DriSteem HUMIDI-TECH, HUMIDI-TECH DI, VM-2, VM-4, VM-6 Installation, Operation And Maintenance Manual

...
READ AND SAVE THESE INSTRUCTIONS
HUMIDI-TECH and
HUMIDI-TECH DI
ELECTRIC STEAM HUMIDIFIERS
Installation, Operation
and
Maintenance Manual
2
TABLE OF CONTENTS
To the purchaser and installer
Thank you for purchasing our HUMIDI-TECH® humidifier. We have designed and built this equipment to give you complete satisfaction and trouble-free service for many years. Familiarizing yourself with this manual will help ensure proper operation of the equipment for years to come.
This manual covers the installation and maintenance procedures for both the HUMIDI-TECH and HUMIDI-TECH DI humidifiers.
DRI-STEEM Humidifier Company
General information
Product overview ................................................................. 3
Dimensions .......................................................................... 4
Electrical specifications, capacities and weights ................. 5
Installation
Locating and mounting the humidifier .................................. 6
Piping ................................................................................... 6
Wiring .................................................................................. 9
Dispersion
Using space distribution units (SDU-E and SDU-I) ..... 11
Using dispersion tubes ................................................ 14
Using a RAPID-SORB® dispersion assembly ............. 16
Drip tee installation ...................................................... 17
Interconnecting piping tables ....................................... 18
Operation
Start-up procedures ........................................................... 19
Control ............................................................................... 20
Maintenance
Maintenance procedures ................................................... 21
Troubleshooting guide ....................................................... 24
Replacement parts............................................................. 26
Warranty ........................................................................... 32
3
HUMIDI-TECH® HUMIDIFIER OVERVIEW
Deionized water models (HUMIDI-TECH DI)
The HUMIDI-TECH DI, shown here, is specifically designed for use with deionized or reverse osmosis water.
Standard water models (HUMIDI-TECH)
The standard water HUMIDI-TECH unit requires water conductivity of at least 100 µS/cm to operate. It will not operate with water treated by reverse osmosis or deionization processes (see DI water model below).
OM-82-4
Removable evaporating chamber
Slide assembly under evaporating chamber provides easy removal for cleaning
INCOLOY alloy-sheathed immersion heaters
Keyholes for wall mounting
Water fill DN10 (3/8") (female)
DN40 or DN50 flexible vapor hose, pipe or tubing connects to dispersion tube(s) or to an SDU
Condensate return line
Duct
Electrical area
Electrical conduit knockouts
DN20 (¾") threaded skimmer port and overflow drain
Water fill access hole
Condensate return line
Electrical area
Removable evaporating chamber
INCOLOY alloy-sheathed immersion heaters
Duct
Electrical conduit knockouts
Slide assembly under evaporating chamber provides easy removal for cleaning
Water fill access hole
Keyholes for wall mounting
Water fill DN10 (3/8") (female)
Float cutoff switch
OM-82-5
Ball valve
DN20 (¾") threaded skimmer port and overflow drain
DN40 or DN50 flexible vapor hose, pipe or tubing connects to dispersion tube(s) or to an SDU
4
HUMIDI-TECH® DIMENSIONS
50 mm
409 mm
57 mm
472 mm
146 mm
38 mm
Venting
DN20 (¾") tank drain
DN20 (¾") frame drain
57 mm
DC-1167
13 mm hole in base for water fill line
Power wire knockout
Steam outlet
276 mm
57 mm
Top view
614 mm
Power wiring knockout
Left side view
Front view
614 mm
16 mm
19 mm
38 mm
146 mm
Bottom view
Control wiring knockout
50 mm
25 mm
Control or SDU wiring knockout
5
HUMIDI-TECH® SPECIFICATIONS
Electrical specifications, capacities and weights
Table notes:
All HUMIDI-TECHs operate at 50/60 Hz.
* For wire sizing, the highest leg draw is shown
due to current imbalance.
** SDU-E is not an available option for these
HUMIDI-TECH models if using SSR control.
*** Models with SDU or SSR options have
additional electronic components housed within the HUMIDI-TECH cabinet. Therefore, if adding an SDU or SSR, add the following to the HUMIDI-TECH shipping and operating weights:
– SDU-I: 5.5 kg – SDU-E: 4 kg – SSR control: 1 kg
Model
number
kW
Single-phase 230 V Three-phase 400 V
Shipping
weight
kg***
Operating
weight
kg***
Steam
capacity kg/h
I max. A
Steam
capacity kg/h
I max. A
VM-2 2 2.5 8.0 2.7 -- 36 43
VM-4 4 5.0 16.0 5.4 8.7* 36 43
VM-6 6 7.5 24.0 8.2 13.0* 40 55
VM-8 8 10.0 31.9 10.9 17.3* 40 55
VM-10 10 12.5 39.9 13.6 15.2* 42 63
VM-12 12 15.0 47.9 16.3 17.3 42 63
VM-14 14 17.5 -- 19.1 20.2 42 63
VM-16 16 20.0 -- 21.8 23.1** 42 63
VM-21 21 26.3 -- 28.6 30.3** 43 69
VM-25 25 31.3 -- 34.0 36.1** 43 69
VM-30 30 37.6 -- 40.8 43.3** 46 71
VM-34 34 42.6 -- 46.3 49.1** 46 71
Notes about SDUs (Space Distribution Units):
 The SDU-I is available for models VM-2 through
VM-10.
• The SDU-E is available for all HUMIDI-TECH models except Models VM-16 through VM-34 using three-phase 400V power with the SSR control option.
 SDUs ship separately from the HUMIDI-TECH.
SDU weights
SDU
model
Shipping weight
Operating weight
kg kg
SDU-I 31 26
SDU-E 28 23
6
HUMIDI-TECH piping
Water makeup piping may be of any code­approved material (copper, steel, or plastic). The final connection size is DN10 (3/8"). In cases where water hammer may be a possibility, a shock arrestor should be considered. Water pressure must be between 175 kPa and 550 kPa.
Drain piping may be of any code-approved material (copper, steel, or plastic rated for 100 °C minimum). If drainage by gravity is not possible, use a small lift pump (DRI-STEEM Part No. 400281).
The final connection size is DN20 (3/4") for tank and frame drains. This connection size should not be reduced. (See figures on the following pages for proper drain piping configurations.) The tank drain should be piped separately from the frame drain, as shown, to prevent backflow of drain water into the humidifier cabinet.
Install a union in the water supply line as shown in the drawings on the next two pages to allow tank removal.
Locating and mounting the humidifier
The HUMIDI-TECH humidifier is designed to attach to the wall with coach screws, and it should be installed in a space located near an air duct system.
