DriSteem HUMIDI-TECH, HUMIDI-TECH DI, VM-2, VM-4, VM-6 Installation, Operation And Maintenance Manual

...
READ AND SAVE THESE INSTRUCTIONS
HUMIDI-TECH and
HUMIDI-TECH DI
ELECTRIC STEAM HUMIDIFIERS
Installation, Operation
and
Maintenance Manual
2
TABLE OF CONTENTS
To the purchaser and installer
Thank you for purchasing our HUMIDI-TECH® humidifier. We have designed and built this equipment to give you complete satisfaction and trouble-free service for many years. Familiarizing yourself with this manual will help ensure proper operation of the equipment for years to come.
This manual covers the installation and maintenance procedures for both the HUMIDI-TECH and HUMIDI-TECH DI humidifiers.
DRI-STEEM Humidifier Company
General information
Product overview ................................................................. 3
Dimensions .......................................................................... 4
Electrical specifications, capacities and weights ................. 5
Installation
Locating and mounting the humidifier .................................. 6
Piping ................................................................................... 6
Wiring .................................................................................. 9
Dispersion
Using space distribution units (SDU-E and SDU-I) ..... 11
Using dispersion tubes ................................................ 14
Using a RAPID-SORB® dispersion assembly ............. 16
Drip tee installation ...................................................... 17
Interconnecting piping tables ....................................... 18
Operation
Start-up procedures ........................................................... 19
Control ............................................................................... 20
Maintenance
Maintenance procedures ................................................... 21
Troubleshooting guide ....................................................... 24
Replacement parts............................................................. 26
Warranty ........................................................................... 32
3
HUMIDI-TECH® HUMIDIFIER OVERVIEW
Deionized water models (HUMIDI-TECH DI)
The HUMIDI-TECH DI, shown here, is specifically designed for use with deionized or reverse osmosis water.
Standard water models (HUMIDI-TECH)
The standard water HUMIDI-TECH unit requires water conductivity of at least 100 µS/cm to operate. It will not operate with water treated by reverse osmosis or deionization processes (see DI water model below).
OM-82-4
Removable evaporating chamber
Slide assembly under evaporating chamber provides easy removal for cleaning
INCOLOY alloy-sheathed immersion heaters
Keyholes for wall mounting
Water fill DN10 (3/8") (female)
DN40 or DN50 flexible vapor hose, pipe or tubing connects to dispersion tube(s) or to an SDU
Condensate return line
Duct
Electrical area
Electrical conduit knockouts
DN20 (¾") threaded skimmer port and overflow drain
Water fill access hole
Condensate return line
Electrical area
Removable evaporating chamber
INCOLOY alloy-sheathed immersion heaters
Duct
Electrical conduit knockouts
Slide assembly under evaporating chamber provides easy removal for cleaning
Water fill access hole
Keyholes for wall mounting
Water fill DN10 (3/8") (female)
Float cutoff switch
OM-82-5
Ball valve
DN20 (¾") threaded skimmer port and overflow drain
DN40 or DN50 flexible vapor hose, pipe or tubing connects to dispersion tube(s) or to an SDU
4
HUMIDI-TECH® DIMENSIONS
50 mm
409 mm
57 mm
472 mm
146 mm
38 mm
Venting
DN20 (¾") tank drain
DN20 (¾") frame drain
57 mm
DC-1167
13 mm hole in base for water fill line
Power wire knockout
Steam outlet
276 mm
57 mm
Top view
614 mm
Power wiring knockout
Left side view
Front view
614 mm
16 mm
19 mm
38 mm
146 mm
Bottom view
Control wiring knockout
50 mm
25 mm
Control or SDU wiring knockout
5
HUMIDI-TECH® SPECIFICATIONS
Electrical specifications, capacities and weights
Table notes:
All HUMIDI-TECHs operate at 50/60 Hz.
* For wire sizing, the highest leg draw is shown
due to current imbalance.
** SDU-E is not an available option for these
HUMIDI-TECH models if using SSR control.
