• 1" or 2" NPT (DN25 or DN50),
determined by maximum steam
capacity
• 3" (DN80) fl ange, for humidifi cation
steam from STS humidifi er only
3/4" NPT (DN20)
1/2" NPT (DN15)
3/4" NPT (DN20)
• 1" (DN25) connection, same as
dimension A;
• 2" (DN50) connection, dimension A
+ 1" (dimension A + 25 mm)
• 3" (DN80) fl ange, dimension A +
6.5" (dimension A + 165 mm)
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
1
Page 4
INSTALLATION
Field assembly
UNPACK THE DISPERSION ASSEMBLY
• Remove shipping materials from the dispersion assembly, being careful not
to bump or scrape the white PVDF dispersion tube insulation.
• Do not lay dispersion tubes (if shipped loose by request or by shipping
necessity) across or under anything that could compress or damage the
insulation. Compressing insulating material may reduce its R-value.
VERIFY THAT THE ORDER IS COMPLETE
Verify that all panel and piping components are included in the delivery. Check
the packing list, and see the tables on Page 32.
• Orders may include control valve(s), humidity transmitters or humidistats,
airfl ow switches, and a control cabinet.
Note the dispersion assembly serial number:
• The serial number will be required to ensure proper identifi cation of
replacement parts.
CAUTION
Remove clear poly fi lm; do not remove white PVDF insulation.
High-Effi ciency Tubes are sleeved in clear poly fi lm for protection during processing, shipping, and
installation. Leave the clear poly fi lm on until installation is complete so the insulation stays clean.
Remove and discard the clear poly fi lm before start-up by tearing it along the
perforations. Do not remove the white PVDF insulation.
• Keep fl ame away from the insulating material to avoid damage.
• Indirect, low-intensity UV-C light from germicidal lamps will not cause the insulating material to degrade.
• Do not tighten mounting clamps or fasteners to any part of the dispersion tube.
mc_071211_1530
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
2
Page 5
Field assembly
INSTALLATION
LAY OUT THE PANEL COMPONENTS
Orient the panel components on a large, fl at working surface.
ATTACH THE FLANGES
Guide the fl anges onto the threaded studs of the header assembly, and start the
locknuts onto the threads fi nger-tight.
ATTACH THE TOP FRAME ASSEMBLY
Span the fl anges with the top frame assembly. Align the locating buttons on the
fl anges and top frame, and insert screws.
TIGHTEN THE FLANGE LOCKNUTS
Torque the eight fl ange locknuts to 16 ft-lb (22 N-m) using a 7/16" deep-well
socket.
INSTALL THE DISPERSION TUBES
Note: Do not remove the poly fi lm from the dispersion tubes until after the
panel is installed.
Ensure that each dispersion tube has the seal and spring in place (see
Figure 3-1). Push the dispersion tube plug end into the top frame hole
to compress the spring. Seat the seal end in the corresponding header hole
on the bottom. Rotate the dispersion tubes so the tubelets discharge steam
perpendicular to the airstream. See Figure 9-1.
Note: These assembly instructions are for
Ultra-sorb Model XV panels shipped
unassembled by request or as required.
Panels with overall height more
than 98" (2490 mm) are shipped
unassembled.
FIGURE 3-1: ULTRA-SORB MODEL XV COMPONENTS
Screw
Top frame
assembly
Spring
Flange
Flange
locknut
Header
assembly
OM-7484
Plug
Ring
Seal
Dispersion tube
assembly
Insulation
Table 3-1:
Ultra-sorb Model XV components
ComponentQty.
Header assembly1
Dispersion tubeVaries
Top frame assembly1
Flanges2
Screws8
Flange locknuts8
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
3
Page 6
INSTALLATION
Piping
FIGURE 4-1: ULTRA-SORB MODEL XV PIPING COMPONENTS WITH ON/OFF
SHUTOFF VALVE, FLOAT SWITCH, PRESSURIZED STEAM SOURCE
Applications with control
cabinet operating internal
heat exchanger.
From
pressurized
steam source
Install inlet strainer within
3' (1 m) of Ultra-sorb
Model XV. Strainer
should be same pipe size
or larger than modulating
steam valve. 2-position
shutoff valve may be
smaller than strainers and
modulating steam valve.
To condensate return main
Note: Dashed lines indicate provided by installer.
FIGURE 4-2: ULTRA-SORB MODEL XV PIPING COMPONENTS WITH TEMPERATURE
SWITCH, PRESSURIZED STEAM SOURCE
2-position
shutoff valve
Modulating steam
valve
Steam trap
Ultra-sorb Model XV
steam dispersion panel
Float switch
To condensate
return main
Applications with full-time
operation of internal heat
exchanger.
Steam
trap
OM-7656d
From
pressurized
Install inlet strainer
within 3' (1 m) of
Ultra-sorb Model
XV. Strainer should
be same pipe size
or larger than
modulating steam
valve. 2-position
shutoff valve may
be smaller than
strainers and
electric modulating
steam valve.
To condensate return main
Note: Dashed lines indicate provided by installer.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
4
steam source
Modulating
steam valve
Steam trap
To condensate return main
Ultra-sorb Model XV
steam dispersion panel
Temperature switch
(install as close to heat
exchanger outlet as
possible)
Steam trap
OM-7878
Page 7
Piping
FIGURE 5-1: ULTRA-SORB MODEL XV PIPING WITH STS HUMIDIFIER
Steam to heat exchanger from pressurized steam source,
humidifi cation steam from STS humidifi er
Insulated steam
supply tubing
Cold fi ll water
Steam trap
STS humidifi er
Modulating
steam valve
Inlet
strainer
Isolation valve (by others)
From pressurized steam source
Connection
end of
header
(see inset
below)
Header
On/off valve
(optional)
Pressurized steam to heat exchanger
Pressurized condensate to return main
Dispersion tube
INSTALLATION
Ultra-sorb XV dispersion panel
OM-7902
Open drain
(temper to local code)
Steam trap
To condensate return main
Drane-kooler™ water
tempering device
Steam trap
Pressurized condensate to return main
Connection end of header
Humidifi cation steam
from STS humidifi er
From pressurized
steam source
On-off
solenoid
valve
Float switch
OM-7654_2016
Note: Tubing union shown at steam connection. For STS humidifi er,
connection may also be 3" (DN80) fl ange.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
5
Page 8
INSTALLATION
Selecting the location
FIGURE 6-1: PLACING A DISPERSION ASSEMBLY IN AN AIR HANDLING UNIT
Outside air
Exterior
building
wall
Relief air
Economizer
control device
Preheat coil
Motorized
air dampers
Filters
Return airfl ow
Cooling coil
Heating coil
ABD
3' to 5' (1 to 1.5 m)
10' to 15' (3 to 4.5 m)
10' to 15' (3 to 4.5 m)
Duct high limit humidity control
for dispersion locations A, B
Airfl ow proving switch
Fan
C
DC-1081
mc_092507_1530
Supply airfl ow
Airfl ow proving switch
Duct high limit humidity control
for dispersion location C
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
6
Page 9
Selecting the location
DETERMINE STEAM DISPERSION PANEL PLACEMENT
Dispersed steam must be absorbed into the airfl ow before it comes in
contact with duct elbows, fans, vanes, fi lters, or any object that can cause
condensation and dripping.
• Install the Ultra-sorb panel in a location where discharged water vapor will
be absorbed by the airstream.
• Place the Ultra-sorb panel where the air temperature is capable of
absorbing discharged steam without causing condensation at or after the
unit. This will normally be downstream of the heating coil where the air is
warmest.
