drum-style furnace, 1000 Installation, Operating And Maintanance Instructions

Page 1
Page 2
Furnace Humidifier
2
FREQUENTLY ASKED QUESTIONS
Question:
Answer: The unit will work on most forced air furnaces incorporating a heating source, a supply duct, and a return duct at least 8” in width.
Comment: The technology used in this humidifier to deliver moisture to the air is the simplest and easiest style, a bypass type evaporative humidifier. Your furnace fan creates a pressure difference between the supply air (hot, high pressure) and return air (cold, low pressure). By installing a bypass tube between the supply and return duct a small amount of air is forced (via the pressure difference) to flow from the supply duct through the humidifier’s evaporator pad and back into the return duct. What will differ from furnace to furnace or home to home is how much moisture or capacity you will get from the unit. There are several factors which will affect this, how old is your home, how old is your furnace, how well insulated is your home. For example, the capacity for this unit is 15 US gallons per 24 hrs of operation. This is based on ARI standards (120’F hot air temp, 60’F water supply temp, 0.5” static pressure difference between supply & return duct), used by all humidifier manufacturers. If your furnace is a hi efficiency or pulse type furnace the hot air temperature may be less, or the length of time the furnace burner is on may be less; therefore as a rule of thumb we would say you would get approx. 75% to 80% of rated output.
Question: How much moisture does the humidifier deliver to
the air in my home?
Answer: This model will deliver 15 US Gallons (12.5 Imperial gallons, 57 litres) per 24 hours of operation.
Comment: 24 hours of operation means at design conditions; your furnace will only deliver the required hot air (120’F) when it is on. Your furnace should not cycle more than 1/3 of the time so the 24 hours of humidifier operation may take up to 3 days to complete.
Question: How much water does this humidifier use?
Answer: This humidifier is 100% efficient, meaning all the water it uses is delivered to the air to humidifier your home. It will use 15 US gallons (12.5 Imperial gallons, 57 litres) per 24 hrs of operation.
Comment: As mentioned above 24 hours of operation means at design conditions – your furnace will only deliver the required hot air (120’F) when it is on. Your furnace should not cycle more than 1/3 of the time so the 24 hours of humidifier operation may take up to 3 days to complete.
Question: I’m replacing an old humidifier on my furnace
can I use the old components?
Answer: You should replace all the components to ensure good operation. You may be able to utilize the existing duct cut outs for the new install however some reworking may be required.
Comment: As a rule we like to see you change all the components, particularly the water supply tube. As over time minerals, solids, or sludge may have built up, these will very quickly clog the water inlets, or over time the tube may have become worn or leaky. Replace the bypass duct as well, there may be secondary dampers unseen which will block air or again
What type of furnaces will this humidifier work on?
there may be unseen wear. The same goes for electrical components or wiring these may be malfunctioning or worn out. Note: If you have a humidifier which was interlocked with your furnace (meaning the humidifier only came on when the furnace came on) then the old transformer is wired in with your furnace. Do not attempt to disconnect this transformer from the furnace only disconnect the low voltage side wires for the humidifier and tape over the terminals.
Question: I’ve installed the humidifier on my furnace and it
is functioning properly but I do not feel anything and humidistat reading is not changing, is the humidifier working?
Answer: As long as there is hot air going through the humidifier and there is water pan and the drum assembly is getting wet then moisture is being delivered to the air in your home.
Comment: All year, and especially during the winter months when many combustion appliance are operating in your home, fresh outdoor air is required to ensure a healthy environment for your family. Do not think of your home as a sealed bubble, no matter how well insulated, all homes breath (some more than others). The cold dry outside air is mixing with the air in your home constantly, even when your furnace is not running. A furnace humidifier will work to offset the constant effect the dry outside air has on your home, and your home’s furnishings. Throughout the winter there is a constant diminishing and replenishing of moisture levels in the home, conditions inside and out rarely remain stagnant for any length of time.
Installation
• READ THESE INSTRUCTIONS FULLY BEFORE INSTALLING THIS PRODUCT.
• SAVE THESE INSTRUCTIONS FOR REFERENCE.
• SHUT THE WATER OFF BEFORE WORKING ON THE HUMIDIFIER.
• SHUT THE POWER OFF BEFORE WORKING ON THE HUMIDIFIER.
• TAKE PRECAUTION WHEN CUTTING OR HANDING METAL PCS. (CUT DUCT WORK), SHARP EDGES CAN CAUSE SERIOUS INJURY.
• WHEN DRILLING OR CUTTING INTO DUCTING BE EXTREMELY CAREFUL NOT TO DAMAGE AIR­CONDITIONING COILS OR OTHER FURNACE APPARATUS.
• THIS UNIT MUST BE INSTALLED IN 8” WIDE DUCT MINIMUM.
• DO NOT INSTALL THIS UNIT WHERE EXTREME TEMPERATURES EXIST (BELOW 8˚C / 45˚F OR ABOVE 63˚C / 145˚F).
• THIS UNIT IS NOT SUPPLIED WITH A DRAIN TUBE. HOWEVER WE DO RECOMMEND YOU PURCHASE AND INSTALL A INSTRUCTIONS) TO PROTECT AGAINST WATER OVERFLOW.
• FOR THIS UNIT TO OPERATE PROPERLY IT MUST BE INSTALLED ON A FORCED AIR HEATING SYSTEM WITH A SUPPLY DUCT AND RETURN DUCT.
