WARNING: This manual contains information on limitations regarding product use and function and
information on the limitations as to liability of the manufacturer. The entire manual should be carefully read.
WWW.DIYALARMFORUM.COM
SAFETY INSTRUCTIONS for SERVICE PERSONNEL
WARNING: When using equipment connected to the TELEPHONE NETWORK, there are basic safety instructions
that should always be followed. Refer to the SAFETY INTRUCTIONS provided with this product; save them for
(future) reference. Instruct the end-user regarding the safety precautions that shall be observed when operating this
equipment.
Before Installing The Equipment
Do NOT use a sharp or metal object to open the packaging!
Ensure your package includes the following items:
•User’s Guide (Manual) including the SAFETY INSTRUCTIONS.
READ and SAVE These Instructions!
Follow All WARNINGS AND INSTRUCTIONS specified within these Instruction and/or on the equipment.
•Equipment SCW904x
•Power Supply, Direct Plug-In
•Mounting Hardware.
Selecting A Suitable Location For The Alarm Controller
Use the following list as a guide to find a suitable place for this equipment:
•Locate it near a telephone socket and a power outlet.
•Select a place that is free from vibration and shocks.
•Place the Alarm Controller on a flat, stable surface and follow the Installation suggestions.
Do NOT locate this product where persons will walk on the secondary circuit cable(s).
Do NOT use extension cords to PLUG-IN the Power Supply of this equipment.
AVOID setting up the equipment near heaters, air conditioners, ventilators, and/or refrigerators
Do NOT connect the Alarm Controller to electrical outlets on the same circuit as large appliances.
Do NOT select a place that exposes your alarm controller to direct sunlight, excessive heat, moisture, vapors, chemicals or dust.
Do NOT install this Equipment near water. (e.g., Bath Tub, Wash Bowl, Kitchen/Laundry sink, In a wet basement, or near swimming pool, etc.).
Do NOT install this equipment and its accessories in areas where there is a risk of explosion.
Do NOT connect this Alarm Controller to electrical outlets controlled by wall switches or automatic timers; avoid interference sources.
SAFETY Precautions required during Installation:
•NEVER install this EQUIPMENT and/or TELEPHONE WIRING during A Lightning Storm!
•NEVER touch uninsulated Telephone wires or Terminals unless the telephone line has been disconnected at the network interface.
•Ensure that Cables are positioned so that accidents can not occur. Connected Cables must NOT be subject to excessive mechanical strain
•Use Only the Power Supply supplied with this equipment. Use of unauthorized power supplies may cause damage.
•The AC Socket/Outlet powering the equipment shall be located near the equipment and shall be easily accessible.
WARNING:
THIS EQUIPMENT HAS NO MAINS ON/OFF SWITCH. THE PLUG OF THE DIRECT PLUG-IN POWER SUPPLY IS INTENDED TO SER VE AS
THE DISCONNECTING DEVICE IF THE EQUIPMENT MUST BE QUICKLY DISCONNECTED. IT IS IMPERATIVE THAT ACCESS TO THE
MAINS PLUG AND ASSOCIATED MAINS SOCKET/OUTLET, IS NEVER OBSTRUCTED.
This Installation Guide provides the basic installation, wiring and programming information for the PowerSeries Self Contained
Wireless (SCW) Security System.
This publication covers the following versions of the SCW Security System:
SCW9045-433 v1.0
SCW9047-433 v1.0
TECHNICAL SUMMARY
SCW9045-868 v1.0
SCW9047-868 v1.0
These models are not UL/ULC Listed (intended for European market only)
This equipment, SCW Alarm System shall be installed and used
within an environment that provides the pollution degree max 2
and over-voltages category II NON-HAZARDOUS LOCATIONS,
indoor only. The equipment is DIRECT PLUG-IN connected and
is designed to be installed, serviced and/or repaired by servicepersons only; [service person is defined as a person having
the appropriate technical training and experience necessary to
be aware of hazards to which that person may be exposed in
performing a task and of measures to minimize the risks to that
person or other persons]. There are no parts replaceable by the
end-user within this equipment.
The power supply must be direct plug-in, fail safe, withdou-
ble or reinforced insulation between primary and secondary
circuits. In EU countries it must meet the applicable require-
ments of the Low Voltage Directive and protected as per the
EN60950-1:2001 Standard Requirements. In all other countries,
it must be of an approved type acceptable to the local authorities; it is the installer’s responsibility to ensure that the socketoutlet that the transformer is plugged-in, is near the equipment
and is easily accessible.