• Do not place the Ultra-sorb panel in an outside air intake unless the air is
fi rst tempered with a preheat coil.
• Do not place the Ultra-sorb panel near the entrance of a high-effi ciency
fi lter. The fi lter will remove visible moisture and become waterlogged.
See the Caution “Installing Ultra-sorb upstream from fi lter media” on Page
28.
INSTALLATION
• Do not place the Ultra-sorb panel where discharged visible mist will
impinge directly on a metal surface.
PLACEMENT IN AN AIR HANDLING UNIT (FIGURE 6-1)
• Location A is the best choice. Installing downstream of heating and cooling
coils provides the most even fl ow through the dispersion unit; plus, the
heated air provides an environment for best absorption.
• Location B is the second-best choice. However, in change-over periods, the
cooling coil will eliminate some moisture for humidifi cation.
• Location C is the third-best choice. Air leaving a fan is usually very turbulent
and can cause vapor to not absorb at the expected non-wetting distance.
Allow for more distance if installing downstream of a fan.
• Location D is the poorest choice. The cooler air at this location requires an
increased non-wetting distance.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
7
Page 10
INSTALLATION
Mounting and support
INSTALLATION IN A COLD AIR STREAM
When a steam dispersion panel is installed in a duct that will carry cold air,
determine the dew point temperature. If the psychrometric chart reveals that
saturation may occur, protection should be provided. A high-limit humidistat or
thermostat set to cut off the steam dispersion panel at a safe temperature can
be used for this purpose. See Figure 8-1.
PLACEMENT UPSTREAM FROM AN ELBOW OR DUCT SPLIT
Due to Ultra-sorb's rapid steam absorption performance, installation upstream
from elbows or duct splits can be done with confi dence. See Figure 8-2.
INSTALLATION ABOVE VALUABLE EQUIPMENT
Water piping and humidifi ers should not be installed above expensive
equipment. A condensing or leaking water pipe or other accidental water
spillage could cause serious damage to the equipment below. When such
an installation cannot be avoided, install a galvanized drip pan under the
humidifi er piping, valve, etc. to catch and drain away unintended water. See
Figure 8-3.
See also “Optional header overfl ow P-trap water seal” on Page 17.
PANEL SUPPORT
The duct or air handler section and Ultra-sorb panel must be properly
supported to carry the weight of the assembly. The weight of the piping must
be supported by the building structure rather than by the Ultra-sorb unit.
Otherwise, the weight may impose stress on the connections, causing them to
fracture and leak.
mc_071311_1540
FIGURE 8-1:
INSTALLATION IN A COLD AIR STREAM
Extended trails of
Cold
air
fl ow
High limit duct humidistat 10' to 15'
(3 to 4.5 m) downstream from Ultra-sorb
OM-197
mc_052411_0830
FIGURE 8-2: UPSTREAM PLACEMENT
Airfl ow
Airfl ow
FIGURE 8-3:
INSTALLATION ABOVE VALUABLE
EQUIPMENT
Ultra-sorb
Airfl ow
Ultra-sorb
Ultra-sorb
Ultra-sorb
OM-178
fog may develop
Elbow
Non-wetting
distance
Duct split
Vapor absorption
Duct
area
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
8
Drip pan
Pipe to drain size as required
OM-198
* This length of duct should have sealed seams
and should be at least three times the height
of the Ultra-sorb panel.
mc_101410_0955
2" (50 mm)
Ceiling line
Page 11
Mounting and support
INSTALLATION
Where allowed, screws and drill bits must not penetrate more than 3/4" (20
mm) into the header assembly. See Figure 10-1 for allowable drill and
screw locations.
Ultra-sorb Model XV must be installed in horizontal airfl ows only.
MOUNTING IN A DUCT
Mounting fl anges on both sides of the unit and the header and frame can be
used as mounting surfaces (see Figure 10-1). A matching fl ange or metal frame
is required on the ductwork for connection to the Ultra-sorb fl anges. Use a #12
self-drilling and tapping screw 3/4" (20 mm) long, spacing not to exceed 12"
(305 mm). If an angle-iron frame is provided on the duct section, a longer
screw may be required.
MOUNTING IN AN AIR HANDLER
Metal support frames should be anchored to the air handler casing. When
mounting the Ultra-sorb to a metal support frame, use 1/4 - 20 nuts and bolts
or #12 self drilling and tapping screws. Fastener spacing should not exceed
6" (150 mm).
FIGURE 9-2: PREVENTING DUCT AIR LEAKS
Duct smoke detector
Do not install a duct smoke detector
downstream from the Ultra-sorb panel. If
downstream installation is required, install it far
enough from the Ultra-sorb panel to avoid false
alarms.
Dispersion tube orientation
Verify that the steam discharge tubelets are
perpendicular to the airstream (see Figure
9-1). The spring-loaded dispersion tubes
easily rotate for proper orientation.
FIGURE 9-1:
DISPERSION TUBE ORIENTATION
TubeletDispersion tube
Airfl ow
Airfl ow
OM-150a
Perimeter of top frame along duct fl ange
Four inside corners
Ultra-sorb panels that penetrate a duct section
must be sealed with HVAC caulking or a similar
weather sealant to prevent air leakage. Panels
should be sealed at locations shown.
Top outside corners
Both sides of cover seam
OM-7482
mc_101410_0845
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
9
Page 12
INSTALLATION
Installation drawings:
FIGURE 10-1: ULTRA-SORB MODEL XV IN A DUCT (HORIZONTAL AIRFLOW ONLY)
2. Steam supply line to unit and piping are not included.
3. Dispersion tubes are available on 3", 4", 6", 9" and 12" (76, 102, 152, 229, and 305 mm) centers.
4. Ultra-sorb steam dispersion panels will be assembled, crated, and shipped intact in all sizes up to 98" (2490 mm) overall height. Any Ultra-sorb
can be shipped unassembled by request, requiring fi eld assembly.
5. Standard sizes are 12" x 12" up to 144" x 144" in 1" increments (305 x 305 mm up to 3660 x 3660 mm in 25 mm increments). Larger sizes are
available.
6. Install the panel level. If slope cannot be avoided, ensure that the slope is toward the drain end of the panel.
7. Drill or screw through the header assembly only where shown.
Screws and drill bits must not penetrate more than 3/4" (20 mm) into the header assembly. Use 1/4–20 nuts and bolts or #12 self drilling and
tapping screws for mounting the Ultra-sorb to a metal support frame.
3/4" (20 mm) max length (See Note 7)
Add center support required for all units
greater than 60" (1524 mm) wide.
No screws through bottom
of header assembly
assembly
1/2" (13 mm)
No screws
through end of
header assembly
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
10
Page 13
Mounting in an air handlerInstallation drawings:
FIGURE 11-1: ULTRA-SORB MODEL XV IN AN AIR HANDLER (HORIZONTAL AIRFLOW ONLY)
• 1" or 2" NPT
(DN25 or DN50),
determined by
maximum steam
capacity
• 3" (DN80) fl ange,
STS humidifi er
connection only
Coil
height
INSTALLATION
AHU
height
Tubelets perpendicular to airfl ow
AHU wall
Humidifi cation steam to header
Add center support required for all units
Steam from pressurized steam
source to heat exchanger
Notes:
1. Dashed lines indicate provided by installer.
2. See Figures 12-1 and 12-2 for trap clearance alternatives.
3. Steam supply line to unit and piping are not included.
4. Dispersion tubes are available on 3", 4", 6", 9" and 12" (76, 102 152, 229, and 305 mm)
centers.
