ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
ii
Page 3
Unpacking High-Effi ciency Tubes
UNPACKING HIGH-EFFICIENCY TUBES
NOTE: If you have an Ultra-sorb without High-effi ciency dispersion tubes (noninsulated tubes), please skip to the next page.
UNPACKING
• Remove the dispersion assembly from the shipping container; be careful not
to damage the PVDF insulating material on the dispersion tubes.
• Some dispersion panels are shipped unassembled. Do not lay HighEffi ciency Tubes across or under anything that could compress or damage
the insulating material. Compressed insulating material has a reduced
R-value.
• Before start-up, remove the clear poly fi lm covering the insulation by tearing
it along the perforation. Do not use a knife or sharp object to remove the
poly fi lm.
CAUTION
Remove clear poly fi lm; do not remove white PVDF insulation.
High-effi ciency tubes are sleeved in clear poly fi lm for
protection during, shipping, and installation. Leave the clear
poly fi lm on until installation is complete.
Remove and discard the clear poly fi lm before start-up by
tearing it along the perforations. Do not remove the white
PVDF insulation.
• Keep fl ame away from the insulation to avoid damage.
• PVDF is resistant to UV light. UV-C light from
germicidal lamps will not cause the insulating
material to degrade.
• Do not tighten mounting clamps or fasteners to any part of the dispersion tube.
High-efficiency tube option
Dispersion assemblies with the High-Effi ciency
Tube option are designed to produce
signifi cantly less dispersion-generated
condensate and airstream heat gain, which
reduces wasted energy by up to 85%.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
1
Page 4
INSTALLATION
Ultra-sorb Model MP fi eld assembly
Note: These assembly instructions are for Ultra-sorb Model MP panels shipped
unassembled by request or as required. Panels with overall height more
than 98" (2490 mm) are shipped unassembled.
LAY OUT THE PANEL COMPONENTS
Place the panel components on a large, fl at working surface.
ATTACH THE TOP FRAME ASSEMBLY
Span the fl anges with the top frame assembly. Align the locating pins on the
fl anges and top frame, and insert screws.
TIGHTEN THE FLANGE LOCKNUTS
Torque the eight fl ange locknuts to 16 ft-lb (22 N-m) at 100 rpm maximum
using a 7/16" deep-well socket.
INSTALL THE DISPERSION TUBES
Note: Do not remove the poly fi lm from the dispersion tubes until after the
panel is installed.
FIGURE 2-1: ULTRA-SORB MODEL MP COMPONENTS
Top frame
assembly
Locating pins
Left side
fl ange
Flange
locknut
Dispersion
tube
Insulation
Header
assembly
OM-7846
Right side fl ange
Table 2-1:
Ultra-sorb Model MP components
ComponentQty.
Header assembly1
Dispersion tubesVaries
Top frame assembly1
Side fl anges2
ScrewsVaries
Flange locknuts8
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
2
Page 5
Ultra-sorb Model MP fi eld assembly
INSERT DISPERSION TUBES INTO AN UNASSEMBLED ULTRA-SORB PANEL
If the Ultra-sorb Model MP panel was shipped unassembled, the dispersion
tubes need to be inserted into the panel.
Note: Use soapy water to lubricate end of tubes where inserted into rubber
grommet.
1. Insert tube into rubber grommet at panel header, with open end at bottom.
Insert at a slight angle to not interfere with top frame of Ultra-sorb panel.
2. Press downward on tube so to clear stud at top of tube. Align tube with
rivet nut on top of the header.
3. Once aligned, turn the tube three full rotations into rivet nut for proper
engagement.
4. Turn the tube backwards so that the steam tubelets face the next tube,
perpendicular to air flow. Face the lowest tubelet of each tube in the same
direction so the facing tubelets are at staggered heights.
