DSC Skyroute CL3050 ver 1.2 Installation & Programming Manual

Page 1
Universal Wireless Communicator
Compatible with all PowerSeries keypads
Installation & Programming Guide
ver 1.2
WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. Read the entire manual carefully.
CL3050
Page 2
Location
Test Time & Day
Additional Notes
For Your Records
CONNECT 24
Note: Only authorized dealers can enroll a wireless system to Connect 24.
Dealer application forms and additional information on the Connect 24 Voice Response Unit can be found at the Connect 24 web site.
The information required for activation is listed below. Ensure that all information is available before calling the Connect 24 Voice Response Unit.
TM
Enrollment Information
http://www.connect24.com/dealer.htm
USA 1-888-251-7458 CAN 1-888-955-5583
Profile Number ...................................................5 digits I___I___I___I___I___I
The profile number provides Central Station Receiver information.
Installer ID Number............... 8-9 digits I___I___I___I___I___I___I___I___I___I
An Installer ID number was provided for each installer listed on the Dealer Enrollment Form. This number can be found on the authorized Installer Card sent with the Dealer Confirmation Form.
Installer PIN Number................................................ 4 digits I___I___I___I___I
Each Installer provided a 4 digit PIN number on the Dealer Enrollment Form. If you have forgotten your PIN Number contact Connect 24.
Central Station Account number ............ 2-6 digits I___I___I___I___I___I___I
This is the Account Number that will be sent to the Central Station.
NOTE: 4-digits maximum for Contact ID format.
Skyroute MIN....................10 digits I___I___I___I___I___I___I___I___I___I___I
The Skyroute Mobile Identification Number identifies the Skyroute transmitter. The 10-digit MIN is located on the label affixed to your Skyroute Transmitter.
System ID Number (SID)................................ 5 digits I___I___I___I___I___I
The System ID Number informs Connect 24 and the cellular network the home area that your transmitter is installed in. When this number is programmed into
an alarm panel it is entered in HEX format. When entering this number into the Connect 24 Voice Response Unit, it is entered in Decimal Format.
Page 3
Table of Contents
Section 1: Introduction............................................................................ 1
1.1Specifications.......................................................................................................... 2
1.2Unpacking .............................................................................................................. 2
Section 2: Quick Start.............................................................................. 3
2.1Installation.............................................................................................................. 3
2.2Testing .................................................................................................................... 4
2.3Resetting to Factory Defaults .................................................................................. 4
Section 3: Controls & Indicators ............................................................. 5
3.1LED Indicators......................................................................................................... 5
3.2Enroll Button........................................................................................................... 6
3.3Terminal Connections.............................................................................................. 6
Section 4: Power up Sequence ............................................................... 7
Section 5: System Programming ............................................................ 8
Section 6: Programming Descriptions.................................................... 8
[01]Zone 1-2 Definitions ..............................................................................................8
[02]Zone 3-8 Definitions ..............................................................................................9
[03]Zone 1-2 Loop Response........................................................................................ 9
[10]Skyroute CL3050 Mode of Operation..................................................................... 9
[11]Skyroute CL3050 Configuration Options 1........................................................... 10
[12]Skyroute CL3050 Configuration Options 2........................................................... 11
[13]Skyroute CL3050 Trouble Output Mask ................................................................11
[15]System Time ........................................................................................................ 12
[16]System Day.......................................................................................................... 13
[17]Test Transmission Time ......................................................................................... 13
[18]Test Transmission Day........................................................................................... 13
[20]Transmission Options ...........................................................................................13
[21]System Event Communication Options................................................................. 15
[22]Input Supply Fail Tx Delay .................................................................................... 15
[23]Generic Zone Reporting Timer ............................................................................. 15
[24]Number of Attempts............................................................................................ 15
[25]Response Wait Time............................................................................................. 15
Section 7: Programming Worksheets................................................... 16
Glossary of Terms .................................................................................. 20
Appendix A: Reporting Codes.............................................................. 22
i
Page 4
NOTE:
ii
Page 5
Introduction
Section 1: Introduction
The Skyroute CL3050 is a standalone wireless communicator that sends alarm system infor­mation to Connect 24. Connect 24 then forwards this information to the central station. The Skyroute CL3050 has four modes of operation. It can operate in one of three opera­tional modes or; if it is connected to a keypad, in the programming mode. The Skyroute CL3050 is pre-programmed with the most commonly used settings for quick installation. If required the default options can be custom programmed.
NOTE: For UL Installations, use mode 2 or 3 ONLY.
Mode 1: Bell Follower
In Mode 1, the Skyroute CL3050 monitors the Bell Output of the control panel. The system identifies the Bell Output cadence and transmits the corresponding Fire or Burglar alarm reporting code to Connect 24. Refer to the appropriate control panel Installation Manual.
NOTE: Not for UL Listed installations.
Mode 2: 2-Zone Panel
In Mode 2, the system will configure itself for 2 zone, stand alone operation.
NOTE: UL Listed for residential burglary installations ONLY.
Mode 3: 8-Zone Panel
If the Skyroute CL3050 detects a PC5108 expander card on power up it will auto­matically configure itself for 8-zone standalone operation with normally closed loops.
NOTE: Standalone operation is intended for household fire and burglary and it is considered ancillary operation for commercial fire and burglary installations.
Programming Mode
If the Skyroute CL3050 detects a keypad on power up it will go into the program­ming mode. Programming mode allows the installer to custom program system options. Refer to Section 5, Programming Descriptions; and Section 6, Program­ming Worksheets for programming options and default settings.