• THE HUMIDIFIER AND THE BYPASS COLLAR DAMPER ARE TO BE INSTALLED ON DUCTING ONLY. UNDER NO CIRCUMSTANCES MOUNT ANY COMPONENT TO THE FURNACE BODY.
1
/2” DRAIN TUBE (SEE SECTION INSTALLATION
Page 3
Furnace Humidifier
INSTALLATION AND OPERATING INSTRUCTIONS:
Furnace Humidifier
3
• ELECTRICAL WIRING, WATER SUPPLY, AND DRAIN TUBE MUST NOT KINK OR COME INTO CONTACT WITH SHARP EDGES OR HOT SURFACES.
• IF REPLACING AN EXISTING FURNACE HUMIDIFIER, WE RECOMMEND YOU REPLACE ALL COMPONENTS TO ENSURE PROPER HUMIDIFIER OPERATION.
• THE INSTALLATION OF THIS PRODUCT MUST COMPLY WITH NATIONAL AND LOCAL ELECTRICAL, PLUMBING, BUILDING, AND MECHANICAL CODES.
REQUIRED TOOLS
• Safety glasses
•Workgloves
• Electric or cordless drill
3
• Drill bits (
• Tin snips
• Full size Philips or Roberstons screw driver
• Short handle Philips or Roberstons screw driver
• Adjustable wrench
• Utility knife
• Pliers
• Level
• Tape
• Measuring tape or ruler
• Medium-grit sand paper
• Pencil
/8",1/8",7/32”,7/64")
no more than 30” to ensure maximum air flow through the humidifier.
3. The supplied flex bypass tube is cut to the proper length and pulled tight to ensure maximum air flow.
4. The humidistat is located a minimum of 6” upstream of the humidifier, where moist air will enter the return duct.
5. The bypass damper is fully open.
6. The humidifier is mounted level on the duct.
7. There is nothing inside the duct behind the bypass collar and damper or the humidifier body.
8. The humidifier body and the bypass collar and damper are level.
IDEAL INSTALLATION
Figure 1
Damper fully open
SUPPLY DUCT
HOT AIR
RETURN DUCT
COLD AIR
No more
than 30"
8" wide duct minimum
Bypass collar and unit level
Bypass tube pulled tight and cut to length
SELECTION OF LOCATION
TO MOUNT THE HUMIDIFIER
All bypass type furnace-mount humidifiers rely on the pressure difference which exists between the supply duct (hot air) and the return duct (cold air) to create an air flow through the humidifier’s evaporator pad. The air will ALWAYS flow from hot (high pressure) to cold (low pressure).
•INSTALLATION TIP: Before starting fully plan out the installation. Check for the locations of the humidifier, bypass collar & damper, and the humidistat and associated sensors. Plan the length and type of ducting required, the water supply, the water drain, the electrical wiring, and a constant 120 volt outlet to plug in the transformer. This will ensure your installation goes as easy and quickly as possible
1. The humidifier body and bypass tube are installed at eye level, easily accessible for installation and routine maintenance.
2. The space between the humidifier body and bypass tube are
Not all installations will be as shown above – in cases where:
• The bypass duct required is more than the supplied 30”
• The bypass collar and damper must be installed above or below the humidifier
• The bypass collar and damper must be installed perpendicular to the humidifier
Use hard metal duct and hard metal elbows. This will minimize the amount of air-
SNAP OFF AND SAVE
flow restriction.
Figure 2
Page 4
Furnace Humidifier
4
HUMIDIFIER BODY INSTALLATION
This humidifier is designed to be mounted on the return duct (cold air) for safety reasons. This will minimize the exposure to high temperatures and extend product/component life. Always take precaution to ensure that water supply tube, water drain tube, any electrical wiring does not become kinked or come into contact with sharp edges or hot surfaces. Keep in mind that the humidistat must be mounted at least 6” upstream from the humidifier cabinet, where moist air enters the duct.
CAUTION: When cutting or drilling into ducting take care not to damage any air-conditioning coils or other furnace apparatus.
CAUTION: Wear safety glasses and work gloves when installing this unit, sharp metal edges can cause severe injury.
CAUTION: Turn the furnace off before starting this installation.
This humidifier cabinet consists of two side panels (bypass side panel and motor side panel), a front cover, and a water pan. The surface of the duct will form the rear of the humidifier cabinet.
STEP #1: RIGHT HAND DUCTING OR LEFT HAND DUCTING
Once you have decided the best location for the humidifier determine if the unit must be left or right hand ducting. This will depend on whether the hot air duct is to the left or right of the cold air duct. (Fig. 3) The side panels are symmetrical so setting up for left or right hand ducting is done by flipping the panel 180 degrees. (Fig. 4)
RIGHTHAND DUCTING
SUPPLY DUCT
RETURN DUCT
COLD AIR
HOT AIR
LEFTHAND DUCTING
RETURN DUCT
SUPPLY DUCT
HOT AIR
COLD AIR
STEP #2: MOUNTING THE HUMIDIFIER CABINET ON THE DUCT
If you have not already done so, remove the humidifier side panels from the carton. Locate the “Humidifier Cabinet Mounting Template”.
CAUTION: When cutting or drilling into ducting take care not to damage any air-conditioning coils or other furnace apparatus.