Consider the following when selecting the location of the humidifier:
• Convenient access to duct
• Electrical and plumbing connections
• Required clearances
• External water seal requirements
Electrical power supply, water makeup piping and drain piping must also be considered. Electrical power supply connections are made at the lower or upper right rear corner of the unit. Water makeup and drain piping connections are made at the lower left rear corner.
When mounting on a stud wall (studs with 406 mm centres), locate studs and position coach screws in place so that each of the screws (406 mm apart) will center on a stud. Mark hole locations and predrill 6 mm diameter pilot holes using mounting template on the HUMIDI-TECH box. Secure frame to wall with coach screws provided.
For hollow block or poured concrete wall mounting, position template in place and mark the holes. Drill appropriate pilot hole for two 10 mm toggle bolts or two 10 mm machine bolt lead anchors. Secure frame in place.
HUMIDI-TECH® MOUNTING AND PIPING
Clearance recommendations
For recommended service and maintenance purposes, maintain the following clearances:
Top: 460 mm
Floor: 610 mm
Supporting wall
Left side: 305 mm
DC-1201
Right side electrical controls: 915 mm
Front: 915 mm
Secured to supporting wall
To dispersion unit
7
HUMIDI-TECH® PIPING
Notes:
• Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet.
• Dashed lines indicate provided by installer.
• The water supply inlet is more than 25 mm above the skim/overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required, however, governing codes prevail.
• Install a union in the water supply line as shown to allow tank removal.
Shock arrester recommended to reduce water hammer
DN10 (3/8") connection to water supply line; water pressure must be between 175 kPa and 550 kPa; water conductivity minimum 100 µS/cm
Water supply line
Spill funnel. Plumb to floor drain
25 mm air gap
DN20 (¾") tank drain, skimmer and P-trap piping, rated for 100 °C. If piping run is over 3 m increase pipe to DN32 after P-trap.
Open floor drain. Refer to governing codes for drain pipe size and maximum temperature requirements.
Cover
Electrical conduit knockouts provided top and bottom:
• Combination, with knockout diameters of 22.3 mm and
28.6 mm
• Combination, with knockout diameters of 28.6 mm and
34.9 mm
Install level
Steam vapor hose (maximum run 3 m). May also use pipe or tubing.
DC-1136
DN20 (¾") frame drain and P-trap piping, rated for 100 °C
Two keyholes for wall mounting, 406 mm on center
300 mm
50 mm
HUMIDI-TECH (standard water) field piping overview
Frame drain
Unions by installer
8
HUMIDI-TECH® PIPING
HUMIDI-TECH DI (deionized/reverse osmosis water) field piping overview
DN10 (3/8") connection to water supply line; water pressure must be between 175 kPa and 550 kPa; water chloride content must be less than 3 ppm; first 1 m of supply line must be rated for 100 °C
Water supply line
Spill funnel. Plumb to floor drain
25 mm air gap
DN20 (¾") tank drain and P-trap piping, rated for 100 °C; if piping run is over 3 m increase pipe to DN32 after P-trap
Open floor
drain. Refer to
governing codes for drain
pipe size and maximum
temperature requirements.
Cover
Electrical conduit knockouts provided top and bottom:
• Combination, with knockout diameters of 22.3 mm and
28.6 mm
• Combination, with knockout diameters of 28.6 mm and
34.9 mm
Install level
DC-1139
DN20 (¾") frame drain and P-trap piping, rated for 100 °C
Two keyholes for wall mounting, 406 mm on center
300 mm
50 mm
Frame drain
Strainer, by installer
If water piping to humidifier is non-metallic, we recommend a 50 mm water seal in the supply line to isolate steam during DI/RO water system maintenance
Notes:
• Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet.
• Dashed lines indicate provided by installer.
• The water supply inlet is more than 25 mm above the overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required, however, governing codes prevail.
• Install a union in the water supply line as shown to allow tank removal.
Unions by installer
Steam vapor hose (maximum run 3 m). May also use pipe or tubing.
9
HUMIDI-TECH wiring
All wiring must be in accordance with all governing codes, and with the HUMIDI-TECH® or HUMIDI-TECH DI wiring diagrams. The diagrams are located inside the removable subpanel cover on the right-hand side of the humidifier cabinet. Power supply wiring must be rated for 105 °C.
Refer to the maximum load (I max. A) on the rating plate, and use the tables on the following page to determine the appropriate wire, conduit and fused disconnect requirements.
When selecting a location for installing the HUMIDI-TECH, avoid areas close to sources of electromagnetic emissions such as power distribution transformers.
Grounding requirements
The earth must be made by solid metal to metal connections. The ground must be a good radio frequency earth. Ground wire should be same size as power wiring.
Shielded/screened cable drain wire connection to lug
Note: For maximum E.M.C. effectiveness, all humidity, temperature, and airflow controls should be wired
using multicolored shielded/screened plenum-rated cable with a drain wire for the shield/screen. The drain wire should be connected to the shield/screen ground terminal with its length kept to less than 50 mm.
Shield/screen ground lug
Microprocessor board
VAPOR-LOGIC
3
keypad on front of cabinet
OM-1505
HUMIDI-TECH® WIRING
Field wiring requirements
Note: Control wiring and power wiring must be run in
dedicated or separate earthed metal conduit, cable trays or trunking.
OM-1007
Fused disconnect (provided by installer) sized per tables on next page
Power supply (provided by installer) cable sized per tables on next page
0.6 m to 1.9 m,
1.7 m recommended
Right side view of HUMIDI-TECH
10
Fuse/breaker requirements
Note:
Semiconductor fusing is recommended with the SSR option.
230 Volt single phase
A
Wire size
mm
2
Groun d wire size
mm
2
0 - 18 2.5 2.5
18.1 - 24 4 4
24.1 - 30.7 6 6
30.8 - 42.7 10 10
42.8 - 57 16 16
57.1 - 75.7 25 16
75.8 - 93.7 35 16
93.8 - 113.2 50 25
113.3 - 144 70 35
144.1 - 174 95 50
174.1 - 201.7 120 70
400 Volt three phase
I max. A Breaker size
0 - 8.0 10
8.1 - 10.4 13
10.5 - 12.8 16
12.9 - 16 20
16.1 - 20 25
20.1 - 25.6 32
25.7 - 32 40
32.1 - 40 50
40.1 - 50.4 63
50.5 - 64 80
64.1 - 80 100
80.1 - 100 125
100.1 - 128 160
128.1 - 160 200
A
Wire size
mm
2
Ground wire size
mm
2
0 - 15.7 2.5 2.5
15.8 - 21 4 4
21.1 - 27 6 6
27.1 - 37.5 10 10
37.6 - 51 16 16
51.1 - 66.7 25 16
66.8 - 82.5 35 16
82.6 - 100.5 50 25
100.6 - 128.2 70 35
128.3 - 155.2 95 50
155.3 - 179.2 120 70
HUMIDI-TECH® WIRING
11
HUMIDI-TECH® DISPERSION
SDU field wiring
The SDU can be mounted directly above the HUMIDI-TECH.
