DriSteem Vapormist, Vapormist DI Installation, Operation And Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS
®
VAPORMIST and
VAPORMIST DI
ELECTRIC STEAM HUMIDIFIERS
Installation, Operation
and
Maintenance Manual
call 1-800-328-4447
TABLE OF CONTENTS
To the purchaser and installer
Thank you for purchasing our VAPORMIST® humidifier. We have designed and built this equipment to give you complete satisfaction and trouble-free service for many years. Familiarizing yourself with this manual will help ensure proper operation of the equipment for years to come.
This manual covers the installation and maintenance procedures for both the VAPORMIST and VAPORMIST DI humidifiers.
DRI-STEEM Humidifier Company
General information
Product overview ................................................................. 3
Dimensions .......................................................................... 4
Electrical specifications, capacities and weights ................. 5
Installation
Locating and mounting the humidifier .................................. 6
Piping ................................................................................... 6
Wiring .................................................................................. 9
Dispersion
Using space distribution units (SDU-E and SDU-I) ..... 10
Using Single Tubes ..................................................... 13
Using a RAPID-SORB® dispersion panel .................... 15
Drip tee installation ..................................................... 16
Interconnecting piping tables ...................................... 17
Operation
Start-up procedures ........................................................... 18
Control ............................................................................... 19
Maintenance
Maintenance procedures ................................................... 20
Troubleshooting guide ....................................................... 23
Replacement parts ............................................................ 25
Notes ................................................................................. 31
Warranty ........................................................................... 32
2
VAPORMIST® HUMIDIFIER OVERVIEW
Standard water models (VAPORMIST)
The standard water VAPORMIST unit requires water conductivity of at least 100 µS/cm (2 grains/gallon) to operate. It will not operate with water treated by reverse osmosis or deionization processes (see DI water model below).
1½" (DN40) or 2" (DN50) flexible vapor hose, pipe or tubing connects to dispersion tube(s) or to an SDU
Water fill ¼" NPT (female)
Keyholes for wall mounting
Water fill access hole
¾" NPT (DN20) coupling, skimmer port and overflow drain
Electrical conduit knockouts
Removable evaporating chamber
Duct
Electrical area
INCOLOY alloy-sheathed immersion heaters
Condensate return line
Slide assembly under evaporating chamber provides easy removal for cleaning
Deionized water models (VAPORMIST DI)
The VAPORMIST DI, shown here, is specifically designed for use with deionized or reverse osmosis water.
1½" (DN40) or 2" (DN50) flexible vapor hose, pipe or tubing connects to dispersion tube(s) or to an SDU
Float cutoff switch
Water fill ¼" NPT (female)
Keyholes for wall mounting
Water fill access hole
¾" NPT (DN20) coupling, skimmer port and overflow drain
Electrical conduit knockouts
OM-82-4
Duct
Electrical area
INCOLOY alloy-sheathed immersion heaters
Condensate return line
Removable
Ball valve
Slide assembly under evaporating chamber provides easy removal for cleaning