*** Models with SDU or SSR options have
additional electronic components housed within the HUMIDI-TECH cabinet. Therefore, if adding an SDU or SSR, add the following to the HUMIDI-TECH shipping and operating weights:
– SDU-I: 5.5 kg – SDU-E: 4 kg – SSR control: 1 kg
Model
number
kW
Single-phase 230 V Three-phase 400 V
Shipping
weight
kg***
Operating
weight
kg***
Steam
capacity kg/h
I max. A
Steam
capacity kg/h
I max. A
VM-2 2 2.5 8.0 2.7 -- 36 43
VM-4 4 5.0 16.0 5.4 8.7* 36 43
VM-6 6 7.5 24.0 8.2 13.0* 40 55
VM-8 8 10.0 31.9 10.9 17.3* 40 55
VM-10 10 12.5 39.9 13.6 15.2* 42 63
VM-12 12 15.0 47.9 16.3 17.3 42 63
VM-14 14 17.5 -- 19.1 20.2 42 63
VM-16 16 20.0 -- 21.8 23.1** 42 63
VM-21 21 26.3 -- 28.6 30.3** 43 69
VM-25 25 31.3 -- 34.0 36.1** 43 69
VM-30 30 37.6 -- 40.8 43.3** 46 71
VM-34 34 42.6 -- 46.3 49.1** 46 71
Notes about SDUs (Space Distribution Units):
 The SDU-I is available for models VM-2 through
VM-10.
• The SDU-E is available for all HUMIDI-TECH models except Models VM-16 through VM-34 using three-phase 400V power with the SSR control option.
 SDUs ship separately from the HUMIDI-TECH.
SDU weights
SDU
model
Shipping weight
Operating weight
kg kg
SDU-I 31 26
SDU-E 28 23
6
HUMIDI-TECH piping
Water makeup piping may be of any code­approved material (copper, steel, or plastic). The final connection size is DN10 (3/8"). In cases where water hammer may be a possibility, a shock arrestor should be considered. Water pressure must be between 175 kPa and 550 kPa.
Drain piping may be of any code-approved material (copper, steel, or plastic rated for 100 °C minimum). If drainage by gravity is not possible, use a small lift pump (DRI-STEEM Part No. 400281).
The final connection size is DN20 (3/4") for tank and frame drains. This connection size should not be reduced. (See figures on the following pages for proper drain piping configurations.) The tank drain should be piped separately from the frame drain, as shown, to prevent backflow of drain water into the humidifier cabinet.
Install a union in the water supply line as shown in the drawings on the next two pages to allow tank removal.
Locating and mounting the humidifier
The HUMIDI-TECH humidifier is designed to attach to the wall with coach screws, and it should be installed in a space located near an air duct system.
Consider the following when selecting the location of the humidifier:
• Convenient access to duct
• Electrical and plumbing connections
• Required clearances
• External water seal requirements
Electrical power supply, water makeup piping and drain piping must also be considered. Electrical power supply connections are made at the lower or upper right rear corner of the unit. Water makeup and drain piping connections are made at the lower left rear corner.
When mounting on a stud wall (studs with 406 mm centres), locate studs and position coach screws in place so that each of the screws (406 mm apart) will center on a stud. Mark hole locations and predrill 6 mm diameter pilot holes using mounting template on the HUMIDI-TECH box. Secure frame to wall with coach screws provided.
For hollow block or poured concrete wall mounting, position template in place and mark the holes. Drill appropriate pilot hole for two 10 mm toggle bolts or two 10 mm machine bolt lead anchors. Secure frame in place.
HUMIDI-TECH® MOUNTING AND PIPING
Clearance recommendations
For recommended service and maintenance purposes, maintain the following clearances:
Top: 460 mm
Floor: 610 mm
Supporting wall
Left side: 305 mm
DC-1201
Right side electrical controls: 915 mm
Front: 915 mm
Secured to supporting wall
To dispersion unit
7
HUMIDI-TECH® PIPING
Notes:
• Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet.
• Dashed lines indicate provided by installer.
• The water supply inlet is more than 25 mm above the skim/overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required, however, governing codes prevail.
• Install a union in the water supply line as shown to allow tank removal.
Shock arrester recommended to reduce water hammer
DN10 (3/8") connection to water supply line; water pressure must be between 175 kPa and 550 kPa; water conductivity minimum 100 µS/cm
Water supply line
Spill funnel. Plumb to floor drain
25 mm air gap
DN20 (¾") tank drain, skimmer and P-trap piping, rated for 100 °C. If piping run is over 3 m increase pipe to DN32 after P-trap.
Open floor drain. Refer to governing codes for drain pipe size and maximum temperature requirements.
Cover
Electrical conduit knockouts provided top and bottom:
• Combination, with knockout diameters of 22.3 mm and
28.6 mm
• Combination, with knockout diameters of 28.6 mm and
34.9 mm
Install level
Steam vapor hose (maximum run 3 m). May also use pipe or tubing.
