Manufactured by : STOVE BUILDER INTERNATIONAL INC.
250, de Copenhague, Saint-Augustin-de-Desmaures (Quebec), Canada G3A 2H3
Tel: (418) 878-3040
Fax: (418) 878-3001
www.drolet.ca
This manual is available for free download on the manufac turer’s web site. It is a copyrighted
document. Re-sale is strictly prohibited. The manufacturer may update this manual from time
to time and cannot be responsible for problems, injuries, or damages arising out of the use of
information contained in any manual obtained from unauthorized sources.
READ AND KEEP THIS MANUAL FOR REFERENCE
45280A
Printed in Canada 01-05-2012
INTRODUCTION
Stove Builder International, one of the most important wood stove and fireplace manufacturers in North
America, congratulates you on your purchase and wishes to help you get maximum satisfaction from your
wood stove. In the pages that follow, we will give you advice on wood heating and controlled combustion
as well as technical specifications regarding installation, operation and maintenance of the model you have
chosen.
The instructions pertaining to the installation of your wood stove in North America comply with ULC-S627
and UL-1482 standards.
Read this entire manual before you install and use your new stove. If this stove is not properly
installed, a house fire may result. To reduce the risk of fire, follow the installation instructions.
Failure to follow instructions may result in property damage, bodily injury, or even death.
Consult your municipal building department or fire officials about restrictions and installation
requirements in your area and the need to obtain a permit.
KEEP THIS INSTRUCTION MANUAL FOR FUTURE REFERENCE.
CAUTIONS:
THE INFORMATION GIVEN ON THE CERTIFICATION LABEL AFFIXED TO THE APPLIANCE ALWAYS OVERRIDES
THE INFORMATION PUBLISHED, IN ANY OTHER MEDIA (OWNER’S MANUAL, CATALOGUES, FLYERS,
MAGAZINES AND/OR WEB SITES).
HOT WHILE IN OPERATION. KEEP CHILDREN, CLOTHING AND FURNITURE AWAY.CONTACT MAY CAUSE SKIN
BURNS.
DO NOT USE CHEMICALS OR FLUIDS TO IGNITE THE FIRE.
DO NOT LEAVE THE STOVE UNATTENDED WHEN THE DOOR IS SLIGHTLY OPENED DURING IGNITION.
DO NOT BURN WASTE,FLAMMABLE FLUID SUCH AS GASOLINE, NAPHTHA, OR MOTOR OIL.
DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
ALWAYS CLOSE THE DOOR AFTER IGNITION.
REGISTER YOU WARRANTY ONLINE
To receive full warranty coverage, you will need to show evidence
of the date you purchased your stove. Keep your sales invoice. We
also recommend that you register your warranty online at
*Why is the BTU indicated on the EPA label smaller than the one advertised?
You will notice a difference between the BTU output as indicated on the unit’s white EPA label affixed to the glass and the BTU
as advertised on our web site and/or product literature. The maximum BTU output we advertise for this unit is what will be
obtained with a full load of seasoned cordwood inserted inside the firebox. The EPA output, on the other hand, is what has been
obtained during emissions testing. The EPA test procedure requires that a special type of wood be used and positioned inside the
firebox in a manner that does not represent the way the firebox volume would normally be utilized using seasoned cordwood. The
EPA test load is typically much smaller. Hence, the BTU as per the EPA label is reduced. The BTU output that should be
considered by a normal user is the one we advertise for seasoned cordwood.
*Why is the BTU indicated on the EPA label smaller than the one advertised?
You will notice a difference between the BTU output as indicated on the unit’s white EPA label affixed to the glass and the BTU
as advertised on our web site and/or product literature. The maximum BTU output we advertise for this unit is what will be
obtained with a full load of seasoned cordwood inserted inside the firebox. The EPA output, on the other hand, is what has been
obtained during emissions testing. The EPA test procedure requires that a special type of wood be used and positioned inside the
firebox in a manner that does not represent the way the firebox volume would normally be utilized using seasoned cordwood. The
EPA test load is typically much smaller. Hence, the BTU as per the EPA label is reduced. The BTU output that should be
considered by a normal user is the one we advertise for seasoned cordwood.
5
TIPS ON WOOD HEATING
Wood is a renewable energy. It is also a very clean heat source when used with appliances
that are certified by the U.S. Environmental Protection Agency (EPA), a standard accepted
in Canada as well.
EPA-certified wood stoves are different than conventional wood stoves. Burning with an EPAcertified wood stove may therefore require that you modify some of your heating habits. To get
the most satisfaction out of your new wood-heating system, please make sure you go through the
following check list.
