless Communicator
Section 3: Controls and Indicators
Figure 2
Antenna
Mounting Holes
Green LED
Yellow LED
Battery (6 VDC)Battery (6 V)
1.3 Ah
Wire Access
DC
SW2
Tamper Switch
RED BLK YEL GRN COM PGM
3.1 LED Indicators (see figure 2)
Yellow LED
During normal operation, the yellow LED will indicate the system status with a
series of flashes as indicated below.
SW1
Red LED
Enroll Button
No. of
FlashesIndication
1
2
3
4
5
6
7
8
9
No trouble conditions present
Low battery
Input supply failure
Not enrolled at Connect 24
No service available
Radio failure
PC5108 failure
Failure to communicate
Zone tamper/fault trouble
5
Page 10
Controls and Indicators
NOTE: Multiple trouble conditions are displayed (flashed) in sequence.
Red LED
The red LED will flash to provide event transmission status for the following
events:
1 Flash
1 Flash
2 Flashes
Enroll button held down for 2 seconds
Event transmitted to cellular network
Event acknowledged by Connect 24.
Green LED
The green LED will light continuously if the (RSSI) signal is acceptable. If signal
strength is not acceptable the LED will turn OFF. Detailed information on signal
strength can be accessed by momentarily pressing and releasing the enroll
button. The green, yellow and red LEDs will light to indicate the range of signal
strength. Refer to Section 2 Step 3.
3.2 Enroll Button (see figure 2)
The Skyroute CL3050 Enroll button is located on the outside of the plastic housing directly below the status LEDs. The enroll button performs three functions.
•Pressing and releasing this button momentarily during the first 15 seconds
of power up will toggle between Mode 1 and Mode 2 to enable mode
selection.
•Pressing and releasing this button momentarily at any time after the power
up sequence will display the detailed RSSI status indicated above.
•Holding this button down for a period of 2 seconds continuously will cause
the Skyroute CL3050 to send a test transmission to Connect 24, this long
debounce will be indicated by the red LED flashing once.
3.3 Terminal Connections (see figure 2)
RED10.6-14V
NOTE: 12V
PC5108 zone expander. Mode 1 and Mode 2 may be operated with an
AC Supply.
BLK10.6-14V
YELMode 1* - The YEL terminal functions as the Bell input.
Mode 2 - This terminal functions as the zone 1 input.
Mode 3 - This terminal connects to the YEL Keybus terminal when
using a PC5108 zone expander or PowerSeries keypad.
GRNMode 1* - The GRN terminal functions as the TLM Trouble input.
Mode 2 - This terminal functions as the zone 2 input.
Mode 3 - This terminal connects to the GRN Keybus terminal when
using a PC5108 zone expander or PowerSeries keypad.
COMMode 1* - This terminal functions as the common terminal for the Bell
Input on the YEL terminal, the TLM trouble input on the GRN terminal
and the Trouble Output on the PGM terminal.
Mode 2 - This terminal functions as the common terminal for zone 1
(YEL) and zone 2 (GRN).
Mode 3 - This terminal functions as the common terminal for the
Trouble Output
DC
Positive Input or 10.6-14V
DC is required for programming or for operation with a
DC
Ground or 10.6-14V
AC
AC
NOTE: Mode 1 is not intended for UL Installations.
6
Page 11
Skyroute CL3050 Universal Wireless Communicator
PGM - The PGM output is
dedicated for Skyroute
CL3050 trouble indications. If a control panel is
not monitoring the Skyroute CL3050, an LED or a
buzzer can be connected
between this terminal and
the RED terminal for trouble
indication. The PGM terminal switches low from an
open-collector state. Connect to the control panel
using a Single EOL configuration as shown in 6 Pro-
gramming Descriptions
Section [13] on page 11.
NOTES: The PGM output
can sink 50 mA (maximum).
For UL Installations, use DSC
RM-1 Relay Module.
LED Output with
current limiting
resistor
Optional relay
driver output
To External
Supply
Skyroute CL3050
RED BLK YEL GRN COM PGM
LED 560
+ Coil -
Relay
NC Com
Section 4: Power up Sequence
On first-time power up, the Skyroute CL3050 will generate a random test transmission time and random day of the week to send it. The installer can then
change this information if required.