INSTALLATION
5. Tighten the locknut down to the top header to 10 in-lbs (1.13 N-m).
Note: If the rivet nut pulls through, add a ¼"-20 nut on each side of the
top flange to secure the tube.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
3
Page 6
INSTALLATION
Ultra-sorb Model MP mechanical specifi cations
FIGURE 4-1: ULTRA-SORB MODEL MP DIMENSIONS
Top view
Connections
side view
4" steam
inlet
G
H
Note:
See Table 5-1: Ultra-sorb MP dimensions
All except with
4" steam inlet
G
H
Blank
side view
A
D
B
Header
A’
J
B’
E
F
C
OM-7915_mp
Elevation view
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
4
Table 4-1:
Ultra-sorb Model MP unit capacity
Evaporative steam Pressurized steam (2-50 psi)
lbs/hrkg/hrlbs/hrkg/hr
70031827201235
Table 4-2:
Ultra-sorb Model MP tube capacity*
Tubeslbs/hrkg/hr
Uninsulated4018.1
1.5"
Insulated4319.5
Uninsulated7734.9
2.0"
Insulated8036.3
* If face height (B') is <17" (432 mm), consult
DriSteem or see DriCalc for the correct calculation.
Page 7
INSTALLATION
Ultra-sorb Model MP mechanical specifi cations
Table 5-1:
Ultra-sorb Model MP dimensions
DimensionInches (mm)
A Unit width15" (380 mm) min, 147" (3735 mm) max, in ½" (13 mm) increments
A' Face width12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments
B Unit height*19.375" (492 mm) min, 151.375" (3845 mm) max, in ½" (13 mm) increments
B' Face height12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments
C Frame depth
D Frame enclosure1.5" (38 mm)
E Header enclosure 5.85" (149 mm)
F Mounting fl ange1.5" (38 mm)
G Humidifi cation
steam inlet
H Drain port
(internal thread)
J Overall width
* Panels with unit height more than 120" (3048 mm) have two-piece side fl anges and are shipped with brackets for easy fi eld assembly. Panels
with unit height more than 98" (2490 mm) are shipped unassembled.
7.2" (183 mm)
2.3" (58 mm) for side drain port (H) when 4" coupling (DN100) steam inlet
1" or 2" NPT coupling, for pressurized steam
1½" or 2" NPT coupling, for evaporative steam
3" or 4" flange, for evaporative steam
DN25 or DN50 BSPT nipple, for pressurized steam
DN50, DN80, or DN100 BSPT nipple, for evaporative steam
1½" or 2" (DN40 or DN50) hose, for evaporative steam
¾" NPT (DN20) coupling
1" NPT coupling, dimension A + 1/8";
1½" NPT coupling, dimension A + ½";
2" NPT coupling, dimension A + 1"
3" and 4" flange connection, dimension A + 6.5"
DN25, DN50, DN80 BSP nipple, dimension A + 38 mm
DN100 BSP nipple, dimension A + 64 mm
1½" or 2" (DN40 or DN50) hose connection, dimension A + ½" (dimension A + 13 mm)
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
5
Page 8
INSTALLATION
Selecting the location
DETERMINE HUMIDIFIER PLACEMENT
Dispersed steam must be absorbed into the airfl ow before it comes in
contact with duct elbows, fans, vanes, fi lters, or any object that can cause
condensation and dripping.
• Install the Ultra-sorb panel in a location where discharged water vapor will
be absorbed by the airstream.
• Place the Ultra-sorb panel where the air temperature is capable of
absorbing discharged steam without causing condensation at or after the
unit. This will normally be downstream from the heating coil where the air is
warmest.
• Do not place the Ultra-sorb panel in an outside air intake unless the air is
tempered with a preheat coil.
• Do not place the Ultra-sorb panel near the entrance of a high-effi ciency
fi lter. The fi lter will remove visible moisture and become waterlogged. See
the Caution "Installing the Ultra-sorb panel upstream from fi lter media" on
page 21.
• Do not place the Ultra-sorb panel where discharged visible mist will
impinge directly on a metal surface.
mc_071111_1710
PLACEMENT IN AN AIR HANDLING UNIT
• Location A is the best choice. Installing downstream from heating and
cooling coils provides laminar fl ow through the dispersion unit; plus, the
heated air provides an environment for best absorption.
• Location B is the second-best choice. However, conditions when both
cooling and humidifi cation is needed, the cooling coil will eliminate some
moisture for humidifi cation.
• Location C is the third-best choice. Air leaving a fan is usually very turbulent
and can cause vapor to not absorb at the expected non-wetting distance.