WWW.DIYALARMFORUM.COM
IMPORTANT NOTE!
The wiring (cables) used for installation of the SCW Alarm System and accessories, shall be insulated with PVC, TFE, PTFE,
FEP, Neoprene or Polyamide.
(a) The equipment enclosure must be secured to the building
structure before operation.
(b) Internal wiring must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections;
- Loosening of terminal; connections;
- Damage of conductor insulation
(c) Disposal of the used battery packs shall be made according
to the waste recovery and recycling regulations applicable to
the intended market.
(d) Before servicing, DISCONNECT the power and telephone
connection.
(e) Do NOT route any wiring over circuit boards.
1
Self Contained Wireless Alarm System v1.0
Insert Screwdriver in slots indicated
Gently pry open cover with screwdriver
until cover separates
Remove cover screw
1.1 Installation:
1
If required, separate the front and back covers by removing the cover screw then inserting a small slotted screw
driver between the front and back covers and gently twist
the screwdriver to separate.
Route Telephone line wiring, I/O Wiring, and AC power
2
through a single or double ganged junction box and
through cutout in the back cover see Fig. 2 Mounting &
Wiring details. If Programming with DLS, See “4.1 Local
Programming with PC-Link” on page 10. If using Template
programming or Advanced Keypad programming continue
to the next step.
Secure the back cover to the junction box with the screws
3.
provided (2 screws for single gang box or 4 screws for a
double ganged box). For drywall (surface mount) secure
to wall using 4 #6 3/4” wood screws and drywall plugs.
See figure 2, Mounting & Wiring Details for hole locations.
If mounting unit on a double ganged box with the wall
tamper feature, secure the back plate to the right side of
the ganged box using the center mounting holes. This will
provide the tamper switch with unobstructed access to the
wall surface
4. Connect wiring to the terminals indicated. See Section 1.2
Wiring for details.
Do NOT apply power until wiring is completed.
5. Connect battery cable connector to the PC Board.
Position the cover onto the back plate. Ensure tamper
6.
switch is positioned for effective operation.
Insert cover in the lower slot at a 35° to 55° angle then
7.
snap cover in place. An audible click will be heard.
Apply power to System.
8.
Enroll devices. Enter [
9.
See Section 2, Wireless Device Enrollment.
If performing Template programming, enter [
10.
Code][899]. See Section 3, Template Programming
Enter Advanced Programming if required.
11.
See Section 5, Advanced Programming.
Test System by violating zones and verifying successful
12.
transmission to the central station.
See DLS Programming on page 10 for reprogramming an
existing Installation.
AC Power must be present for the Alarm system to answer
Incoming calls from DLS
After the initial installation 24 Hrs. is required to fully charge
the standby battery.
][8][Installer Code][898].
][8][Installer
Battery
Strain Relief
Third Hand
AC ACAux1 I/O 2+-Ring Tip R-1 T-1
12 V
Tamper Switch
Tamper Switch
Cover screw hole
DC
PGM/ZonesAC Power
Telephone Line
Red Grn Gra Brn
2
WWW.DIYALARMFORUM.COM
1.2 Wiring
Burglary Zone Wiring Chart
Wire
Gauge
Max wire Length to End-of-line Resistor
(feet/meters)
223000 / 914
204900 / 1493
196200 / 1889
187800 / 2377
Figures are based on maximum wiring resistance of 100Ω
I/O
I/O
T-1
R-1
TIP
RING
RJ-31X
RED
GRN
BRN
GRA
1. Zone Wiring
Zones can be wired for Normally Open, Normally Closed Contacts with Singleend-of-line (SEOL) resistors or Double End-of-Line (DEOL) resistors. Observe
the following guidelines
•For UL/ULC listed installations use SEOL or DEOL only.
•Minimum 22 AWG wire, maximum 18 AWG
•Do NOT use shielded wire
•Wire run resistance shall not exceed 100Ω. Refer to the chart below.
Normally Closed Loops - Do NOT use for UL Installations
Single End-of-Line Resistor Wiring
Double End-of-Line Resistor Wiring
2. PGM/Aux Power Wiring
PGMs switch to ground when activated by control panel.