OM-55-1
Air intake vents
Steam outlet
OM-56-1
The SDU can be mounted remotely from the HUMIDI-TECH.
SDU-E
Field wiring for fan and airflow proving switch
HUMIDI-TECH
Electrical panel right side view
vmsbpnlasm-11-a-o&m
SDU-I: Provides instant, internal absorption
The Space Distribution Unit Internal Absorption (SDU-I) disperses humidity with no visible vapor trail or wetness, making the HUMIDI-TECH® with an SDU-I ideal for use in finished spaces. When room RH is 45% or less, the SDU-I fan mixes room air and steam to ensure complete absorption before discharge as humidified air. The SDU-I is available for models VM-2 through VM-10.
SDU-E: For higher capacity units
The Space Distribution Unit External Absorption (SDU-E) is designed for higher capacity dispersion. The SDU-E is available for all HUMIDI-TECH models except Models VM-16 through VM-34 using three-phase 400 V power with the SSR control option.
Mounting the SDU-I and SDU-E
Both SDUs may be mounted on a wall directly above the HUMIDI-TECH cabinet or mounted on a wall remote from the HUMIDI-TECH. Use the mounting template on the box for correct placement. Two coach screws are provided with each fan unit.
Note: See the following pages for more information about SDU-I and SDU-E.
12
HUMIDI-TECH® DISPERSION
Installing Space Distribution Units (SDUs)
Provide at least 150 mm clearance on each side of the SDU.
Field wiring is required to connect the SDU fan and airflow proving switch terminals to the respective HUMIDI-TECH electrical panel terminals. Refer to the external connections diagram in the package shipped with your unit.
A HUMIDI-TECH with an SDU is a class-one-rated assembly. It has been tested and is in compliance with the requirements to be mounted in areas accessible to the general public.
When performing HUMIDI-TECH maintenance
If the SDU-E or SDU-I is installed immediately above the HUMIDI-TECH, disconnect both hose clamps on the steam hose, grip the hose and rotate it to break it loose from the tubing, and then slide the hose up onto the SDU steam tube until sufficient clearance is provided to move the tank.
SDU-E mechanical detail
DC-1078
57 mm
DN40 or DN50 steam inlet
614 mm
Steam outlet
472 mm
276 mm
57 mm
Front view
Side view
DN40 steam inlet
472 mm
614 mm
Air intake grille
Humidified air discharge grille
276 mm
SDU-I mechanical detail
Front view
Side view
DC-1076
409 mm
DN40 or DN50 steam inlet
409 mm
Note: Maximum ambient RH must not exceed 45% for the SDU-I to operate properly.
13
HUMIDI-TECH® DISPERSION
SDU-E: Rise, throw and spread
SDU-E minimum non-wetting distances in meters
Table notes:
Rise: Minimum non-wetting height above the steam outlet of the SDU-E Throw: Minimum non-wetting horizontal distance from the steam outlet of the SDU-E. Spread: Minimum non-wetting width from the steam outlet of the SDU-E.
Model
40% RH@ 21°C 50% RH@ 21°C 60% RH@ 21°C
Rise Throw Spread Rise Throw Spread Rise Throw Spread
VM-2 0.30 1.5 0.30 0.50 2.0 0.50 0.80 2.3 0.80
VM-4 0.30 1.5 0.30 0.50 2.0 0.50 0.80 2.3 0.80
VM-6 0.30 1.5 0.30 0.50 2.0 0.50 0.80 2.3 0.80
VM-8 0.30 1.7 0.30 0.50 2.0 0.50 0.80 2.3 0.80
VM-10 0.50 1.8 0.50 0.60 2.1 0.60 1.0 2.5 1.0
VM-12 0.50 1.8 0.50 0.60 2.1 0.60 1.0 2.5 1.0
VM-14 0.60 2.1 0.60 0.60 2.1 0.60 1.0 2.7 1.0
VM-16 0.60 2.1 0.60 0.60 2.1 0.60 1.0 2.7 1.0
VM-21 0.60 2.3 0.60 0.80 3.0 0.80 1.0 3.7 1.0
VM-25 0.60 2.5 0.60 0.80 3.2 0.80 1.1 3.8 1.1
VM-30 0.60 2.5 0.60 0.80 3.2 0.80 1.1 3.8 1.1
VM-34 0.60 2.5 0.60 0.80 3.2 0.80 1.1 3.8 1.1
Steam outlet
Air intake grille
Rise
Spread
Throw
DC-1027
As steam is discharged from the SDU-E, it quickly cools and turns to a visible fog that is lighter than air. As this fog is carried away from the SDU-E by the airstream, it tends to rise toward the ceiling. If this fog contacts solid surfaces (columns, beams, ceiling, pipes, etc.) before it disappears, it could collect and drip as water. The greater the space relative humidity, the more the fog will rise, throw and spread.
The table below lists the minimum rise, throw and spread non-wetting distances for SDU-E area-type humidifiers at 40%, 50% and 60% RH in the space. Surfaces cooler than ambient temperature, or objects located within this minimum dimension, may cause condensation and dripping. To avoid steam impingement on surrounding areas, observe the minimum non-wetting distances in the table below.
The SDU-E contains a 926 m3/h blower and an airflow proving switch field-wired to the HUMIDI-TECH humidifier electrical panel. A wiring diagram of the SDU-E is included with the unit.
On a call for humidity, the humidifier begins producing steam and the start relay energizes the SDU-E blower. When the call for humidity is satisfied, the VAPOR-LOGIC
® 3
microprocessor keeps the blower running to disperse residual moisture using a time-delay.
14
Notes:
• Use DRI-STEEM's hard pipe adapter kit to connect the steam outlet to hard pipe. Use a hose clamp to connect the steam outlet to vapor hose. Use a hose cuff and clamps to connect the steam outlet to tubing.
• Thin-walled tubing heats up faster than heavy­walled pipe causing less steam loss at start-up.
• Hard pipe or tubing diameter must match HUMIDI-TECH steam outlet size (DN40 or DN50).
• See the Maximum Steam Carrying Capacity and Steam Loss tables on Page 18.
• Maximum capacity of dispersion tube (without condensate drain): – DN40: 13 kg/h – DN50: 25.8 kg/h
• Orient dispersion tube so that tubelets (steam orifices) point up.
• When mounting the humidifier above the level of dispersion tube, see the drawing on Page 17.