During power up, the Skyroute CL3050 will look for a keypad on the Keybus, if
one is found, it will go into the programming mode. If no keypad is found, it will
look for a PC5108 zone expander module. If a zone expander is found, it will
automatically configure itself for mode 3. If no Keybus modules are present, the
Skyroute CL3050 will power up in mode 1. During the first 15 seconds of power
up, any zone scanning will be shunted. During this time the installer can momentarily press the enroll button on the Skyroute CL3050 to toggle between mode 1
and mode 2. Upon power up the green LED will be flashing on and off. This will
indicate to the installer that he/she can change the mode to 1 or 2. The red LED
will indicate mode 1 and the yellow LED will indicate mode 2. If neither red or yellow LED is lit, then the Skyroute CL3050 has detected a PC5108 module, the
mode cannot be changed by pressing the enroll button if a PC5108 module is
connected to the Skyroute CL3050.
If a keypad is detected on Keybus, the green LED will stop flashing, and the red
LED will begin flashing to indicate that programming mode is active.
7
Page 12
Section 5: System Programming
The Skyroute CL3050 is programmed using any PowerSeries keypad. Refer to
Section 1.1 Specifications.
NOTE: Power down the Skyroute CL3050 when connecting or removing other
Keybus modules from the system. If the Skyroute CL3050 is connected to a control panel (mode 1), the control panel must also be powered down.
1.Connect keypad Keybus connections to the RED, BLK, YEL and GRN termi-
nals of the Skyroute CL3050.
RED BLK YEL GRN COM PGM
+12 VDC
Ground
To Keybus
Connections
on Keypad
Not Connected
System Programming
2.Connect a +12VDC supply across the RED and BLK terminals.
Upon detecting the keypad on power up, the Skyroute CL3050 will begin
driving Keybus and will blank the keypad with all LEDs and icons off.
NOTE: The red LED on the Skyroute CL3050 will flash continuously if a
keypad is detected.
3.Press the star [*] key to gain access to the programming section.
Programming is done with a 2-digit section entry. When programming is
complete, power down the Skyroute CL3050 and remove the keypad.
Section 6: Programming Descriptions
[01] Zone 1, 2 Definitions
When the Skyroute CL3050 is in Mode 2 or 3, there are 14 options that can be
programmed as zone types. All of the zone types with the exception of 00 (null
zone), 13 (CL3050 communications zone) and 14 (trouble zone) are straightforward. Since all the zones are 24-hour type zones, selecting any listed zone type
will simply select which identifier should be used for reporting the alarm. Programming a zone as 00 (null zone) will disable the zone input on the Skyroute
CL3050 or PC5108 hardware. Programming any zone as type 13 (CL3050 communications zone) will disable all communications unless that zone input is closed
(short condition). Programming a zone as 14 ( trouble zone) will enable an additional reporting code to be sent with the daily/weekly test transmission (if
enabled). If all zones are restored and there are no trouble conditions present on
the Skyroute CL3050, a periodic test transmission code (RP00) will be sent. otherwise a periodic test off-normal code (RY00) will be sent instead.
NOTE: Do NOT program more than 1 CL3050 communications zone or trouble
zone on the Skyroute CL3050.
Default - [01] zones 1 & 2
Modes 2, 3
8
Page 13
Skyroute CL3050 Universal Wireless Communicator
[02] Zone 3 - 8 Definitions
This allows programming of the six additional zone definitions when operating in
mode 3 with a PC5108 zone expander. See section [01] for details
Default - [01] zones 3 - 8
[03] Zone 1, 2 Loop Response
This entry determines how quickly a zone will respond to changes in state.
NOTE: This does not affect zones on a PC5108 zone expander card.
Default - 05 (0.5 seconds) 01-FF Hex x 0.1 seconds.
[10] Skyroute CL3050 Mode of Operation
[01]Mode 1 - Bell Follower Operation
RED BLK YEL GRN COM PGM
Input Voltage
10.6-14 V or V
Bell Input
TLM Input
System Common
Trouble Output
ACDC
Mode 3
Modes 2
RED BLK YEL GRN COM PGM
NC
Relay
Com
NO
Alternate connection for
Control Panels where Bell
switches High
BELL+ BELL-
In this mode, the YEL terminal is connected to the bell output of a control panel.
