DriSteem XT-10, XT-20, XT-100, XT-30, XT-150 Installation, Operation And Maintenance Manual

...
XT Series
Electrode Steam Humidifier
Installation, Operation,
and Maintenance Manual
Safety precautions
Read this manual before installing humidifier.
Leave manual with product owner.
DRI-STEEM technical support
800-328-4447
WARNING!
is product must be installed by qualied HVAC and electrical contractors and in compliance with local, state, and federal codes. Improper installation may cause property damage, severe personal injury, or death as a result of electric shock, burns, and/or re.
Page ii • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Table of contents
Installation
Specifications ........................................... 2
Dimensions ............................................ 3
Choosing a location .....................................4
Mounting the humidifier .................................5
Fill cup extension installation ............................. 7
Supply water and drain piping ............................8
Field wiring ...........................................11
Humidistat and transmitter placement ....................13
Wiring diagrams ....................................... 14
Dispersion ............................................20
General instructions
Selecting the dispersion assembly location .............20
Interconnecting piping requirements ..................21
Drip tee installation ................................24
Single Tube and Multiple Tube .......................25
Rapid-sorb
........................................29
XT Steam Blower
................................20
................................... 36
Operation
Principle of operation ..................................44
End-of-season drain ....................................45
Extended shutdown ....................................45
Safety functions ........................................45
Display panel operation .................................46
Operating modes ......................................47
Sequenced application ..................................54
Humidifier start-up ....................................54
System messages .......................................56
Maintenance
Maintenance procedures
................................58
Troubleshooting .......................................61
Replacement parts .....................................65
Two-year limited warranty .......................Back cover
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 1
Table 2-1: XT Series humidifier specifications
Installation: Specifications
Model
number kW
XT-10 3.4 10 4.5 16.2 14.0 12.2 7.0 5.6 9.4 8.1 4.1 3.2 27.6 12.5 29.8 13.5
XT-20 6.7 20 9.1 32.2* 27.9* 24.2 14.0 11.2 18.6 16.1 8.1 6.4 29.8 13.5 38.6 17.5
XT-30 10.1 30 13.6 —————28.0 24.3 12.1 9.7 43.0 19.5 70.5 32
XT-50 16.8 50 22.7 —————46.6 40.4 20.2 16.2 43.0 19.5 70.5 32
XT-75 25.1 75 34.0 ———————30.3 24.2 65.0 29.5 114.6 52
XT-100 33.5 100 45.4 ———————40.4 32.3 67.2 30.5 116.8 53
XT-150 50.3 150 68.0 ———————
XT-200 67.0 200 90.7 ———————
Maximum
steam capacity
lbs/hr kg/h 208V 240V 277V 480V 600V 208V 240V 480V 600V lbs kg lbs kg
Single-phase Three-phase
Current draw (amps)
2 ×
30.3**
2 ×
40.4**
2 ×
24.2**
2 ×
32.3**
Shipping
weight
137.8 62.5 242.5 110
142.2 64.5 246.9 112
Maximum operating
weight
Note:
* For these models, shipping weight = 43 lbs (19.5 kg) and maximum operating weight = 70.5 lbs (32 kg) ** Double units require two circuits.
Page 2 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Installation: Dimensions
Figure 3-1: Dimensions
Models XT-10, XT-20, XT-30, XT-50, XT-75, XT-100 Models XT-150, XT-200
Top view
1.8"
F
C
Front view
Bottom view
Water fill line connection
E
1.8"
K*
B
Drain
J
H
1.4" G
Table 3-1: Dimensions by model number
D
Dispersion outlet
A
4.5"
7.8"
17.4"
Electrical knockouts
4.3"
1.5"
1"
OM-7374
Top view
Front view
Bottom view
1.8"
1.8"
F
C
K*
B
Drain
Water fill line connection
J
H
1.4" 1.4"
D
E
Dispersion outlet
G
D
E
1.8"
A
Electrical knockouts
G
OM-7419
XT-10
Callout
A 14.5 368 17.4 442 18.9 480 38.9 988
B 22.9 581 24.9 632 26.9 683 26.9 683
C 8.4 213 11.7 297 14.3 363 14.3 363
D 10.0 254 12.8 325 14.4 366 14.4 366
E 5.5 140 6.9 175 7.3 185 7.3 185
F 4.0 102 5.8 147 6.8 173 6.8 173
G 5.5 140 6.9 175 7.3 185 7.3 185
H 4.0 102 5.8 147 6.8 173 6.8 173
J 4.0 102 7.5 191 8.8 224 8.8 224
K 32.9 836 34.9 886 36.9 937 36.9 937
Note:
* Dimension K includes 10" (254 mm) for a fill cup extension. A fill cup extension is a required component when the humidifier is connected to a Rapid-sorb or Ultra-sorb dispersion
assembly or when the maximum developed length of piping/hose from humidifier to dispersion assembly/blower is more than 20' (6 m).