evaporating chamber
OM-82-5
3
VAPORMIST® DIMENSIONS
Left side view
Venting
Top view
2.25" (57 mm)
Steam outlet
Front view
18.6"
(472 mm)
10.9"
(276 mm)
24.2"
(614 mm)
2" (50 mm)
2" (50 mm)
1" (25 mm)
Power wiring knockout
Control or SDU wiring knockout
2.25" (57 mm)
16.1"
(409 mm)
1.50" (38 mm)
5.75" (146 mm)
Bottom view
0.50" (13 mm) hole in base for water fill line
0.75" (19 mm)
1.50" (38 mm)
5.75" (146 mm)
0.63" (16 mm)
¾" NPT (DN20) frame drain
¾" NPT (DN20) tank drain
2.25" (57 mm) Power wire
knockout
Control wiring knockout
24.2"
(614 mm)
4
DC-1167
VAPORMIST specifications
VAPORMIST® SPECIFICATIONS
VM
model
number
2 6 2.7 16.7 9.6 8.3 4.2 3.3 -- -- -- -- 2 80 36 95 43
4 12 5.4 33.3 19.2 16.7 8.3 6.7 16.7** 14.4** 7.2** 5.8** 4 80 36 95 43
6 18 8.2 -- 28.8 25.0 12.5 10.0 25.0** 21.7** 10.8** 8.7** 6 88 40 122 55
8 24 10.9 -- 38.5 33.3 16.7 13.3 33.3** 28.9** 14.4** 11.5** 8 88 40 122 55
10 30 13.6 -- -- 41.7 20.8 16.7 29.1** 25.3** 12.6** 10.1** 10 93 42 139 63
12 36 16.3 -- -- -- 25.0 20.0 33.3 28.9 14.4 11.5 12 93 42 139 63
14 42 19.1 -- -- -- 29.2 23.3 38.9 33.7 16.8 13.5 14 93 42 139 63
16 48 21.8 -- -- -- 33.3 26.7 44.4 38.5 19.2 15.4 16 93 42 139 63
21 63 28.6 -- -- -- 43.8 35.0 -- -- 25.3 20.2 21 95 43 152 69
25 75 34.0 -- -- -- -- 41.7 -- -- 30.1 24.1 25 95 43 152 69
30 90 40.9 -- -- -- -- -- -- -- 36.1 28.9 30 101 46 156 71
34 102 46.3 -- -- -- -- -- -- -- 40.9 32.7 34 101 46 156 71
Steam
capacity
lbs/hr kg/h Single-phase Three-phase
120V 208V* 240V* 480
Table notes:
* On 208V/240V/single-phase/three-wire and on
208V/three-phase/four-wire supplies, the neutral line provides a separate 120V circuit for the SDU fan unit.
** For wire sizing, the highest leg draw is shown due
to current imbalance.
† Add the following to VAPORMIST weights if using
an SDU option:
Current draw (amps) kW Shipping
600V †208V* 240V †480V †600V
weight ‡
lbs kg lbs kg
Notes about SDUs (Space Distribution Units):
• The SDU-I is available for models VM-2 through VM-8, and all VM-10 models except those using 240V, three­phase power with SSR control.
• The SDU-E is available for all VAPORMIST models except those models using 240V/480V/600V/three­phase power with the SSR control option and drawing more than 21.7 amps.
• SDUs ship separately from the VAPORMIST.
– SDU-I: 12 lbs (5.5 kg) – SDU-E: 9 lbs (4 kg) Note: These weights are for additional control components housed within the VAPORMIST cabinet. See the SDU weights table at right for SDU weights (shipped separately).
‡ Add the following if using the SSR option:
– For single-phase or three-phase models drawing
SDU weights
SDU
model
SDU-I 68 31 58 26
SDU-E 61 28 51 23
Shipping weight Operating weight
lbs kg lbs kg
less than 21.7 amps, add 2 lbs (1 kg)
– For three-phase models drawing more than
21.7 amps, add 4 lbs (2 kg)
All VAPORMISTs operate at 50/60 Hz.
Operating
weight ‡
5
VAPORMIST® MOUNTING AND PIPING
Locating and mounting the humidifier
The VAPORMIST humidifier is designed to attach to the wall with lag bolts, and it should be installed in a space located near an air duct system, unless using a Space Distribution Unit (SDU) for dispersion.
Consider the following when selecting the location of the humidifier:
• Convenient access to duct
• Electrical and plumbing connections
• Required clearances
• External water seal requirements
Electrical power supply, water makeup piping and drain piping must also be considered. Electrical power supply connections are made at the lower or upper right rear corner of the unit. Water makeup and drain piping connections are made at the lower left rear corner.