The Skyroute CL3050 monitors the output for burglary and fire cadences and
transmits the appropriate events. For any type of pulsed cadence, the Skyroute
CL3050 will send a generic Fire event, for any steady bell the Skyroute CL3050
will send a generic Burglary event. The GRN terminal is a trouble input which can
be connected to a system output to alert the Skyroute CL3050 of a system TLM
fault. This will enables the Skyroute CL3050 to be used as a back-up communicator only. If not used, this input must to connected to COM. The bell
cadence will be determined as follows:
•Bell must be on for longer then 300mS to be considered a "pulse"
•Bell must be on for 3 seconds continuous to be considered "steady"
•Bell must be off for 3 seconds continuous to be considered "silenced"
•Bell must pulse on and off 3 times to be considered "pulsed", 3rd off-time
will trigger event
BellReport CodeGroup
Pulsed
Steady
FA98
BA98
Fire
Burglary
NOTE: Mode 1 is not intended for UL Installations.
9
Page 14
[02]Mode 2 - (2) 24-Hour Zones
In this mode, the YEL and GRN
terminals on the Skyroute
CL3050 will be used as zone
inputs. These zones will support
the DSC standard EOL configuration and loop response. Programming sections will allow the
installer to change the default
zone types and attributes. The
Skyroute CL3050 will continuously monitor these zones and
transmit any alarms that occur to
the central station.
NOTE: Use Mode 2 for UL residential burglary installations.
[03]Mode 3 - (8) 24-Hour Zones
In this mode, the Skyroute
CL3050 is connected to a
PC5108 zone expander using the
corresponding RED, BLK, YEL and
GRN terminals. The Skyroute
CL3050 will drive the Keybus to
communicate with the PC5108.
A +12V
DC
supply connected to
the RED and BLK terminals is
required when using this mode.
The Programming sections allow the installer to change the default zone types
and attributes. The Skyroute CL3050 continuously monitors these zones and
transmits any alarms that occur to the central station.
Input Voltage
10.6-14 V or V
Zone 1 Input
Zone 2 Input
Zone Common
Trouble Output
+12 V
ACDC
DC
Ground
To Keybus
Connections
on PC5108
System Common
Trouble Output
Programming Descriptions
RED BLK YEL GRN COM PGM
RED BLK YEL GRN COM PGM
NOTES: This configuration can not be used with an AC supply.
Jumpers on the PC5108 must be set as follows:
OFF
J1
J2
J3
ON
OFF
ON
J4
J5
J6
OFF
ON
Default - [01 -03] dependant on start up configuration.
NOTES: Use Mode 3 for UL Installations.
PC5108 must be installed in its own enclosure or in the same cabinet as the control panel.
All connections are power limited.
[11] Skyroute CL3050 Configuration Options 1
Option 1 - A Channel Selected/ B Channel Selected. All Modes
This Option determines whether cellular channel “B” or channel “A” is used. In
Canada, Channel B is used (Default). In the USA refer to the SID list for the channel of the cellular service provider in your area. Default - Channel B
Normally Closed Loops can be wired as shown. Multiple Normally Closed contacts can be wired in series. For Double or Single EOL resistors this option must be
set to OFF. Default - Normally Closed (N/C) Loops.
This option selects Double EOL resistors (ON) or Single EOL resistors (OFF) wired
as indicated
Single EOL resistors allows the use
of N/C and/or Normally Open contacts.
CZxCZxCZx
Double EOL resistors allows the
zone to be monitored for fault,
tamper, secure and violated conditions. Only Normally Closed contacts
can be used in this configuration
CZxCZx
5.6K ohm
5.6K ohm
5.6K ohm
Tamper
Contact
5.6KΩ
5.6KΩ
5.6KΩ
5.6KΩ
NOTES: Option 2 must be set to OFF to enable these options. Default - OFF
Option must be ON for UL Installations.
Option 4 - Test Once a Day Enabled/DisabledAll Modes
Allows transmission test daily. Default - Disabled.
NOTE: Option must be ON for UL Installations.
Option 5 - Test Once a Week Enabled/DisabledAll Modes
Allows transmission test weekly. Default - Enabled
NOTE: This option will be overridden If option 4 is set for daily test transmissions.
Option must be OFF for UL Installations.
Option 6 - Enrolled with Connect 24 /Not EnrolledAll Modes
This option is set automatically during the enrollment procedure with
Connect 24. IF the Skyroute CL3050 is reset to the default settings this option
must be set to ON for the Skyroute CL3050 to resume communications.