** XT-20 models using 208V single-phase power or 240V single-phase power have dimensions equal to Models XT-30 and XT-50.
XT-20**
inches mm inches mm inches mm inches mm
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 3
XT-30 XT-50
XT-75
XT-100
XT-150 XT-200
Choosing a location
Important:
Install humidifier only in locations that meet the following temperature and relative humidity (RH) requirements:
Maximum ambient temperature: 104
Minimum ambient temperature: 41
Maximum ambient humidity: 80% RH (non-condensing)
Note:
To open the humidifier electrical access door, rotate the screw counter-clockwise ¼ turn. The door pivots toward the front of the unit from the bottom of the door. To close the electrical access door, position screw slot so that it is horizontal and then push the door shut. Make sure sides of painted door go outside stainless steel enclosure.
To open the humidifier steam cylinder access door, rotate the screw counter-clockwise ¼ turn, lift door out of position, and remove ground wire. Replace door in reverse order of these instructions.
Figure 4-1: Recommended minimum clearances
°F (40 °C)
°F (5 °C)
Choosing a location for the humidifier
When selecting a location for the humidifier, consider the following:
Proximity to duct
Install the humidifier near the air duct system where the
dispersion assembly will be located. The maximum recommended length for vapor hose connecting a single humidifier to a dispersion assembly is 10' (3 m). The maximum recommended developed length for tubing or pipe connecting a single humidifier to a dispersion assembly is 20' (6 m). See the dispersion section of this manual for more information about installing dispersion assemblies.
• Elevation of the installed dispersion assembly
The recommended installation location for the dispersion
assembly is at an elevation higher than the humidifier. However, if the dispersion assembly must be installed at an elevation lower than the humidifier, install a drip tee and drain as shown in Figure 24-1. Before installing a dispersion assembly or interconnecting piping, review all pitch requirements in the dispersion section of this manual.
Required clearances (see Figure 4-1)
Electrical connections
Electrical power supply connections are made at the bottom panel
corner of the electrical enclosure. The system wiring is inside the cover of the control cabinet. See the field wiring instructions starting on Page 11.
• Supply water and drain piping connections
Water supply piping connections are made on the bottom left
side of the unit. Drain piping connections are made at the bottom center of unit. See the field piping illustration and instructions starting on Page 8.
• Exterior wall insulation
Do not install the humidifier on an exterior wall unless that wall
is properly insulated.
Top: 16" (400 mm)
Side: 4" (100 mm)
Floor: 16" (400 mm)
Page 4 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Between units: 4" (100 mm)
Front: 36" (914 mm)
OM-7359
Choosing a location for the dispersion assembly and control devices
See Page 20 for recommended installation locations for the dispersion assembly. See Page 13 for recommended installation locations for control devices such as humidistats and transmitters.
Mounting the humidifier
Figure 5-1: Mounting keyhole locations by model number
Models XT-10, XT-20, XT-30, XT-50, XT-75, XT-100 Models XT-150, XT-200
A
WARNING!
Mount humidifier per the instructions in this manual and to a structurally stable surface. Improper mounting of humidifier may cause the humidifier to fall off the wall resulting in severe personal injury or death.
A
G
D
A
D
C
E
B
F
OM-7360
D
Table 5-1: Mounting dimensions
XT-10
XT-20*
inches mm inches mm inches mm inches mm
A 3.9 99 7.1 180 7.5 191 7.5 191
XT-30 XT-50
XT-75
XT-100
XT-150 XT-200
C
C
E
B
F
OM-7420
B 14 356 16.3 414 19.1 485 19.1 485
C 3.1 79 3.6 91 3.4 86 3.4 86
D 3 76 2.1 53 3.4 86 3.4 86
E 2.8 71 3 76 2.8 71 2.8 71
F 3.8 97 3.2 81 2.6 66 2.6 66
G 17.1 434
Note:
* XT-20 models using 208V single-phase power or 240V single-phase power have
dimensions equal to Models XT-30 and XT-50.