The chimney is the engine that drives the wood-heating system. Use a chimney that is UL-
listed, with an inner diameter to match the stove’s outlet collar (6” for all Drolet wood
stoves);
Try to run the chimney inside the building for as much length as you can. A tall and
warm chimney will produce a good draft;
Try to install your chimney straight up and avoid 90 degree turns in the flue pipe and
offsets in the chimney;
Make sure that the chimney is tall enough and its top is clear of obstacles so it can
produce a stable draft;
Use a chimney thermometer installed at a distance of approximately 18 inches on the
flue pipe above the stove. Flue gases should reach at least 350oF before you close the
stove’s primary air intake completely. Operate your unit within the comfort zone
indicated on the thermometer;
To reduce the risk of smoke spillage into the room upon reloading your stove, leave the
primary air intake completely open for a few minutes. This will heat up the chimney and
build up draft before you open the stove door;
Maximize hot air circulation! Our wood stoves are designed to easily receive a variable
speed blower that will improve heat distribution in front of the stove;
Remember that wood stoves produce radiant heat. Since heat rises, the use of floor
traps will greatly improve the heat transfer to rooms upstairs;
Use a mobile home approved stove if you are going to install your wood-heating system
in a mobile home. A fresh air kit must be connected to the stove. Never install your
wood stove in a bedroom;
Burn only dry cordwood;
Make sure you have a good bed of red coals before you load your stove with logs
exceeding 3 inches in diameter;
Read and keep you owner’s manual. It will provide you with tips on how to run a
successful wood-heating system.
6
SECTION 1.0 INSTALLATION
When installed and operated as described in these instructions, the Eastwood EPA wood stove is suitable
for use as a freestanding wood stove in residential installations. The Eastwood EPA wood stove is not
intended for installation in a bedroom or a mobile home.
In Canada, the CSA B365 Installation Code for Solid Fuel Burning Appliances and Equipment and the CSA
C22.1 Canadian National Electrical Code are to be followed in the absence of local code requirements. In
the USA, the ANSI NFPA 70 National Electrical Code and NFPA 211 Standard for Chimneys, Fireplaces,
Vents and Solid Fuel-Burning Appliances are to be followed in the absence of local code requirements.
In addition to the national installation and/or local building codes, fire officials (or other authorities having
jurisdiction) should be contacted to determine what restrictions and installation requirements might apply
locally.
We recommend that our wood burning hearth products be installed and serviced by professionals who are
certified in the United States by NFI (National Fireplace Institute
Technical Training) or in Quebec by APC (Association des Professionnels du Chauffage).
1.1 GENERAL INSTALLATION
®
) or in Canada by WETT (Wood Energy
CAUTION:
MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING THE
DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN HAZARDOUS CONDITIONS. WHERE SUCH ACTION IS
CONSIDERED, THE MANUFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE.
DO NOT CONNECT THIS UNIT TO ANY AIR DISTRIBUTION SYSTEM.
CRACKED AND BROKEN COMPONENTS,e.g. GLASS PANELS OR CERAMIC TILES, MAY RENDER THIS INSTALLATION
UNSAFE.
A SOURCE OF FRESH AIR INTO THE ROOM OR SPACE HEATED SHALL BE PROVIDED WHEN REQUIRED.
CONNECT THE STOVE ONLY TO A LINED MASONRY CHIMNEY CONFORMING TO NATIONAL AND LOCAL BUILDING
CODES FOR USE WITH SOLID FUEL, OR TO A LISTED FACTORY BUILT CHIMNEY SUITABLE FOR USE WITH SOLID
FUEL.
This heating unit must serve as a supplementary heat source. An alternative heat source should be
available in the home if needed. The manufacturer cannot be responsible for additional heating costs
associated with the use of an alternative heat source.
It is highly recommended that the user buys this product from a retailer who can provide installation and
maintenance advices.
7
1.2 POSITIONING THE STOVE
It is very important to position the wood stove in an area that will favour the most efficient heat distribution
throughout the house. The stove should therefore be installed in the room where the most time is spent, and
in the most spacious room possible. Recall that wood stoves produce radiating heat, the heat we feel when
we are close to a wood stove. A wood stove also functions by convection, that is through the displacement
of hot air accelerated upwards and its replacement with cooler air at the floor level. The stove’s convection
effect is facilitated by the installation of a blower.