Default - Not Enrolled.
Options 7, 8 - System UseAll Modes
CAUTION: Do NOT change these settings unless it is requested by DSC technicalsupport personnel. Default - OFF.
This option limits the number of alarm events transmitted per zone to 8 until the
counter has been reset (counter automatically resets at midnight), then event
transmissions will resume. Default - Enabled
NOTES: Tampers and Faults will be counted unless they are disabled in section [20].
Option must be OFF for UL Installations.
Options 2 - 8 Future Use
[13] Skyroute CL3050 Trouble Output mask
The PGM output is dedicated for trouble indications. If a control panel is not
monitoring the Skyroute CL3050, an LED or a buzzer can be connected between
this terminal and the RED terminal for a trouble indication. The PGM terminal
switches low from an open-collector state. Connect to the control panel using a
single EOL resistor configuration.
All Modes
11
Page 16
Programming Descriptions
.
Control Panel
Zx COM
NOTE: A relay may be required for proper operation in other configurations.
See paragraph 3.3 Terminal Connections.
Option 1 - Low batteryAll Modes
Skyroute CL3050
RED BLK YEL GRN COM PGM
5.6K
If the battery voltage drops below 5.72V
DC.
battery voltage rises to 5.87V
Default - ON
DC
a trouble will be indicated until the
Option 2 - Input Supply FailureAll Modes
If AC power is absent or if DC power drops below 8.8V
terminals, this
trouble is indicated. Default - ON
DC
on the RED and BLK
Option 3 - Zone Fault/Tamper (DEOL Only)Modes 2, 3
A trouble will be indicated if any zone reports a fault or tamper condition. In Section [11], Option [2] must be set to OFF and Option [3] must be set to ON for this
option to be enabled. Default - OFF
Option 4 - No Service AvailableAll Modes
This trouble is indicated If the system is unable to detect cellular service.
Default - ON
Option 5 - Radio FailureAll Modes
This trouble is indicated if there is an internal fault with the cellular radio.
Default - ON
Option 6 - PC5108 FailureMode 3
This trouble is indicated if a PC5108 supervisory or Keybus fault occurs.
NOTE: The PC5108 tamper is communicated only, therefore it can only be
enabled by turning on section 20 option 7 and section 21 option 5. There is no
local annunciation for this event. Default - ON
Option 7 - Failure to Communicate (FTC)All Modes
This trouble will be indicated if no acknowledgement has been received from
Connect 24 after three attempts. Default - ON
Option 8 - Skyroute CL3050 TamperAll Modes
This trouble will be indicated if the cover is removed from the Skyroute CL3050
activating the on-board tamper switch. Default - OFF
[15] System Time
When the time and day have been programmed, the values are saved and are
used as the current time and day whenever the Skyroute CL3050 does a power
up. Time and day programming is only required if the installer desires the Skyroute CL3050 to test transmit at a specific time and/or day. There is no "loss of
time" trouble on the Skyroute CL3050.
Default - 0000 - 2359
All Modes
12
Page 17
Skyroute CL3050 Universal Wireless Communicator
NOTE: If AC Power is detected, it will be used to provide the time base for the
internal clock. If AC power is not detected the internal clock will automatically
use the crystal time base.
[16] System Day of the Week
See section [15].
Option 1. (Sunday) Default - ON
Option 2 - 8. (Monday - Saturday) Default - OFF
[17] Test Transmission Time
When the Skyroute CL3050 is powered up for the first time, or after a default
reset; it will check if the test transmission time and day are programmed. If they
are not, a random time (0000 - 2359) will be programmed into this location. The
Skyroute CL3050 will randomly generate this value.
NOTE: Due to traffic volume, when selecting test transmission times, select a
time that is not on the :30 minute mark (e.g., 02:24, 04:07).
[18] Test Transmission Day
When the Skyroute CL3050 is powered up for the first time, or after a default, it
will check if the test transmission time and day are programmed. If they are not,
a random day (Sunday-Saturday) will be programmed into this location. The Skyroute CL3050 will randomly generate this value. Because one test transmission
weekly is the most common configuration, this will allow the installer to setup
the Skyroute CL3050 without keypad programming.
Option 1-8. Default - [Random] - One only will be enabled.
All Modes
All Modes
All Modes
[20] Transmission Options
When the following options are enabled the reporting codes listed in Appendix A
are sent to Connect 24.