5. Ultra-sorb steam dispersion panels will be assembled, crated, and shipped intact in all sizes
up to 98" (2490 mm) overall height. Any Ultra-sorb can be shipped unassembled by request,
requiring fi eld assembly.
6. Standard sizes are 12" x 12" up to 144" x 144" in 1" increments (305 x 305 mm up to 3660
x 3660 mm in 25 mm increments).
Larger sizes are available.
• Metal support frames should be anchored to the air handler casing.
• Drill or screw through the header assembly only where shown in Figure 10-1. Screws and drill
bits must not penetrate more than 3/4" (20 mm) into the header assembly.
• Use 1/4–20 nuts and bolts or #12 self drilling and tapping screws.
• Fastener spacing should not to exceed 6" (150 mm).
• When Ultra-sorb Model XV is installed in bypass air applications provide additional bracing for
the unsupported side(s).
• Install the panel level. If slope cannot be avoided, ensure that the slope is toward the drain end
of the panel.
Pressurized
condensate out to
return main
greater than 60" (1524 mm) wide.
Header
OM-7657a
CAUTION
Use a backup wrench
Use a backup wrench on all
plumbing connections. Failure to
use a backup wrench could cause
damage to the Ultra-sorb Model XV.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
11
Page 14
INSTALLATION
Recommendations and steam inlets
RECOMMENDATIONS
Trapping - steam supply and pressurized condensate return
• Low pressure, up to 15 psi (103 kPa) — fl oat and thermostatic (steam)
trap (Figure 12-1)
• High pressure, more than 15 psi (103 kPa) — inverted bucket trap
(Figure 12-2)
• Lifting condensate — Steam trap (up to 15 psi/103 kPa) or inverted
bucket trap (Figure 12-3)
Driest steam
To ensure driest steam, take humidifi er steam off the top of the steam main
(not the side or bottom).
Airfl ow proving switch
Use an airfl ow proving switch to prevent humidifi cation steam from entering
the header if air is not moving in the duct.
High limit humidistat
To prevent over saturation use a high limit (duct mounted) humidistat (Figure
6-1). Mount it 10' to 15' (3 to 4.5 m) downstream from the Ultra-sorb
panel, and set it at 80 to 90% RH.
HEAT EXCHANGER PRESSURIZED BOILER STEAM INLET (SEE FIGURE 11-1)
Steam pressure for steam entering the heat exchanger must be least 5 psig
(35 kPa) to vaporize condensate in the header.
Integral heat exchanger
• Ultra-sorb Model XV employs an integral
heat exchanger to pressurize and lift
condensate up to 12" per psi (300 mm
per 6.9 kPa) of steam pressure.
• Steam pressure entering the heat exchanger
must be at least 5 psig (35 kPa).
• Condensate may be piped to the condensate
return main.
FIGURE 12-1: ULTRA-SORB MODEL XV
STEAM TRAP DIMENSIONS
6" (152 mm) Steam trap clearance
Note: Dashed lines indicate provided by
installer.
OM-7655
FIGURE 12-2: LIFTING CONDENSATE WITH ULTRA-SORB MODEL XV
Elevated condensate
return main
Ultra-sorb XV steam
dispersion panel
Modulating
2-position
shutoff control
valve
Inlet
strainer
control valve
OM-7879
Steam trap
Check valve
(by others)
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
12
Page 15
Controls
CONTROL OPTIONS
CONFIRMING STEAM DISPERSION PANEL CONFIGURATION
The Ultra-sorb XV steam dispersion panel utilizes a built-in heat exchanger to
evaporate condensate generated in the humidifi cation process. For maximum
energy effi ciency, this requires a unique control sequence that operates a
2-position shutoff valve for the heat exchanger, in addition to a modulating
valve for humidifi cation control. A fl oat switch in the steam dispersion panel
header, along with control sequence timings assure effective condensate
management along with humidifi cation output based on demand.
Control options are described in Table 16-1.
CONTROL OPTION #1 - DRISTEEM CONTROL CABINET
The Ultra-sorb XV dispersion panel is provided with controls by DriSteem.
Operation of both the 2-position shutoff valve, and modulating control valve
is coordinated by the electronic controller provided in the DriSteem control
cabinet. A demand signal or space RH is sent to the DriSteem controller, and
the controller opens/closes the two steam valves based on the signal and
inputs including the steam dispersion panel fl oat switch, and (optionally) a duct
air fl ow switch and humidity high limit control.
Note: The Ultra-sorb XV control cabinet utilizes the same control board as other
DriSteem products, when confi gured as a Vapor-logic controller. The Ultra-sorb
XV application fi rmware is different from Vapor-logic control. Board wiring
terminal connections do not have the same functions as used for the Vaporlogic controller. Please refer to the wiring diagram included with the unit for
proper wiring. Field confi guration of the Ultra-sorb XV board is as described
in the following paragraphs. Adjust the Vapor-logic control signals and setting
from the Vapor-logic keypad interface or web server. Refer to the Vapor-logic
IOM for further details.
INSTALLATION
WARNING
Electric shock hazard
Only qualifi ed electrical personnel
should perform fi eld wiring installation
procedures. Improper wiring or contact
with energized circuits can cause
property damage, severe personal
injury, or death as a result of electric
shock and/or fi re.
Do not open control cabinet or
subpanel access panels until electrical
power is disconnected.
CAUTION
Damage from debris
When drilling penetrations in the
control cabinet, protect all internal
components from debris, and vacuum
out the control cabinet when fi nished.
Failure to comply with this directive
can damage sensitive electronic
com po nents, cause erratic operation
or failure, and void your DriSteem
warranty.
Important:
Failure to follow these wiring procedures can
result in erratic operation or failure.
This product has been tested at the factory for
proper operation. Product failures resulting from
faulty handling, incorrect wiring, or shorting of
wires together on external components are not
covered under your DriSteem warranty. Review
information and di a grams before proceeding.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
13
Page 16
INSTALLATION
Controls
FLOAT SWITCH
Wire the fl oat switch to the DriSteem control cabinet. A wiring diagram is
included with the unit.
Under normal conditions the float switch in the Ultra-sorb Model XV header
is closed, and the modulating steam valve or STS humidifi er operates
according to the humidifi cation control system’s call for humidity. In the
event condensate levels rise in the humidifi er header, the fl oat switch rises
and the circuit opens, activating a condensate mitigation sequence. Refer
to the sequence of operation on page 33.
If you suspect problems with the fl oat switch operation, see float switch
maintenance instructions on Page 31. These instructions must be
followed for the float switch to function properly.
AIR FLOW SWITCH
Air fl ow indication is required. Indication can be provided by a BAS input
or air fl ow switch wired to the DriSteem control cabinet. Wire the air fl ow
switch to the DriSteem control cabinet as shown in the diagram included
with the unit. The steam dispersion panel will not run if the air fl ow switch
input of the DriSteem controller is left open. A circuit-closing jumper is
provided on the controller board input and must be removed to the air fl ow
input.
HIGH LIMIT HUMIDISTAT
Wire the duct high limit humidistat to the DriSteem control cabinet. Refer to
the Vapor-logic external connections diagram or the Vapor-logic IOM for
wiring instructions.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
14
Page 17
Controls
CONTROL OPTION #2 – ELECTRIC TEMPERATURE SWITCH ONLY; CONTINUOUS HEAT
EXCHANGER OPERATION
The DriSteem control cabinet is not provided. An electric modulating control
valve is controlled by a 2-10 VDC/4-20 mA signal from a control system (BAS)
or modulating humidistat. Optional air fl ow switch, high limit humidistat are
wired in series with 24 VAC control circuit of the modulating control valve. See
the wiring diagrams provided with the unit.