Figure 1
CL3050
1
Page 6
1.1 Specifications
Power Supply Ratings Voltage: 10.6-14 V Current: 500 mA (Max) Low DC Trouble: 8.8 V Low DC Restore: 9.0 VDC Low AC Trouble: 7.5 V Low AC Restore: 8.0 V
Current Drain Standby: 100 mA Receiving: 150 mA Transmitting: 850 mA (350 mA from external power supply)
RF Power Output: 600 mW
Antenna Gain: 0 db
Battery Charging Voltage: 6.87 V Low Battery Restore: 5.87 V Low Battery Trouble: 5.72 VDC Critical Shutdown: 5.0 VDC
Operating Modes
Bell Follower 2-24Hr Zones 8-24Hr zones (with PC5108)
Event Buffer (communications): 32 Events (not viewable)
Dimensions: 5 1/8” x 7 3/4” x 2”
Weight: 0.5 lbs. (0.2Kg)
EEPROM Memory
Programmable by all PowerSeries Keypads PC5508/KP5508Z: 8 Zone LED keypad PC5516Z/KP5516Z: 16 Zone LED keypad PC5532Z/KP5532Z: 32 Zone LED keypad LCD5500Z/KPL5500Z: Programmable Message LCD Keypad LCD5501Z/KP5501Z: Fixed Message LCD Keypad
AC or VDC
DC
AC
AC
DC
DC
Introduction
1.2 Unpacking
Verify that the following items have been included.
Skyroute CL3050 (rechargeable battery included)
1
Installation & Programming Guide
1
Antenna
1
Mounting screws
4
5.6K resistors
4
Enclosure screw
1
Remove antenna from protective bubble pack and install in unit.
CAUTION: Install antenna before connecting battery or power leads to this unit. Transmis­sion without an antenna can cause permanent damage. When removing cover of this unit DO NOT touch or handle exposed electrical devices and components. Electrostatic discharge (ESD) can permanently damage this unit or reduce the reliability and life expectancy of components.
2
Page 7
Skyroute CL3050 Universal Wireless Communicator
Section 2: Quick Start
2.1 Installation
1 Determine The Operating mode required
The operating mode (modes 1, 2, or 3) will determine how the unit is to be wired up. Refer to section 6, Programming Descriptions, section [10] for available options and for programming defaults. See section 4, Power up Sequence for selection of Operating and Programming modes.
NOTE: For UL Installations, use only mode 2 or 3.
2 Determine the Mounting Location
Select a mounting location in a dry, protected area. The mounting location should be positioned so that it is at least 30 cm. away from physical contact with any person.
NOTE: Do Not exceed the following recommendations for wire run distances
Keybus and zone wiring should be run using minimum 22 gauge quad
(0.5mm). Two pair twisted is preferred.
a keypad, PC5108, or zone wiring can not exceed 1,000'/305m (in wire
length) from the Skyroute CL3050.
Shielded wire is not necessary unless wires are run in an area that may present
excessive RF noise or interference.
Refer to section 6, Programming Descriptions, section [10] for zone wir-
ing details.
NOTE: Generally, the higher the location and the closer that the Skyroute CL3050 is to an outside wall, the better the signal strength will be.
3 Checking Signal Strength
•Remove front cover
Connect Battery to the RED and BLK flying leads.
Connect AC Power source or 12 V
Allow unit to power up
NOTE: The unit does not need to be enrolled with Connect 24 to check signal strength.
When the green LED stops flashing, press and release the enroll button.
Ensure that Radio Signal Strength Indication (RSSI) is greater than the mini-
mum acceptable level as indicated below. If the signal level is not accept­able, reposition and retest the Skyroute CL3050 until an acceptable signal strength is found.
Red LED Yellow LED Green LED Signal Strength
On On On On On
Flash
On On On
Flash
Off Off
DC
to RED & BLK terminals.
On
Flash
Off Off Off Off
>87%
69-87%
*52-68%
34-51% 16-33%
0-15%
*Minimum recommended signal strength for enrollment
4 Route Wiring to Mounting Location
Route wiring from the hardwired zones or control panel as required.
NOTE: Route wiring through conduit to a junction box if possible. Mount the Skyroute Panel.
3
Page 8
5 Mount Unit
Remove the front cover if required
Disconnect flying leads from battery and power leads from the RED and BLK
Remove two screws securing battery clamp. Remove battery
Mount backplate of unit to wall or over electrical junction box using the
NOTE: DO NOT connect the battery to the flying leads and AC or DC power to the terminal strip until all other wiring connections are completed.
Route wiring through the access holes provided and connect to terminal
Power up unit by connecting battery and power source.
Front cover is to be securely fastened with screw provided.
6 Enroll Unit
Call Connect 24 and Enroll the Skyroute CL3050. Refer to back of Front Cover for contact information and a list of information required to complete the enroll­ment with the Connect 24 Voice Response Unit.
2.2 Testing
Quick Start
terminals (if connected).
four screws provided.
strip.
Program Mode: If you have wired the unit to power up in the programming mode. Follow the steps outlined in Section 6, Programming Descriptions and record the program settings in Section 7, Programming Worksheets.
Test Transmission - Pressing and holding the enroll button for 2 seconds will send a test transmission to the central station via Connect 24. Refer to Enroll Button in Section 3, Controls and indicators for test transmission details.
Mode 1: Disable the telephone line connected to the control panel. Simulate Burglar and Fire Zone violation. Verify that the Skyroute CL3050 transmits the events to the central station.
Mode 2 & 3: Simulate Faults, Tampers, and Zone violations in accordance with the settings outlined in Sections 6, Programming Descriptions. Verify that the Skyroute CL3050 transmits the events to the central station.
2.3 Resetting to Factory Defaults
NOTE: Resetting to factory defaults is required to change mode of operation.
Remove Power from the Skyroute CL3050; disconnect battery and control
panel if applicable (mode 1).
Disconnect all wiring from the YEL and GRN terminals.
Connect a jumper wire between the YEL and GRN terminals.
Apply power to the system.
NOTE: When the hardware default has been completed; the yellow, green and red LEDs will flash on and off continuously.
Remove power from the system.
NOTE: To resume communications with Connect 24, Section [11], Option 6 must be set to ON. To do this; the system must be powered up in programming mode. Refer to Section 5 System Programming.
Reconnect all original wiring and reapply power to the system.