Options 1, 2 - Zone Alarm/Zone Alarm RestoresModes 2, 3
When a zone is violated or restored, the reporting codes listed in Appendix A will
be sent.
NOTES: If generic reporting is enabled and multiple alarms occur during the
delay programmed in Section [23], only one alarm reporting code will be sent.
Zone alarm restorals enabled with generic zone reporting enabled can cause
unpaired events to be sent to Connect 24.
Option 1. Default - ON, Option 2. Default - OFF
Options 3, 4 - Zone Fault, Zone Fault RestoresModes 2, 3
When the system sees a short circuit across any zone, a zone fault is generated.
DEOL resistors are required for zone fault reporting. In Section [11], Option [2]
must be set to OFF and Option [3] must be set to ON; In Section [13], Option 3
must be set to ON and the Skyroute CL3050 must be operating in mode 2 or 3.
Option 3. Default - OFF, Option 4. Default - OFF
Options 5, 6 - Zone Tamper, Zone Tamper RestoresModes 2, 3
All Modes
13
Page 18
Programming Descriptions
When the system sees an open circuit across any zone a zone tamper is generated. DEOL resistors are required for zone tamper reporting. In Section [11],
Option [2] must be set to OFF and Option [3] must be set to ON. In Section [13],
Option [3] must be set to ON and the Skyroute CL3050 must be operating in
mode 2 or 3.
Option 5. Default - OFF, Option 6. Default - OFF
Option 7 - System Maintenance EventsAll Modes
When this option is enabled, the maintenance events enabled in Section [21] are
transmitted using the codes listed in appendix A.
Default - ON,
Option 8 - Generic ZonesModes 2, 3
The Skyroute CL3050 supports generic and detailed zone alarm reporting. By
default, the Skyroute CL3050 will be in generic zone reporting mode. When in
this mode, all zone types are divided into four reporting groups; BA Burg, FA Fire,
PA Panic, UA Technical. If any zone from this group initiates a transmission, the
generic reporting code for this event is sent, additional violations from other
zones from the same group will be ignored until that group's timer has expired.
See table below for zone type grouping.
Each zone group has it's own timer. The default time is 5 minutes and is programmed in Section [23]. If any zone in a group initiates an event, the timer will
start running and the generic event will be sent. If any additional zones from the
same group initiate an event before that group's timer expires, the event will be
ignored. This generic zone reporting mode only applies to zone alarms. Alarm
restorals, tamper/tamper restorals and fault/fault restorals are not grouped
together into generic reporting groups.
The generic identifier will be sent with 98 as it's zone number, this is a special
combination recognized by Connect 24 as a generic event. When the generic
zone reporting toggle is disabled, each zone alarm for each zone type will then
send it's own identifier. Default - ON.
NOTE: The CL3050 communication zone and trouble zone will always send
detailed reporting codes.
Detailed
Reporting Code
-
BA
FA
PA
UA
GA
KA
MA
QA
WA
ZA
SA
HA
Generic
Reporting Code
-
BA
FA
PA
UA
UA
FA
PA
PA
UA
UA
UA
PA
14
Page 19
Skyroute CL3050 Universal Wireless Communicator
[21] System Event Communication Options
NOTE: Section [20], Option [7] must be enabled for these events to be communicated.
Option 1 - Input Supply FailureAll Modes
If AC power is absent or if DC power drops below 8.8V
terminals, a
expired. Default - ON,
Option 2 - Low BatteryAll Modes
If the battery voltage drops below 5.72V
When the battery voltage rises to 5.87V
Default - ON.
Option 3 - Skyroute CL3050 TamperAll Modes
Removing the cover on the Skyroute CL3050 will send a tamper reporting code
to Connect 24. Default - OFF.
Option 4 - PC5108 Module FaultMode 3
Indicates a Keybus communications fault condition. Default - OFF.
Option 5 - PC5108 TamperMode 3
Removing the cover on the PC5108 will send a tamper reporting code to
Connect 24. Default - OFF.
Option 6 - TLM Trouble ReportAll Modes
Indicates a telephone line trouble if a CL3050 communications zone is violated.
Default - OFF.
trouble will be sent after the delay programmed in section [22] has
[22] Input Supply Fail TX Delay
DC
on the RED and BLK
DC
a trouble will be sent to Connect 24.
