DSC FSB-210 Series, FSB-210B, FSB-210BT Installation And Operation Instructions Manual

FSB-210 Series Smoke Detector
DO
Installation and Operating Instructions
Read this instruction sheet thoroughly before installation and use of the FSB-210 Series Smoke Detector
This Installation Sheet must be used in conjunction with the appropriate Alarm Controller Installation Manual.
'alarm' threshold and send the alarm signal to the control
LED
Place magnet here
T
N
I
A
P
T
O
N
DO
Alignment Marks
Control Panel Compatibility
FSB-210 smoke detectors are addressable system detec­tors that are only for use with DSC fire and security con­trol panels equipped with the compatible interface. The FSB-210 smoke detectors cannot be used with a standard 2-wire smoke detector interface. Any standard 2-wire smoke detector, including the DSC FSA Series, will not operate on an addressable circuit. The FSB-210 series and the FSA Series are not compatible, interchangeable or substitutable. The addressable interfaces have a proprietary power and signaling system. Voltage ratings are not indicative of compatibility. The current rating is provided for circuit loading calculations only. Please refer to the control panel information for details on the installation of addressable circuits. FSB-210 detectors are compatible with the following con­trol units:
• PC5010/PC5015/PC5020/PC5020CF v2.x with PC5100 interface module. Maximum 32 detectors can be installed.
• PC4010/PC4010CF/PC4020/PC4020CF v3.x. Maximum 112 detectors can be installed.
Operation
Approximately every 7 to 8 seconds the unit tests for a smoke or heat alarm condition. During this sequence the unit also performs self diagnostics, and checks for faults. During normal operation the LED will flash every 50 seconds.
Smoke Alarm
The smoke detector has a nominal fixed alarm sensitivity (refer to the Specifications section on the back page) and it will go into alarm when the signal level exceeds the
panel. During an alarm the LED will flash every second.
Smoke - Drift Compensation
The detector automatically compensates for long-term environmentally induced changes to maintain a constant smoke sensitivity. When the drift compensation has reached its high or low limit of adjustment, the detector will go into the trouble state.
Heat Alarm
The heat detector will go into alarm when the heat signal level exceeds the heat alarm threshold (135ºF/57ºC); and send the alarm signal to the control panel. During an alarm the LED will flash every second.
Alarm Indications
Condition LED
Normal/Sensitivity in Production Range Flash 1/50s
Alarm Smoke/Heat Flash 1/1s
Low Power Trouble OFF
Other Fault/Trouble OFF
Smoke Test - Failed OFF
Installer Instructions
1. Smoke Detector Placement
On smooth ceilings, detectors may be spaced 9.1m (30ft) apart as a guide. Other spac­ing may be required depend­ing on ceiling height, air movement, the presence of joists, uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72, Chap­ter 11 or other appropriate national standards for instal­lation recommendations.
•Do NOT locate smoke detectors at the top of peaked or
gabled ceilings; the dead air space in these locations may prevent the unit from detecting smoke. Avoid areas with turbulent air flow, (near doors, fans or windows). Rapid air movement around the detector may prevent smoke from entering the unit.
•Do NOT locate detectors in areas of high humidity.
•Do NOT locate detectors in areas where the temperature
rises above 38ºC (100ºF) or falls below 5ºC (41ºF).
Install Smoke detectors in accordance with NFPA 72, Chapter 11:“Smoke detectors shall be installed outside
of each sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family liv­ing unit, including basements and excluding crawl spaces and unfinished attics. In new construction, a smoke detector also shall be installed in each sleeping room.”
2. Mount Smoke Detector Backplate
Mount backplate on standard
Locking
Ta b
4” octagonal electrical box using the screws provided.
NOTE: Power supply must be supplied from a UL Listed alarm control unit. Install wir­ing in accordance with the appropriate national and local electrical codes.
Mounting Holes
3. Wiring
Refer to the connection dia­gram in this section. Before connecting the unit, prepare the wires from the electrical box for connection; the wires should not be frayed or bent.
CAUTION: If power connec­tions are reversed, the unit will not operate. The unit is protected against damage from incorrect wiring.
When wiring is completed, inspect the wiring and cor-
rect any errors before apply­ing power to the unit. When the wiring has been thoroughly reviewed, neatly insert the wires into the elec­trical box and secure the unit to the mounting plate. NOTE: This equipment should be installed in accordance with the National Fire Protection Association Standard 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269).
Dust Cover
The dust cover is intended to protect the smoke detector from dust and dirt entry while the unit is not in service.
CAUTION: The dust cover protects the unit ONLY when it is not in service. Remove the dust cover before use.
Device Enrollment
The serial number located on the back of the device must be enrolled into the alarm control panel via Installer’s Pro­gramming ([ lined for Power panels in the PC5100 Installation Manual and for the PC4010/4020 v3.x in the control panel Instal­lation Manual.
WARNING: Connect only DSC addressable series devices to the addressable loop connections. Connec­tion of any other type of device will impair operation. Devices other than addressable series devices which require power to operate must be powered separately.
,][8] [Installer Code]). This procedure is out-
Do NOT use looped wire under terminals for system supervision. Break the wire run to provide supervision of connections.
4. Mounting
Detector Installation
Position the detector on to the base plate using the detector and base plate alignment marks. Press the detector gently in place while rotating the detector clock­wise until the detector snaps into place. Remove the side tab from the locking tab to lock in place (optional).
Removal: If the side tab is removed to lock the detector, depress tab with a small flat blade screwdriver and rotate the detector counter-
Alignment
Marks
Mounting
Surface
Detector
CLOSE
Backplate
Tabs
clockwise until the alignment marks line up. Remove detector.
OPEN
5. Test Unit
1. Program the Panel for Smoke Test. Refer to the Alarm Control Panel Installation Manual for details.
NOTE: If the detector is in one of the following states when test is initiated, it will not enter an alarm state:
• Compensation trouble.
• Failure of heat or smoke detector.
• Other internal faults that could prevent a smoke or heat alarm.
2. Use the FSD-100 meter to read the trouble status after testing. Refer to the FSD-100 User Guide for details.
NOTE: Place the meter close to the LED until it begins to flash every 2 seconds. Then hold the meter on the oppo­site side of the LED and read the message. The detector will send out a test message 7 times in a 2-second inter­val until the LED stops flashing.
6. Compensation Reset
Cleaning, replacement of the smoke sensor, or other changes may change the background signal/noise of the detector; this requires the drift compensation be reset. Compensation trouble is one of the faults indicated when the LED indicator is OFF.
• Remove power from the unit, then press and hold the test button for 30 seconds to power down unit.
• Power up unit while pressing the test button.The LED will flash; when 5 seconds has elapsed. Release the test button within 1 second after the fifth LED flash.
• The LED will flash every 8 seconds for 1 minute. When the detector stops flashing test the detector to verify normal operation.
Loading...
+ 2 hidden pages