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 5
WARNING!
Mount humidifier per the instructions in this manual and to a structurally stable surface. Improper mounting of humidifier may cause the humidifier to fall off the wall resulting in severe personal injury or death.
Mounting the humidifier (continued)
Prepare humidifier for mounting
Unpack unit from shipping carton and remove steam cylinder door. Disconnect electrode and high water sensor connectors from steam cylinder. Pull pins from brackets that retain steam cylinder. Remove steam cylinder from drain valve body.
Mount humidifier
Mount the humidifier so that it is plumb. See Figures 8-1 and 9-1 for an installation overview.
When mounting on a wood stud wall (studs 16" [406 mm] on center), locate studs and attach spanner board so that each of the screws centers on a stud. Mark hole locations per Table 5-1 and predrill 1/8" (3 mm) diameter pilot holes. Secure cabinet to spanner board with screws provided.
When mounting on a metal stud wall, locate the studs (16" [406 mm] on center) and drill a ¼" (6 mm) hole through the studs and wall. Mount spanner board with ¼" (6 mm) bolts through the wall, studs, and a backing plate on the backside of the wall and secure with a nut and washer.
If 16" (406 mm) on-center studs are not available, mount spanner boards on the wall, spanning two studs. If two horizontal boards are used, locate one at the top of the cabinet for the mounting screws and the other board located 3.5" (89 mm) on center from the bottom of the cabinet.
For hollow block or poured concrete wall mounting, mark mounting holes per Table 5-1. Drill pilot holes sized for the proper concrete anchors. Secure cabinet in place using four screws.
Page 6 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Fill cup extension installation
Install fill cup extension kit (if applicable)
A fill cup extension kit is required with all Rapid-sorb and Ultra-sorb dispersion assemblies or when the maximum developed length of piping/hose from humidifier to dispersion assembly/ blower is more than 20' (6 m).
1. Remove hose clamps attached to fill cup extension bracket.
2. Remove Phillips screw near large opening on top enclosure and retain for use in Step 4.
3. Feed tubes through left rear opening on top of steam cylinder enclosure.
4. Mount bracket with screw from Step 2 (see Figure 7-1).
5. Slip smaller hose clamp (D18) from Step 1 over smaller diameter hose and slide open end of hose onto fill valve body connection. Tighten hose clamp.
6. Slip larger hose clamp (D21) from Step 1 over larger diameter hose (the one attached to cone bottom of fill cup) and slide open end of hose onto drain valve body connection. Tighten hose clamp.
7. Place overflow tube with elbow into hole of drain cup plate.
Replace steam cylinder
1. Slide steam cylinder (with warning label facing toward operator) into drain valve body while making sure side tabs engage brackets.
2. Reconnect electrode and high water sensor connectors to steam cylinder (refer to unit wiring diagram located in electrical enclosure).
Figure 7-1: Fill cup extension installation
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 7
OM-7385
Supply water and drain piping
Figure 8-1: Field piping overview for models XT-10, XT-20, XT-30, XT-50, XT-75, and XT-100
Steam vapor hose; may also use tubing or pipe. See Table 22-1 for maximum piping lengths. Tubing or pipe must be grounded.
Fill valve (with screen)
Continuous copper water supply line; water pressure must be between 25 psi and 80 psi (175 kPa and 550 kPa)
Shock arrester recommended to reduce water hammer, by installer
Adapter
Pitch 1/8”/ft (1%)
Inlet strainer, by installer
Supply valve, by installer
¾" (DN20) metallic drain piping. If piping run is over 10' (3 m) increase pipe to 1¼" (DN32).
Install plumb
towards drain
Spill funnel. Plumb to floor drain
Refer to governing codes for drain pipe size and maximum discharge water temperature. Offset humidifier from spill funnel to prevent flash steam from rising into the humidifier.