Allow for more distance if installing downstream from a fan.
• Location D is the poorest choice. The cooler air at this location requires an
increased non-wetting distance.
mc_062111_0715
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
6
Page 9
Selecting the location
FIGURE 7-1: PLACING A DISPERSION ASSEMBLY IN AN AIR HANDLING UNIT
INSTALLATION
Outside air
Exterior building
wall
Relief air
Economizer
control device
Preheat coil
Motorized
air dampers
Filters
Heating coil
DC-1081
mc_092507_1530
Return airfl ow
Cooling coil
ABD
3' to 5' (1 to 1.5 m)
8' to 12' (2.4 to 3.7 m)
8' to 12' (2.4 to 3.7 m)
Duct high limit humidity control
for dispersion locations A, B
Airfl ow proving switch
Fan
C
Airfl ow proving switch
Duct high limit humidity control
for dispersion location C
Supply airfl ow
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
7
Page 10
INSTALLATION
Mounting and support
INSTALLATION IN A COLD AIR STREAM
When a humidifi er is installed in a duct that will carry cold air, determine
the dew point temperature. If the psychrometric chart reveals that saturation
may occur, protection should be provided. A high-limit humidistat or humidity
transmitter can be used for this purpose. See Figure 8-1.
PLACEMENT UPSTREAM FROM AN ELBOW OR DUCT SPLIT
Installation upstream from elbows or duct splits can be done. See Figure
8-2 if placed upstream a minimum of the non-wetting distance.
INSTALLATION ABOVE VALUABLE EQUIPMENT
Water piping and humidifi ers should not be installed above expensive
equipment. A condensing or leaking water pipe or other accidental water
spillage could damage the equipment below. When such an installation cannot
be avoided, install a drip pan under the humidifi er piping, valve, etc. to catch
and drain away unintended water. See Figure 8-3.
PANEL SUPPORT
The duct or air handler section and Ultra-sorb panel must be properly
supported to carry the weight of the assembly. The weight of the piping must
be supported by the building structure rather than by the Ultra-sorb unit.
Excessive weight on the Ultra-sorb panel may stress the connections, causing
them to fracture and leak.
mc_071311_1540
FIGURE 8-1: INSTALLATION IN A COLD
AIR STREAM
Extended trails of
Elbow
Non-
wetting
OM-7862
fog may develop
Duct
Cold
air
fl ow
High limit duct humidistat 10' to 15' (3 to 4.5 m)
downstream from Ultra-sorb
OM-197
mc_052411_0830
FIGURE 8-2: UPSTREAM PLACEMENT
Air fl ow
Ultra-sorb
Ultra-sorb
Air fl ow
Ultra-sorb
distance
Duct split
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
8
FIGURE 8-3: INSTALLATION ABOVE
VALUABLE EQUIPMENT
Ultra-sorb
Vapor absorption
Air fl ow
Drip pan
Pipe to drain size as required
* This length of duct should have sealed seams
and should be at least three times the height
of the Ultra-sorb panel.
OM-198
mc_101410_0955
area
2" (50 mm)
Ceiling line
Page 11
Mounting and support
INSTALLATION
The Ultra-sorb panel can operate with air fl ow in either direction. The steam
supply and condensate drain connections must be connected to the header
assembly. To locate connections, the panel may be rotated 180º to the
preferred side of the AHU or duct.
Once installed, verify that all steam discharge tubelets are pointed
perpendicular to the airstream (see Figure 9-1). Loosen the jam nut at
the top of the tube to allow rotation of the dispersion tubes for proper tubelet
orientation.
When removing and installing the dispersion tubes, verify that the replacement
grommets are seated in their grooves and lubricated. When sliding the
dispersion tube into the grommet, be careful not to cut the grommet.
Note: To prevent leakage, use HVAC caulking or a similar weather sealant to
seal all places where the Ultra-sorb installation hardware and fi ttings
penetrate the wall of the duct.