Test System - Refer to Section 2.2
4
Page 9
Skyroute CL3050 Universal Wireless Communicator
Section 3: Controls and Indicators
Figure 2
Antenna
Mounting Holes
Green LED
Yellow LED
Battery (6 VDC)Battery (6 V )
1.3 Ah
Wire Access
DC
SW2
Tamper Switch
RED BLK YEL GRN COM PGM
3.1 LED Indicators (see figure 2)
Yellow LED
During normal operation, the yellow LED will indicate the system status with a series of flashes as indicated below.
SW1
Red LED
Enroll Button
No. of Flashes Indication
1 2 3 4 5 6 7 8 9
No trouble conditions present Low battery Input supply failure Not enrolled at Connect 24 No service available Radio failure PC5108 failure Failure to communicate Zone tamper/fault trouble
5
Page 10
Controls and Indicators
NOTE: Multiple trouble conditions are displayed (flashed) in sequence.
Red LED
The red LED will flash to provide event transmission status for the following events:
1 Flash 1 Flash
2 Flashes
Enroll button held down for 2 seconds Event transmitted to cellular network Event acknowledged by Connect 24.
Green LED
The green LED will light continuously if the (RSSI) signal is acceptable. If signal strength is not acceptable the LED will turn OFF. Detailed information on signal strength can be accessed by momentarily pressing and releasing the enroll button. The green, yellow and red LEDs will light to indicate the range of signal strength. Refer to Section 2 Step 3.
3.2 Enroll Button (see figure 2)
The Skyroute CL3050 Enroll button is located on the outside of the plastic hous­ing directly below the status LEDs. The enroll button performs three functions.
Pressing and releasing this button momentarily during the first 15 seconds
of power up will toggle between Mode 1 and Mode 2 to enable mode selection.
Pressing and releasing this button momentarily at any time after the power
up sequence will display the detailed RSSI status indicated above.
Holding this button down for a period of 2 seconds continuously will cause
the Skyroute CL3050 to send a test transmission to Connect 24, this long debounce will be indicated by the red LED flashing once.
3.3 Terminal Connections (see figure 2)
RED 10.6-14V
NOTE: 12V PC5108 zone expander. Mode 1 and Mode 2 may be operated with an AC Supply.
BLK 10.6-14V
YEL Mode 1* - The YEL terminal functions as the Bell input.
Mode 2 - This terminal functions as the zone 1 input. Mode 3 - This terminal connects to the YEL Keybus terminal when
using a PC5108 zone expander or PowerSeries keypad.
GRN Mode 1* - The GRN terminal functions as the TLM Trouble input.
Mode 2 - This terminal functions as the zone 2 input. Mode 3 - This terminal connects to the GRN Keybus terminal when
using a PC5108 zone expander or PowerSeries keypad.
COM Mode 1* - This terminal functions as the common terminal for the Bell
Input on the YEL terminal, the TLM trouble input on the GRN terminal and the Trouble Output on the PGM terminal. Mode 2 - This terminal functions as the common terminal for zone 1 (YEL) and zone 2 (GRN). Mode 3 - This terminal functions as the common terminal for the Trouble Output
DC
Positive Input or 10.6-14V
DC is required for programming or for operation with a
DC
Ground or 10.6-14V
AC
AC
NOTE: Mode 1 is not intended for UL Installations.
6
Page 11
Skyroute CL3050 Universal Wireless Communicator
PGM - The PGM output is dedicated for Skyroute CL3050 trouble indica­tions. If a control panel is not monitoring the Sky­route CL3050, an LED or a buzzer can be connected between this terminal and the RED terminal for trouble indication. The PGM termi­nal switches low from an open-collector state. Con­nect to the control panel using a Single EOL configu­ration as shown in 6 Pro-
gramming Descriptions Section [13] on page 11.
NOTES: The PGM output
can sink 50 mA (maximum). For UL Installations, use DSC RM-1 Relay Module.
LED Output with current limiting resistor
Optional relay driver output
To External Supply
Skyroute CL3050
RED BLK YEL GRN COM PGM
LED 560
+ Coil -
Relay
NC Com
Section 4: Power up Sequence
On first-time power up, the Skyroute CL3050 will generate a random test trans­mission time and random day of the week to send it. The installer can then change this information if required.
During power up, the Skyroute CL3050 will look for a keypad on the Keybus, if one is found, it will go into the programming mode. If no keypad is found, it will look for a PC5108 zone expander module. If a zone expander is found, it will automatically configure itself for mode 3. If no Keybus modules are present, the Skyroute CL3050 will power up in mode 1. During the first 15 seconds of power up, any zone scanning will be shunted. During this time the installer can momen­tarily press the enroll button on the Skyroute CL3050 to toggle between mode 1 and mode 2. Upon power up the green LED will be flashing on and off. This will indicate to the installer that he/she can change the mode to 1 or 2. The red LED will indicate mode 1 and the yellow LED will indicate mode 2. If neither red or yel­low LED is lit, then the Skyroute CL3050 has detected a PC5108 module, the mode cannot be changed by pressing the enroll button if a PC5108 module is connected to the Skyroute CL3050. If a keypad is detected on Keybus, the green LED will stop flashing, and the red LED will begin flashing to indicate that programming mode is active.
7
Page 12
Section 5: System Programming
The Skyroute CL3050 is programmed using any PowerSeries keypad. Refer to
Section 1.1 Specifications.
NOTE: Power down the Skyroute CL3050 when connecting or removing other
Keybus modules from the system. If the Skyroute CL3050 is connected to a con­trol panel (mode 1), the control panel must also be powered down.
1. Connect keypad Keybus connections to the RED, BLK, YEL and GRN termi-
nals of the Skyroute CL3050.
RED BLK YEL GRN COM PGM
+12 VDC
Ground
To Keybus Connections on Keypad
Not Connected
System Programming
2. Connect a +12VDC supply across the RED and BLK terminals.
Upon detecting the keypad on power up, the Skyroute CL3050 will begin driving Keybus and will blank the keypad with all LEDs and icons off.
NOTE: The red LED on the Skyroute CL3050 will flash continuously if a keypad is detected.
3. Press the star [*] key to gain access to the programming section.
Programming is done with a 2-digit section entry. When programming is complete, power down the Skyroute CL3050 and remove the keypad.