DC-1136
DN20 (¾") frame drain and P-trap piping, rated for 100 °C
Two keyholes for wall mounting, 406 mm on center
300 mm
50 mm
HUMIDI-TECH (standard water) field piping overview
Frame drain
Unions by installer
8
HUMIDI-TECH® PIPING
HUMIDI-TECH DI (deionized/reverse osmosis water) field piping overview
DN10 (3/8") connection to water supply line; water pressure must be between 175 kPa and 550 kPa; water chloride content must be less than 3 ppm; first 1 m of supply line must be rated for 100 °C
Water supply line
Spill funnel. Plumb to floor drain
25 mm air gap
DN20 (¾") tank drain and P-trap piping, rated for 100 °C; if piping run is over 3 m increase pipe to DN32 after P-trap
Open floor
drain. Refer to
governing codes for drain
pipe size and maximum
temperature requirements.
Cover
Electrical conduit knockouts provided top and bottom:
• Combination, with knockout diameters of 22.3 mm and
28.6 mm
• Combination, with knockout diameters of 28.6 mm and
34.9 mm
Install level
DC-1139
DN20 (¾") frame drain and P-trap piping, rated for 100 °C
Two keyholes for wall mounting, 406 mm on center
300 mm
50 mm
Frame drain
Strainer, by installer
If water piping to humidifier is non-metallic, we recommend a 50 mm water seal in the supply line to isolate steam during DI/RO water system maintenance
Notes:
• Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet.
• Dashed lines indicate provided by installer.
• The water supply inlet is more than 25 mm above the overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required, however, governing codes prevail.
• Install a union in the water supply line as shown to allow tank removal.
Unions by installer
Steam vapor hose (maximum run 3 m). May also use pipe or tubing.
9
HUMIDI-TECH wiring
All wiring must be in accordance with all governing codes, and with the HUMIDI-TECH® or HUMIDI-TECH DI wiring diagrams. The diagrams are located inside the removable subpanel cover on the right-hand side of the humidifier cabinet. Power supply wiring must be rated for 105 °C.
Refer to the maximum load (I max. A) on the rating plate, and use the tables on the following page to determine the appropriate wire, conduit and fused disconnect requirements.
When selecting a location for installing the HUMIDI-TECH, avoid areas close to sources of electromagnetic emissions such as power distribution transformers.
Grounding requirements
The earth must be made by solid metal to metal connections. The ground must be a good radio frequency earth. Ground wire should be same size as power wiring.
Shielded/screened cable drain wire connection to lug
Note: For maximum E.M.C. effectiveness, all humidity, temperature, and airflow controls should be wired
using multicolored shielded/screened plenum-rated cable with a drain wire for the shield/screen. The drain wire should be connected to the shield/screen ground terminal with its length kept to less than 50 mm.
Shield/screen ground lug
Microprocessor board
VAPOR-LOGIC
3
keypad on front of cabinet
OM-1505
HUMIDI-TECH® WIRING
Field wiring requirements
Note: Control wiring and power wiring must be run in
dedicated or separate earthed metal conduit, cable trays or trunking.
OM-1007
Fused disconnect (provided by installer) sized per tables on next page
Power supply (provided by installer) cable sized per tables on next page
0.6 m to 1.9 m,
1.7 m recommended
Right side view of HUMIDI-TECH
10
Fuse/breaker requirements
Note:
Semiconductor fusing is recommended with the SSR option.
230 Volt single phase
A
Wire size
mm
2
Groun d wire size
mm
2
0 - 18 2.5 2.5
18.1 - 24 4 4
24.1 - 30.7 6 6
30.8 - 42.7 10 10
42.8 - 57 16 16
57.1 - 75.7 25 16
75.8 - 93.7 35 16
93.8 - 113.2 50 25
113.3 - 144 70 35
144.1 - 174 95 50
174.1 - 201.7 120 70
400 Volt three phase
I max. A Breaker size
0 - 8.0 10
8.1 - 10.4 13
10.5 - 12.8 16
12.9 - 16 20
16.1 - 20 25
20.1 - 25.6 32
25.7 - 32 40
32.1 - 40 50
40.1 - 50.4 63
50.5 - 64 80
64.1 - 80 100
80.1 - 100 125
100.1 - 128 160
128.1 - 160 200
A
Wire size
mm
2
Ground wire size
mm
2
0 - 15.7 2.5 2.5
15.8 - 21 4 4
21.1 - 27 6 6
27.1 - 37.5 10 10
37.6 - 51 16 16
51.1 - 66.7 25 16
66.8 - 82.5 35 16
82.6 - 100.5 50 25
100.6 - 128.2 70 35
128.3 - 155.2 95 50
155.3 - 179.2 120 70