Hose and clamps
3/8" (DN10) O.D. copper; compression fitting on fill valve
1" (25 mm) air gap required
WARNING!
Drain piping surface may be hot. Touching or contact with hot pipe may cause severe personal injury.
Page 8 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
OM-7362
Supply water quality
XT Series humidifiers use normal tap water or softened water to generate humidification steam. Water conductivity must be within the range of 125 to 1250 μS/cm (which, in many cases, is roughly equivalent to 3.4 to 36.3 grains/gallon). Demineralized water cannot be used because it is not conductive. Do not use heated supply water because unheated supply water is required for drain water tempering.
Supply water and drain piping (continued)
Figure 9-1: Field piping overview for Models XT-150 and XT-200
Steam vapor hose; may also use tubing or pipe. See Table 22-1 for maximum piping lengths. Tubing or pipe must be grounded.
Adapter
Install plumb
Fill valve (with screen)
Continuous copper water supply line; water pressure must be between 25 psi and 80 psi (175 kPa and 550 kPa)
Shock arrester recommended to reduce water hammer, by installer
Inlet strainer, by installer
Supply valve, by installer
Pitch 1/8”/ft (1%)
towards drain
3/8" (DN10) O.D. copper; compression fitting on fill valve
Supply water piping
Use only copper for supply water piping—do not use rubber or plastic. A strainer is recommended to be installed in the supply piping before the fill valve. The fill valve connection size is a 3/8" (DN10) compression fitting. In cases where water hammer may be a possibility, consider installing a shock arrestor. Water pressure must be between 25 psi and 80 psi (175 kPa and 550 kPa).
¾" (DN20) metallic drain piping up to second drain connection, then increase pipe to 1¼" (DN32)
1" (25 mm) air gap required
Spill funnel. Plumb to floor drain
Refer to governing codes for drain pipe size and maximum discharge water temperature. Offset humidifier from spill funnel to prevent flash steam from rising into the humidifier.
Hose and clamps
OM-7362
Important: Thoroughly flush the
supply water piping to remove pipe residue and stagnant water before connecting piping to the humidifier. Pipe residue and stagnant water in the water supply piping can cause the humidifier to not reach required steam capacity.
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 9
Supply water and drain piping (continued)
Figure 10-1: Drain piping detail
Drain cup
Hose clamp (field supplied)
¾" (DN20) copper
Note:
* A D29 bolt hose clamp and black rubber hose
ship with each humidifier. These parts can also be ordered from DRI-STEEM. See the replacement parts section of this manual for part numbers.
D29 bolt hose clamp
Black rubber hose
Pitch 1/8”/ft (1%) towards drain
Open drain
1" (25 mm) air gap
OM-7379
Humidifier drain piping
Drain piping must be code-approved copper or steel rated for 212 °F (100 °C) minimum. The final connection size is ¾" (DN20) copper for the steam cylinder drain. Do not reduce this connection size.
See Figures 8-1 and 9-1 for typical installation dimensions and requirements.
If drainage by gravity is not possible, use a reservoir pump rated for 212 °F (100 °C) water.
A 10" (254 mm) piece of hose is provided to function as the flexible connection from the drain cup to the field installed drain plumbing. A D29 hose clamp is provided to secure the drain hose to the drain cup.
See Figure 10-1 for drain piping detail.
If the equivalent length of pipe from the humidifier drain to the plumbing system drain is more than 10' (3 m), increase the pipe size to 1¼" (DN32).
Page 10 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Field wiring
Humidifier field wiring
All wiring must be in accordance with all governing codes and with the unit wiring diagram. The unit wiring diagram is inside the electrical control cabinet. Power supply wiring must be rated for 105 °C.
When selecting a location for installing the humidifier, avoid areas close to sources of electromagnetic emissions such as power distribution transformers.
Do not loop power wiring.
Do not use aluminum wire.
Field wiring connections and requirements
Conduit knockouts are provided on the bottom of the electrical control cabinet. Control wiring knockouts are on the bottom front; power wiring knockouts are on the bottom rear.
CAUTION! Adding alternate conduit connections is not
recommended; however, if making holes and knockouts in the humidifier cabinet, protect all internal components from debris and vacuum out cabinet when finished. Failure to comply with this caution can damage sensitive electronic components and void the DRI-STEEM warranty.