DC
the system will send a restore.
All Modes
This value determines the delay (default 0700 = 7 hrs) before an input supply failure reporting code is sent if programmed. See Section [21], Option [1] and Section [20], Option [2]. Default - 0700 (=7 hrs)
[23] Generic Zone Reporting Timer
This hex value determines the delay before a generic zone reporting code is sent,
if programmed in Section 20 Option 8.
NOTE: There are four separate timers for Burglary, Fire, Panic and Supervisory;
the delay programmed is the same for each timer.
Default - 1E (300 seconds / 5 minutes) Range equals 01-FF Hex seconds x 10
[24] Number of Attempts
This value determines how many attempts are made to send an event to
Connect 24. Default - 03
NOTES: For UL Installations in Mode 2, minimum 5, maximum 10 attempts
required.
For UL Installations in Mode 3, the combination of attempts between DACT and
Skyroute shall be minimum 5 and maximum 10.
[25] Response Wait Time
This value determines how long the Skyroute CL3050 will wait for a response
from Conect 24 before attempting to resend the same event.
Default - FA (250 seconds) range equals 01-FF Hex seconds.
NOTE: For UL Installations this must be 90 seconds (5A).
Modes 2, 3
All Modes
All Modes
15
Page 20
Programming Worksheets
Section 7: Programming Worksheets
Zone Definitions (For Sections [01] -[02])
00 Null Zone (Not Used)
01 Burglary
02 Fire
03 Panic
04 Technical
* Not for use in UL Installations.
[01] Zone 1-2 Definitions
DefaultDefault
01I___I___I Zone 101 I___I___IZone 2
[02] Zone 3-8 Definitions
DefaultDefault
01I___I___I Zone 301 I___I___IZone 4
01I___I___I Zone 501 I___I___IZone 6
01I___I___I Zone 701 I___I___IZone 8
[03] Zone 1-2 Loop Response 01-FF (Hex 0.1 second increments), mode 2 only
DefaultDefault
05I___I___I Zone 105 I___I___IZone 2
05 Gas*
06 High Temp*
07 Medical*
08 Emergency
09 Water Level*
NOTE: Option must be disabled for UL Installations.
[13] Skyroute CL3050 Trouble Mask
DefaultOpt Option OnOption Off
ONI___I1Low BatteryDisabled
ONI___I2Input Supply FailureDisabled
OFFI___I3Zone Fault/Tamper (DEOL
only)
ONI___I4No Service AvailableDisabled
ONI___I5Radio FailureDisabled
ONI___I6PC5108 FailureDisabled
ONI___I7Failure to Communicate Disabled
OFFI___I8Skyroute CL3050 Tamper Disabled**
[15] System Time
DefaultRange
Swinger Shutdown Disabled
Disabled
0000 I___I___I___I___I0000-2359Hrs/Mins
[16] System Day
Default OptOption OnOption Off
ONI___I1SundayDisabled
OFFI___I2MondayDisabled
OFFI___I3TuesdayDisabled
OFFI___I4WednesdayDisabled
OFFI___I5ThursdayDisabled
OFFI___I6FridayDisabled
OFFI___I7SaturdayDisabled
OFFI___I8For Future Use
[17] Test Transmission Time
DefaultRange
Random I___I___I___I___I 0000-2359Random on power up unless pro-
grammed
17
Page 22
Programming Worksheets
[18] Test Transmission Day *Selected at random on power up
Default OptOption OnOption Off
* I___I 1SundayDisabled
* I___I 2MondayDisabled
* I___I 3TuesdayDisabled
* I___I 4WednesdayDisabled
* I___I 5ThursdayDisabled
* I___I 6FridayDisabled
* I___I 7SaturdayDisabled
* I___I 8For Future Use
[20] Transmission Options
Default OptOption OnOption Off
ONI___I1Zone AlarmsDisabled
OFFI___I2Zone Alarm RestoresDisabled**
OFFI___I3Zone FaultDisabled**
OFFI___I4Zone Fault RestoresDisabled**
OFFI___I5Zone TamperDisabled**
OFFI___I6Zone Tamper RestoresDisabled**
ONI___I7System Maintenance
Events
ONI___I8Generic Zone ReportingDetailed Zone Reporting**
[21] System Event Communication Options
Default OptOption OnOption Off
ONI___I1Input Supply FailureDisabled
ONI___I2Low BatteryDisabled
OFFI___I3Skyroute CL3050 Tamper Disabled**
OFFI___I4PC5108 Module FaultDisabled**
OFFI___I5PC5108 TamperDisabled**
OFFI___I6TLM Trouble ReportDisabled**
[22] Input Supply Fail TX Delay
DefaultRange
0700 I___I___I___I___I 0000-
2359
Disabled**
Hrs/Mins
[23] Generic Zone Reporting Timer
DefaultRange
1E I___I___I 01-FF(Hex seconds ×10)
