Manufactured by : STOVE BUILDER INTERNATIONAL INC..
1700, Léon-Harmel, Québec (Québec) G1N 4R9
Tel : (418 ) 527-3060
Fax : (418 ) 527-4311
www.drolet.ca
READ AND KEEP THIS MANUAL FOR REFERENCE
45138A
INTRODUCTION
Stove Builder International, one of the most important wood stove and fireplace manufacturers in North
America, congratulates you on your purchase and wishes to help you get maximum satisfaction from your
wood stove. In the pages that follow, we will give you advice on wood heating and controlled combustion as
well as technical specifications regarding installation, operation and maintenance of the model you have
chosen.
The instructions pertaining to the installation of your wood stove in North America comply with ULC-S627
and UL-1482 standards.
Read this entire manual before you install and use your new stove. If this stove is not properly
installed, a house fire may result. To reduce the risk of fire, follow the installation instructions. Failure
to follow instructions may result in property damage, bodily injury, or even death.
Consult your municipal building department or fire officials about restrictions and installation
requirements in your area and the need to obtain a permit.
K
EEP THIS INSTRUCTIONS MANUAL FOR FUTURE REFERENCE
.
CAUTIONS:
•
HOT WHILE IN OPERATION
BURNS
•
DO NOT USE CHEMICALS OR FLUIDS TO IGNITE THE FIRE
•
DO NOT LEAVE THE STOVE UNATTENDED WHEN THE DOOR IS SLIGHTLY OPENED DURING IGNITION
•
DO NOT BURN WASTE, FLAMMABLE FLUID SUCH AS GASOLINE, NAPHTHA, OR MOTOR OIL
•
DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM
Wood is a renewable energy. It is also a very clean heat source when used with appliances that are
certified by the U.S. Environmental Protection Agency (EPA), a standard accepted in Canada as well.
EPA-certified wood stoves are different than conventional wood stoves. Burning with an EPA-certified wood
stove may therefore require that you modify some of your heating habits. To get the most satisfaction out of
your new wood-heating system, please make sure you go through the following check list.
The chimney is the engine that drives the wood-heating system. Use a chimney that is UL-listed, with
an inner diameter to match the stove’s outlet collar (6” for all Drolet wood stoves);
Try to run the chimney inside the building for as much length as you can. A tall and warm
chimney will produce a good draft;
Try to install your chimney straight up and avoid 90 degree turns in the flue pipe and offsets in the
chimney;
Make sure that the chimney is tall enough and its top is clear of obstacles so it can produce a stable
draft;
Use a chimney thermometer installed at a distance of approximately 18 inches on the flue pipe
above the stove. Flue gases should reach at least 350oF before you close the stove’s primary air
intake completely. Operate your unit within the comfort zone indicated on the thermometer;
To reduce the risk of smoke spillage into the room upon reloading your stove, leave the primary
air intake completely open for a few minutes. This will heat up the chimney and build up draft
before you open the stove door;
Maximize hot air circulation! Our wood stoves are designed to easily receive a variable speed
blower that will improve heat distribution in front of the stove;
Remember that wood stoves produce radiant heat. Since heat rises, the use of floor traps will
greatly improve the heat transfer to rooms upstairs;
Use a mobile home approved stove if you are going to install your wood-heating system in a
mobile home. A fresh air kit must be connected to the stove. Never install your wood stove in a
bedroom;
Burn only dry cordwood;
Make sure you have a good bed of red coals before you load your stove with logs exceeding 3
inches in diameter;
Read and keep you owner’s manual. It will provide you with tips on how to run a successful wood-
heating system.
5
SECTION 1.0 - INSTALLATION
When installed and operated as described in these instructions, the Sahara wood stove is suitable for use as a
freestanding wood stove in residential installations. The Sahara wood stove is not intended for installation in
a bedroom or a mobile home.
In Canada, the CSA B365 Installation Code for Solid Fuel Burning Appliances and Equipment and the CSA
C22.1 Canadian National Electrical Code are to be followed in the absence of local code requirements. In the
USA, the ANSI NFPA 70 National Electrical Code and NFPA 211 Standard for Chimneys, Fireplaces, Vents
and Solid Fuel-Burning Appliances are to be followed in the absence of local code requirements.
In addition to the national installation and/or local building codes, fire officials (or other authorities having
jurisdiction) should be contacted to determine what restrictions and installation requirements might apply
locally.
1.1 GENERAL INSTALLATION
CAUTION:
•
MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING THE
DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN HAZARDOUS CONDITIONS
CONSIDERED, THE MANUFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE
.
WHERE SUCH ACTION IS
.
• D
O NOT CONNECT THIS UNIT TO ANY AIR DISTRIBUTION SYSTEM
•
CRACKED AND BROKEN COMPONENTS
UNSAFE
• A
•
C
CODES FOR USE WITH SOLID FUEL, OR TO A LISTED FACTORY BUILT CHIMNEY SUITABLE FOR USE WITH SOLID FUEL
.
SOURCE OF FRESH AIR INTO THE ROOM OR SPACE HEATED SHALL BE PROVIDED WHEN REQUIRED
ONNECT THE STOVE ONLY TO A LINED MASONRY CHIMNEY CONFORMING TO NATIONAL AND LOCAL BUILDING
, e.g.