WARNING!
Only qualified electrical personnel should perform field wiring installation procedures. Improper wiring or contact with energized circuits may cause property damage, severe personal injury, or death as a result of electric shock and/or fire.
d
Figure 11-1: Field wiring requirements
Power supply
Fused disconnect
Humidifier
Control component placement
Follow the guidelines on Page 13 for placing humidistats, transmitters, and airflow proving switches.
More on the next page ▶
OM-7363
Notes:
• Control wiring and power wiring must be run in dedicated or separate earthed metal conduit, cable trays, or trunking.
• Separate the line voltage wiring from low voltage control circuit wiring when routing electrical wiring inside the humidifier cabinet.
• Do not use chassis or safety grounds as current­carrying commons. Never use a safety ground as a conductor or neutral to return circuit current.
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 11
Field wiring (continued)
Proper wiring prevents electrical noise.
Electrical noise can produce undesirable effects on electronic control circuits, which affects controllability. Electrical noise is generated by electrical equipment such as inductive loads, electric motors, solenoid coils, welding machinery, or fluorescent light circuits. The electrical noise or interference generated from these sources (and the effect on controllers) is difficult to define, but the most common symptoms are erratic control or intermittent operational problems.
Important:
• For maximum EMC effectiveness, wire all humidity, high limit, and airflow controls using multicolored shielded/screened plenum-rated cable with a drain wire for the shield/screen. Connect the drain wire to the shield/screen ground terminal with wire less than 2" (50 mm) in length.
• Do not ground shield at the device end.
Below are field wiring connection instructions:
Connect to line power.
Refer to the wiring diagram or the data plate on the outside of the
cabinet for wire sizing amperage.
Connect to control signal wiring
from a humidistat, transmitter, or signal by others. See the control wiring diagrams on pages 14-19.
Connect remote signal wiring.
When wired to a remote signaling device, two relays indicate if there is a fault with draining, filling, or water level control functions of the humidifier, or if a required maintenance interval has been reached. See the control wiring diagrams on pages 14-19. To enable the remote signaling device, connect wiring to control terminals 9 (N.O.), 10 (N.C.), 11 (C) for Relay 1, and connect wiring to control terminals 26 (N.O.), 27 (N.C.), and 28 (C) for Relay 2.
Connect to the duct airflow proving switch and duct high limit humidistat wiring (recommended optional devices). If not used,
jumper H-H terminals unless on/off humidistat is installed.
WARNING!
DRI-STEEM strongly recommends installing a duct airflow proving switch and a duct high limit humidistat. These devices prevent the humidifier from making steam when there is no airflow in the duct or when the RH level in the duct is too high. Failure to install these devices can result in excessive moisture in the duct, which can cause bacteria and mold growth or dripping through the duct.
Grounding requirements
A safety grounding system that meets national, state, and local electrical codes is required. The ground connection must be made with solid metal to metal connections. Ground wire should be the same size as power wiring.
Control input wiring
XT Series humidifiers accept RH or demand signals from DRI-STEEM control components or from a signal by others. For wiring connection requirements, first determine which control scenario applies. Then, refer to the corresponding control input wiring diagram shown on the following pages, or located inside the accessory box.
Page 12 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Humidistat and transmitter placement
Humidistat and transmitter locations are critical
Humidistat or transmitter location has a significant impact on humidifier performance. In most cases, it is recommended that you do not interchange duct and room humidity devices. Room humidity devices are calibrated with zero or little airflow; whereas duct humidity devices require air passing across them. Recommended humidistat and transmitter locations (see Figure 13-1): A This is the ideal sensing location because this placement ensures the
best uniform mix of dry and moist air with stable temperature control.
B This location is acceptable, but the room environment may affect
controllability such as when the humidistat or transmitter is too close to air grilles, registers, or heat radiation from room lighting.
C This location is acceptable because it provides a good uniform
mixture of dry and moist air, but if an extended time lag exists between moisture generation and sensing, make sure the control contractor extends the sampling time.
D This location behind a wall or partition is acceptable for sampling
the entire room if the sensor is near an air exhaust return outlet. This location is also typical of humidistat or transmitter placement for sampling a critical area.
E These locations are not acceptable because they may not represent
actual overall conditions in the space.