CAUTION: Wear safety glasses and work gloves when installing this unit. Sharp metal edges can cause severe injury.
CAUTION: Turn off the furnace before beginning this installation.
DRILLING THE HOLES AND MAKING THE CUTOUT
1. Use adhesive tape to affix the template onto the duct in the selected location. Use the level
Figure 5
DRILL HOLES
line on the template to ensure the humidifier cabinet will be mounted level.
2. Drill the 4 marked
1
/8” side panel
HUMIDIFIER
CUT-OUT
mounting holes. (Fig. 5)
3
3. Using a
/8” drill bit (not supplied) drill a hole inside the rectangle area marked “Humidifier Cut Out”. (Fig. 6)
Figure 6
DRILL CUT-OUT
4. Using the3/8” hole as a starting point cut out the Humidifier Cut Out area marked on the template using tin snips (not supplied). Cut
HUMIDIFIER
CUT-OUT
on the outside of the lines to ensure the cabinet will fit.
5. Remove remaining portion of the template from the duct.
Figure 7
MOUNTING THE BYPASS SIDE PANEL
Figure 3
Flipped 180˚
Figure 4
Flipped 180˚
6. Mount the bypass side panel to the duct first. This is the side of the humidifier closest to the hot air duct.
7. Use 2 of the supplied screws to secure the bypass side panel onto the duct work. The screws will install through two holes on the bypass side panel flange into two of the holes drill in #2. (Fig. 7)
MOUNTING THE MOTOR SIDE PANEL
8. Repeat the last two steps for the motor side panel. (Fig. 8)
9. After the side panels are mounted onto the duct install the two strips of gasket on the duct in between the two sides top and bottom, as shown in figure 9.
Figure 8
Figure 9
BOTTOM
GASKET
Page 5
Furnace Humidifier
5
MOUNTING THE WATER PAN
10. Install the water pan into the side panels. The water
DRAIN FITTING TO
THE REAR OF PAN
pan will install with the drain fitting to the rear of the humidifier. (Fig. 10)
IMPORTANT NOTE: IF YOU ARE PLANNING ON INSTALLING A DRAIN TUBE
Figure 10
(NOT SUPPLIED) DRILL OUT THE DRAIN FIT TING AS SHOWN IN THE SECTION “OVERFLOW DRAIN CONNECTION” BEFORE INSTALLING THE DRUM. ONLY DRILL OUT THE DRAIN FITTING IF YOU ARE INSTALLING A DRAIN TUBE. YOU WILL HAVE PURCHASE THE TUBE SEPARATELY.
11. Position the water pan between the sides so that the flange on either side of the water pan is resting on ribs on the inside of either side panel. (Fig. 11)
SIDE
PAN EL R IB
WATER
PAN FLANGE
12. Before the water pan is fully installed you will have to slightly deflect the front of both side panels (one at a time) to insert the hooks on the front of the water pan
Figure 12
Figure 11
into slots on the front of the side panels. (Fig. 12) As you are doing this be sure that the rear of the water pan flange is sliding under the upper ribs at the rear of the side panels. (Fig. 13) Once the water pan is in the proper position, secure the water pan in place using the
DEFLECT
SLIGHTLY
SIDE PANEL
SLOT
WATER PAN
HOOK
DEFLECT
SLIGHTLY
two #6 screws provided in the hardware pack (fig. 13b)
Figure 13
SIDE PANEL
UPPER RIB
PAN FLANGE IN BETWEEN
SIDE PANEL LOWER RIB
Figure 13b
INSTALLING THE FLOAT AND
VALVE ASSEMBLY
Figure 14a
Note before installing the float and valve assembly you will have to remove the proper double “D” knockout, refer to figure 14A. Using a screw driver remove the lower knockout closest to the water pan.
KNOCK OUT THE LOWER DOUBLE D HOLE
13. Once the pan is in place install the float & valve assembly, first remove the
white mounting nut (Fig. 14)
FLOAT ASSEMBLY
insert the threaded portion of the float valve into the double D hole and secure in place with the white mounting nut removed
WHITE MOUNTING NUT
Figure 14
earlier. Hold the valve as straight as possible while tightening so an accurate water level can be maintained. (Fig. 15)
Figure 15
INSTALLING THE BEARING INTO THE BYPASS SIDE PANEL
HAND HOLDING FLOAT STRAIGHT
14. Retrieve the Bearing which was removed from the bypass side panel at the beginning of the installation (Fig. 16) and install it
WRENCH TIGHTENING NUT
into the center of the bypass side panel. (Fig. 17) If replacing or repairing a bearing insert a slotted
Figure 17
BEARING
Figure 16
BEARING SNAPPED IN COMPLETELY AND U SHAPE UP
screw driver into the back top of the bearing and rotate the screw driver, the bearing will pop out of the side panel. (Fig. 17B)
Figure 17b
ROTAT E TO DISLODGE THE BEARING
INSTALLING THE DRUM AND EVAPORATOR PAD ASSEMBLY
15. Retrieve the drum and evaporator pad assembly. This assembly is made up of the drum the evaporator pad, and the drum shaft, you will notice this assembly has an open end and a closed end. (Fig. 18)
16. Starting with the closed end install the drum shaft into the center of the motor coupling then install the other end of the drum shaft into the bearing, gently pushing down in place to position. (Fig. 19)
DRUM EVAPORATOR PAD ASSEMBLY
BEARING
MOTOR COUPLING
CLOSED END
DRUM SHAFT
Figure 18
EVAPORATOR PAD
OPEN END
DRUM CAGE
CLOSED END
MOTOR
Figure 19
STEP #3: MOUNTING THE BYPASS COLLAR AND DAMPER
The humidifier comes with a collar & damper mounting template. If possible ensure the bypass collar will be level to the humidifier duct connection. Try to keep the bypass collar within 30” of the humidifier. To ensure you have clear access to all components do not install the flexible bypass tube until all water and electrical connections are made to the humidifier.
