DSC FSA-410D Series, FSA-410DS, FSA-410DST, FSA-410DRS, FSA-410DRST Installation And Operating Instructions Manual

...
FSA-410D Series Smoke Alarm
Installation and Operating Instructions
Read this instruction sheet thoroughly before installation and use of the FSA-410D Smoke Alarm
LED/Test Button
Piezo Sounder
T
N
I
A
P
T
O
N
DO
Alignment Marks
Introduction
The FSA-410D is a 4-wire photoelectric smoke alarm with optional: fixed temperature heat detector, auxiliary form C relay, and/or remote LED output.
Operation
Approximately every 7 to 8 seconds the unit tests for a smoke or heat alarm condition. During this sequence the unit also performs self diagnostics, and checks for faults. During normal operation the LED will remain on to indicate energization of the unit and the sounder will not sound.
Smoke Alarm
The smoke detector has a nominal fixed alarm sensitivity (refer to Specifications on back page) and it will go into alarm when the signal level exceeds the 'alarm' threshold. During an alarm the LED will shut off, the sounder will sound continuous beeps and the alarm relay will be activated.
Remote Alarm - Interconnection
Multiple alarms can be connected using the PRM-4W Polarity Reversal Module. When a fire alarm occurs, the unit will signal the
PRM-4W to reverse the polarity of the 4-wire loop. This will acti­vate the sounders of all units connected on the loop. Refer to the PRM-2W/4W Installation Manual for installation details.
Smoke - Drift Compensation
The unit automatically compensates for long-term environmen­tally induced changes to maintain a constant smoke sensitivity. When the drift compensation has reached its high or low limit of adjustment, the unit will go into the trouble state.
Heat Alarm
The heat detector will go into alarm when the heat signal level exceeds the heat alarm threshold (135ºF/57ºC). During an alarm the LED will shut off. The sounder will sound continuous beeps and the alarm relay will be activated.
Alarm Restore
When the smoke clears from the unit and the heat signal falls below the ‘restore’ level, the unit will automatically reset itself.
Alarm Indications
Condition LED Sounder
Normal/Sensitivity in Production Range
Smoke Alarm OFF Steady See Note A
Heat Alarm OFF Steady A See Note
Alarm Restore ON OFF D D
Remote Alarm ON Steady D D
Low Power Trouble ON OFF D D
Other Fault / Trouble ON CHIRP 1/50s D D
Test Switch - Failed ON CHIRP 1/50s D D
Test Switch - Pass OFF Steady A A
A = Activated / D = Deactivated
ON OFF D D
NOTE: For models FSA-410DFIS, the relay is deactivated, for all other models the relay is activated during the condition.
Alarm Aux.
Relay
FormA
Relay
FormC
Installer Instructions
1. Smoke Alarm Placement
On smooth ceilings, units may be spaced 9.1m (30 ft) apart as a guide. Other spacing may be required depending on ceiling height, air movement, the presence of joists, uninsulated ceilings, etc. Refer to CAN/ULC-S553-02 for installation recommendations.
Do NOT locate smoke alarms at the top of peaked or gabled ceil­ings; the dead air space in these locations may prevent the unit from detecting smoke. Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector may prevent smoke from entering the unit.
Do NOT locate units in areas of high humidity.
Do NOT locate units in areas where the temperature rises above 38ºC (100ºF) or falls below 5ºC (41ºF).
2. Mount Smoke Alarm Backplate
Locking Tab
Mounting Holes
Mount backplate on standard 4” octag­onal electrical box using the screws pro­vided.
NOTE: Power must be supplied from a ULC Listed power supply or alarm con­trol unit auxiliary output. Install wiring in accordance with the appropriate national and local electrical codes.
CAUTION: The dust cover protects the unit when not in service. Remove the dust cover before use.
3. Wiring
Refer to the wiring diagrams in this installation sheet and those provided in the Installation Manual of the alarm control panel being used with the unit. Before connecting the unit, prepare the wires from the electrical box for connection; Do not use frayed or bent wire.
10-30 VDC
V V
NO C
NOTE: Power supply shall be rated for the application. Refer to electrical ratings when calculating the maximum current required for an installation.
NO C NO C
NOTE: Optional Remote
NO C
Alarm Relay
Aux Relay
LED
NO NC C
OPTIONAL
NO C
Heat Alarm
Relay 'A'
FSA-410DFIS
Smoke Alarm
Relay 'C'
NO NC C
LED must have a series resistor. Please see speci­fications.
When wiring is completed, inspect the wiring and correct any errors before applying power to the unit. When the wiring has been thoroughly reviewed, neatly insert the wires into the elec­trical box and secure the unit to the mounting plate.
4. Mounting
Detector Installation:
Close
Position the detector on to the base plate using the detector and base plate alignment marks. Press the detector gently in place while
Tab
Open
Alignment Marks
rotating the detector clockwise until the detector snaps into place. Remove the side tab from the locking tab to lock in place (optional).
Removal: If the side tab is removed to lock the detector, depress tab with a small flat blade screwdriver and rotate detec­tor counter-clockwise until the alignment marks line up. Remove detector.
5. Test Unit
Initiate test by pressing the test button for greater than 5 sec­onds.
Alarm activation is indicated by the LED, the sounder, and the alarm reporting to the control panel. If the smoke detectors are inter-connected using model PRM-4W and a detector is tested, then all detectors will sound. The detector restores to normal when the test button is released or when the magnet is removed.
NOTE: Allow a minimum of 20 seconds between test activa­tions.
NOTE: If the detector is in one of the following states when a test is initiated; it will not enter an alarm state.
1. Compensation trouble.
2. Failure of heat or smoke detector.
3. Other internal faults that could prevent a smoke or heat alarm.
NOTE: Smoke sensitivity of installed detectors can be measured without removal or an alarm being generated using the FSD-100 Smoke Detector Test Meter.
Test Unit with FSD-100 Smoke Detector Test Meter
To test the unit using the FSD-100, set the test meter up to read devices as per the instructions supplied with the test instrument. Depress the test button (or place the FSD-100 on the outside edge of the plastics beside the test button to activate the reed switch on units without sounder) on the smoke detector for 1 second and release.
NOTE: If the test button is held for 5 seconds or longer, an alarm will be generated.
Move the test meter over the center of the detector, wait until you hear the test meter beep, remove the unit and the informa­tion can be immediately reviewed. Please see the instructions supplied with the FSD-100 Smoke Detector Test Meter for more information.
6. Compensation Reset
Cleaning, replacement of the smoke sensor, or other changes may change the background signal/noise of the detector; this requires the drift compensation be reset. Compensation trouble is one of the faults indicated when the LED indicator is OFF while the sounder is chirping.
1. Remove power from the unit, then press and hold the test button for 30 seconds to power down unit.
2. Power up unit while pressing the test button. The LED will flash; when 5 seconds has elapsed. Release the test button within 1 second after the fifth LED flash.
3. The LED will flash every 8 seconds for 1 minute. When the detector stops flashing test the detector to verify normal operation.
Loading...
+ 2 hidden pages