• Failure to follow the recommendations on this page may result in excessive back pressures on the humidifier. This may lead to dispersion tube(s) spitting, steam blowing through water seals, or leaking gaskets.
• The table at right shows hose kit sizes by humidi­fier model. A hose kit includes vapor hose, a dispersion tube and hardware. Note that the capacities of models VM-30 and VM-34 require multiple tube assemblies and therefore cannot use a hose kit. For multiple tube assemblies, see information on RAPID-SORB on Page 16.
HUMIDI-TECH® DISPERSION
Humdifier
models
Hose kit
(vapor hose, dispersion
tube and hardware)
Maximum
capacity of
dispersion tube
(kg/hr)
VM 2-8
1½" (DN40) hose kit
wi thout dra in
13
VM 10-16
1½" (DN40) hose kit
with drain
25.8
2" (DN50) hose kit
wi thout dra in
25.8
VM 21-25
2" (DN50) hose kit
with drain
38.6
VM 30-34
These models require multiple tube
assemblies and cannot use a hose kit.
Hose kit sizing by model
Single tube without condensate drain
DC-1447
Duct
Single dispersion tube without condensate drain
HUMIDI-TECH humidifier
Secure and seal escutcheon plates
Mounting nut M10
Tube pitch: 15%
Pitch: 1%
See the first note below.
90° long sweep or two 45° elbows
Interconnecting plumbing may be hose, tubing or hard pipe. Insulate tubing and hard pipe to reduce steam loss.
Dispersion tube escutcheon plate
82.5 mm
82.5 mm
OM-351-1
15
HUMIDI-TECH® DISPERSION
Notes:
• Use DRI-STEEM's hard pipe adapter kit to connect the steam outlet to hard pipe. Use a hose clamp to connect the steam outlet to vapor hose. Use a hose cuff and clamps to connect the steam outlet to tubing.
• Thin-walled tubing heats up faster than heavy-walled pipe causing less steam loss at start-up.
• Hard pipe or tubing diameter must match HUMIDI-TECH steam outlet size (DN40 or DN50).
• See the Maximum Steam Carrying Capacity and Steam Loss tables on Page 18.
• Maximum capacity of dispersion tube with condensate drain: – DN40: 25.8 kg/h – DN50: 38.6 kg/h
• Orient dispersion tube so that tubelets (steam orifices) point up.
• The dispersion tube must be pitched a minimum of 1% toward the drain when using a condensate drain. Condensate drain tubing must be pitched a minimum of 2% toward the escutcheon plate. Condensate drain is not provided when steam flow is 15 kg/h or less.
• When mounting the humidifier above the level of dispersion tube, see the drawing on Page 17.
• Failure to follow the recommendations on this page may result in excessive back pressures on the humidifier. This may lead to dispersion tube(s) spitting, steam blowing through water seals, or leaking gaskets.
• See the Hose Kit Sizing table on the previous page.
Mounting nut M10
Pitch tube toward drain 1%
Single dispersion tube with condensate drain
DC-1449
Duct
Interconnecting plumbing may be hose, tubing or hard pipe. Insulate tubing and hard pipe to reduce steam loss.
HUMIDI-TECH humidifier
Secure and seal escutcheon plates
DN15 (½" O.D.) condensate drain tube. Pitch 2% toward escutcheon plate.
DN8 (1/4" thread)
DN20 (minimum) condensate drain tube by installer. Must be suitable for 100 °C water.
Open drain. Refer to governing codes for drain pipe size and maximum temperature requirements.
25 mm air gap
Water seal
125 mm
150 mm
recommended
Pitch: 1%
Single tube with condensate drain
90° long sweep or two 45° elbows
See the first note below.
Pitch: 2%
Pitch: 1%
Escutcheon plates:
Dispersion tube Condensate drain
82.5 mm
82.5 mm
82.5 mm
82.5 mm
OM-351-1
16
HUMIDI-TECH® DISPERSION
RAPID-SORB dispersion assembly
Condensate drain DN20 (3/4" thread)
Notes:
• Use DRI-STEEM's hard pipe adapter kit to connect the steam outlet to hard pipe. Use a hose clamp to connect the steam outlet to vapor hose. Use a hose cuff and clamps to connect the steam outlet to tubing.
• Thin-walled tubing heats up faster than heavy-walled pipe causing less steam loss at start-up.
• Hard pipe or tubing diameter must match HUMIDI-TECH steam outlet size (DN40 or DN50).
• See the Maximum Steam Carrying Capacity and Steam Loss tables on Page 18.
• Position dispersion tubes perpendicular to horizontal airflow.
• Pitch header toward condensate drain.
• Make sure header and tubes are square in the duct, slanting only to allow the pitch of the header.
• Secure header at both ends.
• Dashed lines indicate provided by installer.
• Dispersion tube sizes: – DN40 – DN50
• When mounting the humidifier above the level of the RAPID-SORB, see the drawing on Page 17.
• Failure to follow the recommendations on this page may result in excessive back pressures on the humidifier. This may lead to dispersion tube(s) spitting, steam blowing through water seals, or leaking gaskets.
DC-1448
Duct
Stainless steel support by DRI-STEEM
HUMIDI-TECH humidifier
Header pitch: 1% minimum
DN20 copper
Open drain. Refer to governing codes for drain pipe size and maximum temperature requirements.
25 mm air gap
125 mm minimum
150 mm recommended
Airflow
Dispersion tube
Point tubelets perpendicular to airflow
Slip coupling or hose cuff
Support bracket that has 11 mm mounting holes at top, bottom and end
Pitch: 1%
Position L-bracket so that flange is upstream of dispersion tubes. Drawing shows L-bracket positioned for airflow back to front.
Secure and seal escutcheon plates
Interconnecting plumbing may be hose, tubing or hard pipe. Insulate tubing and hard pipe to reduce steam loss.
90° long sweep or two 45° elbows
See the first note below.
82.5 mm
82.5 mm
OM-351-1
Dispersion tube escutcheon plate
17
HUMIDI-TECH® DISPERSION
Drip tee installation
Install a drip tee as shown below when the humidifier is mounted higher than the dispersion device, when interconnecting hose or piping needs to go over an obstruction, or when interconnecting piping runs are long. IMPORTANT: Vapor hose must be supported to prevent sagging or low spots.
Obstruction
Pitch: 1%
HUMIDI-TECH
humidifier
Tubing or pipe drip tee, by installer. DRI-STEEM part numbers for 304 stainless steel inline tees:
• 1½" (DN40): No. 162710
• 2" (DN50): No. 162712
Funnel or floor drain. Refer to governing codes for drain pipe size and maximum temperature requirements.
25 mm air gap
200 mm minimum
150 mm recommended
To dispersion device
DC-1450
Dashed lines indicate provided by installer.