1.3 CLEARANCES TO COMBUSTIBLES AND FLOOR PROTECTOR
To install your appliance correctly, it is extremely important to respect all clearances to any combustibles as
indicated on your stove’s certification label.
Clearances to combustible materials
(see figure 1.3 to match each letter to a clearance)
MODEL A B C D E F K L
EASTWOOD
1500
20"
(508 mm)
19
"
(483 mm)
CLEARANCES (SINGLE WALL PIPE)
CANADA / USA
14
"
(356 mm)
23
"
(584 mm)
29
"
(737 mm)
(610 mm)
24
48
"
"
(1220
mm)
84
"
(213 cm)
EASTWOOD
1800
MODEL A B C D E F K L
EASTWOOD
1500
EASTWOOD
1800
18"
(457 mm)
20"
(508 mm)
18"
(457 mm)
18
"
(457 mm)
19
"
(483 mm)
18
"
(457 mm)
12"
(305 mm)
CLEARANCES (DOUBLE WALL PIPE)
14
"
(356 mm)
12"
(305 mm)
21”
(533 mm)
CANADA / USA
23
"
(584 mm)
21”
(533 mm)
28”
(711 mm)
29
"
(737 mm)
28”
(711 mm)
21”
(533 mm)
24
"
(610 mm)
21”
(533 mm)
48"
(1220
mm)
48
"
(1220
mm)
48"
(1220
mm)
84
"
(213 cm)
84
"
(213 cm)
84
"
(213 cm)
8
FIGURE 1.3 Clearances to combustible materials and floor protection
9
Floor protector
If the stove is to be installed on top of a combustible floor, it must be guarded by a non combustible
material as shown on figure 1.3 (see the dotted line area).
FLOOR PROTECTOR*
G
H
I
J
M
N
CANADA USA
8’’ (205 mm) – Note 1 N/A (Canada only)
8’’ (205 mm) N/A (Canada only)
18’’ (460 mm)
From door opening
16’’ (410 mm)
From door opening
N/A (USA only) 8’’ (205 mm)
8’’ (205 mm) N/A (Canada only)
N/A (USA only) Note 2
*Steel with a minimum thickness of 0.015’’ (0.38 mm) or ceramic tiles sealed together with grout. No
protection is required if the unit is installed on a non-combustible floor (ex: concrete).
Note 1 : The floor protection at the back of the stove is limited to the stove’s required clearance if
such clearance is smaller than 8 inches (205 mm).
Note 2 : Only required under the horizontal section of the connector. Must exceed each side of the
connector by at least 2 inches (51 mm).
Reduced clearances using shielding
You may decrease the clearances by installing heat radiation shields between the walls or the ceiling and the
stove. These heat radiation shields must be installed permanently, and can include sheet metal, a rigid noncombustible sheet or a masonry wall.
Clearances of not less than 1" (25 mm) and not more than 3" (76 mm) between the bottom of the shield and
the floor and not less than 3" (76 mm) between the top of the shield and the ceiling must be respected to
allow vertical air circulation behind the shield. The shield must extend 20" (500 mm) above the stove top
and 18" (450mm) to each side of the stove (see graphic 1).
Following the installation of such a heat radiation shield, the clearances mentioned on the stove certification
plate may be reduced as stated in the following table.
10
TYPE OF PROTECTION
Sheet metal, a minimum of 0,024" (0,61mm) spaced out at
least 1" (25mm) by non-combustible spacers (see graphic 2).
Ceramic tiles, or an equivalent non-combustible material on
fire-proof supports spaced out at least 1" (25 mm) by noncombustible spacers (see graphic 3).
Ceramic tiles, or an equivalent non-combustible material on
fire-proof supports with a minimum of 0,024" (0,61 mm) sheet
metal backing spaced out at least 1" (25 mm) by noncombustible spacers (see graphic 4)
Reducing Clearances With
Shielding
Sides and
Rear/Back
67% 50%
50% 33%
67% 50%
Top
Brick spaced out at least 1" (25 mm) by non-combustible
spacers (see graphic 5)
Brick with a minimum of 0,024" (0,61 mm) sheet metal
backing spaced out at least 1" (25 mm) by non-combustible
spacers (see graphic 6).
50% N/A
67% N/A
11
Graphic 1
A- Minimum clearance required between the appliance and an unshielded combustible ceiling.
B- 20 in. (500 mm) minimum;
C- 1 in. (25 mm) minimum;
D- Between 1 in. and 3 in. (25 mm and 75 mm);
E- 3 in.(75 mm) minimum;
F- 18 in. (457 mm) minimum.