Connect the plus side of the device to be activated to the AUX+ Terminal. Connect the minus terminal to the PGM. Each PGM can provide 50mA output.
NOTE: The control panel can provide a maximum of 100mA of AUX current for
PGMs, relays, LED’s etc. Min/Max operating voltages for PGMs, relays and
modules is 10.2V
NOTE: Battery Voltage (6.0-8.4VDC) is boosted internally to supply 12VDC on
the AUX+ output by setting Sect[014] Opt[4] to ON. This option must be
enabled for PGMs used in UL/ULC Residential Burg installations. This output
can NOT be used for UL/ULC Fire installations.
DC - 13.75VDC
3. Telephone Line Wiring
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-31x
Connector as indicated. Use 24 AWG wire minimum for wiring.
For connection of multiple devices to the telephone line, wire in the sequence
indicated.
Communication format is programmed in section [350].
Telephone Call Directions are programmed in section [351]-[376].
Note: For UL Listed Installations,the Installer must verify the communication format with the supervising station at the time of the installation.
4. Battery 5. AC Wiring
A 1500 mAHr Ni-Mh battery pack is included to meet standby power requirements
NOTE: UL/ULC Residential Burglary installations require 4 Hr. power standby
time plus 4 minutes alarm annunciation.
NOTE: UL/ULC Residential Fire installations require 24 Hr. power standby
plus 5 minutes alarm annunciation
NOTE: Battery life is 4-5 years under typical operating conditions. Battery
capacity deteriorates with age and number of charge/discharge cycles.
Replace battery every 4-5 years.
WWW.DIYALARMFORUM.COM
LED output with
current limiting
resistor and
optional Relay
driver output
AC Transformer Requirements:
Primary:120VAC, 50/60Hz., 0.33A
240VAC, 50/60Hz., 0.165A
Secondary: 16.5VAC/20VA
The following Transformers shall be used:
UL Listed Installations - PTD1620U, PTD1640U (60Hz.)
ULC Listed installations - PTD1620, PTD1640 (60Hz.)
EU Installations - PTD1620T-EU (50 Hz.)
3
Self Contained Wireless Alarm System v1.0
NOTE: Do not connect transformer to a receptacle controlled by a switch.
For UL/ULC Installations use a Class 2, power limited, plug-in transformer
4
WWW.DIYALARMFORUM.COM
Section 2: Wireless Device Enrollment
Section 2: Wireless Device Enrollment
Before a wireless device can be recognized by the security system, it must be enrolled.
Devices that are not enrolled will be ignored by the system. See “Section [904]: Wireless Module Placement Test” on page44.
Device Enrollment must be performed close to the alarm system.
Maximum signal strength is required to ensure that the correct devic e is being enroll ed.
1. Enter Wireless Enrollment Mode
Enter [][8] [Installer Code] [898] on the system keypad.
2. Activate Wireless Device
- For FOBs & Panic Pendants - Press any button
- For PIRs, Smoke and Glass Break Detectors - Activate Tamper
- For Contact Switches - Close Contacts
3. Verify Device Electronic Serial Number (ESN)
When a device is activated the Alarm system will display the corresponding 6-digit ESN on the keypad.
Verify that the ESN displayed corresponds to the ESN on the device.
Note: The first digit of the ESN indicates the following:
2
denotes contact
3
denotes PIR/Glass Break Detector
4
denotes Smoke Detector
5
denotes Pendant
6&9
denotes FOB
4. Press [*] to confirm correct ESN, or press [#] to delete device if incorrect.
If the ESN displayed on keypad does NOT correspond to the ESN on the device being enrolled.
- Deactivate the wireless device
- Press the # key to repeat the enrollment process.
- Perform these steps until the correct ESN is displayed
If the device fails to enroll (i.e., incorrect ESN) attempt manual programming and testing of the device
before determining that the device is faulty . Maximum signal strength is required to ensure that the correct
device is being enrolled.
5. Enter Zone Number
After confirming that the device ESN is correct, the installer will be prompted to enter a zone number.
If the installer selects a zone that is currently in use, the installer will be prompted to overwrite the current
zone or select a new zone. If all zones are in use the installer will be prompted to overwrite the selected zone.