F These locations are not acceptable. Do not place humidistats or
transmitters near windows, door passageways, or areas of stagnant airflow.
G This is the best location for a duct high limit humidistat or humidity
transmitter.
Figure 13-1: Recommended humidistat and transmitter locations
Outside air
Damper control
Relief air
Return air
A
C
Window
E
F
Doorway
(2.4 m to 3.7 m)
minimum
AHU
Wall or partition
D
B
EF
Window
8' to 12'
F
High limit humidistat or high limit transmitter (set at 90% RH maximum) for VAV applications
Airflow switch or differential pressure switch (sail type recommended for VAV applications)
G
Vapor absorption has taken place
Point of vapor absorption
Humidifier dispersion assembly
Turning vanes
DC-1084M
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 13
Wiring diagrams
Figure 14-1: Control wiring diagrams for humidity transmitter external connections to XT Series humidifiers
Page 14 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Wiring diagrams (continued)
Figure 15-1: Control wiring diagrams for humidistat external connections to XT Series humidifiers
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 15
Wiring diagrams (continued)
Figure 16-1: Control wiring diagrams for signal by others external connections to XT Series humidifiers
Page 16 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Wiring diagrams (continued)
Figure 17-1: Wiring diagram for sequenced XT Series humidifiers with a modulating duct humidistat
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 17
Wiring diagrams (continued)
Figure 18-1: Wiring diagram for sequenced XT Series humidifiers with a modulating room humidistat
Page 18 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Wiring diagrams (continued)
Figure 19-1: Wiring diagram for sequenced XT Series humidifiers with a modulating 0-10 VDC signal by others
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 19
Dispersion: General instructions
Where to find more dispersion information
In this document:
• Interconnecting piping and drip tee installation, pages 21-24
• Single Tube and Multiple Tube installation instructions, pages 25-28
• Rapid-sorb pages 29-35
• XT Steam Blowers, pages 36-43
On our web site:
The following documents can be viewed, printed or ordered from our web site,
www.dristeem.com
• Catalogs (which include dispersion nonwetting distance graphs):
– XT Series Humidifier – Ultra-sorb
• Installation, Operation, and Maintenance manuals:
– Ultra-sorb
DRI-STEEM Design Guide
• loss tables and general humidification information)
On Dri-calc:
Dri-calc sizing and selection software, and may be ordered at our web site, www.dristeem.com. Included in Dri-calc:
®
installation instructions,
®
(includes steam
®
is our humidification system
Selecting the dispersion assembly location
• For each dispersion device, DRI-STEEM documents distances required for absorption to occur. If you have questions about absorption distances, see the absorption tables in the XT Series catalog, available for viewing, printing or ordering at www.dristeem.com
• It is important that the dispersion assembly be positioned where the water vapor being discharged is carried off with the airstream and is absorbed before it can cause condensation or dripping in the duct.
• In general, the dispersion assembly is best placed where the air can most readily absorb the moisture being added without causing condensation at or after the unit. This normally will be after the heating coil or where the air temperature is highest.
• Place the dispersion assembly such that absorption will occur before the intake of a high efficiency filter. The filter can remove the visible moisture and become waterlogged.
• Place the dispersion assembly such that absorption will occur before coming in contact with any metal surface.
• Place the dispersion assembly such that absorption will occur before fire or smoke detection devices.
• Place the dispersion assembly such that absorption will occur before a split in the duct. Otherwise, the dispersion assembly may direct more moisture into one duct than the other.
• When draining dispersion condensate to an open drain, provide a 1" (25 mm) gap between the condensate drain piping and the drain. Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam, or condensing on nearby surfaces may occur.
• A comprehensive library of installation guide documents, including:
– Rapid-sorb installation instructions for vertical airflows – Recommended dispersion placement within a duct or air handler
Or call us at 800-328-4447
While obtaining documents from our web site or from Dri-calc is the quickest way to review our literature, we'd also be happy to mail to you any literature you need.
Page 20 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
IMPORTANT:
Failure to follow the recommendations in this section can result in excessive back pressures on the humidifier. This will result in unacceptable humidification system performance such as water siphoning from the steam cylinder, blown water seals, erratic water level control, and spitting condensate from the dispersion tube(s).
Loading...
+ 50 hidden pages