DN20
90° long sweep or two 45° elbows
Insulate tubing and hard pipe to reduce steam loss
18
HUMIDI-TECH® DISPERSION
Steam loss of interconnecting vapor hose, tubing and pipe
Notes:
This data is based on an ambient air temperature of 27 °C, fiberglass insulation, copper tubing, and Schedule 40 pipe.
Maximum steam carrying capacity and length of interconnecting vapor hose, tubing and pipe*
Notes:
* Based on total maximum pressure drop in hose, tubing or piping of 1250 Pa
** Maximum recommended length for vapor hose is 3 m. Longer distances may cause kinking or low spots.
*** To minimize loss of capacity and efficiency, insulate tubing and piping.
Developed length equals measured length plus 50% of measured length, to account for pipe fittings.
Vapor hose
Copper or stainless steel tubing
and Schedule 40 steel pipe
Hose I.D.
(DN)
Maximum
capacity
(kg/h)
Maximum
length**
(m)
Tube
or pipe
size***
(DN)
Maximum
capacity
(kg/h)
Maximum
developed
length
(m)
40 68 3 40 68 6.1
50 113 3 50 100 9.2
Description
Nominal hose, tubing
or pipe size
Steam loss Insulation thickness
Noninsulated Insulated
DN kg/h/m kg/h/m mm
Hose
40 0.220 N/A N/A
50 0.300 N/A N/A
Tubing
40 0.164 0.030 50
50 0.210 0.037 50
Pipe
40 0.330 0.030 50
50 0.380 0.037 50
19
Introduction
After the system has been properly installed and connected to both electrical and water supplies, it may be started.
Start-up and checkout procedures Mounting
Check mounting to verify that the unit is level and securely supported before filling with water.
Piping
Verify that all piping connections have been completed as recommended and that water pressure is available.
Standard makeup water piping
(HUMIDI-TECH models)
Use cold or hot makeup water. If the water pressure is above 415 kPa and/or water hammer would be objectionable, install a pressure­reducing valve or shock arrester. Even though the HUMIDI-TECH has an internal 25 mm air gap, governing codes may require backflow prevention.
Important: Minimum water supply pressure is 175 kPa.
DI makeup water piping
(HUMIDI-TECH DI models)
In this unit the electronic probe control is replaced by float valve control. A float switch provides heater protection in the event of a low-water condition and is common to all DI humidifiers. The wiring diagram is located inside the electrical panel cover.
HUMIDI-TECH® START-UP AND OPERATION
Electrical
Verify electrical connections before start-up.
Do not remove the electrical panel cover or heater terminal cover until electrical power is disconnected. Safety first.
• Verify that all wiring connections have been made in accordance with all governing codes and the HUMIDI-TECH wiring diagram. The external connections diagram will be found in the packet with this manual.
• Verify that all DIN rail-mounted components are securely fastened to DIN rail.
• Verify that all power terminal screws and lugs are tight from power block to heaters. See the table on Page 22 for torque specifications.
• Verify that all plugs located under the humidifier cover are completely plugged in.
CAUTION: Only qualified electrical personnel should perform start-up procedure.
Electronic probe control
(standard water HUMIDI-TECH models only) A three-probe conductivity sensor cycles a solenoid-operated water fill valve to maintain proper water levels.
OM-211-3
Fill valve on
Fill valve off
Low water
20
VAPOR-LOGIC
® 3
control
VAPOR-LOGIC3 is the standard controller for the HUMIDI-TECH. For more information regarding the operation of the VAPOR-LOGIC3 microprocessor, see the VAPOR-LOGIC3Installation, Operation and Maintenance Manual.
Control system start-up/checkout
1. Confirm that proper grounding and an approved earth ground are provided.
2. Confirm that the control signal connected to the VAPOR-LOGIC
® 3
system is compatible with the VAPOR-LOGIC3 program. Identify the VAPOR-LOGIC3 program code on the wiring diagram. Refer to the VAPOR-LOGIC3 manual to decipher the code using the nomenclature description.
3. Confirm all wiring is correct per wiring diagram.
4. Confirm J17, J18 and J19 shunt connectors on VAPOR-LOGIC3 board are in their correct position per wiring diagram. See the VAPOR-LOGIC3 manual for the physical locations.
5. Confirm that the keypad is mounted on the HUMIDI-TECH with modular cable routed away from high voltage circuits and connected to the J2 female connector on the control board.
6. Turn on water supply. Confirm drain valve is closed.
HUMIDI-TECH® START-UP AND OPERATION
7. Turn on power. The keypad will display the introduction of VAPOR-LOGIC3 and will then enter AUTO mode.
8. The system will initiate filling of the tank with water. The keypad will display "Filling" as part of the idle screen information.
9. Airflow switch input must be closed.
10. High limit humidistat input must be closed or variable air volume (VAV) control system high limit transmitter must be connected.
11. Sufficient water in the tank, airflow switch closed, high limit humidistat closed, and a call for humidity will activate the heat output.
If the tank does not contain water and the heat output is activated by the VAPOR-LOGIC3 control system, a serious failure will result. Immediately remove power from the system and verify that all wiring has been completed per the wiring instructions in the manual and the unit wiring diagram.
12. During normal operation, the keypad will display humidifier operating status. See the VAPOR-LOGIC3 manual for descriptions to change any of the operating parameters.
21
HUMIDI-TECH® MAINTENANCE
The best way to determine how often your particular system will need maintenance is to remove the cover and inspect it after its first three months of duty. Potable water carries a variety of minerals and other materials in a mix that varies from location to location. This variation in water quality, combined with the hours of operation and duty cycle, will determine your own unique maintenance schedule.
Water quality makes a difference
1. Light to moderately hard water (35 mg/l to 170 mg/l) requires:
• Annual cleaning
• Regular skimming
2. High mineral content water (more than 170 mg/l) requires:
• Cleaning frequency determined by use and
water quality
• Regular skimming
• Periodic drain and flush cycles
3. DI/RO water (HUMIDI-TECH DI models) requires:
• No regular cleaning (regular inspections
are advised)
• No regular skimming or drain and flush
cycles
• Regular verification that water processing
equipment is operating correctly. The presence of chlorides in improperly processed DI water will eventually cause pitting and failure of the tank and its components.
4. To dramatically reduce mineral accumulation inside the standard water models, use softened water. (Solids, like silica, are not removed in the softening process.)
Standard water models (HUMIDI-TECH)
Proper skimming, draining and flushing
1. Skimming will remove most water impurities at the surface, ensuring proper surface tension and an even boil. Skimming will remove most entrained contaminants that have not yet precipitated as scale.
2. Draining and flushing will remove entrained contaminants and assist in removing precipitated contaminants like scale and silica.