** Option must be ON for UL Installations.
18
Page 23
Programming Worksheets
[24] Number of Attempts
DefaultRange
03 I___I___I 01-FF(Hex)
[25] Response Wait Time
DefaultRange
FA I___I___I 01-FF(Hex seconds)
For UL Installations program 5A.
19
Page 24
Glossary of Terms
Glossary of Terms
CellemetryA network allowing short data packets to be sent on cellular control chan-
nels.
Connect 24Connect 24 is the service provider that provides the Skyroute service to the
security industry and links the Skyroute cellemetry communicator to the central station.
RSSIRadio Signal Strength Indication - This value is transmitted to Connect 24
during the periodic test transmission and can be viewed after power up by
pressing the enroll button.
SIDSystem Identification Number - ID Number of the Cellular provider
MINMobile Identification Number - The 10 digit decimal number used for regis-
trations and pages (the phone number of the Skyroute CL3050).
PageA transmission that is sent from the Cellemetry Gateway to the Cellemetry
Radio
RegistrationA transmission that is sent from the Cellemetry Radio to the Cellemetry
Gateway
20
Page 25
Skyroute CL3050 Universal Wireless Communicator
Appendix A: Reporting Codes
EventsReporting CodesEventsReporting Codes
SIA
Zone AlarmsZone Restores
Burglary ZoneBAXXE130Burglary ZoneBHXXR130
Fire ZoneFAXXE110Fire ZoneFHXXR110
Panic ZonePAXXE120Panic ZonePHXXR120
Technical ZoneUAXXE140Technical ZoneUHXXR140
Gas Zone*GAXXE151Gas Zone*GHXXR151
High Temp Zone*KAXXE158High Temp Zone*KHXXR158
Medical Zone*MAXXE100Medical Zone*MHXXR100
Emergency ZoneQAXXE120Emergency ZoneQHXXR120
Water Level Zone*WAXXE154Water Level Zone*WHXXR154
Low Temp Zone*ZAXXE140Low Temp Zone*ZHXXR140
Sprinkler Zone*SAXXE110Sprinkler Zone*SHXXR110
Hold-up ZoneHAXXE122Hold-up ZoneHHXXR122
Trouble ZoneYX00E300Trouble ZoneYZ00R300
Zone Fault AlarmsZone Fault Restores
Burglary ZoneUTXXE300Burglary ZoneUJXXR300
Fire ZoneFTXXE373Fire ZoneFJXXR373
Panic ZoneUTXXE300Panic ZoneUJXXR300
Technical ZoneUTXXE300Technical ZoneUJXXR300
Gas Zone*UTXXE300Gas Zone*UJXXR300
High Temp Zone*UTXXE300High Temp Zone*UJXXR300
Medical Zone*UTXXE300Medical Zone*UJXXR300
Emergency ZoneUTXXE300Emergency ZoneUJXXR300
Water Level Zone*UTXXE300Water Level Zone*UJXXR300
Low Temp Zone*UTXXE300Low Temp Zone*UJXXR300
Sprinkler Zone*STXXE200Sprinkler Zone*SJXXR200
Hold-up ZoneUTXXE300Hold-up ZoneUJXXR300
Trouble ZoneUT00E380Trouble ZoneUJ00R380
Contact
ID
SIA
Contact
ID
* Not for use in UL Installations.