ELECTRIC TEMPERATURE SWITCH
Install the temperature switch (Figure 20-1) to prevent the header
from flooding with condensate if the heat exchanger cools, such as if
the condensate return main becomes flooded or the trap fails closed.
DriSteem's temperature switch is a temperature-actuated make-break
switch. The temperature at which it switches is adjustable and should be
set at 210 °F (99 °C).
INSTALLATION
• Install the sensing element of the temperature switch in the condensate
return piping between the Ultra-sorb heat exchanger outlet and the
inlet to the steam trap, as shown in Figure 20-1. Include a tee with
a 1/2" (DN15) pipe thread opening to receive the sensing element.
When steam surrounds the sensing element, the switch will “make,”
allowing the steam dispersion panel valve to open.
• Install all wiring according to national and local electrical codes, and
size transformer VA to load VA.
• When using a temperature switch to control the on-off heat exchanger
valve, follow the wiring instructions supplied with the modulating
humidification-steam control valve.
CONTROL OPTION #3 – PNEUMATIC TEMPERATURE SWITCH ONLY; CONTINUOUS
HEAT EXCHANGER OPERATION
The DriSteem control cabinet is not provided. A pneumatic modulating control
valve is sent a 3-15 PSI signal from a pneumatic humidistat or other pneumatic
device, to modulate the valve based on humidity demand.
• The 2-position shutoff valve is not used. Steam supply to the panel’s
internal heat exchanger is continuous.
PNEUMATIC TEMPERATURE SWITCH
Install the pneumatic temperature switch as shown in (Figure 20-2). The
temperature switch will prevent the header from flooding with condensate
by closing the modulating steam valve if the heat exchanger cools (if
the condensate return main becomes flooded or the trap fails closed).
DriSteem's pneumatic temperature switch is a temperature-actuated openclosed pneumatic switch. The pneumatic signal (3-15 PSI) is maintained
above 210°F (99°C) and is opened (bled off) below 200°F (93°C).
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
15
Page 18
INSTALLATION
Controls
CONTROL OPTION #4 – CONTROLS BY BAS/CONTROLS CONTRACTOR
The BAS or controls contractor will provide the necessary controller and
programming logic to sequence the steam dispersion panel valves as
described for Control Option #1. This includes providing control outputs for the
modulating control valve and 2-position shutoff valve. Refer to the BAS controls
contractor wiring diagrams for specifi c valve and fl oat switch connection
terminals.
Table 16-1:
Boiler steam application control options
Heat exchanger and humidifi er
control option
Control Cabinet with time delay
(#1)
Coordinated Heat exchanger and
humidifi cation control through
DriSteem control cabinet.
2-position shutoff
valve
Electric - Wired to
DriSteem control
cabinet
Modulating control
valve
Electric - Wired to
DriSteem control
cabinet
Float switch in header
Yes - Wired to control
cabinet
Temperature switch at
condensate outlet
No
(optional)
DriSteem control
cabinet
Yes
Temperature switch only
(Electric)
(#2)
The heat exchanger operates
continuously (100%). Electric
temperature switch opens, shutting
off the power to the modulating
valve if the condensate backs up in
the heat exchanger (failed trap).
Temperature switch only
(Pneumatic)
(#3)
The heat exchanger operates
continuously (100%). Pneumatic
temperature switch opens, closing
the modulating valve if the
condensate backs up in the heat
exchanger (failed trap).
BAS Control
(#4)
Controls by BAS/controls
contractor; Contractor to provide
and follow control sequence of
Control Option #1
®
Control by STS
(#5)
Control by STS humidifi er
humidifi er
Not UsedElectricNoYes- ElectricNo
Not UsedPneumaticNoYes - PneumaticNo
Electric - Wired to
BAS controller
Optional if chosen
with Ultra-sorb XV
Electric - Wired to
BAS controller
Chosen for inlet
to STS - Electic or
Pneumatic
Yes - Wired to BAS
controller
Yes - Wired to STS
humidifi er
Vapor-logic®
controller
No
(optional)
Optional if chosen
with Ultra-sorb XV
No - Control provided
No
by STS humidifi er
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
16
Page 19
Controls
OM-7
493
INSTALLATION
ULTRA-SORB XV WITH DRISTEEM STEAM-TO-STEAM (STS) HUMIDIFIER
If the Ultra-sorb XV panel is used in conjunction with a DriSteem Steam-toSteam (STS) humidifi er, atmospheric steam generated from the STS is piped
to the Ultra-sorb XV and distributed through the dispersion header to the
humidifi er tubes.
Pressurized boiler steam (5 PSI minimum), as used to source the STS unit heat
exchanger, is also used to operate the Ultra-sorb XV internal heat exchanger
enabling condensate evaporation in the humidifi er panel header. See Figure
5-1 for piping connections.
Optional Ultra-sorb XV control devices are located as shown in Figure
5-1 and wired to the Vapor-logic controller provided with the associated
STS humidifi er. Devices may include a 2-position solenoid valve for XV heat
exchanger control, and fl oat or temperature switch(es).
• Refer to the wiring diagram provided with the STS unit for wiring
connections.
OPTIONAL HEADER OVERFLOW P-TRAP WATER SEAL
Ultra-sorb Model XV is designed to vaporize the condensate generated in a
properly designed, installed, operated, and maintained system. An optional,
header overfl ow p-trap (Figure 17-2) is recommended if any of the following
are true:
FIGURE 17-1: ULTRA-SORB MODEL XV
CONTROL CABINET
12" (305 mm)
12" (305 mm)
OM-7533
6" (152 mm)
Notes:
• Electrical power requirements: 120 VAC,
1.0 Amps, or 230 VAC, 0.5 Amps
• Components are 24 VAC, powered by
a transformer in the control cabinet. 50
VA available from internal transformer for
operation of two 24 VAC control valves.
• Maximum distance from control cabinet to
Ultra-sorb Model XV is 50’ (15 m).
• There is not a fl oat switch installed in the dispersion panel header.
• Boiler chemicals are causing heavy material deposition on heat exchanger.
Before operating the Ultra-sorb, and after extended shutdown periods, prime
the P-trap with about 1 cup (200 mL) of water. A water seal cannot be assured
via condensate generated within the humidifi er header. Do not feed the P-trap
with a water source to maintain prime, as this will force water into the header.
FIGURE 17-2: ULTRA-SORB MODEL XV
OPTIONAL HEADER OVERFLOW P-TRAP
WATER SEAL
Connection end of header
Connect optional P-trap
overfl ow water seal if
fl oat switch is not used.
1.25" (32 mm) rise
Fill cap
12" (305 mm) seal
OM-7493
Note: After the water seal, run a 1½" (DN40)
drain line to an open drain with a 1"
(25 mm) air gap. Water seal must
cover height of internal heat exchanger
tube as shown to provide condensate
evaporation in normal operating
conditions.
10.75" (273 mm)
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
17
Page 20
INSTALLATION
Controls
FIGURE 18-1: CONTROL CABINET
Status LED
Controller board
Wiring
terminal
block
120/208/240/480V to 24 VAC transformer, 75 VAC
OM-7882
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
18
Page 21
Ultra-sorb XV operation
OPERATION
1. STEAM SUPPLY INLET
Humidifi cation steam from the modulating steam valve (Figure 4-2) or
STS humidifi er (Figure 19-1) passes through the steam supply inlet into the
Ultra-sorb header.