OPEN END
Page 6
Furnace Humidifier
6
CAUTION: When cutting or drilling into ducting take care not to damage any air-conditioning coils or other furnace apparatus.
CAUTION: Wear safety glasses and work gloves when installing this unit. Sharp metal edges can cause severe injury.
1. Use adhesive tape to affix the bypass template onto the duct in the selected location.
1
2. Drill the 3 marked
3. Using a
3
/8” drill bit (not supplied) drill a hole inside the circular
/8” holes.
area marked collar cut out.
3
4. Using the
/8” hole drilled earlier as a starting point cut out the Collar Cut Out area marked on the template using tin snips (not supplied).
5. Mount the bypass collar and damper (Fig. 20) using the three supplied screws. The air damper should be installed in the open
TOP SCREW FOR DAMPER MOUNTING
DAMPER OPEN
position. The top screw secures the damper.
Figure 20
•INSTALLATION TIP If replacing an existing humidifier which has been installed on your furnace you may be able to use the existing cut-outs, however replace the components, bypass collar and damper, and bypass ducting. The majority of furnace humidifiers use 6" ducting for bypass.
NOTE: The optimum tightness of the nylon compression nut will
leave a gap of approximately
3
/16” between the nylon
compression nut and the nylon hex nut.
INSTALLING THE SADDLE VALVE TO THE WATER PIPE
The water supply for the humidifier is provided from an existing cold water pipe by using a self-piercing saddle valve. In order for you to use the supplied plastic tubing, select the nearest cold water pipe suitable for saddle valve installation.
1. Turn the main water supply off.
2. Rotate the saddle valve handle so that the piercing pin does not protrude beyond the top clamp.
3. With the rubber gasket in the fixed position, clamp the saddle valve on the selected location of the cold water pipe and mount the bolts and nuts to the saddle clamps.
4. To pierce the copper pipe, simply turn valve handle clock­wise until you feel that it is firmly seated. (Fig. 24)
NOTE: Do not open the valve now. Proceed with the mounting of the plastic tubing to the saddle valve first.
SELF
PIERCING
VALVE
RUBBER
GASKET
ROTATE CLOCKWISE TO PIERCE PIPE
PIERCING PIN
TOP CLAMP
BOTTOM CLAMP
Figure 24
CONNECTING THE PLASTIC TUBING TO THE SADDLE VALVE
STEP #4: WATER SUPPLY AND DRAINAGE CONNECTION
WATER CONNECTION TO THE HUMIDIFIER
IMPORTANT: Connect the tubing to the humidifier FIRST before connecting to the saddle valve.
1. SAND THE END (Fig. 21) of the plastic water supply tube. FAILURE TO DO SO MAY RESULT IN LEAKS. Use medium sandpaper (not provided) approx
1
/4” from the end in a rotating
1 motion. This assures a non-
Figure 21
slipping, trouble free connection.
2. Slide the nylon compression nut and the black rubber ferrule onto the sanded plastic tubing and then fit the brass insert into the end of the plastic tubing. (Fig. 22)
Figure 22
BLACK RUBBER
NYLON COMPRESSION NUT
FERRULE
BRASS INSERT
SANDED TUBE
Figure 23
3. Push the plastic tubing firmly into the humidifier’s float valve threaded water inlet. Carefully begin tightening the nut by hand. Use an adjustable wrench to finish tightening. (Fig. 23)
1. Cut the plastic tubing with a sharp knife to the proper length to fit between the humidifier and the saddle valve.
2. SAND THE END (Fig. 21) of the plastic water supply tube. FAILURE TO DO SO MAY RESULT IN LEAKS. Use medium
1
sandpaper (not provided) approx 1
/4” from the end in a rotating motion. This assures a non-slipping, trouble free connection.
BRASS INSERT
SANDED TUBE
3. Slide the brass compression nut and nylon ferrule onto the
NYLON FERRULE
BRASS NUT
sanded plastic tube and fit the brass insert in the end of the
Figure 25
tubing. (Fig. 25)
4. Push the tubing firmly into the saddle valve threaded water outlet, carefully begin tightening the compression nut by hand (be careful not to cross the threads). Use and adjustable wrench to finish tightening the brass compression nut. Do not over-tighten.
OVERFLOW DRAIN CONNECTION (OPTIONAL)
NOTE: WE STRONGLY RECOMMEND YOU INSTALL A DRAIN TUBE TO PROTECT YOUR PROPERTY IN CASE OF WATER LEAKAGE. IF YOU ARE PLANNING ON INSTALLING A DRAIN TUBE ONTO THE UNIT YOU WILL HAVE TO PURCHASE THE REQUIRED LENGTH OF TUBING AND A HOSE CLAMP SEPARATELY. AS WELL YOU SHOULD HAVE DRILLED OUT THE DRAIN FITTING BEFORE INSTALLING THE WATER PAN ONTO THE FURNACE. ONLY DRILL OUT THE WATER PAN IF
YOU PLAN TO INSTALL A DRAIN TUBE.