Section 6: Programming Descriptions
[01] Zone 1, 2 Definitions
When the Skyroute CL3050 is in Mode 2 or 3, there are 14 options that can be programmed as zone types. All of the zone types with the exception of 00 (null zone), 13 (CL3050 communications zone) and 14 (trouble zone) are straightfor­ward. Since all the zones are 24-hour type zones, selecting any listed zone type will simply select which identifier should be used for reporting the alarm. Pro­gramming a zone as 00 (null zone) will disable the zone input on the Skyroute CL3050 or PC5108 hardware. Programming any zone as type 13 (CL3050 com­munications zone) will disable all communications unless that zone input is closed (short condition). Programming a zone as 14 ( trouble zone) will enable an addi­tional reporting code to be sent with the daily/weekly test transmission (if enabled). If all zones are restored and there are no trouble conditions present on the Skyroute CL3050, a periodic test transmission code (RP00) will be sent. other­wise a periodic test off-normal code (RY00) will be sent instead.
NOTE: Do NOT program more than 1 CL3050 communications zone or trouble zone on the Skyroute CL3050.
Default - [01] zones 1 & 2
Modes 2, 3
8
Page 13
Skyroute CL3050 Universal Wireless Communicator
[02] Zone 3 - 8 Definitions
This allows programming of the six additional zone definitions when operating in mode 3 with a PC5108 zone expander. See section [01] for details Default - [01] zones 3 - 8
[03] Zone 1, 2 Loop Response
This entry determines how quickly a zone will respond to changes in state.
NOTE: This does not affect zones on a PC5108 zone expander card. Default - 05 (0.5 seconds) 01-FF Hex x 0.1 seconds.
[10] Skyroute CL3050 Mode of Operation
[01] Mode 1 - Bell Follower Operation
RED BLK YEL GRN COM PGM
Input Voltage
10.6-14 V or V Bell Input
TLM Input System Common Trouble Output
AC DC
Mode 3
Modes 2
RED BLK YEL GRN COM PGM
NC
Relay
Com
NO
Alternate connection for Control Panels where Bell switches High
BELL+ BELL-
In this mode, the YEL terminal is connected to the bell output of a control panel. The Skyroute CL3050 monitors the output for burglary and fire cadences and transmits the appropriate events. For any type of pulsed cadence, the Skyroute CL3050 will send a generic Fire event, for any steady bell the Skyroute CL3050 will send a generic Burglary event. The GRN terminal is a trouble input which can be connected to a system output to alert the Skyroute CL3050 of a system TLM fault. This will enables the Skyroute CL3050 to be used as a back-up communi­cator only. If not used, this input must to connected to COM. The bell cadence will be determined as follows:
Bell must be on for longer then 300mS to be considered a "pulse"
Bell must be on for 3 seconds continuous to be considered "steady"
Bell must be off for 3 seconds continuous to be considered "silenced"
Bell must pulse on and off 3 times to be considered "pulsed", 3rd off-time
will trigger event
Bell Report Code Group
Pulsed Steady
FA98 BA98
Fire Burglary
NOTE: Mode 1 is not intended for UL Installations.
9
Page 14
[02] Mode 2 - (2) 24-Hour Zones
In this mode, the YEL and GRN terminals on the Skyroute CL3050 will be used as zone inputs. These zones will support the DSC standard EOL configura­tion and loop response. Pro­gramming sections will allow the installer to change the default zone types and attributes. The Skyroute CL3050 will continu­ously monitor these zones and transmit any alarms that occur to the central station.
NOTE: Use Mode 2 for UL residential burglary installations.
[03] Mode 3 - (8) 24-Hour Zones
In this mode, the Skyroute CL3050 is connected to a PC5108 zone expander using the corresponding RED, BLK, YEL and GRN terminals. The Skyroute CL3050 will drive the Keybus to communicate with the PC5108. A +12V
DC
supply connected to the RED and BLK terminals is required when using this mode. The Programming sections allow the installer to change the default zone types and attributes. The Skyroute CL3050 continuously monitors these zones and transmits any alarms that occur to the central station.
Input Voltage
10.6-14 V or V Zone 1 Input
Zone 2 Input Zone Common Trouble Output
+12 V
AC DC
DC
Ground
To Keybus Connections on PC5108
System Common
Trouble Output
Programming Descriptions
RED BLK YEL GRN COM PGM
RED BLK YEL GRN COM PGM
NOTES: This configuration can not be used with an AC supply. Jumpers on the PC5108 must be set as follows:
OFF
J1 J2 J3
ON OFF ON
J4 J5 J6
OFF ON
Default - [01 -03] dependant on start up configuration. NOTES: Use Mode 3 for UL Installations.
PC5108 must be installed in its own enclosure or in the same cabinet as the con­trol panel. All connections are power limited.
[11] Skyroute CL3050 Configuration Options 1
Option 1 - A Channel Selected/ B Channel Selected. All Modes
This Option determines whether cellular channel “B” or channel “A” is used. In Canada, Channel B is used (Default). In the USA refer to the SID list for the chan­nel of the cellular service provider in your area. Default - Channel B
Option 2 - Normally Closed Loops/ End-of-line Resistors Mode 2, 3
Normally Closed Loops can be wired as shown. Multiple Normally Closed con­tacts can be wired in series. For Double or Single EOL resistors this option must be set to OFF. Default - Normally Closed (N/C) Loops.
NOTE: Option must be OFF for UL Installations.
10
Page 15
Skyroute CL3050 Universal Wireless Communicator
Option 3 - Double EOL Resistors/Single EOL Resistors Mode 2, 3
This option selects Double EOL resistors (ON) or Single EOL resistors (OFF) wired as indicated
Single EOL resistors allows the use of N/C and/or Normally Open contacts.
CZxCZxCZx
Double EOL resistors allows the zone to be monitored for fault, tamper, secure and violated condi­tions. Only Normally Closed contacts can be used in this configuration
CZx CZx
5.6K ohm
5.6K ohm
5.6K ohm
Tamper Contact
5.6K
5.6K
5.6K
5.6K
NOTES: Option 2 must be set to OFF to enable these options. Default - OFF Option must be ON for UL Installations.