WWW.DIYALARMFORUM.COM
5
Self Contained Wireless Alarm System v1.0
If the installer attempts to enroll a device already on the system, the keypad will briefly indicate that it is a
duplicate ESN.
Place wireless detectors in the desired locations and perform the wireless placement test.
Reposition devices if necessary to achieve the required signal strength.
Zone Dependant Devices (Detectors)
After the zone has been selected the keypad will display zone type 03. The Installer may enter an alternate zone type if required. When the zone
type has been selected the device will be enrolled.
For FOBs, the device is enrolled when the slot is selected. Zone type is not requested.
6
WWW.DIYALARMFORUM.COM
Section 3: Template Programming
Section 3: Template Programming
Template programming allows the Installer to quickly program the minimum functions required for basic operation. The installer is prom pted to
enter a 4-digit code that selects predefined zone definitions, reporting code formats, Troubles & Restorals, and DLS setup (see Digit 1 - 4 tables
below). The Installer is then prompted to enter the Central Station Telephone Number & Account Code, DLS Access Code, Entry & Exit Delays
and Installer Code (see entry 5-9 below).
Selecting [][8] [Installer Code] [899] displays the default settings for the first 4 options below.
Once this section has been entered, the Installer cannot exit until all sections are completed.
Enter new data and/or Press # key to accept the displayed data and proceed to the next section.
Changing a single digit, then pressing the # key will advance to the next section but will not save the
changed data. Enter all 4 digits or scroll to the end of template programming and exit to save data.
•Digit 1 selects 1 of the following 6 options for Zone definitions for the first 8 zones. A ‘0’ in the digit 1 location
indicates that the default settings for the first 8 zones are in place unless overridden. See Section [001]-[002] on page 16 for defaults.
OptionZn1Zn2Zn3Zn4Zn5Zn6Zn7Zn81 Delay 1
113334444 2 Delay 2
2133555588 3 Instant
3133555587 4 Interior
411333333 5 Interior Stay/Away
513365555 6 Delayed Stay/Away
6133655588 87 Delayed 24Hr. Fire (Wireless)
Refer to Section 8 for zone definition details88 Standard 24 Hr. Fire (Wireless)
•Digit 2 selects 1 of the following 6 options for Reporting Codes
Opt#Phone Line 1Programming Section Phone Line 2Programming Section
Disabled[380] Opt 1 OFFDisabled
1
SIA automatic Reporting Codes enabled [350] 1st Phone # [04]
2
[380] Opt 1 ON
[381] Opt 3 OFF
Contact ID Reporting Codes enabled[350] 1st Phone # [03]
3
[380] Opt 1 ON
[381] Opt 7 OFF
SIA automatic Reporting Codes enabled [350] 1st Phone #[04]
4
[380] Opt 1 ON
[381] Opt 3 OFF
Contact ID Reporting Codes enabled[350] 1st Phone # [03]
5
[380] Opt 1 ON
[381] Opt 7 OFF
Contact ID Reporting Codes enabled[350] 1st Phone # [03]
Enable Opening/Closings call directions for Phone 2
FF=Communicates in Automatic Mode, XX=Not Used
•Installer Lead-in/Lead-out and DLS Lead-in/Lead-out
DLS Lead In
Sect [347] Opt 4
DLS Lead Out
Sect [347] Opt 5
Disabled for all Template Options except Option 8
Installer Lead Out
Sect [347] Opt 11
Installer Lead In
Sect [347] Opt 12
Digit 4 indicates/selects 1 of the 3 following DLS Connections
Option
1
2
3
Double Call
Sect [401] Opt 1
Call Back
Sect [401] Opt 3
#Rings
Sect [406] Opt 3
0
8
8
After the 4th digit is entered you will be prompted to enter the following Data.
Refer to Section 8 for additional programming functions.
Entry 5Central Station Telephone Number
- Enter 32 Character Telephone number - See Section [301] for details.
[367]Opt 2 ON
Entry 6Central Station Account Code
- Enter the 6-digit code - See Section [310] for details.
Entry 7DLS Access Code
- Enter the 6-digit code - See Section [403] for details.
Entry 8Entry Delay1, Exit Delay
- Enter Entry Delay1, Exit Delay - See Section [005] entries [1], [3] for details.
Entry 9Installer Code
- Enter a 4 or 6-digit entry depending on setting of Section [701] Opt 5 - See Section [006] for details.
