DOL 53 AMMONIA (NH3) SENSOR
EN
Technical User Guide

dol-sensors a/s Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
EN – TECHNICAL USER GUIDE
SAFETY-RELATED INFORMATION
Before using this product, carefully read the Technical user guide.
Strictly follow the Technical user guide. The user must fully understand and strictly observe the instructions. Use the product only for the
purposes specified in the Intended use section of this document.
Do not dispose of the Technical user guide. Ensure that they are retained and appropriately used by the product user.
Comply with all local and national rules and regulations associated with this product.
Use only genuine spare parts and accessories, or the proper functioning of the product may be impaired.
Do not use a faulty or incomplete product. Do not modify the product.
Notify the supplier in the event of any component fault or failure.
WARNING SYMBOLS
MEANING OF THE WARNING SYMBOLS
The following warning symbols are used in this document to identify and highlight the relevant warning texts which require increased care and
attention on the part of the user. The meanings of the warning symbols are defined as follows:
Indicates a potentially hazardous situation which, if not avoided, could result in physical injury, or damage to the product or
environment. It may also be used to alert against unsafe practices.
Indicates additional information on how to use the product.
PRODUCT DESCRIPTION
DOL 53 consists of an electrochemical diffusion sensor and signal processing electronics. DOL 53 works like a "nose". DOL 53 only transmits the
concentration measured at the sensor. The measuring unit ppm (parts per million) is a volume concentration. DOL 53 is connected to suitable
control unit over a 3-wire cable. The measuring signal during normal operation is between 0 V and 10 V.
DOL 53 is used for the stationary continuous monitoring of ammonia concentrations in the ambient air under atmospheric conditions
1. Connector and coupling
2. Mounting lug
3. Sensor element
4. Mounting ring
5. LED green/yellow
6. DOL 53 housing
7. Dust cap

dol-sensors a/s Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
EN – TECHNICAL USER GUIDE
MOUNTING GUIDE
For optimum measurements DOL 53 should be installed at the centre of the area to be monitored. DOL 53 must be installed out of reach of
animals, accessible for maintenance work, suspended from the lug at the end of the housing or alternatively with a mounting bracket on the wall.
DOL 53 must not be mounted near the fresh air supply, in front of windows or doors, large electrical consumers (electromagnetic
influences), in exhaust air ducts, behind air washers or behind screens. DOL 53 must not be mounted in inaccessible areas.
Protect against direct exposure to dust or splash water. For wall mounting, unobstructed gas entry must be ensured.
DOL 53 must be mounted vertically with the sensor pointing down; ±30° at a
location with low vibration and, as far as possible, stable temperatures.
NOTICE DOL 53 must not be suspended from the electric cable.
The scope of delivery includes an approx. 2.5-meter-long cable connection (5) for
the electrical installation up to the junction box (1). For the electrical supply and
signal transmission to the control unit cables with adequate cross-section must be
used. Connect the cable from the installation kit to the connector (4) and in the
junction box (1). Connect the GND cable in the control unit to protective earth.
The cable must be routed in a manner to obtain a "water loop" (2) for water to
drop off. Insert the cable into the clamping device (3) at the mounting lug. Attach
with a cable tie. Do not stress the cable.
SENSOR INSTALLATION
1. Remove the sensor element from the metal container.
2. Insert it into DOL 53 (6).
3. Secure it with the mounting ring (7).