2. HEADER
Humidifi cation steam fl ows through the insulated header, up the High-
Effi ciency Tubes, and into the airstream.
3. HEAT EXCHANGER
Pressurized steam enters the heat exchanger inlet. The heat exchanger
vaporizes dispersion-generated condensate, while pressurized condensate
returns to the boiler via the condensate return main.
FIGURE 19-1: ULTRA-SORB MODEL XV
WITH STS; STEAM INLETS DETAILED
Humidifi cation
steam from STS
steam-to-steam
humidifi er
From
pressurized
steam source
OM-7654-inlets
Note: Dashed lines indicate
provided by installer.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
19
Page 22
OPERATION
Ultra-sorb XV operation
TEMPERATURE SWITCH
The temperature switch circuit’s sequence of operation is a safety sequence: In
the unlikely event that excessive header condensate cools the heat exchanger
while humidifying, the temperature sensor drops below operating temperature,
and the switch opens. This signals the modulating steam valve or STS
humidifi er control system to stop humidifi cation steam from entering the header
and prevents further condensate production.
See the temperature switch sensor in Figure 20-1 and Figure 20-2.
FIGURE 20-2: PNEUMATIC TEMPERATURE SWITCH
Pneumatic
temperature
switch
Pneumatic
valve
Restrictor
.007 dia.
orifi ce
Pneumatic
supply by
others 0-20
psi (0-138
kPa)
XV-4
FIGURE 20-1: ELECTRIC TEMPERATURE
SWITCH
Electric temperature switch
(install as close to heat
exchanger outlet as possible)
Note: Dashed lines indicate
provided by installer.
OM-7536
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
20
Page 23
Sequence of operation
FIGURE 21-1: CONTROL COMPONENTS - CONTROL OPTION #1
OPERATION
Ultra-sorb XV steam
dispersion panel
Modulating control valve
2-position (ON/OFF) shutoff
control valve with end switch
Inlet strainer
Float switch
Control cabinet
2-10V/4-20mA
humidifi cation
demand signal
from BAS or
humidistat
Important: If the steam valve and heat exchanger control is to be provided
directly by a separate BAS controller (Control Option #4 without use of
DriSteem control cabinet), inputs and valve output controls must be linked to a
BAS controller and sequenced as described below.
120V/230V
1 amp/0.5 amp power
Diagnostic/
alarm output(s)
to BAS (optional)
Trap
OM-7880
DRISTEEM CONTROL CABINET INCLUDING 2-POSITION SHUTOFF VALVE AND FLOAT
SWITCH
The following control sequence is accomplished through use of the DriSteem
control cabinet to provide maximum energy effi ciency and operational
reliability, through proper timing of operation of the 2-position (on-off) shutoff
valve, and modulating control valve. Required inputs include demand signal,
and safety interlocks of air fl ow and header/heat exchanger fl oat switch.
1. Upon air handling unit startup (Occupied Mode), air flow switch enables
2-position (On-Off), normally closed, spring return shutoff valve actuator.
Start/stop of fan provided by BAS or other control command.
a. If air fl ow interlock is provided by BAS, then the BAS must provide a
contact closure to the DriSteem control cabinet air fl ow switch input.
2. The 2-position (On/Off) shutoff valve opens only if air flow is detected,
and if demand for humidification is present.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
21
Page 24
OPERATION
Sequence of operation
3. Humidification demand is provided by a control signal to the DriSteem
control cabinet. When the demand signal is sufficient, steam will flow to
1) the internal heat exchanger and 2) the modulating control valve that
provides steam output based on demand.
4. As the 2-position shutoff valve opens (approx. 75 seconds), the heat
exchanger in the steam dispersion panel begins operating. The heat
exchanger will continue to operate any time there is duct air flow and
humidification demand.
5. The shutoff valve actuator includes an end switch that enables the
modulating control valve if the shutoff valve is over 90% open. The end
switch of the shutoff valve actuator is wired to an input of the steam
dispersion panel controller. If the input is not made, the modulating control
valve will remain closed.
6. If the shutoff valve does not reach 90% open after 4 minutes (determined
by actuator end switch), the steam dispersion panel controller will close the
shutoff valve and activate a failure alarm contact on the control board, and
provide LED alarm indication on the controller. See Figure 21 [DriSteem
alarm point to be wired to BAS as specified.]
7. When the steam dispersion panel controller verifies the shutoff valve is
open, it allows the modulating control valve to modulate based on the
control signal, providing a 2-10 VDC signal from the control board to the
valve actuator. At low/no demand signal or space RH above setpoint and
outside the PID band, the valve is closed. At high demand or space RH
below setpoint, the valve opens. Modulating control valve is spring-return
to fail to the closed position.
8. When the air handling unit fan stops (Unoccupied Mode by command
of BAS, or other means) the air flow input wired to the steam dispersion
panel controller opens, and controller returns the modulating control valve
to the closed position.
9. After the modulating control valve is closed, the 2-position shutoff valve
remains open, to maintain steam flow through the heat exchanger for 15
minutes to evaporate any remaining condensate in the steam dispersion
panel header.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
22
Page 25
Sequence of operation
10. After fifteen minutes of heat exchanger operation, the 2-position shutoff
valve will close (Twenty-five second close time). The end switch of the
shutoff valve opens to assure the modulating control valve is closed
whenever the heat exchanger is off.
11. A float switch is located in the steam dispersion panel header, and wired
to the DriSteem controller. The switch circuit will open if condensate (water)
depth in the header rises 1/2” above the heat exchanger tube.
a. If the condensate level rises above the fl oat switch point, the controller
drives the modulating control valve closed, stopping steam fl ow and the
possibility of condensate generation.
12. The steam dispersion panel controller monitors the elapsed time starting
when a high condensate level occurs.
13. If the header condensate level falls below the float switch height, the
modulating valve will resume normal control as set by BAS/control input.
14. If the level remains at/above the switch, the modulating valve will remain
closed.
OPERATION
15. The time interval for condensate management will increase each time
the level is exceeded. The time provided to lower/evaporate condensate
is initially 2 minutes, and increases by 1 minute intervals each time the
condensate level is exceeded, to fifteen minutes maximum.
16. If the condensate level stays below the float switch for more than fifteen
minutes, the incremental timer will be reset.
17. If the incremental timer cycle (2 minutes through fifteen minute iterative
cycle) is exceeded, and if condensate has not remained below the
condensate level switch, the 2-position shutoff valve will be closed. The
controller will activate diagnostic outputs (1 NC/ 1 NO) to indicate
condensate clearing failure. (The controller provides on-board diagnostic
LED to indicate “Condensate Clearing Failure” (see page 25).
18. If the power is reset or interrupted to the unit the entire sequence will be
re-initiated.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
23
Page 26
OPERATION
Sequence of operation
FULL-TIME HEAT EXCHANGER OPERATION WITH ELECTRIC OR PNEUMATIC
TEMPERATURE SWITCH
With control options #2 and #3, a 2-position (On-Off) shutoff control valve
is not used (see Figure 4-2). The Ultra-sorb XV internal heat exchanger
operates any time pressurized steam is available to the dispersion panel. Install
the temperature switch downstream of the internal heat exchanger to prevent
operation of the modulating control valve if steam is not fl owing through the
heat exchanger.