WWW.DIYALARMFORUM.COM
9
Self Contained Wireless Alarm System v1.0
Insert Circuit board between
Fingers at 45° angle.
Ensure that board locks in place behind notches
Lower Board until supported by fingers
Section 4: DLS Programming
4.1 Local Programming with PC-Link
Follow the steps below in the sequence indicated to set up local programming using DLS:
New Installations (Refer to section 1.1 Installation on page 2)
1. Connect the AC Wiring before mounting the back plate.
In a new installation the backup battery requires 24 Hrs. charging.
AC Power is required for PC-Link Programming until battery is charged.
2. Secure the front cover to the backplate
3. Connect the PC-Link cable between the Computer with DLS Software installed and the header pins on the alarm panel to be programmed.
Connecting the DLS PC to the system will automatically initiate the connection.
4. When programming has been completed remove the PC-Link cable and the front cover from the backplate
5. Complete the installation
Existing Installations (Refer to section 1.1 Installation on page 2)
1. Remove the front plate and place it into the third hand – keeping the battery connected. See Figure 3, Third Hand
Figure 3, Third Hand
2. Place the PC-Link cable on the header pins and the downloading session will occur.
3. Upon completion of the session remove the PC-Link cable.
4. Remove the front plate from the third hand and secure it to the back plate.
4.2 Remote Programming (via telephone line)
Refer to Section “[401] Downloading Options” on page 25 and page 40 for details.
AC Power must be present for the Alarm system to answer Incoming calls from DLS
10
WWW.DIYALARMFORUM.COM
Section 5: Operation
Section 5: Operation
The LCD keypad displays the description and status indicator lights represent alarm functions and status. This section describes basic keypad
commands. Refer to the User Guide for detailed descriptions of all keypad commands.
Press the [#] key to reset the keypad if an error has been made entering user codes or keypad commands
5.1 – Away Arming
The Ready light must be ON to arm the system. If the Ready light is OFF, ensure all protected doors and windows are secure or bypassed. To arm
the system in the Away mode, either press and hold the Away function button for 2 seconds or enter a valid user code and leave the premises
through a door programmed as Delay. Upon pressing a function key or entering an access co de, the Armed light will turn ON. If the Audible Exit
Delay option is enabled, the keypad will beep once every second during the exit delay (and three times a second during the last 10 seconds) to
alert the user to leave. The Ready light will turn off when the Exit Delay ends.
5.2 – Stay Arming
The Ready light must be ON to arm the system. If the Ready light is OFF ensure all protected doors and windows are secure or bypassed. To arm
the system in the Stay mode, either press and hold the Stay function button for 2 seconds or enter a valid user code and stay within the premises
(do NOT violate a door programmed as Delay). Upon pressing a function key or entering an access code, the Armed light will turn ON. If the
Stay function button is used, the keypad will not beep during the exit delay to avoid annoying the person staying in the premises. If a user code
was used, the keypad will beep if the Audible Exit Delay option is enabled. The Ready light will turn off when the Exit Delay ends.
5.3 – Disarming
The user must enter through a door programmed as Delay. Upon entering, the keypad will emit a steady tone (and emit a pulsing tone during the
last 10 seconds of entry delay) to alert the user to disarm the system. Enter a valid user code to disarm the system. If an alarm occurred while the
panel was armed, the keypad will display ‘Alarm in Memory’. Press the [#] key to return the keypad to the Ready state.
5.4 – [] Commands
The following is a list of the [] commands available and a description of each:
[][1] – Bypass/Re-activate Stay/Away and Night Zones
Press [][1] to enter the bypass mode. If the Code Required for Bypass option is enabled, enter a vali d user code. The keypad will display ‘Scroll
to View Zones’. The keypad will di splay the programmed zone labels for the zones and include the letter ‘O’ in the bottom, right corner if the
zone is violated or the letter ‘B’ if the zone is bypassed. Scroll to the appropriate zone and press the [] key to change the bypass status (or enter
the 2-digit zone number). Once the correct zones are bypassed, press [#] to exit.
Additional Bypass Commands:
Bypass Recall:Press [99]. The keypad will recall the last group of zones that were bypassed
Clear Bypass:Press [00]. The keypad will clear the bypass on all zones.
Save Bypass:Press [95]. The keypad will save which zones are manually bypassed.