Page 7
Furnace Humidifier
7
REQUIRED SEPARATELY PURCHASED PARTS FOR DRAINAGE INSTALLATION:
5
/8”OD1/2” ID DRAIN HOSE, LENGTH AS PER YOUR
• INSTALLATION.
5
• HOSE CLAMP FOR
/8”ODHOSE.
1. Measure the required length of drain tube from the bottom of the humidifier to an appropriate floor drain.
2. Prepare the drain fitting at the rear of the water pan before installing the water pan onto the furnace.
1
3. Referring to figure 26, first drill a small hole (
/8” dia) centered
from the bottom of the drain fitting up through the pan.
3
Figure 26
4. Then using a carefully enlarge the hole to allow
/8” drill bit
for free flow of water.
5. Once the drain fitting has been drill and the water pan installed onto the furnace you may install
5
the drain tube (
/8”OD,1/2”ID)
not supplied.
6. First install a5/8”hoseclamp (not supplied) over the end of the drain tube, then push the drain tube up over the drain fitting and secure in place with the hose clamp. (Fig. 27)
DRAIN FITTING
HOSE CLAMP
DRAIN HOSE
Figure 27
7. Feed the other end of the drain tube to a floor drain, secure to the floor drain using a tie strap or cable tie (not supplied).
STEP #5: ELECTRICAL INSTALLATION
This unit is supplied with a 24 volt plug in transformer. The transformer must be plugged into a constant (one that will not be shut off) 120 volt outlet. The transformer is supplied with 10 feet of low voltage wire which must feed the humidistat and the humidifier’s drum motor. Select an outlet within the 10 feet.
HUMIDISTAT
The humidifier is supplied with an exclusive universal humidistat which can be either wall mounted as furnished or, with a few minor changes, be mounted on the return (cold) air plenum/duct. Either wall mounting or plenum/duct mounting works equally well for humidity sensing and control. Wall mounting provides easy access to adjust the humidistat setting since it is located in the living area. Plenum/Duct mounting provides a simple installation (you should not have to purchase extra low voltage wire or fish the wires through the wall).
installations, the humidistat is installed near the heating thermostat for easy adjustment and wiring.)
3. Because the humidistat will be located further away from the humidifier you will have to purchase approximately 15 to 20 feet of 20 ga low voltage wire.
4. Drill a small hole in the wall and then fish the low voltage wire out thru the hole. Leave approximately 6 inches of low voltage wire leads outside the hole for humidistat connection.
5. Remove the cover plate from the humidistat and you will see four holes at the corners of the base plate mount the
90˚ WIRE TERMINALS FOR LOW VOLTAGE WIRE CONNECTIONS
4 SCREWS PROVIDED FOR MOUNTING TO THE WALL
BASE PLATE
humidistat on the wall using the (4) 1” long screws provided. Make sure it is level and the
3/8” HOLE
low voltage wire is coming out thru the
3
/8” hole on the base plate. (Fig. 28)
KNOB
CONTROL LABEL
COVER PLATE
Figure 28
6. Strip the low voltage wires and make connections to the humidistat using the two 90˚ wire terminals provided. Replace the cover plate.
7. Install the knob onto the humidistat control shaft.
PLENUM/DUCT MOUNTING
1. As shipped, the humidistat is ready for wall mounting. You must first convert the humidistat from wall mounting to plenum/duct mounting. The control mechanism must be in the air stream in order to sense and control the humidity.
2. Remove the cover plate and discard it.
3. Remove the control mechanism from the
Figure 29
PRE-CUT PLENUM HOLE
base plate by removing the two holding screws at the back, and then, turning the control mechanism 180˚ upside down to allow the shaft to protrude
1
out through the
/2” hole on the base plate (NOTE: base plate remains in the same
KNOB
CONTROL LABEL
CONTROL MECHANISM
SHAFT
BASE PLATE
HOLDING SCREWS
position and only the control mechanism is turned (Fig. 29).
4. Replace the two screws to hold the control mechanism to the base plate.
5. Attach the two 90˚ electrical terminals to the humidistat.
WALL MOUNTING
1. Your humidistat is furnished in the “wall mounting” mode, no changes to the humidistat are necessary, because the circuit is low voltage (24 V), no switch box is required.
2. Select a location about five (5) feet above the floor on an inside wall where normal air circulation exists. (In most residential
6. Use adhesive tape (not provided) to affix the humidistat opening template to the pre-selected location and then drill
3
the 4 mounting holes and a
/8” hole in the area mark
humidistat cutout.
3
7. Using the
/8” hole as a starting point make the cutout cutting
on the outside of the line.
8. Skip to low voltage wiring section.
Page 8
Furnace Humidifier
8
LOW VOLTAGE WIRING
The 24 volt plug in transformer has 10 feet of low voltage wire attached. Your 120 Volt outlet should be located close enough to connect the end of the low voltage wire to the drum motor and have the duct mounted humidistat located in between. DO NOT PLUG THE TRANSFORMER IN UNTIL INSTALLATION IS COMPLETE.