When mounting on a stud wall (studs 16" [406 mm] on center), locate studs and position lag bolts in place so that each of the bolts will center on a stud. Mark hole locations and predrill ¼" (6 mm) diameter pilot holes using mounting template on the VAPORMIST box. Secure frame to wall with lag bolts provided.
VAPORMIST piping
Water makeup piping may be of any code-approved material (copper, steel, or plastic). The final connection size is ¼" NPT (DN8). In cases where water hammer may be a possibility, a shock arrestor should be considered. Water pressure must be between 25 psi and 80 psi (175 kPa and 550 kPa).
Drain piping may be of any code-approved material (copper, steel, or plastic rated for 212 °F [100 °C] minimum). If drainage by gravity is not possible, use a small pump (DRI-STEEM Part No. 400280).
The final connection size is ¾" NPT (DN20) for tank and frame drains. This connection size should not be reduced. (See the drawings on the following pages for proper drain piping configurations.) The tank drain should be piped separately from the frame drain, as shown, to prevent backflow of drain water into the humidifier cabinet.
Install a union in the water supply line as shown in the drawings on the next two pages to allow tank removal.
For hollow block or poured concrete wall mounting, position template in place and mark the holes. Drill appropriate pilot holes for two 3/8" (10 mm) toggle bolts or two 3/8" (10 mm) machine bolt lead anchors. Secure frame in place.
Clearance recommendations
For recommended service and maintenance purposes, maintain the following clearances:
Top (when SDU is not mounted directly above the
To dispersion unit
Secured to supporting wall
Left side: 12" (305 mm)
VAPORMIST): 18" (460 mm)
Right side electrical controls: 36" (915 mm)
Supporting wall
Front: 36" (915 mm)
Floor: 24" (610 mm)
6
DC-1201
VAPORMIST® PIPING
VAPORMIST (standard water) field piping overview
Steam vapor hose
¼" NPT (DN8) connection to water supply line; water pressure must be between 25 psi and 80 psi (175 kPa and 550 kPa); water conductivity minimum 2 grains/gallon (100 µS/cm)
Two keyholes for wall mounting, 16" (406 mm) on center
Unions by installer
Water supply line
Shock arrester recommended to reduce water hammer
¾" NPT (DN20) tank drain, skimmer and P-trap piping, rated for 212 °F (100 °C). If piping run is over 10' (3 m) increase pipe to 1¼" (DN32) after P-trap.
12"
(300 mm)
(maximum run 10' [3 m]). May also use pipe or tubing.
2" (50 mm)
Install plumb
Electrical conduit knockouts provided top and bottom:
• Combination, for ½" and ¾"conduit connectors (knock­out diameters
22.3 mm and
28.6 mm)
• Combination, for ¾" and 1" conduit connectors (knock­out diameters
28.6 mm and
34.9 mm)
1" (25 mm) air gap
Spill funnel. Plumb to floor drain
Open floor drain. Refer to local codes for drain pipe size and maximum temperature requirements.
Frame drain
¾" NPT (DN20) frame drain and P-trap piping, rated for 212 °F (100 °C)
Cover
Notes:
• Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet.
• Dashed lines indicate provided by installer.
• The water supply inlet is more than 1" (25 mm) above the skim/overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required, however, local codes prevail.
• Install a union in the water supply line as shown to allow tank removal.
DC-1136
7
VAPORMIST® PIPING
VAPORMIST DI (deionized/reverse osmosis water) field piping overview
¼" NPT (DN8) connection to water supply line; water pressure must be between 25 psi and 80 psi (175 kPa and 550 kPa); water chloride content must be less than 3 ppm; first 3' (1 m) of supply line must be rated for 212 °F (100 °C)
Two keyholes for wall mounting, 16" (406 mm) on center
Water supply line
Strainer, by installer
If water piping to humidifier is non-metallic, we recommend a 2" (50 mm) water seal in the supply line to isolate steam during DI/RO water system maintenance
¾" NPT (DN20) tank drain and P-trap piping, rated for 212 °F (100 °C); if piping run is over 10' (3 m) increase pipe to 1¼" (DN32) after P-trap
1" (25 mm) air gap
Spill funnel. Plumb to floor drain
Unions by installer
12"
(300 mm)
Open floor
drain. Refer
to local codes for drain
pipe size and maximum
temperature requirements.