Recall Save:Press [91]. The keypad will recall the bypassed zones that were saved.
Re-activate Stay/Away and Night Zones:
Press [][1] when the system is armed in the Stay mode to change the armed status to Away mode or Night mode. The system will add the Stay/
Away zones back into the system after the exit delay time expires.
If any zones are programmed as Night Zones (zone definition 37) pressing [][1] will activate the Night
mode instead of Away mode.
WWW.DIYALARMFORUM.COM
11
Self Contained Wireless Alarm System v1.0
[][2] – Trouble Display
Refer to Appendix E: Troubleshooting Guide, for troubleshooting assistance and a detailed description of all troub le conditions.
[][3] – Alarm Memory Display
Pressing the scroll <> keys will display an “Alarms in Memory” messa ge if an alarm occurred during the last armed period. Pressing [][3] will
display the message “Scroll to view Alarms”. Scrolling will display the zones that went into alarm. To clear the Memory, arm then disarm the
system.
[][4] – Door Chime Enable/Disable
Press [][4]. The keypad will emit 3 rapid beeps to indicate that the door chime feature is now enabled and a steady 2-second tone if it is now disabled. The same function can be performed by pressing and holding the Chime function button for 2 seconds.
[][5] – Program User Codes
The following table identifies available user codes:
CodeTypeFunction
[01] – [16]
[40]
General User Codes
Master Code
Arm, disarm, attribute functions
All functions, arm, disarm, program user codes
Programming User Codes:
Press [][5] followed by the Master Code. The keypad will display the first user (user 01) and include the letter ‘P’ if the user code is programmed. Scroll to the appropriate user and press the [] key to program the user (or enter the 2-digit user number). Enter a new 4 or 6-digit user
code or press [] to delete the user code. After the user code is programmed or deleted, scroll to another user or press [#] to exit.
Programming User Attributes:
Press [][5] followed by the Master Code or Supervisor Code. Press [9] followed by the 2-digit user to change to the user attributes.
[1]Supervisor’s Code
This attribute makes the code valid when entering the [][5] User Code Programming section and [][6] User
Functions. Note, these codes can only program codes which have equal or lesser attributes. This attribute will also
allow this user to create bypass groups if an access code is required to enter into [][1] Bypassing.
[2]Duress Code
Duress codes are standard user codes that will transmit the Duress Reporting Code whenever the code is ent ere d t o
perform any function on the system.
[3]User can manually bypass zones if Bypassing requires an access code.
[4]-[6]Future Use
[7]The panel will squawk the bell output when the user arms or disarms when in Away Armed mode.
[8]One-time Use Code
The One-time-use Code allows unlimited arming but only permits a single disarming once a day.
The Disarm function is restored at midnight.
To change the user attributes, press the number corresponding to the attribute or scroll to the desired attribute and press []. When the correct
attributes are assigned to the user, press [#] to exit. To change the user attributes for another user, press [9] followed by the 2-digit user number.
When finished, press [#] to exit.
These attributes affect the operation of wireless keys
Duress codes are not valid when entering [*][5], [*][6] or [*][8] sections and will transmit a duress alarm.
Duplicate codes and codes that are +/- 1 of an existing code can not be programmed.
[][6] – User Functions
Press [][6] followed by the Master Code, then press the number corresponding to the following functions or scroll to the desired option, then
press [].
[1]Program Time and Date: Enter the time and date using the following format [HH:MM] [MM/DD/YY]. Program the time using
military standard (e.g., 8:00 pm = 20:00 hours).
[2]-[3]Future Use
12
WWW.DIYALARMFORUM.COM
Section 5: Operation
[4]System Test: The panel will activate the keypad buzzer, LCD pixels and all keypad status lights for 2 seconds followed by 2
seconds of full volume alarm, then transmit a reporting code to the central station (if programmed).
[5]Enable DLS: The panel will temporarily enable DLS double-call for 6 hours.
[6]User Initiated DLS: The panel will attempt to call the DLS computer.
[7]Future Use
[8]User Walk Test Mode: The panel will switch into User Walk Test Mode. The panel will display the base mode menu.