1. The humidifier motor lead wire has two push-on terminals which will mate with the 2 terminals at the end of the low voltage wire on the transformer. Connect these wires together.
2. In the area where the humidistat is to be mounted position the low voltage wire harness and carefully separate the 2 wires apart. (Fig. 30)
3. Cut one of the conductors and strip the insulation from both ends. (Fig. 31)
Figure 30
CUT THE MIDDLE AND SEPARATE APPROX. 3”
LOW VOLTAGE WIRE SET
Figure 31
CUT ONE OF THE CONDUCTORS AND STRIP THE ENDS
LOW VOLTAGE WIRE SET
4. Connect the stripped ends to the 90˚ terminals on the plenum/duct mount humidistat or to the low voltage wire from the humidistat wall mounted in the living area (depending on which humidistat installation you chose).
5. Complete the installation of the Duct mounted humidistat.
6. Mount the humidistat onto the return duct by using the four 1” long sheet metal screws provided (Note the small rectangular notch at the bottom provided for the access of the low voltage wire to the humidistat wiring terminals.)
7. Remove the paper backing from the control label and apply the label onto the face of the base plate.
8. Install the knob onto the humidistat control shaft.
STEP #6: ADJUSTING THE WATER LEVEL
TURNING THE WATER ON
1. Turn on the water supply at both the main water supply and the self-piercing saddle valve. Check to see if water leaks at any joints. If there is a leakage, tighten the compression nut to correct the problem.
2. Water should flow gently into the water pan. If it flows too slow or too fast, adjust the self-piercing saddle valve.
ADJUSTING THE WATER LEVEL
KNOB (ROTATE TO ADJUST THE WATER LEVEL)
1. The water level is adjusted by altering the height of the float.
STEP # 7: COMPLETING THE INSTALLATION.
CHECK THE ELECTRICAL WIRING
1. Plug the transformer in and turn up the humidistat to that it is calling for humidity, 50% +.
2. The drum should start rotating – either direction is fine.
3. Adjust the humidistat down to the off position and the humidifier will shut off.
INSTALLING THE BYPASS TUBE
4. Retrieve the flexible bypass tube and two spring clamps
5. Install the bypass tube on the bypass collar and damper first.
Figure 33
SPRING CLAMP
FLEX TUBE
6. Slide one of the 6” spring clamps supplied over one end of the bypass tube. (Fig. 33)
7. Slide this same end of the bypass tube over the flange of the collar and secure inplace with the spring clamp. (Fig. 34)
8. Slide the other 6” spring clamp over
COLLAR FLANGE
SPRING CLAMP
FLEX TUBE
Figure 34
the other end of the bypass tube.
9. Slide this end of the bypass tube onto the humidifier’s bypass side panel and secure in place with the spring clamp.
INSTALLING THE FRONT COVER
10. Retrieve the humidifier’s front cover.
MOUNTING PEG
FRONT COVER
11. At the top rear of the front there are 2 mounting pegs (Fig. 35). These pegs will fit into round slots at the top/rear
MOUNTING PEG
of both side panels (Fig. 36).
12. With the front cover in the fully open position (not attached to the humidifier), tilt the cover at approx a 30˚ angle and insert one of the
ROUND SLOT FOR
FRONT COVER
Figure 35
front cover pegs into the round slot (Fig. 37).
13. To finish installing the front cover
slightly deflect the top/rear of the opposite side panel and insert the other peg into the round slot (Fig. 38).
Figure 36
14. With the front cover installed grasp the bottom and pull down
until fully closed, it will snap closed at the bottom (Fig. 39).
Installation is now complete. Move to humidifier operation section.
2. Rotate the knob of the valve seat (Fig. 32).
Figure 32
3. Adjust the float in such away so that it closes the automatic valve when the selected water level has been reached.
4. The maximum water level in the pan should not exceed from the top of the water pan.
INSTALL COVER FULLY
OPEN AT 90˚ ANGLE
1
/2”
Figure 37
Figure 38 Figure 39
SNAP
CLOSED
SNAP
CLOSED
Page 9
Furnace Humidifier
9
HUMIDIFIER OPERATION
ROTATING DRUM HUMIDIFIER
Because this rotating drum humidifier utilizes a water pan/reservoir the unit is 100% efficient, all the water used is delivered to the air. For this reason the unit does not have to be interlocked with the furnace cycles, the drum can rotate whether the furnace is heating or not, no water will be wasted and the humidistat will control the amount of moisture delivered to the air.
CONTROLLING THE HUMIDITY LEVEL
The mechanical humidistat supplied with this unit is to control the amount of moisture added to the air in your home – It will sense the relative humidity level in the air and work as an ON/OFF switch to control the humidifier, regardless of whether the furnace is running.
At the beginning of the heating season it may take sometime to build up the relative humidity level in your home to the desired level – For the first few weeks turn the humidistat up high to ensure the humidifier will run. After you feel that you have achieved the desired relative humidity level turn the humidistat down until it cycles the humidifier OFF. The humidifier will then work to maintain the relative humidity at that level.
RECOMMENDED MANUAL HUMIDISTAT SETTINGS
OUT SIDE AIR TEMPERATURE MAXIMUM RELATIVE HUMIDITY SETTING
-20°F /-30°C 15%
-10°F /-25°C 20%
0°F / -20°C 25%
+10°F/ -10°C 30%
+20°F/ -5°C 35%
30%F/ 0˚C 40%
ABOVE 45% MAXIMUM
If condensation continues to form on windows at these settings reduce the humidistat setting by successive 5% increments. After each reduction in setting allow 6 hours for equilibrium to be reached before readjustment.