dol-sensors a/s Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 55 88 Fax +45 72 17 59 59 www.dol-sensors.com
EN – TECHNICAL USER GUIDE
ELECTRIC CONNECTION
The electrical installation must only be carried out by specialist personnel paying attention to the relevant regulations for
electrical equipment.
OPERATION
Switch on the supply voltage at the control unit. After activation or after an interruption of the supply voltage the sensor must warm up for a defined
period. This is indicated by the LED flashing green/yellow.
The warmed up fault-free operation of DOL 53 is indicated after max. 30 minutes by the green LED being illuminated.
A faulty operating state is indicated by the yellow LED flashing.
MAINTENANCE GUIDE
The sensor element must be replaced after 3 years of operation at the latest. End of service life see date on the sensor element rating plate.
Carry out the daily visual inspection to detect operation readiness.
Have specialists carry out the annual inspection and calibration.
Replace the dust filter upstream of the sensor element if clogged. A clogged filter prolongs the response time of the sensor
element. This affects the sensitivity. The dust filter must always be replaced prior to calibration.
CLEANING
Clean DOL 53 surface with lukewarm water. Check for mechanical damage.
DOL 53 must be removed during cleaning and disinfection. After removing the connector, screw on the screw plug. A missing
screw plug leads to corrosion of the connector.
DISPOSAL
Dispose of the product in accordance with the applicable rules and regulations.
TRANSPORT
Danger of damage to the sensor. The sensor must not be transported unpacked in air traffic. The sensor can loose its measuring
sensitivity.

dol-sensors a/s Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
EN – TECHNICAL USER GUIDE
TROUBLESHOOTING
Contact the supplier in case of a damaged DOL 53.
No measured value at the control
unit.
Electrical connection faulty or interrupted.
Check installation for cable break.
DOL 53 aligned incorrectly, not vertical.
Install DOL 53 in accordance with assembly
instructions, vertical ±30°.
Sensor element faulty or used up.
Incorrect measured value at the
control unit.
Check sensitivity with test gas.
Unexpected measured value at the
control unit.
Brief interference pulses <5 seconds.
Interference caused by electrical equipment, e.g.
lighting, fans or heaters; identify device and
suppress interference.
Dynamic signal fluctuations with a period of more
than 5 seconds can arise from turbulence with fresh
air.
Not activity, continue to monitor.
DOL 53 was cleaned with water, condensation.
Wipe DOL 53 dry with a paper towel.
Electrical supply faulty or interrupted.
Check installation for cable break. Check operation
of the power supply unit of the control unit. Check
electric voltage in the junction box or at the sensing
head with a multi-meter.
Short circuit in supply cable.
Check installation for short circuit.
Overvoltage or undervoltage at the sensing head.
Check operation of the power supply unit of the
control unit: Check electric voltage at the sensing
head with a multi-meter.
Incorrect voltage (e.g. 230 V AC) applied,
electronics damaged.
Replace the sensing head.
Sensing head faulty.
Replace the sensing head, contact supplier.
Alternating green and yellow
Sensor is warning up to be ready for
measurements, signal level 0 V.
No activity, flashing stops after max. 30 minutes.
Constant green
Concentration measurement in the test window 40
ppm to 60 ppm, result of a test with 50 ppm test
gas.
No activity, flashing stops after max. 5 minutes.
Internal fault detected by electronics, signal level 0
V.
Replace the sensing head.
Flashing yellow
Measured concentration below - 5 ppm, below the
measuring range, signal level 0 V.
If the fault continues for more than 1 day replace
sensor.
Measured concentration above 105 ppm outside
the measuring range.
Ventilate with fresh air.
Alternating green and yellow
Age monitoring, sensor older than 3 years, service
life expired, see date on sensor rating plate.

dol-sensors a/s Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 55 88 Fax +45 72 17 59 59 www.dol-sensors.com
EN – TECHNICAL USER GUIDE
TECHNICAL DATA
Max. sensor element storage period
See date on the label, sensor element box or shipping carton
Warranty for sensor element and sensing
head
2 years from delivery date
Expected sensor element service life
3 years from commissioning, expiration date see sensor element rating plate
Rated voltage 24 V (18 V to 30 V DC); DC < 0.2 Vss
Signal transmission to the control unit
0 V to 10 V corresponds to 0 to 100 ppm
Signal transmission resolution
1.5 ppm or ±10% of the measured value
< ±10 % of the measured value/year
Temperature range (operational)
Air pressure (operational)
Temperature range (storage)
Typical detergents, disinfectants, alcohol, surfactants, peracetic acid, soap
DIMENSIONAL SKETCH
EN – TECHNICAL USER GUIDE