Option 4 - Test Once a Day Enabled/Disabled All Modes
Allows transmission test daily. Default - Disabled. NOTE: Option must be ON for UL Installations.
Option 5 - Test Once a Week Enabled/Disabled All Modes
Allows transmission test weekly. Default - Enabled NOTE: This option will be overridden If option 4 is set for daily test transmissions.
Option must be OFF for UL Installations.
Option 6 - Enrolled with Connect 24 /Not Enrolled All Modes
This option is set automatically during the enrollment procedure with Connect 24. IF the Skyroute CL3050 is reset to the default settings this option must be set to ON for the Skyroute CL3050 to resume communications. Default - Not Enrolled.
Options 7, 8 - System Use All Modes
CAUTION: Do NOT change these settings unless it is requested by DSC technical support personnel. Default - OFF.
[12] Skyroute CL3050 Configuration Options 2
Option 1 - Swinger Shutdown Enabled/Disabled Modes 2, 3
This option limits the number of alarm events transmitted per zone to 8 until the counter has been reset (counter automatically resets at midnight), then event transmissions will resume. Default - Enabled
NOTES: Tampers and Faults will be counted unless they are disabled in section [20]. Option must be OFF for UL Installations.
Options 2 - 8 Future Use
[13] Skyroute CL3050 Trouble Output mask
The PGM output is dedicated for trouble indications. If a control panel is not monitoring the Skyroute CL3050, an LED or a buzzer can be connected between this terminal and the RED terminal for a trouble indication. The PGM terminal switches low from an open-collector state. Connect to the control panel using a single EOL resistor configuration.
All Modes
11
Page 16
Programming Descriptions
.
Control Panel
Zx COM
NOTE: A relay may be required for proper operation in other configurations.
See paragraph 3.3 Terminal Connections.
Option 1 - Low battery All Modes
Skyroute CL3050
RED BLK YEL GRN COM PGM
5.6K
If the battery voltage drops below 5.72V
DC.
battery voltage rises to 5.87V
Default - ON
DC
a trouble will be indicated until the
Option 2 - Input Supply Failure All Modes
If AC power is absent or if DC power drops below 8.8V terminals, this
trouble is indicated. Default - ON
DC
on the RED and BLK
Option 3 - Zone Fault/Tamper (DEOL Only) Modes 2, 3
A trouble will be indicated if any zone reports a fault or tamper condition. In Sec­tion [11], Option [2] must be set to OFF and Option [3] must be set to ON for this option to be enabled. Default - OFF
Option 4 - No Service Available All Modes
This trouble is indicated If the system is unable to detect cellular service. Default - ON
Option 5 - Radio Failure All Modes
This trouble is indicated if there is an internal fault with the cellular radio. Default - ON
Option 6 - PC5108 Failure Mode 3
This trouble is indicated if a PC5108 supervisory or Keybus fault occurs.
NOTE: The PC5108 tamper is communicated only, therefore it can only be enabled by turning on section 20 option 7 and section 21 option 5. There is no local annunciation for this event. Default - ON
Option 7 - Failure to Communicate (FTC) All Modes
This trouble will be indicated if no acknowledgement has been received from
Connect 24 after three attempts. Default - ON
Option 8 - Skyroute CL3050 Tamper All Modes
This trouble will be indicated if the cover is removed from the Skyroute CL3050 activating the on-board tamper switch. Default - OFF
[15] System Time
When the time and day have been programmed, the values are saved and are used as the current time and day whenever the Skyroute CL3050 does a power up. Time and day programming is only required if the installer desires the Sky­route CL3050 to test transmit at a specific time and/or day. There is no "loss of time" trouble on the Skyroute CL3050. Default - 0000 - 2359
All Modes
12
Page 17
Skyroute CL3050 Universal Wireless Communicator
NOTE: If AC Power is detected, it will be used to provide the time base for the internal clock. If AC power is not detected the internal clock will automatically use the crystal time base.
[16] System Day of the Week
See section [15]. Option 1. (Sunday) Default - ON Option 2 - 8. (Monday - Saturday) Default - OFF
[17] Test Transmission Time
When the Skyroute CL3050 is powered up for the first time, or after a default reset; it will check if the test transmission time and day are programmed. If they are not, a random time (0000 - 2359) will be programmed into this location. The Skyroute CL3050 will randomly generate this value.
NOTE: Due to traffic volume, when selecting test transmission times, select a time that is not on the :30 minute mark (e.g., 02:24, 04:07).
[18] Test Transmission Day
When the Skyroute CL3050 is powered up for the first time, or after a default, it will check if the test transmission time and day are programmed. If they are not, a random day (Sunday-Saturday) will be programmed into this location. The Sky­route CL3050 will randomly generate this value. Because one test transmission weekly is the most common configuration, this will allow the installer to setup the Skyroute CL3050 without keypad programming. Option 1-8. Default - [Random] - One only will be enabled.
All Modes
All Modes
All Modes
[20] Transmission Options
When the following options are enabled the reporting codes listed in Appendix A are sent to Connect 24.
Options 1, 2 - Zone Alarm/Zone Alarm Restores Modes 2, 3
When a zone is violated or restored, the reporting codes listed in Appendix A will be sent.
NOTES: If generic reporting is enabled and multiple alarms occur during the delay programmed in Section [23], only one alarm reporting code will be sent. Zone alarm restorals enabled with generic zone reporting enabled can cause unpaired events to be sent to Connect 24.