GLASS PANELS OR CERAMIC TILES, MAY RENDER THIS INSTALLATION
.
.
.
1.2 POSITIONING THE STOVE
It is very important to position the wood stove in an area that will favour the most efficient heat distribution
throughout the house. The stove should therefore be installed in the room where the most time is spent, and
in the most spacious room possible. Recall that wood stoves produce radiating heat, the heat we feel when we
are close to a wood stove. A wood stove also functions by convection, that is through the displacement of hot
air accelerated upwards and its replacement with cooler air at the floor level. The stove’s convection effect is
facilitated by the installation of a blower.
6
1.3 CLEARANCES
Clearances to any combustibles when measured directly from the floor protector to the ceiling must be a
minimum of 84" (2134 mm). Clearances to any combustibles when measured directly from the front of the
stove must be a minimum of 48" (1219 mm). The stove must also be placed so as to maintain the minimum
clearances to combustible walls specified for each type of connector used. See Table 1.3 below for all
clearance measures. Refer to Figure 1.3 for a diagram of each of the measures A through C.
Single walled connector
Unit:
To sidewall (A) 15" (381 mm) 15" (381 mm)
To back wall (B) 16" (406 mm) 10" (254 mm)
To corner (C) 9" (229 mm) 9" (229 mm)
Listed double walled
connector
TABLE 1.3 Clearances to combustible materials
FIGURE 1.3 Clearances to combustible materials
7
1.3.1 Reduced clearances using shielding
You may decrease the minimum clearances to combustible materials by installing heat radiation shields
between the walls or the ceiling and the stove. Those heat radiation shields must be installed permanently,
and must be made of a heat-resistant or heat-tolerant material. Consult the table below:
Reducing Clearances With
TYPE OF PROTECTION
Sides and
Rear/Back
Shielding
Top
Sheet metal, a minimum of 0,013" (0,33 mm) spaced out at
least 7/8" (21 mm) by non-combustible spacers.
Ceramic tiles, or an equivalent non-combustible material on
fire-proof supports spaced out at least 7/8" (21 mm) by noncombustible spacers.
Ceramic tiles, or an equivalent non-combustible material on
fire-proof supports with a minimum of 0,013" (0,33 mm)
sheet metal backing spaced out at least 7/8" (21 mm) by noncombustible spacers.
Brick spaced out at least 7/8" (21 mm) by non-combustible
spacers.
Brick with a minimum of 0,013" (0,33 mm) sheet metal
backing spaced out at least 7/8" (21 mm) by noncombustible spacers.
Source: CSA Standard B365-1991, Table 4, Page 27
67% 50%
50% 33%
67% 50%
50% N/A
67% N/A
8
1.4 FLOOR PROTECTOR
If the stove is to be installed on top of a combustible floor, it must be guarded by a non-combustible material
extending at least 18” (300mm) from the front and 8” (200mm) from the sides and the back of the firebox., as
shown in Figure 1.4 below.
Please note that a floor protection is required with the pedestal models for spark and ash shielding, but not for
limiting floor temperatures from the radiant heat of the stove. The stove was designed and safety tested so that
without any protection, the floor would not overheat.
Please refer to local building codes for suitable floor protection materials.
FRONT
18” (300 mm)
8” (200 mm)
SIDES
BACK
8” (200 mm)
FIGURE 1.4 Floor protector
C
AUTION
:
DO NOT INSTALL IN A BEDROOM
.
9
SECTION 2.0 CHIMNEY (FLUE SYSTEM)
2.1 DEFINITIONS
For clarity, the following definitions should be used with respect to these instructions:
• A chimney system consists of a connector off the top of the stove, and a chimney, which attaches to
the connector and terminates outside the house.
• A chimney can be a masonry chimney (of masonry construction with an inside liner), or a factory
built chimney.
• A factory built chimney can be a double walled chimney (two concentric pipes with insulation -
sometimes referred to as an insulated solid pack) or an air cooled chimney (three concentric pipes,
with insulation between the first and second pipes, and air between the second and third pipes).
• A single walled connector is a single pipe.
• A double walled connector has two concentric pipes, no insulation, and is an air cooled connector.
2.2 CHIMNEY
CAUTION:
• DO NOT fill any framed space around the factory-built chimney with insulation or any other material.
Insulation placed in this area could cause adjacent combustibles to overheat.
• Do not use makeshift compromises during installation as they may be safety hazards, and a fire could
result.
• Do not connect this unit to a chimney system serving another appliance.
• Do not cut rafters or ceiling joists without first consulting a building official to ensure structural
integrity is not compromised.
Your wood stove may be hooked up with a factory built or masonry chimney. If you are using a factory built
chimney, it must comply with UL103 (USA) or ULCS629 (Canada) standards. It must therefore be a 6”
(152mm) HT Type (2100°F) chimney. It is extremely important that it be installed according to the
manufacturer's specifications. The manufacturers’ installation instructions and specified clearances should
always be followed in accordance with local and national installation codes. In Canada the CSA B365 and the
CSA C22.1 installation codes are to be followed. In the USA the ANSI NFPA 70 and ANSI NFPA 211
installation codes are to be followed.
10
Loading...
+ 24 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.