If condensation persists with progressively lower settings made during a 3 day period turn off the water supply at the saddle valve, turn the humidistat to OFF and consult your heating contractor.
When your house is unoccupied for longer than 3 days during the winter always set the humidistat down to 15% so that severe weather during your absence will not result in condensation which may cause damage to your home.
ACHIEVING AND MAINTAINING A HUMIDITY LEVEL
Outside conditions are the primary factor affecting the humidity level in your home. The colder it gets outside the less moisture the outside air will have, your home brings in the outside air and the humidifier will work to add moisture to it. As outside conditions change the humidity level in your home will change as well. Other factors which will affect humidity levels in the home include, how many air-changes your ventilation system delivers, the amount of people occupying the home, air leaks, the use of showers, exhaust fans, HRV’s, and the use of fireplaces or wood stoves.
SAFELY OPERATING A FURNACE HUMIDIFIER
Proper control of the relative humidity level in the home is key to ensuring good Indoor Air Quality (IAQ) for your home as well as protecting against moisture damage.
Although a relative humidity environment of 45 to 50% may be desirable, setting your humidistat at that point when outside air temperatures are below 30˚F (-1˚C) can cause condensation on windows and walls. Continued condensation for extended periods of time may result in structural damage. Use the chart below as a guide for maximum relative humidity settings at the different outdoor air temperatures.
SUMMER SHUT DOWN
During the summer season the humidity level in the air is quite high. Therefore it is advisable to shut off the humidifier system. Complete the following steps at the end of the winter season.
1. Close the water supply at the saddle valve.
2. Turn the humidistat knob to the OFF position.
3. Empty and clean the water pan.
4. Close the bypass air damper.
CARE AND MAINTENANCE
Because drum humidifiers utilize a water pan/reservoir they are susceptible to water deposits and mineral build up, for this reason we strongly recommend that the yearly maintenance include
• Replacing the evaporator pad
• Cleaning/replacing the float & valve assembly
• Cleaning/replacing the water pan
If you complete all the above tasks at once the amount of time involved will be greatly reduced and your humidifier will continue to work at peak efficiency.
Page 10
Furnace Humidifier
10
CLEANING OR REPLACING THE EVAPORATOR PAD
(Figures 40 a, b, c)
To clean or replace the
Figure 40 a)
evaporator pad follow the steps below.
NOTE: Do not rotate the drum assembly by hand this may cause damage to the gears in the drum motor.
1. Unplug the transformer (turn power off to the humidifier).
2. Turn off the water supply at the saddle valve.
3. Open the humidifier front Cover (Fig. 40a). The cover is snap closed on the left hand side, to release slightly deflect the front cover flange at the bottom left and lift up. In the fully open position the
DEFLECT
LEFTHAND
FLANGE OUT
DRUM EVAPORATOR PAD ASSEMBLY
b)
c)
DRUM SHAFT
STOP LUGS
DISK FLANGE
SPOKES
DEFLECT RIGHTHAND FLANGE OUT
OPEN END FIRST
TILT ASSEMBLY OUT
PULL OUT
BUSHING
cover will stay open.
4. Gently remove the drum/evaporator pad assembly at the bearing end (open end) first. Take care not to lose the bearing which the drum shaft rides in. Once the bearing side is removed you will be able to tilt the drum/evaporator pad assembly out from the motor coupling. (Fig. 40b)
5. Hold the drum assembly in a horizontal position and pull the bushing out with your fingers (Fig. 40c).
6. Slide the evaporator pad off the drum cage.
7. To replace the pad keep the bushing in the extended position and slide the evaporator pad over the spokes until it is against the disc flange.
8. Push the bushing back along the shaft to the stop lugs. The evaporator pad is now locked into position.
9. Replace the drum/evaporator pad assembly completing step 4 in reverse motor coupling end first.
10. Close the front cover.
11. Turn on the water supply and plug the transformer back in.
CLEANING OR REPLACING THE FLOAT VALVE ASSEMBLY/COMPONENTS
(Figures 41 a, b, c)
To clean or replace the float valve assembly/components follow the steps below.
1. Unplug the transformer (turn power off to the humidifier).
2. Turn off the water supply at the saddle valve.
3. Open the humidifier front Cover (Fig. 41a). The cover is snap closed on the left hand side, to release slightly deflect the front cover flange at the bottom left and lift up. In the fully open position the cover will stay open.
4. If you wish to replace the entire float valve assembly included
valve jet shield, disconnect the water supply from the valve’s
Figure 41 a)
threaded inlet by using an adjustable wrench to loosen and remove by hand (Fig. 41b).
5. Loosen the white mounting nut using an adjustable wrench and remove by hand. You can now remove the float and replace with a new one.
DEFLECT
LEFTHAND
FLANGE OUT
b)
DEFLECT RIGHTHAND FLANGE OUT
6. Re-attach the components in reverse order as above.
7. Turn the water back on and check for and repair any leaks.
8. Plug the transformer back in.
9. To replace or clean selected components of the float valve assembly (Fig. 41c), Place your thumb and forefinger around the neck of the float.
c)
VALVE JET SHIELD
PIVET PIN
SQUEEZE HERE (NECK)
KNOB
VALVE SEAT
SPIGOT
FLOAT
10. Squeeze firmly. This will disengage the two pivot pins from the holes at the sides of the valve jet shield and release the float.