1. Upon air handling unit startup (Occupied Mode), air flow switch enables
modulating control valve. Start/stop of fan provided by BAS or other
control command.
a. If air fl ow interlock is provided by BAS, then the BAS must provide a
contact closure in series with the modulating valve 24 VAC power circuit
as shown on the wiring diagram shipped with the Ultra-sorb panel.
2. Humidification demand is provided by a 2-10VDC/4-20mA signal from
BAS/control signal or humidistat, to the modulating control valve.
3. Internal heat exchanger operates continuously. A temperature switch
(electric or pneumatic) senses condensate temperature leaving the heat
exchanger. If the temperature at the outlet of the heat exchanger falls
below 210°F (99°C), the temperature switch closes the modulating control
valve to prevent condensate buildup in the steam dispersion panel header.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
24
Page 27
Sequence of operation
CONTROL CABINET STATUS LED
The control board within the control cabinet includes a large Status LED that
indicates multiple control conditions (see Figure 18-1). The Status LED
is always “blinking”. It will be easy to see that the board is powered and
operating because, at a minimum, it is running the Status LED. The blinking
will be in a 3-stage cycle starting from being dark, with the LED brightness
illuminating up to the fi rst stage of indication. Timing of the 3-stage cycle will
be over approximately four seconds.
CONTROL BOARD LED - DIAGNOSTIC CODES
First Blink (long):Wiring Interlocks
Green OK
Yellow Interlock circuit open: duct high RH limit or no air fl ow
Red On/Off shutoff valve: end switch failed to close
(Manual Reset- Cycle Power)
OPERATION
Second Blink: Condensate level status
Green OK
Yellow System clearing condensate (>1” depth in header)
Red Condensate clearing failure (Manual Reset- Cycle Power)
Third Blink: Humidifi cation demand
Blue No humidifi cation demand
Green Humidifi cation demand to controller
Yellow Clearing condensate: waiting to open control valve
Note: A list of the diagnostic codes are in the control cabinet.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
25
Page 28
OPERATION
Sequence of operation
CONTROL BOARD ALARM OUTPUTS
There are 2 dry contact outputs on the control board that can provide alarm
indications to a BAS or other control system.
• Terminals C-1 to NO-1 are normally open and close upon alarm
condition(s)
• Terminals C-2 to NO-2 are normally closed and will open upon alarm
condition(s)
The conditions under which the alarm conditions occur are:
• If the shutoff valve does not reach 90% open after 4 minutes (actuator end
switch), then the steam dispersion panel controller will close the shutoff
valve and activate the diagnostic alarm contact
• If the condensate timer cycle (2 minutes through 15 minute iterative cycle)
is exceeded, and if condensate has not remained below the condensate
level switch, the 2-position shutoff valve will be closed. The controller will
activate the diagnostic alarm contacts to indicate condensate clearing
failure.
Dry contacts are rated for 125 VAC, 3 AMP or 30 VDC, 3 AMP maximum.
Exceeding this maximum rating can cause the dry contact (relay) component or
the control board to fail.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
26
Page 29
Start-up checklist
OPERATION
1. Ensure all component wiring and piping connections are complete as
shown in the wiring diagrams provided with the unit.
2. Create demand for humidification by providing a demand signal to control
cabinet option 1 or control valves options 2 and 3.
3. Prime the header overflow P-trap, if installed. Ensure that it is installed as
recommended in “Optional header overflow P-trap water seal” on Page
17.
4. Turn on steam to the heat exchanger. Inspect connections for piping leaks.
5. Turn on the modulating steam valve, and check for piping leaks.
6. Ensure that the traps are operating.
7. Check the dispersion tubes for leaks.
8. Ensure that the dispersion tubes are oriented with the tubelets at a right
angle to the airflow. See Figure 9-1.
9. Check for any other leaks from header connections.
10. If a temperature switch is installed (control options #2 or #3), with both
heat exchanger and humidification steam turned on, turn off steam to the
heat exchanger. Make sure the temperature switch turns off the modulating
steam valve to stop humidification steam from entering the dispersion
assembly. Depending on the installation, it may take several minutes for the
steam valve to close.
CAUTION
Remove clear poly fi lm; do not remove
white PVDF insulation.
High-Effi ciency Tubes are sleeved in
clear poly fi lm for protection during
processing, shipping, and
installation.
Tear the clear
poly fi lm along
the perforations,
and remove and
discard it before
start-up.
11. Heat exchanger operation:
• Ensure operating steam pressure is at least 5 psig (35 kPa).
• Ensure on-off and shut-off delay (15 minutes after non humidifi er demand
- control options #1 or #4) conditions are working as intended.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
27
Page 30
OPERATION
Performance data
NON-WETTING DISTANCE
Non-wetting distance is the dimension downstream from the leaving side of the
steam dispersion assembly to the point where wetting of other components will
not occur. Current design conditions may vary from conditions used for system
design.
• The rise in RH (ΔRH) between entering and leaving air has a direct bearing
on the non-wetting distance. As the ΔRH increases, more vapor needs to be
dispersed into the air; thus, the non-wetting distance increases.
• Uneven airfl ow over the Ultra-sorb panel cross-section may result in
nonuniform mixing of steam with air, which may increase absorption
distance.
• A small amount of duct air pressure loss will be present downstream from
the Ultra-sorb panel, depending on air density, velocity, and tube spacing.
See Table 28-2.
CAUTION
Do not install an Ultra-sorb upstream
from fi lter media.
If you must install upstream from fi lter
media, consult DriSteem or your
local DriSteem representative for
recommendations.
Table 28-2:
Ultra-sorb XV air pressure loss
Duct air velocity
(55 ˚F [13 ˚C] at sea level)
fpmm/swcPawcPawcPa
5002.540.0338.30.0338.30.0051.3
10005.080.12130.20.12130.20.0205.1
15007.620.23759.20.23759.20.04611.5
Notes:
• Ultra-sorb panels with 9" (225 mm) or 12" (300 mm) tube spacings have no measurable air pressure loss.
• Use DriSteem’s DriCalc sizing and selection software to calculate your specifi c air pressure loss.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
28
Page 31
Strainer, traps, and valves
STRAINER
Inspect at least twice during the fi rst year. If fouled, inspect more frequently.
STEAM TRAPS
Verify that the steam traps are functioning properly at least twice a year. A
blocked steam trap will be at room temperature. A “blowing” steam trap is
hot and noisy, and the discharge pipe from it is hot for up to 30 feet (9 m).
A properly operating steam trap is hot and makes noise at intervals, and the
discharge pipe is progressively cooler beginning at the trap.
HEADER OVERFLOW P-TRAP WATER SEAL
If this option is used (see “Optional header overfl ow P-trap water seal” on
Page 17), prime the P-trap with about 8 ounces (200 mL) of water whenever
the panel has been idle for 90 days or more.
VALVES
• Electric: Inspect annually to be sure the valve operates freely, closes off
steam tightly, and there are no leaks.
MAINTENANCE
• Pneumatic: Inspect annually to be sure the valve tightly closes off steam,
the stem packing is not leaking steam, and the actuator diaphragm is not
leaking air.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
29
Page 32
MAINTENANCE
Dispersion tubes and heat exchanger
DISPERSION TUBES
• If steam or condensate is evident at the sealing surface, replace the seal.
• Inspect insulating material for dirt and smudges; gently clean with damp
cloth and soapy water or diluted nontoxic, biodegradable cleaner/
degreaser. Do not clean insulating material with a pressure washer; direct
spray could cause damage.