21
Page 26
Skyroute CL3050 Universal Wireless Communicator
EventReporting CodeEventReporting Code
SIA
Zone Tamper AlarmsZone Tamper Restores
Burglary ZoneBTXXE380Burglary ZoneBJXXR380
Fire ZoneFTXXE373Fire ZoneFJXXR373
Panic ZonePTXXE380Panic ZonePJXXR380
Technical ZoneUTXXE380Technical ZoneUJXXR380
Gas Zone*GTXXE380Gas Zone*GJXXR380
High Temp Zone*KTXXE380High Temp Zone*KJXXR380
Medical Zone*MTXXE380Medical Zone*MJXXR380
Emergency ZoneQTXXE380Emergency ZoneQJXXR380
Water Level Zone*WTXXE380Water Level Zone*WJXXR380
Low Temp Zone*ZTXXE380Low Temp Zone*ZJXXR380
Sprinkler Zone*STXXE373Sprinkler Zone*SJXXR373
Hold-up ZoneHTXXE380Hold-up ZoneHJXXR380
Trouble ZoneUTXXE380Trouble ZoneUJXXR380
Generic Zone EventsSystem Events
Generic Burglary BA98E130
Generic Fire FA98E110
Generic Panic ZonePA98E120
Generic SupervisoryUA98E140
Contact
ID
98
98
98
98
Input Supply Fail
Trouble
Input Supply Fail
Restore
Low Battery TroubleYT00E302
Low Battery RestoreYR00R302
Skyroute CL3050
Tamper Alarm
Skyroute CL3050
Tamper Restore
PC5108 Tamper AlarmES00E330
PC5108 Tamper RestoreEJ00R330
PC5108 Supervisory
Trouble
PC5108 Supervisory
Restore
Periodic Test
Transmission
Periodic Test**RP00E602
Periodic Test
with Trouble**
TLM TroubleLT01E351
TLM RestoreLR01R351
SIA
YP00E312
YQ00R312
TA00E137
TR00R137
ET00E330
ER00R330
TXZZE603
RY00E608
Contact
ID
* Not for use in UL Installations.
** Only sent if a trouble zone is programmed.
22
Page 27
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd. could void your
authority to use this equipment.
This equipment generates and uses radio frequency energy and if not installed and used properly, in strict accor-
dance with the manufacturer’s instructions, may cause interference to radio and television reception. It has been type
tested and found to comply with the limits for Class B device in accordance with the specifications in Subpart “B” of
Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in any residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause interference to television or radio reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Re-orient the receiving antenna
• Relocate the alarm control with respect to the receiver
• Move the alarm control away from the receiver
• Connect the alarm control into a different outlet so that alarm control and receiver are on different circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional sugges-
tions. The user may find the following booklet prepared by the FCC helpful: “How to Identify and Resolve Radio/
Television Interference Problems”. This booklet is available from the U.S. Government Printing Office, Washington, D.C. 20402, Stock # 004-000-00345-4.
WARNING: To satisfy FCC RF exposure requirements for mobile transmitting devices, a
separation distance of 30 cm or more must be maintained between the antenna of this
device and persons during device operation.
Industry Canada COMPLIANCE STATEMENT
This Class B digital apparatus meets all requirements of the Canadian interference-causing equipment regulations.
Cet appareil numérique de la Classe B respecte toutes les exigences de règlement sur le matériel brouilleur du
Canada.
IC:160A - CL3050
The term "IC:" before the radio certification number only signifies that Industry Canada technical specifications
were met.
Limited Warranty
DSC warrants that for a period of one year from the date of purchase, the product shall be free of defects in material
and workmanship under normal use and that in fulfillment of any breach of such warranty, DSC shall, at its option,
repair or replace the defective equipment upon return of the equipment to its repair depot. This warranty applies only
to defects in materials and workmanship and not to damage incurred in shipping or handling, or damage due to
causes beyond the control of DSC, such as lightning, excessive voltage, mechanical shock, water damage or damage
arising out of abuse, alteration or improper application of the product.
The foregoing warranty shall apply only to the original purchaser, and shall be in lieu of any and all other warranties,
whether expressed or implied and of all other obligations or liabilities on the part of DSC. This warranty contains the
entire warranty. DSC neither assumes responsibility for, nor authorizes any other person purporting to act on its
behalf to modify or to change this warranty, nor assume for it any other warranty or liability concerning this product.
In no event shall DSC be liable for any direct, indirect or consequential damages, loss of anticipated profits, loss of
time or any other losses incurred by the purchaser in connection with the purchase, installation or operation or
failure of this product.
Important!
Test results are only valid at the time of testing. Results may vary with but are not limited to environmental
and structural changes. Electrical equipment operating in the immediate area may cause interference.
Skyroute, PowerSeries, Connect 24 are trademarks of DSC