Option 1. Default - ON, Option 2. Default - OFF
Options 3, 4 - Zone Fault, Zone Fault Restores Modes 2, 3
When the system sees a short circuit across any zone, a zone fault is generated. DEOL resistors are required for zone fault reporting. In Section [11], Option [2] must be set to OFF and Option [3] must be set to ON; In Section [13], Option 3 must be set to ON and the Skyroute CL3050 must be operating in mode 2 or 3. Option 3. Default - OFF, Option 4. Default - OFF
Options 5, 6 - Zone Tamper, Zone Tamper Restores Modes 2, 3
All Modes
13
Page 18
Programming Descriptions
When the system sees an open circuit across any zone a zone tamper is gener­ated. DEOL resistors are required for zone tamper reporting. In Section [11], Option [2] must be set to OFF and Option [3] must be set to ON. In Section [13], Option [3] must be set to ON and the Skyroute CL3050 must be operating in mode 2 or 3. Option 5. Default - OFF, Option 6. Default - OFF
Option 7 - System Maintenance Events All Modes
When this option is enabled, the maintenance events enabled in Section [21] are transmitted using the codes listed in appendix A. Default - ON,
Option 8 - Generic Zones Modes 2, 3
The Skyroute CL3050 supports generic and detailed zone alarm reporting. By default, the Skyroute CL3050 will be in generic zone reporting mode. When in this mode, all zone types are divided into four reporting groups; BA Burg, FA Fire, PA Panic, UA Technical. If any zone from this group initiates a transmission, the generic reporting code for this event is sent, additional violations from other zones from the same group will be ignored until that group's timer has expired. See table below for zone type grouping.
Zone
Ty p e
Null Burglary Fire Panic Technical Gas* Heat* Medical* Emergency Water* Freezer* Sprinkler* Hold-up
* Not for UL Listed Installations.
Each zone group has it's own timer. The default time is 5 minutes and is pro­grammed in Section [23]. If any zone in a group initiates an event, the timer will start running and the generic event will be sent. If any additional zones from the same group initiate an event before that group's timer expires, the event will be ignored. This generic zone reporting mode only applies to zone alarms. Alarm restorals, tamper/tamper restorals and fault/fault restorals are not grouped together into generic reporting groups. The generic identifier will be sent with 98 as it's zone number, this is a special combination recognized by Connect 24 as a generic event. When the generic zone reporting toggle is disabled, each zone alarm for each zone type will then send it's own identifier. Default - ON.
NOTE: The CL3050 communication zone and trouble zone will always send detailed reporting codes.
Detailed
Reporting Code
-
BA
FA PA
UA GA KA
MA
QA
WA
ZA
SA HA
Generic
Reporting Code
-
BA
FA
PA UA UA
FA
PA
PA UA UA UA
PA
14
Page 19
Skyroute CL3050 Universal Wireless Communicator
[21] System Event Communication Options
NOTE: Section [20], Option [7] must be enabled for these events to be communi­cated.
Option 1 - Input Supply Failure All Modes
If AC power is absent or if DC power drops below 8.8V terminals, a expired. Default - ON,
Option 2 - Low Battery All Modes
If the battery voltage drops below 5.72V When the battery voltage rises to 5.87V Default - ON.
Option 3 - Skyroute CL3050 Tamper All Modes
Removing the cover on the Skyroute CL3050 will send a tamper reporting code to Connect 24. Default - OFF.
Option 4 - PC5108 Module Fault Mode 3
Indicates a Keybus communications fault condition. Default - OFF.
Option 5 - PC5108 Tamper Mode 3
Removing the cover on the PC5108 will send a tamper reporting code to Connect 24. Default - OFF.
Option 6 - TLM Trouble Report All Modes
Indicates a telephone line trouble if a CL3050 communications zone is violated. Default - OFF.
trouble will be sent after the delay programmed in section [22] has
[22] Input Supply Fail TX Delay
DC
on the RED and BLK
DC
a trouble will be sent to Connect 24.
DC
the system will send a restore.
All Modes
This value determines the delay (default 0700 = 7 hrs) before an input supply fail­ure reporting code is sent if programmed. See Section [21], Option [1] and Sec­tion [20], Option [2]. Default - 0700 (=7 hrs)
[23] Generic Zone Reporting Timer
This hex value determines the delay before a generic zone reporting code is sent, if programmed in Section 20 Option 8.
NOTE: There are four separate timers for Burglary, Fire, Panic and Supervisory; the delay programmed is the same for each timer.
Default - 1E (300 seconds / 5 minutes) Range equals 01-FF Hex seconds x 10
[24] Number of Attempts
This value determines how many attempts are made to send an event to Connect 24. Default - 03
NOTES: For UL Installations in Mode 2, minimum 5, maximum 10 attempts required. For UL Installations in Mode 3, the combination of attempts between DACT and Skyroute shall be minimum 5 and maximum 10.
[25] Response Wait Time
This value determines how long the Skyroute CL3050 will wait for a response from Conect 24 before attempting to resend the same event.
Default - FA (250 seconds) range equals 01-FF Hex seconds. NOTE: For UL Installations this must be 90 seconds (5A).
Modes 2, 3
All Modes
All Modes
15
Page 20
Programming Worksheets
Section 7: Programming Worksheets
Zone Definitions (For Sections [01] -[02])
00 Null Zone (Not Used) 01 Burglary 02 Fire 03 Panic 04 Technical * Not for use in UL Installations.
[01] Zone 1-2 Definitions
Default Default
01 I___I___I Zone 1 01 I___I___I Zone 2
[02] Zone 3-8 Definitions
Default Default
01 I___I___I Zone 3 01 I___I___I Zone 4
01 I___I___I Zone 5 01 I___I___I Zone 6
01 I___I___I Zone 7 01 I___I___I Zone 8
[03] Zone 1-2 Loop Response 01-FF (Hex 0.1 second increments), mode 2 only
Default Default
05 I___I___I Zone 1 05 I___I___I Zone 2
05 Gas* 06 High Temp* 07 Medical* 08 Emergency 09 Water Level*
10 Low Temp* 11 Sprinkler* 12 Hold-up 13 CL3050 Communications Zone
(1 zone max.)
14 Trouble Zone (1 zone max.)
[10] Skyroute CL3050 Mode of Operation
Default Default
01 I___I___I 01 - Bell Follower, 02 - 2 Zone, 03 - 8 zone (PC5108 )
NOTE: Use modes 2 and 3 for UL Installations.