Steam vapor hose (maximum run 10' [3 m]). May also use pipe or tubing
2" (50 mm)
¾" NPT (DN20) frame drain and P-trap piping, rated for 212 °F (100 °C)
Frame drain
Install plumb
Electrical conduit knockouts provided top and bottom:
• Combination, for ½" and ¾"conduit connectors (knock­out diameters
22.3 mm and
28.6 mm)
• Combination, for ¾" and 1" conduit connectors (knock­out diameters
28.6 mm and
34.9 mm)
Cover
DC-1139
Notes:
• Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet.
• Dashed lines indicate provided by installer.
• The water supply inlet is more than 1" (25 mm) above the overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required, however, local codes prevail.
• Install a union in the water supply line as shown to allow tank removal.
8
VAPORMIST®WIRING
VAPORMIST wiring
All wiring must be in accordance with all governing codes, and with the VAPORMIST or VAPORMIST DI wiring diagram. The diagrams are located inside the removable subpanel cover on the right side of the humidifier cabinet. Power supply wiring must be rated for 105 °C.
When selecting a location for installing the VAPORMIST, avoid areas close to sources of electromagnetic emissions such as power distribution transformers.
The use of semiconductor fusing sized per the National Electric Code is recommended with the SSR option.
Grounding requirements
The earth must be made by solid metal to metal connections. The ground must be a good radio frequency earth. Ground wire should be same size as power wiring.
Shielded/screened cable drain wire connection to lug
Field wiring requirements
Power supply
Fused disconnect (provided by installer)
(provided by installer)
OM-1007
Note: Control wiring and power wiring must be run in dedicated or separate earthed metal conduit, cable trays or trunking.
VAPOR-LOGIC keypad on front of cabinet
Microprocessor board
3
Right side view of VAPORMIST
OM-1505
Shield/screen ground lug
Note: For maximum EMC effectiveness, all humidity, temperature, and airflow controls should be wired using multicolored shielded/screened plenum-rated cable with a drain wire for the shield/screen. The drain wire should be connected to the shield/screen ground terminal with its length kept to less than 2".
9
VAPORMIST® DISPERSION
SDU-I: Provides instant, internal absorption
The Space Distribution Unit Internal Absorption (SDU-I) disperses humidity with no visible vapor trail or wetness, making the VAPORMIST® with an SDU-I ideal for use in finished spaces. When room RH is 45% or less, the SDU-I fan mixes room air and steam to ensure complete absorption before discharge as humidified air. The SDU-I is available for models VM-2 through VM-8, and all VM-10 models except those using 240 V, three-phase power with SSR control.
SDU-E: For higher capacity units
The Space Distribution Unit External Absorption (SDU-E) is designed for higher capacity dispersion. The SDU-E is available for all VAPORMIST models except those models using 240V/480V/600V/three­phase power with the SSR control option and drawing more than 21.7 amps.
Mounting the SDU-I and SDU-E
Both SDUs may be mounted on a wall directly above the VAPORMIST cabinet or mounted on a wall remote from the VAPORMIST. Use the mounting template on the box for correct placement. Two lag bolts are provided with each fan unit.
The SDU can be mounted directly above the VAPORMIST.
Air intake vents
Steam outlet
OM-55-1
The SDU can be mounted remotely from the VAPORMIST.
Note: See the following pages for more information about SDU-I and SDU-E.
SDU field wiring
OM-56-1
SDU-E
Field wiring for fan and airflow proving switch
VAPORMIST
Electrical panel right side view
10
OM-921
Loading...
+ 22 hidden pages