Additional Keypad Functions:
When scrolling through the list of available functions, the following additional functions are available:
Event Buffer:Used to view the 128-event panel buffer
Brightness Control:Used to adjust the display backlighting level for optimal viewing
Contrast Control:Used to adjust the display contrast level for optimal viewing
Buzzer Control:Used to adjust the keypad buzzer tone for optimal sound
[][7][x] – Command Outputs (1&2)
Press [][7][x]. If the Command Output Code Required option is enabled, enter a valid user code. The panel will activate any PGM output
assigned to the command output.
[][8] – Installer Programming
Press [][8][Installer Code] to enter Installer Programming. Installer programming allows the installer to program all system functions.
Refer to the Section 6: Advanced Programming for details.
[][9][User Code] – No-Entry Arming
Press [][9] followed by a valid user code. The system will arm in the Stay mode and after the exit delay expires, it will remove entry delay. All
zones programmed as Delay will function like Instant zones. The system will flash the Armed light to indicate that the system is armed with no
entry delay.
[][0] – Quick Arm/Quick Exit
Quick Arm: When disarmed, press [][0] to arm the system. The system will arm as if a valid user code was entered.
Quick Exit: When armed, press [
ing the following 2 minute time period without changing the status of the system.
][0] to activate Quick Exit. The system will allow a single zone programmed as Delay to be violated once dur-
5.5 Function Keys
The keypad has 5 programmable one-touch function keys located in a column down the right-side of the keypad. These keys can also be activated
by pressing and holding number [1] through [5] respectively for 2 seconds. The default for these keys are as follows:
This section provides the information necessary to program all required features for a basic system as well as common applications.
6.1 How to Program:
DSC recommends filling in the Programming Worksheet with the required programming information before programming the system. This will
reduce the time required to program and will help eliminate errors.
To e nter Installer Progra mming press [][8] [Installer Code]. The LCD keypad will display ‘Enter Se ction ’. An error to ne indicates the installer
code entered is incorrect. Press [#] to clear any key presses and try again.
The default Installer Code is [5555] .
The Armed and Ready lights indicate programming status:
Armed Light ONPanel waiting for 3-digit section number
Ready Light ONPanel waiting for data to be entered
Ready Light FLASHINGPanel waiting for HEX data to be entered
You cannot enter installer programming while the system is armed or in alarm.
6.2 Programming Toggle Options:
Enter the 3-digit programming section number
Option ONOption OFF
# DisplayedDash [-] Displayed
•The Armed light will turn OFF and the Ready light will turn ON.
•The keypad will display which toggle options are ON or OFF according to the chart.
•To toggle an option ON or OFF, press the corresponding number on the keypad. The display will change accordingly.
•When all the toggle options are configured correctly, press the [#] key to exit the program section.
•The Ready light will turn OFF, the Armed light will turn ON and the LCD will display “Enter Section”.
6.3 Programming Decimal and Hexadecimal (HEX) Data:
•Enter the 3-digit programming section number.
•The Armed light will turn OFF and The Ready light will turn ON.
•Enter the data written in the boxes.
For sections that require multiple 2 or 3 digit numbers, the keypad will double-beep after each 2 or 3 digit entry and move to the next item in the
list. After the last digit in the section is entered, the keypad will beep r apidly 5 times and exit the program section. The Ready lig ht will turn OFF,
the Armed light will turn ON and the LCD will display “Enter Section”.
For sections that do not require data for every box (such as phone numbers) press the [#] key to exit the program section after entering all the
required data. The Ready light will turn OFF, the Armed light will turn ON and the LCD will display “Enter Section”.
At any time the [#] can be pressed to exit any program section. All changes made up to that point will be saved.
In addition to the standard digits 0-9, HEX digits and special dialer functions can also be programmed.
ValueEnterTelephone Dialer
To enter a HEX digit, press the [] key to begin HEX programming. The Ready light
will FLASH. Press the number corresponding to the HEX digit required. The Ready
light will continue to FLASH. Press [
ming. The Ready light will turn ON.
Not Supported
Simulated [] key
Simulated [#] key
Dial tone search
Two second pause
Not Supported
6.4 How to Exit Installer Programming:
To exit installer programming, press the [#] key when the panel is waiting for a 3-digit section number (the Armed light is ON). The LCD will
display the user menu.
6.5 Viewing Programming
The keypad will immediately display all the information programmed when a programming section is entered. Use the ar row keys (< >) to scroll
through the data being displayed. Scroll past the end of the data displayed, or press the [#] key to exit the section.