To inspect and service standard water models
1. Remove the evaporating chamber
• Remove the two fasteners on each side of the cover enclosure (see figure below)
• Remove the enclosure.
Do not remove the electrical panel cover
or heater terminal cover until electrical power is disconnected. Safety first.
• If the HUMIDI-TECH has an SDU mounted directly above it, the SDU cover must be removed before removing the humidifier cover.
• If the tank is hot, cool it down by moving the valve lever located on the back of the drain valve to the manual open position – the fill valve will eventually open allowing cool water to run through the tank until it is cool enough to handle.
• Shut off the water supply.
• Shut off the electrical supply.
• Allow the tank to completely drain.
• Disconnect the fill line at the supply side of the fill valve.
• Disconnect the electrical plugs between the tank components and the back of the electrical panel (includes: power plug, fill plug, drain plug, water level control plug, tank temperature sensor plug and thermal trip plug). DISCONNECT BY PULLING ON
PLUG HOUSING. DO NOT DISCONNECT BY PULLING ON CORD OR WIRES.
• Disconnect the drain union on the back left corner of the frame.
• Disconnect the steam supply hose from the top of the tank.
• Lift the tank foot above the frame flange and slide the tank assembly forward toremove.
Screw cap detail
OM-778-3
22
HUMIDI-TECH® MAINTENANCE
Standard water models (HUMIDI-TECH®, continued)
2. Loosen the four cover bolts and remove the cover assembly from the tank.
3. Clean the tank interior using a putty knife or similar flat instrument.
4. Unplug probe plug assembly. Leave ground wire connected to tank. Unscrew the probe rod assembly and clean the plastic probe housing, ensuring that all passageways are clear. Clean the probe rods using steel wool or a similar mild abrasive material. Inspect the composite plastic probe housing for any signs of cracking, roughness, or deterioration. If found, replace.
5. Install the probe and probe plug assembly. Verify ground wire is solidly connected to tank.
6. Secure the chamber cover, making sure the cover gasket is seated and the chamber is sealed.
7. Re-install the evaporating chamber.
• Reconnect the fill line.
• Reconnect the electrical plugs
(plugs are color coded).
• Reconnect the drain union.
• Reconnect the vapor hose.
8. Verify electrical connections.
• Verify that all DIN rail-mounted components
are securely fastened to DIN rail.
• Verify that all power terminal screws and lugs
are tight from power block to heaters. See the table on this page for torque specifications.
• Verify that all plugs located under the
humidifier cover are completely plugged in.
9. Move the drain valve lever back to the auto position.
10. Turn on the water supply.
11. Turn on the electrical power.
Off-season shut-down procedure
1. Switch off electrical power.
2. Remove enclosure.
3. Shut off water supply to makeup valve.
4. Drain evaporating chamber, and clean if necessary (see “To inspect and service” on previous page).
5. Replace enclosure.
6. Leave chamber dry, power off and the water shut-off valve closed until the next humidification season.
Screw or lug location Torque
Power block 1.8 Nm
Contactor 1.8 Nm
Heater nut
8.5 mm nut 2.2 Nm
9.5 mm nut 2.8 Nm
Heater wire lug
10 mm
2
wire 4.0 Nm
6 mm
2
wire 2.8 Nm
< 6 mm
2
wire 2.2 Nm
HUMIDI-TECH torque specifications
23
HUMIDI-TECH® MAINTENANCE
DI water models (HUMIDI-TECH®DI)
The HUMIDI-TECH DI unit uses DI/RO water. Because these water types are mineral-free, cleaning the evaporating chamber should not be necessary. However, there are some maintenance steps that should be followed to ensure all parts of the unit are in working order
To inspect and service
1. Remove the evaporating chamber.
• Remove the two fasteners on each side of the cover enclosure.
• Remove the enclosure.
Do not remove the electrical panel cover
or heater terminal cover until electrical power is disconnected. Safety first.
• If the HUMIDI-TECH has a space distribution unit (SDU) mounted directly above it, the SDU cover must be removed before removing the humidifier cover.
• If the tank is hot, cool it down by opening the manual ball valve on the side of the tank. The float valve will open allowing cool water to run into the tank until it is cool enough to handle.
• Shut off the water supply.
• Shut off the electrical supply.
• Allow the tank to drain completely.
• Disconnect the fill line at the fill fitting.
• Disconnect the electrical plugs between the tank components and the back of the electrical panel (includes: power plug, low water switch plug, tank temperature sensor plug and thermal trip plug).
DISCONNECT BY PULLING ON PLUG HOUSING. DO NOT DISCONNECT BY PULLING ON CORD OR WIRES.
• Disconnect the drain union on the back left corner of the frame.
• Disconnect the steam supply hose from the top of the tank.
• Lift the tank foot above the frame flange and slide the tank assembly forward to remove.
2. Loosen the four cover bolts and remove the cover assembly from the tank.
3. Inspect the tank interior for debris or pitting.
4. Inspect the valve inlet for debris.
5. Check the operation of the float valve and the condition of the float seat.
6. Check the low water switch to make sure the float slides freely on the stem.
7. Secure the chamber cover making sure the cover gasket is seated and the chamber is sealed.
8. Reinstall the evaporating chamber.
• Reconnect the fill line.
• Reconnect electrical plugs
(plugs are color coded).
• Reconnect drain union.
• Reconnect vapor hose.
9. Verify electrical connections.
• Verify that all DIN rail-mounted components
are securely fastened to DIN rail.
• Verify that all power terminal screws and lugs
are tight from power block to heaters. See the table on Page 22 for torque specifications.
• Verify that all plugs located under the
humidifier cover are completely plugged in.
10. Close the drain valve.
11. Turn on the water supply.
11. Turn on the electrical power.
Off-season shut-down procedure
1. Switch off electric power.
2. Remove enclosure.
3. Shut off water supply to makeup valve.
4. Drain evaporating chamber by opening the drain valve. For units with end-of-season drain, refer to the VAPOR-LOGIC
® 3
manual.
5. Replace enclosure.
6. Leave chamber dry, power off, and water shut­off valve closed until the next humidification season.
24
HUMIDI-TECH® TROUBLESHOOTING GUIDE
Note: Probe rod corrosion or aging probe head material may cause level control system failure. This
generally does not occur in the first two years of operation.
PROBLEM POSSIBLE CAUSE RECOMMENDED ACTION
Humidifier does not heat.
Incorrect or nonexistent supply voltage to unit
Check mai n l ine safety switch. Check main line fuses. Check for proper supply voltage.
Incorrect or nonexistent control voltage
Reset control transformer circuit breaker. Check for 24 VAC control circuit voltage at T-1 and T-2 on the control board.
Humidistat not calli ng Set humidistat to call. Inspect for faulty humidistat.