[11] Skyroute CL3050 Configuration Options 1
Default Opt Option On Option Off
OFF I___I 1 A Channel selected B Channel selected
ON I___I 2 Normally Closed Loops End-of-Line Resistors*
OFF I___I 3 Double End-of-Line Resis-
tors
OFF I___I 4 Test Once a Day Enabled Disabled**
ON I___I 5 Test Once a Week
Enabled
OFF I___I 6 Enrolled with
Connect 24
OFF I___I 7 System Use - Caution: Do not change
OFF I___I 8 System Use - Caution: Do not change
Single End-of-Line Resistors**
Disabled*
Not Enrolled with Connect 24
* Option must be OFF for UL Installations.
** Option must be ON for UL Installations.
16
Page 21
Skyroute CL3050 Universal Wireless Communicator
[12] Skyroute CL3050 Configuration Options 2
Default Opt Option On Option Off
ON I___I 1 Swinger Shutdown
Enabled
OFF I___I 2-8 For Future Use
NOTE: Option must be disabled for UL Installations.
[13] Skyroute CL3050 Trouble Mask
Default Opt Option On Option Off
ON I___I 1 Low Battery Disabled
ON I___I 2 Input Supply Failure Disabled
OFF I___I 3 Zone Fault/Tamper (DEOL
only)
ON I___I 4 No Service Available Disabled
ON I___I 5 Radio Failure Disabled
ON I___I 6 PC5108 Failure Disabled
ON I___I 7 Failure to Communicate Disabled
OFF I___I 8 Skyroute CL3050 Tamper Disabled**
[15] System Time
Default Range
Swinger Shutdown Disabled
Disabled
0000 I___I___I___I___I 0000-2359 Hrs/Mins
[16] System Day
Default Opt Option On Option Off
ON I___I 1 Sunday Disabled
OFF I___I 2 Monday Disabled
OFF I___I 3 Tuesday Disabled
OFF I___I 4 Wednesday Disabled
OFF I___I 5 Thursday Disabled
OFF I___I 6 Friday Disabled
OFF I___I 7 Saturday Disabled
OFF I___I 8For Future Use
[17] Test Transmission Time
Default Range
Random I___I___I___I___I 0000-2359 Random on power up unless pro-
grammed
17
Page 22
Programming Worksheets
[18] Test Transmission Day *Selected at random on power up
Default Opt Option On Option Off
* I___I 1 Sunday Disabled
* I___I 2 Monday Disabled
* I___I 3 Tuesday Disabled
* I___I 4 Wednesday Disabled
* I___I 5 Thursday Disabled
* I___I 6 Friday Disabled
* I___I 7 Saturday Disabled
* I___I 8 For Future Use
[20] Transmission Options
Default Opt Option On Option Off
ON I___I 1 Zone Alarms Disabled
OFF I___I 2 Zone Alarm Restores Disabled**
OFF I___I 3 Zone Fault Disabled**
OFF I___I 4 Zone Fault Restores Disabled**
OFF I___I 5 Zone Tamper Disabled**
OFF I___I 6 Zone Tamper Restores Disabled**
ON I___I 7 System Maintenance
Events
ON I___I 8 Generic Zone Reporting Detailed Zone Reporting**
[21] System Event Communication Options
Default Opt Option On Option Off
ON I___I 1 Input Supply Failure Disabled
ON I___I 2 Low Battery Disabled
OFF I___I 3 Skyroute CL3050 Tamper Disabled**
OFF I___I 4 PC5108 Module Fault Disabled**
OFF I___I 5 PC5108 Tamper Disabled**
OFF I___I 6 TLM Trouble Report Disabled**
[22] Input Supply Fail TX Delay
Default Range
0700 I___I___I___I___I 0000-
2359
Disabled**
Hrs/Mins
[23] Generic Zone Reporting Timer
Default Range
1E I___I___I 01-FF (Hex seconds ×10)
** Option must be ON for UL Installations.
18
Page 23
Programming Worksheets
[24] Number of Attempts
Default Range
03 I___I___I 01-FF (Hex)
[25] Response Wait Time
Default Range
FA I___I___I 01-FF (Hex seconds)
For UL Installations program 5A.
19
Page 24
Glossary of Terms
Glossary of Terms
Cellemetry A network allowing short data packets to be sent on cellular control chan-
nels.
Connect 24 Connect 24 is the service provider that provides the Skyroute service to the
security industry and links the Skyroute cellemetry communicator to the cen­tral station.
RSSI Radio Signal Strength Indication - This value is transmitted to Connect 24
during the periodic test transmission and can be viewed after power up by pressing the enroll button.
SID System Identification Number - ID Number of the Cellular provider MIN Mobile Identification Number - The 10 digit decimal number used for regis-
trations and pages (the phone number of the Skyroute CL3050).
Page A transmission that is sent from the Cellemetry Gateway to the Cellemetry
Radio
Registration A transmission that is sent from the Cellemetry Radio to the Cellemetry
Gateway
20
Page 25
Skyroute CL3050 Universal Wireless Communicator
Appendix A: Reporting Codes
Events Reporting Codes Events Reporting Codes
SIA
Zone Alarms Zone Restores
Burglary Zone BAXX E130 Burglary Zone BHXX R130
Fire Zone FAXX E110 Fire Zone FHXX R110
Panic Zone PAXX E120 Panic Zone PHXX R120
Technical Zone UAXX E140 Technical Zone UHXX R140
Gas Zone* GAXX E151 Gas Zone* GHXX R151
High Temp Zone* KAXX E158 High Temp Zone* KHXX R158
Medical Zone* MAXX E100 Medical Zone* MHXX R100
Emergency Zone QAXX E120 Emergency Zone QHXX R120
Water Level Zone* WAXX E154 Water Level Zone* WHXX R154
Low Temp Zone* ZAXX E140 Low Temp Zone* ZHXX R140
Sprinkler Zone* SAXX E110 Sprinkler Zone* SHXX R110
Hold-up Zone HAXX E122 Hold-up Zone HHXX R122
Trouble Zone YX00 E300 Trouble Zone YZ00 R300
Zone Fault Alarms Zone Fault Restores
Burglary Zone UTXX E300 Burglary Zone UJXX R300
Fire Zone FTXX E373 Fire Zone FJXX R373
Panic Zone UTXX E300 Panic Zone UJXX R300
Technical Zone UTXX E300 Technical Zone UJXX R300
Gas Zone* UTXX E300 Gas Zone* UJXX R300
High Temp Zone* UTXX E300 High Temp Zone* UJXX R300
Medical Zone* UTXX E300 Medical Zone* UJXX R300
Emergency Zone UTXX E300 Emergency Zone UJXX R300
Water Level Zone* UTXX E300 Water Level Zone* UJXX R300
Low Temp Zone* UTXX E300 Low Temp Zone* UJXX R300
Sprinkler Zone* STXX E200 Sprinkler Zone* SJXX R200
Hold-up Zone UTXX E300 Hold-up Zone UJXX R300
Trouble Zone UT00 E380 Trouble Zone UJ00 R380
Contact
ID
SIA
Contact
ID
* Not for use in UL Installations.