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
30
Page 33
Humidifi er de-scaling solution
MAINTENANCE
HEAT EXCHANGER
A poor quality steam source may cause a buildup of deposits on the heat
exchanger which will require periodic cleaning. After 2000 hours of
operation, remove a dispersion tube and check whether the heat exchanger is
coated with material deposits.
Material deposits can be removed from the heat exchanger with DriSteem’s
Humidifi er De-scaling Solution, available from your DriSteem representative. It
is the only cleaner/de-scaler approved for use with DriSteem humidifi ers. Use
of other cleaners/de-scalers may void your DriSteem warranty.
The Usage Instructions shipped with the DriSteem Humidifi er De-scaling
Solution contain important handling, mixing, timing, and pH testing
information.
The following additional instructions are for Ultra-sorb Model XV humidifi er:
1. If a float switch is installed:
– Note position of orientation mark (see Figure 31-1). Mark must be in
same position when fl oat switch is re-installed.
– Remove fl oat switch; the ½" NPT (DN15) port will be used to drain
header.
2. Install a ½" NPT thread drain hose in ½" NPT (DN15) port. After making
sure hose can reach a bucket or drain, elevate end of hose well above
connection.
See DriSteem’s Humidifi er De-scaling Solution
on the Accessories and options page (under
Products) on our website: www.dristeem.com.
WARNING
Humidifi er De-scaling Solution is
corrosive.
Read and follow all warnings and
instructions shipped with the DriSteem
Humidifi er De-scaling Solution.
FIGURE 31-1: ORIENTATION MARK ON
FLOAT SWITCH
Connection end
of header
Important: Check position
of orientation mark before
removing fl oat switch. Mark
must be in same position
after re-installation for fl oat
switch to function properly.
Orientation mark on
fl oat switch - normally
closed (NC) must face
directly upward.
3. Remove a dispersion tube, and add water to header to submerge heat
exchanger (see Figure 31-2).
4. Add 10 ounces of Humidifier De-scaling Solution per foot of header length
(30 mL of solution per 300 mm of header length). A 12-foot (3660 mm)
header requires about 1 gallon (3.8 litres) of solution.
5. After performing de-scaling procedure as described in Usage Instructions
and before resuming operation: Flush and drain header four times to
thoroughly remove Humidifier De-scaling Solution from system.
6. Re-install float switch in port.
mc_063011_0945
FIGURE 31-2: HEADER CROSS SECTION
Pour water into header through dispersion
tube hole to submerge heat exchanger before
adding Humidifi er De-scaling Solution.
Fill water
OM-7492
Heat exchanger
tube inlet and
outlet
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
31
Page 34
MAINTENANCE
Replacement parts
FIGURE 32-1: ULTRA-SORB MODEL XV REPLACEMENT PARTS
1
8
4
5
7
7
9
10
OM-7484b
mc_101410_0835
Table 32-1:
Ultra-sorb Model XV replacement parts
No. DescriptionPart No.
1 Screws, frame (package of 4)191170-010
O-ring, square 1.35" ID (package of 10)191170-015
2
O-ring, square 1.77" ID (package of 10)191171-015
Ring, tube end, 1.5" (package of 1)207010-001
6
3
2
Table 32-1:
Ultra-sorb Model XV replacement parts
No. DescriptionPart No.
7 Flange, sideconsult factory
8 Frame assembly, topconsult factory
9 Header assemblyconsult factory
10 Nut, 1/4-20 (package of 4)191170-035
Ring, tube end, 1.5" (package of 5)191170-020
3
Ring, tube end, 2.0" (package of 1)207010-002
Ring, tube end, 2.0" (package of 5)191171-020
Spring, compression, SST (package of 1)501460-001
4
Spring, compression, SST (package of 5)191170-025
Plug, tube end, 1.5" (package of 1)310260
Plug, tube end, 1.5" (package of 5)191170-030
5
Plug, tube end, 2.0" (package of 1)310261
Plug, tube end, 2.0" (package of 5)191171-030
6 Dispersion tube assemblyconsult factory
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
32
HVAC sealant for duct section applications consult factory
Electric modulating steam valveconsult factory
Pneumatic modulating steam valveconsult factory
On-off valve assemblyconsult factory
Electric temperature switch400260-001
Pneumatic temperature switch307076
Inlet strainerconsult factory
Steam trapconsult factory
Control board408496
Float switch408420-004
Page 35
Troubleshooting
Table 33-1:
Ultra-sorb Model XV troubleshooting guide
ProblemPossible causeAction
Humidifi er discharges
water in duct
• Missing or torn seal• Replace seal.
• Dispersion tube not properly installed• Ensure proper installation. See Figure 3-1.
• Humidifi cation steam is exceeding capacity per
tube
• Ensure humidifi cation is 43 lbs/hr (19.5 kg/h) per tube or less..
Note: For panels with a face height less than 17" (430 mm), contact
MAINTENANCE
DriSteem for assistance.
Humidity exceeds
setting of humidistat
• Steam main overloaded with water due to boiler
discharging water with steam (priming)
• Steam trap not draining properly• Replace, repair, or clean trap as required.
• Humidifi er improperly piped• Correct piping as shown on Pages 4, 5, and 12.
• Surges of condensate in steam supply due to
condensate collecting at low, undripped point in
steam main
• Inadequate steam trap capacity• Replace with larger trap.
• Pressurized condensate is being lifted too high• See “Integral heat exchanger” on Page 12.
• Heat exchanger is caked or dirty• Flush header. See page 31.
• Condensate collecting in header• Increase steam pressure through heat exchanger.
• Temperature switch downstream from heat
exchanger is malfunctioning
• Float switch in header is malfunctioning• Replace or repair.
• Control valve not fully closing• Foreign matter holding valve open; clean valve.
• Faulty or improperly placed humidity controller• Replace controller or relocate per catalog recommendations.
• Poor location of control components• Relocate per catalog recommendations.
• Incompatible control components• Replace per specifi ed recommendations.
• Control valve is hunting• Humidifi er capacity is oversized; change to smaller valve.
• Excessive outside air volume• Check fans, dampers, VAV, etc.
• Locate cause of priming and correct.
• If condensate return main is overloaded, fi nd an alternative method for
draining.
• Install drips and steam traps as required. See “Trapping” on
Page 12.
• See “Optional header overfl ow P-trap water seal” on Page 17.
• Replace or repair.
See fl oat switch instructions in Step 1 on Page 31.
• Valve spring broken; replace spring.
• Valve steam packing too tight; loosen and/or replace packing.
• Steam pressure exceeds close-off rating of valve spring;
replace actuator or valve spring with one that is compatible with the
higher steam pressure.
• Valve installed backwards; re-install.
• Adjust valve linkage.
• Pressure reducing valve is not accurately controlling steam pressure;
repair or replace.
• Boiler pressure is swinging too widely; adjust.
• Mixed air inlet formula: (% outside air) x (moisture content)
+ (% return air) x (moisture content)
= mixed air inlet in lbs/100 cfm
(kg/100 m3/h)
Continued
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
33
Page 36
MAINTENANCE
Troubleshooting
Table 26-1:
Ultra-sorb Model XV troubleshooting guide (continued)
ProblemPossible causeAction
Control system
malfunctioning
Control valves do not open
(with control cabinet)
Air cannot absorb steam
quantity being discharged
Humidifi er is noisy• Steam pressure too high• Reduce pressure.
Duct loses static pressure
downstream from Ultra-sorb
panel
Space humidity will not rise to
humidistat set point
(continued on next page)
• Incorrect control voltage• Verify control board voltage input is 24 VAC.