11. The valve seat and knob can then be pulled off the spigot.
12. When replacing the valve seat be sure that it is pushed down as far as it will go onto the float.
13. Clean components or replace with new parts and reassembly the float.
14. The float valve assembly can be cleaned by using a solution of 50/50 water and vinegar.
15. Close the front cover.
16. Turn on the water supply and plug the transformer back in.
CLEANING OR REPLACING
Figure 42 a)
THE WATER PAN
(Figures 42 a, b, c)
To clean or replace the water pan follow the steps below.
1. Unplug the transformer (turn power off to the humidifier).
DEFLECT LEFTHAND FLANGE OUT
b)
DEFLECT RIGHTHAND FLANGE OUT
2. Turn off the water supply at the saddle valve.
3. Open the humidifier front
THUMB AND FOREFINGER SQUEEZE HERE
Cover (Fig. 42a). The cover is snap closed on the left hand side, to release slightly deflect the front cover flange at the
c)
bottom left and lift up. In the fully open position the cover will stay open.
4. To remove the float from the jet shield place your thumb and forefinger around the
DEFLECT SLIGHTLY
SIDE PANEL
SLOT
WATER PAN HOOK
DEFLECT
SLIGHTLY
Page 11
Furnace Humidifier
11
neck of the float squeeze firmly and this will disengage the 2 pivot pins from the holes at the sides of the valve jet shield. (Fig. 42b)
5. Remove the drum and evaporator pad assembly bearing end first (see instructions above).
6. Remove the two screws which secure the water pan to the side panels, the screws are located at the front, on the underside of the water pan’s side flanges. There is also a set of hooks on either side of the front of the pan which fit into slots on both side panels, to release the water pan deflect each side slightly in the area where the pan attaches and lift up. (Fig. 42c)
7. Once removed from the slots the pan will slide out.
8. Clean in a 50/50 mixture of water and vinegar.
9. Replace all components in reverse order
10. Close the front cover.
11. Turn on the water supply and plug the transformer back in.
WARRANTY
The manufacturer guarantees the for the period of one year from the date of purchase, the product will be free of defects in workmanship and/or material. As well the manufacturer offers a life time warranty on the flow through humidifier body. During the warranty period, we will replace or repair any defective part at no charge if the product is returned prepaid to our factory.
NOTES
This warranty does not cover any labor or shipping costs, or the cost of replacement components as part of routine maintenance (such as Flow Through Humidifier Evaporator Pads, Inlet water Filters, or Orifice Fittings). Any damage or failure caused by abuse, misuse, abnormal usage, faulty installation, or improper maintenance will not be covered by this warranty.
In order to make a claim on this warranty you must be the original consumer of the product and you must contact the manufacturer 1-800-465-7300 between 8 AM and 3:30 PM EST Monday to Friday at the first sign of a defect. You will be required to present to the manufacturer the original bill of sale showing date of purchase, place of purchase, and model purchased. Failure to meet these requirements will void your warranty.
The manufacturer will not be held responsible for any bodily injuries or damages to personal property or real estate whether caused directly or indirectly by the product. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages and some states or provinces do not allow limitations on how long an implied warranty lasts, so these exclusions or limitations may not apply to you. This warranty gives you specific legal rights and you may have other rights which vary from state to state and province to province.
SAVE THIS DOCUMENT AND ATTACH YOUR RECEIPT.
Date of Purchase Date Of Installation
Place of Purchase Brand and Model#
Page 12
Furnace Humidifier
12
1
2
27
6
7
3
17
5
4
15
16
14
19
18
8
9
10
11
12
13
14
22
20
21
29
28
27
26
24
23
25
MODEL 1000
ITEM NUMBER
1
DESCRIPTION
cover (specify brand)
2 humidistat (specify brand)
4
5
motor side panel
6
7
bypass side panel
8
9
10
water level knob
water level knob seat 1/per 01A017084
11
12
13
14
15
16
17
18
nylon compression nut
1/4" plastic water tubing
nylon compression nut 1/per 060010801
19
20
needle valve assembly
21
22
23
24
25
evaporator water pad
26
6" spring wire clamp 2/per 01093800027
28
29
QTY/UNIT
1/per
1/per
PART NUMBER
011483000
01A000000
0109160011/per120/24VAC transformer3
motor
1/per
1/per
01A172235
011481000
tesa foam 8 inches/unit 20221
1/per
011482000
tesa foam 6 3/4 inches/unit 20221
1/per
01A017083
float 1/per 01A900903
jet shield 1/per 01A900906
nylon hex nut
brass insert 01A930041
rubber ferrule
1/per
1/per
1/per
1/per
10 feet/unit
1/pernylon ferrule
1/per
water pan
drum shaft 01A900911
drum cage
bearing
1/per
1/per
1/per
1/per
1/per
060011142
01A010816
0600110801
01A930040
010926001
0PB132055
011484000
01A900914
011509000
01A017256
by-pass tube 3 feet/unit 010917000
collar
air damper
1/per
1/per
01A172107
01A170930
Loading...