21
Page 26
Skyroute CL3050 Universal Wireless Communicator
Event Reporting Code Event Reporting Code
SIA
Zone Tamper Alarms Zone Tamper Restores
Burglary Zone BTXX E380 Burglary Zone BJXX R380
Fire Zone FTXX E373 Fire Zone FJXX R373
Panic Zone PTXX E380 Panic Zone PJXX R380
Technical Zone UTXX E380 Technical Zone UJXX R380
Gas Zone* GTXX E380 Gas Zone* GJXX R380
High Temp Zone* KTXX E380 High Temp Zone* KJXX R380
Medical Zone* MTXX E380 Medical Zone* MJXX R380
Emergency Zone QTXX E380 Emergency Zone QJXX R380
Water Level Zone* WTXX E380 Water Level Zone* WJXX R380
Low Temp Zone* ZTXX E380 Low Temp Zone* ZJXX R380
Sprinkler Zone* STXX E373 Sprinkler Zone* SJXX R373
Hold-up Zone HTXX E380 Hold-up Zone HJXX R380
Trouble Zone UTXX E380 Trouble Zone UJXX R380
Generic Zone Events System Events
Generic Burglary BA98 E130
Generic Fire FA98 E110
Generic Panic Zone PA98 E120
Generic Supervisory UA98 E140
Contact
ID
98
98
98
98
Input Supply Fail Trouble
Input Supply Fail Restore
Low Battery Trouble YT00 E302
Low Battery Restore YR00 R302
Skyroute CL3050 Tamper Alarm
Skyroute CL3050 Tamper Restore
PC5108 Tamper Alarm ES00 E330
PC5108 Tamper Restore EJ00 R330
PC5108 Supervisory Trouble
PC5108 Supervisory Restore
Periodic Test Transmission
Periodic Test** RP00 E602
Periodic Test with Trouble**
TLM Trouble LT01 E351
TLM Restore LR01 R351
SIA
YP00 E312
YQ00 R312
TA00 E137
TR00 R137
ET00 E330
ER00 R330
TXZZ E603
RY00 E608
Contact
ID
* Not for use in UL Installations. ** Only sent if a trouble zone is programmed.
22
Page 27
FCC COMPLIANCE STATEMENT CAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd. could void your
authority to use this equipment. This equipment generates and uses radio frequency energy and if not installed and used properly, in strict accor-
dance with the manufacturer’s instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for Class B device in accordance with the specifications in Subpart “B” of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in any residen­tial installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to television or radio reception, which can be determined by turning the equip­ment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Re-orient the receiving antenna
• Relocate the alarm control with respect to the receiver
• Move the alarm control away from the receiver
• Connect the alarm control into a different outlet so that alarm control and receiver are on different circuits. If necessary, the user should consult the dealer or an experienced radio/television technician for additional sugges-
tions. The user may find the following booklet prepared by the FCC helpful: “How to Identify and Resolve Radio/ Television Interference Problems”. This booklet is available from the U.S. Government Printing Office, Washing­ton, D.C. 20402, Stock # 004-000-00345-4.
WARNING: To satisfy FCC RF exposure requirements for mobile transmitting devices, a separation distance of 30 cm or more must be maintained between the antenna of this device and persons during device operation.
Industry Canada COMPLIANCE STATEMENT
This Class B digital apparatus meets all requirements of the Canadian interference-causing equipment regulations. Cet appareil numérique de la Classe B respecte toutes les exigences de règlement sur le matériel brouilleur du
Canada.
IC:160A - CL3050 The term "IC:" before the radio certification number only signifies that Industry Canada technical specifications
were met.
Limited Warranty
DSC warrants that for a period of one year from the date of purchase, the product shall be free of defects in material and workmanship under normal use and that in fulfillment of any breach of such warranty, DSC shall, at its option, repair or replace the defective equipment upon return of the equipment to its repair depot. This warranty applies only to defects in materials and workmanship and not to damage incurred in shipping or handling, or damage due to causes beyond the control of DSC, such as lightning, excessive voltage, mechanical shock, water damage or damage arising out of abuse, alteration or improper application of the product.
The foregoing warranty shall apply only to the original purchaser, and shall be in lieu of any and all other warranties, whether expressed or implied and of all other obligations or liabilities on the part of DSC. This warranty contains the entire warranty. DSC neither assumes responsibility for, nor authorizes any other person purporting to act on its behalf to modify or to change this warranty, nor assume for it any other warranty or liability concerning this product.
In no event shall DSC be liable for any direct, indirect or consequential damages, loss of anticipated profits, loss of time or any other losses incurred by the purchaser in connection with the purchase, installation or operation or failure of this product.
Important!
Test results are only valid at the time of testing. Results may vary with but are not limited to environmental and structural changes. Electrical equipment operating in the immediate area may cause interference.
Skyroute, PowerSeries, Connect 24 are trademarks of DSC
Page 28
©2003 Digital Security Controls Ltd.
Toronto, Canada • www.dsc.com
Tech Support: 1-800-387-3630 (Canada & US) or 905-760-3036
Printed in Canada 29034673 Rev 001
Direct all comments concerning this publication to pubs@dscltd.com
Loading...