Safety controls open Check safety controls, airflow switch, and high limit humidistat.
Humidifier will not fill.
No water pressure at valve Check water supply/shut-off valves.
Faulty water fill valve Check for 24 volts at the fill valve.
Plugged strainer Check strainer.
Plugged valve Check valve.
Faulty control board Verify control voltage across the fill valve output.
Humidifier does not stop filling.
Lack of tank to probe electrical continuity
Water conductivity must be 100 µS/cm or 34.2 mgO. A d d s a l t to the tank. If this does not solve the problem, consult factory for fur ther advice.
Fill valve stuck open Check valve for foreign matter.
Drain valve not closed Verify that lever on drain valve is in closed position.
Fill valve installed backward Check for correct water flow through valve by noting arrow.
Autodrain mode Humidifier may be in periodic drain and flush. Check controller
display.
Low output
Electric drain valve not seating Correct the cause of leakage or replace valve.
Fill valve stuck open Check valve for foreign matter.
Unit short-cycles
Controller cycle rate set too low Adjust heater cycle time using the VAPOR-LOGIC3 keypad
setup menu. See the VAPOR-LOGIC
3
manual if you need
more information.
Reduced or no output even though water is at the proper level
Heater malfunctioning Verify that proper voltage is being applied to heaters. Check
heater amp draw and compare to wiring diagram ratings.
Malfunctioning control system Replace heater contactor if not functioning. Verify auxiliary
limit controls (humidistat, airflow proving switch, etc.) and reset, replace or calibrate as needed.
Troubleshooting guide for standard water models
25
PROBLEM POSSIBLE CAUSE RECOMMENDED ACTION
Humidifier will not heat.
Control transformer Reset control transformer circuit breaker.
Humidistat is not calling Set humidistat to call. Inspect for faulty humidistat.
Safety controls open Check safety controls, airflow switch, high limit
humidistat, etc.
Low water cutoff Check at board 32 and 33. Measure 0 Volts for closed switch,
approximately 2.5 Volts for AC open sw itch.
Humidifier will not fill.
No water pressure at valve Check manual water supply valve for minimum 25 psi
(175 kPa) water pressure.
Plugged fill valve Check fill valve inlet.
Humidifier does not stop filling.
Open drain valve Obstruction in drain valve will not allow complete closure.
Clean or replace valve.
Manual drain valve not closed Close drain valve.
Fill valve stuck open Check for foreign matter in valve, water-logged float, broken
float arm, or worn valve stopper.
Reduced or no output even though water is at the proper level
Heater malfunctioning Verify that proper voltage is being applied to heaters. Check
heater amp draw and compare to wiring diagram ratings.
Malfunctioning control system Repl ace heater contactor if not functioning. Verify auxiliary
limit controls (humidistat, airflow proving switch, etc.) and reset, replace or calibrate as needed.
Troubleshooting guide for DI water models
HUMIDI-TECH® TROUBLESHOOTING GUIDE
26
HUMIDI-TECH® REPLACEMENT PARTS
OM-778-1
HUMIDI-TECH DI model
HUMIDI-TECH® standard water model
Note: Refer to the tables on the next page for replacement part numbers.
27
HUMIDI-TECH® REPLACEMENT PARTS
HUMIDI-TECH® replacement parts (refer to the drawing on previous page)
* Specify humidifier model and serial numbers
when ordering.
No. Description Qty. Part No.
1
Head bolt, large Phillips, ¼ - 20 X 1"
4 700300-013
2 Thermo cut-out 1 409560-001
3 Cover, heater terminal 1 *
4 Hose clamp, 2" 2 700560-200
5
Hose cuff, 1½" 1 305390- *
Hose cuff, 2" 1 305391- *
6 Cover, tank 1 *
7 Heater element * *
8
Probe assembly with cord and plug
1 406050-100
9
Gasket, 2.50" OD x
1.90" ID
1 309750-004
10
Probe assembly, VM 2-4 1 406270
Probe assembly, VM 6-34 1 406275
11
Valve, ¾" electric, 24V 1 505400-001
Valve, ½" SST ball 1 505000-003
Drain, ¼" NPT E.O.S., 24V solenoid SST w/DIN plug (not shown)
1 505086-003
12 Tank weldment 1 *
13
Valve, ¼" solenoid, 24V w/DIN plug
1 505084-001
Valve, ¼" SST E.O.S. (not shown)
1 505084-002
14 Cabinet enclosure 1 330001-001
15 Hose, ¾" ID 2 307020-002
16 Hose clamp, ¾" 4 700560-075
17
Nut assembly, ¼-20, VM/VMDI 2-4
4 700650
Nut assembly, ¼-20, VM/VMDI 6-34
2 700650
18 Cover, tank gasket 1 *
No. Description Qty. Part No.
19
Washer, No. 8 external tooth, pltd
2 700200-003
20 Nut, 8-32 hex, pltd 6 700200-002
21 Cover, subpanel 1 120277
22
Fill adapter, VM 2-4 1 160226-041
Fill adapter, VM 6-16 1 160224-041
Fill adapter, VM 21-34 1 160224-052
23 Panel, insulation 1 309845-003
24 Sensor, temperature 1 405760
25
Screw, Phillips head, 8-32 x ½"
8 700170-007
26 Frame assembly, chassis 1 165541
27 Clip, wire harness 1 405892-001
28 Clip, temperature sensor 1 408251
29 Valve assembly, float 1 505310
30 Switch, float, 1/8" NPT 1 408420-002
31 Ring, seal, ¼"-18 NPT 1 306365
32
Gasket, bulkhead, 1.60 OD X 1.15 ID
1 309750-005
33 Probe housing, nylon, VM 1 308500
34 Nut, VM heater .475 1 409601-001
35 O-ring, 5/8" EPDM No. 016 1 300400-009
36 Cap, black 4 409593-002
37
DI orifice, VM/VMDI 2-16 1 160229-041
DI orifice, VM/VMDI 21-34 1 160229-052
38 Adapter, 1/4" to 3/8" 1 167121
39 Adapter, 1/4" to 3/8" 1 250405-004
40 Bulkhead nut 1 162721-002
41
Tube weld, low water, short, VMDI 2-4
1 167787
Tube weld, low water, long, VMDI 6-34
1 167788
28
Space Distribution Unit, external absorption (SDU-E)
HUMIDI-TECH® REPLACEMENT PARTS
No. Description Qty. Part. No.
1 Shroud 1 330001-003
2 Blower, SDU99 external assembly 1 *
3 Switch, airflow 1 406190
4 Screw, 8-32 x 1/2" PHMS Philips 4 700170-007
5 Nut retainer, 8-32 4 409593-001
6 Cap, black 4 409593-002
7
Dispersion chamber for SDU with 1½" outlet 1 160445-001
Dispersion chamber for SDU with 2" outlet 1 160445-002
OM-1503
* This is an assembly of multiple parts.