• Incorrect control signal• Verify control signal is valid or RH transmitter is wired.
• Improper wiring connections• Rewire.
• Incorrect humidity sensor• Replace.
• Humidity controller out of calibration• Recalibrate.
• Air fl ow switch input open• Validate/close input.
• No demand signal• Verify control signal is valid or RH transmitter is wired.
• Condensate in header - fl oat switch open• Check if in condensate clearing sequence (LED).
• Wait for condensate clearing cycle.
• Cycle power to control cabinet.
• Humidifi er operates when blower is off• Provide interlock.
• Valve is hunting• See "Control valve is hunting," on facing page.
• Air temperature in duct too low for steam
quantity
• Panel is vibrating• Tighten assembly and/or mounting hardware.
• Improper sealing where Ultra-sorb frame
penetrates duct
• Steam pressure too low• Increase.
• Manual steam valve partially closed• Open.
• Strainer screen partially clogged• Clean.
• Boiler pressure too low• Adjust control.
• Pressure reducing valve not accurately
controlling steam pressure
• Boiler pressure swinging too widely• Adjust controls.
• Incorrect piping• Correct piping as shown on Pages 4, 5, and 12.
• Undersized steam piping• Replace piping.
• Modulating steam control valve not fully
opening
• Incorrect control circuit voltage• Replace components to make all components compatible.
• Incorrect control signal• Replace components.
• Incorrect humidity sensor• Replace.
• Humidity controller out of calibration or is
malfunctioning
• Malfunctioning temperature switch
downstream from heat exchanger not
allowing humidifi cation steam valve to open
• Malfunctioning fl oat switch in header not
allowing humidifi cation steam valve to open
• Raise duct air temperature.
• Seal all panel corners and all cracks between panel and ducts/
fl anges. See Figure 9-1.
• Repair or replace.
• Valve packing is adjusted too tightly, loosen/replace packing.
• Adjust valve linkage.
• Recalibrate humidistat.
• Repair or replace.
• Replace or adjust switch.
• Replace or repair switch.
See fl oat switch instructions in Step 1 on Page 24.
Continued
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
34
Page 37
Troubleshooting
Table 26-1:
Ultra-sorb Model XV troubleshooting guide (continued)
ProblemPossible causeAction
Space humidity will not
rise to humidistat set point
(pneumatic controls)
Condensate collects in
duct
• Air leak in actuator• Repair or replace diaphragm.
• Control air pressure is too low• Adjust pressure.
• Temperature control switch not allowing
modulating steam valve to operate
• Foreign matter preventing control valve from
closing
• Panel is mounted too close to internal devices
(dampers, turning vanes, etc.) in duct
• Uninsulated duct passing through unheated
area (low duct surface temperature)
• Consult DriSteem to assess whether installed panel is correct for
application.
• Clean or replace valve.
• Move panel to a point further upstream from internal devices.
See “Selecting the location” on Page 16.
• More dispersion tubes shortens non-wetting distance. Consult
DriSteem to determine the total number of tubes required.
• Insulate ductwork.
MAINTENANCE
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
35
Page 38
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
36
Page 39
ULTRA-SORB MODEL XV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
37
Page 40
W
ARRANTY
Expect quality from the industry leader
For more than 45 years, DriSteem has been
leading the industry with creative and reliable
humidifi cation solutions. Our focus on quality is
evident in the construction of Ultra-sorb steam
dispersion panels, which feature stainless steel
construction. DriSteem also leads the industry
with a Two-year Limited Warranty and optional
extended warranty.
For more information
www.dristeem.com
sales@dristeem.com
For the most recent product information
visit our Web site: www.dristeem.com
DRI-STEEM Corporation
a subsidiary of Research Products Corporation
DriSteem is an ISO 9001:2008 certifi ed company
U.S. Headquarters:
14949 Technology Drive
Eden Prairie, MN 55344
800-328-4447 or 952-949-2415
952-229-3200 (fax)
European offi ce:
Marc Briers
Grote Hellekensstraat 54 b
B-3520 Zonhoven
Belgium
+3211823595 (voice)
+3211817948 (fax)
E-mail: marc.briers@dristeem.com
Continuous product improvement is a policy of
DriSteem Corporation; therefore, product
features and specifi cations are subject to
change without notice.
TWO-YEAR LIMITED WARRANTY
DRI-STEEM Corporation (“DriSteem”) warrants to the original user that its products will be free from
defects in materials and workmanship for a period of two (2) years after installation or twentyseven (27) months from the date DriSteem ships such product, whichever date is the earlier.
If any DriSteem product is found to be defective in material or workmanship during the applicable
warranty period, DriSteem’s entire liability, and the purchaser’s sole and exclusive remedy, shall
be the repair or replacement of the defective product, or the refund of the purchase price, at
DriSteem’s election. DriSteem shall not be liable for any costs or expenses, whether direct or
indirect, associated with the installation, removal or reinstallation of any defective product. The
Limited Warranty does not include cylinder replacement for electrode steam humidifi ers or media
replacement for Wetted Media Systems.
DriSteem’s Limited Warranty shall not be effective or actionable unless there is compliance with
all installation and operating instructions furnished by DriSteem, or if the products have been
modifi ed or altered without the written consent of DriSteem, or if such products have been subject
to accident, misuse, mishandling, tampering, negligence or improper maintenance. Any warranty
claim must be submitted to DriSteem in writing within the stated warranty period. Defective
parts may be required to be returned to DriSteem. Excluded from the Limited Warranty are all
consumable and wear and tear items such as cylinders, membranes, fi lters, or media replacements.
These items are subject to usual wear and tear during usage.
DriSteem’s Limited Warranty is made in lieu of, and DriSteem disclaims all other warranties,
whether express or implied, including but not limited to any IMPLIED WARRANTY OF
MERCHANTABILITY, ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, any
implied warranty arising out of a course of dealing or of performance, custom or usage of trade.
DriSteem SHALL NOT, UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY DIRECT, INDIRECT,
INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED
TO, LOSS OF PROFITS, REVENUE OR BUSINESS) OR DAMAGE OR INJURY TO PERSONS OR
PROPERTY IN ANY WAY RELATED TO THE MANUFACTURE OR THE USE OF ITS PRODUCTS. The
exclusion applies regardless of whether such damages are sought based on breach of warranty,
breach of contract, negligence, strict liability in tort, or any other legal theory, even if DriSteem has
notice of the possibility of such damages.
By purchasing DriSteem’s products, the purchaser agrees to the terms and conditions of this Limited
Warranty.
EXTENDED WARRANTY
The original user may extend the term of the DriSteem Limited Warranty for a limited number of
months past the initial applicable warranty period and term provided in the fi rst paragraph of this
Limited Warranty. All the terms and conditions of the Limited Warranty during the initial applicable
warranty period and term shall apply during any extended term. An extended warranty term of
an additional twelve (12) months or twenty four (24) months of coverage may be purchased. The
extended warranty term may be purchased until eighteen (18) months after the product is shipped,
after which time no extended warranties are available. When a Dristeem humidifi er is purchased
with a DriSteem RO system, an extended twenty-four (24) month coverage is included.
Any extension of the Limited Warranty under this program must be in writing, signed by DriSteem,
and paid for in full by the purchaser.
DriSteem and Ultra-sorb are registered
trademarks of Research Products Corporation
and are fi led for trademark registration in
Canada and the European community.
Product and corporate names used in this
document may be trademarks or registered
trademarks. They are used for explanation only
without intent to infringe.