Contact DRI-STEEM customer service to order.
29
Space Distribution Unit, internal absorption (SDU-I)
HUMIDI-TECH® REPLACEMENT PARTS
No. Description Qty. Part. No.
1 Shroud 1 330001-002
2 Blower, SDU99 external assembl y 1 *
3 Switch, airflow 1 406190
4 Screw, 8-32 x 1/2" PHMS Philips 6 700170-007
5 Nut retainer, 8-32 6 409593-001
6 Cap, black 6 409593-002
7 Tubelet, 0.375" x 0.375", molded 44 310280-006
* This is an assembly of multiple parts.
Contact DRI-STEEM customer service to order.
OM-1504
30
HUMIDI-TECH® REPLACEMENT PARTS
HUMIDI-TECH® subpanel with SSR
OM-368
No. Description Qty. Part. No.
1 Subpanel, VM99 barrier 1 120801
2 DIN rail, 10.75" long 1 167765-0107
3 Lug, wire 2 409250-003
4 Ground lug, medium 2 408250-018
5 Block, DIN rail terminal end 5 408252-006
6 Transformer, 230/400 V 1 408996-007
7
Wire channel, 1" x 1" 12.5" 408999-001
Wire channel cover 12.5" 408999-002
8
Contactor, 32 A 1 407001-020
Contactor, 60 A 1 407001-021
9 Main board, VL-3 1 408490-001
10 Display board, VL-3 1 408490-002
No. Description Qty. Part. No.
11 Plug, 4-prong female 4 409585-008
12 Terminal block, 3-pole 1 408300-002
13 Fan, cooling 1 408677-001
14 Housing, 75 Amp white connector 4 409585-001
15 Plate, plug retainer 2 409585-009
16
SSR, 480 V, 50 Amp, 1-pole * 408677-002
SSR, 480 V, 50 Amp, 2-pole * 408677-003
SSR, 480 V, 60 Amp, 1-pole * 408677-005
17 Circuit breaker, 4 Amp, 1-pole 1 406775-002
18 Circuit breaker, 1.6 Amp, 1-pole 2 406775-001
19 DIN rail, 2.25" long 1 167765-0022
* Refer to model for correct selection and quantity.
31
HUMIDI-TECH® REPLACEMENT PARTS
HUMIDI-TECH® subpanel with SDU
No. Description Qty. Part No.
1 Subpanel, VM99 barrier 1 120801
2 DIN rail, 8" long 1 167765-008
3 Lug, wire 2 409250-017
4 Ground lug, medium 2 409250-003
5 Block, DIN rail terminal end 4 408252-006
6 Transformer, 230V/400V 1 408986
7
Transformer, 230V/400V,
500 VA CE
1 408996-011
8 Plug, 4-prong female 4 409585-008
9 Terminal block, 3-pole 1 408300-002
10 Fan, cooling 1 408677-001
11
Housing, 75 Amp white connector
4 409585-001
12 Plate, plug retainer 2 409585-009
13 Main board, VL3 1 408490-001
No. Description Qty. Part No.
14 Display board, VL3 1 408490-002
15 Terminal, DIN rail mount 8 408252-001
16 Terminal, ground 1 408252-010
17 End cap, DIN rail mount 1 408252-005
18 Jumper, marathon terminal 2 408252-008
19 Relay, 24V DPDT finder 1 407900-016
20 Relay, socket 1 407900-011
21 Circuit breaker, 4 Amp, 1-pole 4 406775-002
22
Contactor, 60 A 1 407001-021
Contactor, 32 A 1 407001-020
23 DIN rail, 2.25" long 1 167765-0022
24
Channel, wire cover 12.5" 408999-002
Channel, wire 12.5" 408999-001
OM-1502
32
© 2002 DRI-STEEM Humidifier Company Part No. 890000-202 Rev B 03/02
TWO-YEAR LIMITED WARRANTY
DRI-STEEM Humidifier Company (“DRI-STEEM”) warrants to the original user that its products will be free from defects in materials and workmanship for a period of two (2) years after installation or twenty­seven (27) months from the date DRI-STEEM ships such product, whichever date is the earlier.
If any DRI-STEEM product is found to be defective in material or workmanship during the applicable warranty period, DRI-STEEM’s entire liability, and the purchaser’s sole and exclusive remedy, shall be the repair or replacement of the defective product, or the refund of the purchase price, at DRI-STEEM’s election. DRI-STEEM shall not be liable for any costs or expenses, whether direct or indirect, associated with the installation, removal or re-installation of any defective product.
DRI-STEEM’s limited warranty shall not be effective or actionable unless there is compliance with all installation and operating instructions furnished by DRI-STEEM, or if the products have been modified or altered without the written consent of DRI-STEEM, or if such products have been subject to accident, misuse, mishandling, tampering, negligence or improper maintenance. Any warranty claim must be submitted to DRI-STEEM in writing within the stated warranty period.
DRI-STEEM’s limited warranty is made in lieu of, and DRI-STEEM disclaims all other warranties, whether express or implied, including but not limited to any IMPLIED WARRANTY OF MERCHANT­ABILITY, ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, any implied warranty arising out of a course of dealing or of performance, custom or usage of trade.
DRI-STEEM SHALL NOT, UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY DIRECT, INDI­RECT, INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, LOSS OF PROFITS, REVENUE OR BUSINESS) OR DAMAGE OR INJURY TO PERSONS OR PROPERTY IN ANY WAY RELATED TO THE MANUFACTURE OR THE USE OF ITS PRODUCTS. The exclusion applies regardless of whether such damages are sought based on breach of warranty, breach of contract, negligence, strict liability in tort, or any other legal theory, even if DRI-STEEM has notice of the possibility of such damages.
By purchasing DRI-STEEM’s products, the purchaser agrees to the terms and conditions of this limited warranty.
Continuous product improvement is a policy of DRI-STEEM Humidifier Company;
therefore, product features and specifications are subject to change without notice.
DRI-STEEM, HUMIDI-TECH, RAPID-SORB and VAPOR-LOGIC3are registered trademarks of the DRI-STEEM Humidifier Company.
Europe Office: Bell Place, Bell Lane • Syresham, Brackley • NN13 5HP, U.K. Phone: +44 1280 850122 • Fax: +44 1280 850124 E-Mail: 106277.1443@compuserve.com
U.S. Headquarters:
14949 Technology Drive • Eden Prairie, MN 55344 Phone: (800)328-4447 • (952) 949-2415 • Fax: (952) 949-3200 E-Mail: sales@dristeem.com • Web: www.dristeem.com
Loading...