FIGURE 9-1:
DISPERSION TUBE ORIENTATION
Airfl ow
Dispersion tube
Airfl ow
Tubelet
OM-150a
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
9
Page 12
INSTALLATION
Ultra-sorb Model MP mounting - pressurized steam application
FIGURE 10-1: MOUNTING ULTRA-SORB MODEL MP (PRESSURIZED STEAM APPLICATION SHOWN)
Install strainer within 3' (1 m) of Ultra-sorb
1½" (38 mm)
fl ange
Tubelets
perpendicular to
airfl ow
Condensate header
Blanked-off area
Water seal
(see Note 5)
Face width
AHU width
Notes:
1. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on
nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
2. Dashed lines indicate provided by installer.
3. Steam supply line to unit and piping are not included.
4. Mount the Ultra-sorb Model MP vertically (for horizontal airflow only).
5. For pressurized steam applications provide a 10" (255 mm) minimum water seal.
6. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on
nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
7. When mounting an Ultra-sorb in a duct, headers and flanges are mounted outside the duct.
8. 100% of the airflow must pass through the Ultra-sorb, which means that any openings surrounding it must be sealed. The blanked-off area below
the Ultra-sorb provides clearance height for water seals, and condensate piping connections.
9. Due to the pressure drop across the valve, the steam pressure at the header traps is minimal. Condensate must be drained.
10. Dispersion tubes are available at : 3" (76 mm), 4" (102 mm; for 2" diameter only), 6" (152 mm), 9" (228 mm), 12" (305 mm) centers.
11. Ultra-sorb humidifiers will be assembled, crated, and shipped intact in all sizes up to 98" (2490 mm) tall. Ultra-sorb can be shipped
unassembled, by request, requiring field assembly.
12. Sizes are 12" to 144" (305 mm to 3658 mm) x 12" to 144" (305 mm to 3658 mm) in 1" (25 mm) increments.
Valve
Face
height
≥ 2"
(51 mm)
¾" (DN20) pipe thread
Open drain 1" (25 mm) air gap (see Note 1)
AHU/
Overall
height
From
pressurized
steam source
OM-7839
Each Ultra-sorb humidifier is furnished with:
1. Type 304 stainless steel header/separator and dispersion tubes when shipped unassembled.
2. Hardware for connection of dispersion tubes to header when shipped unassembled.
3. Tube grommets for connection when shipped unassembled.
Each Ultra-sorb humidifier used with boiler steam is also furnished with:
1. One 3/4" NPT float and thermostatic trap (≤15 psi steam source) or an inverted bucket trap for steam main drip leg use (>15 psi).
2. Inlet "Y" strainer.
3. Normally closed steam valve with stainless steel parabolic plug and seat.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
10
Page 13
INSTALLATION
Ultra-sorb Model MP mounting - nonpressurized steam application
FIGURE 11-1: MOUNTING ULTRA-SORB MODEL MP (NONPRESSURIZED STEAM APPLICATION SHOWN)
1½" (38 mm)
fl ange
Depending on humidifi cation load,
interconnecting piping may be hose,
tubing, or hard pipe
90˚ long
sweep
or two 45˚
elbows
Insulate
tubing and
hard pipe to
reduce steam
loss
Typical evaporative
humidifi er
Position
tubelets
perpendicular
to airfl ow
Condensate header
Blanked-off area
Water seal
(see Note 4)
Face width
AHU width
Face
height
AHU/Overall
height
≥ 2"
(51 mm)
¾" (DN20) pipe thread
Open drain 1" (25 mm) air gap:
(see Note 1)
*Pitch 1/8"/ft (1%)
OM-7840
Notes:
1. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on
nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
2. When mounting an Ultra-sorb in a duct, headers and flanges are mounted outside the duct.
3. Mount the Ultra-sorb Model MP vertically (for horizontal airflow only).
4. For non-pressurized steam, provide a 5" (127 mm) minimum water seal with a 2" (51 mm) minimum drop from the header connection.
5. 100% of the airflow must pass through the Ultra-sorb, which means that any openings surrounding it must be sealed. The blanked-off area below
the Ultra-sorb provides clearance height for water seals and condensate piping connections.
6. Condensate must be drained.
7. Dispersion tubes are available at: 3" (76 mm), 4" (102 mm; for 2" diameter only), 6" (152 mm), 9" (228 mm), 12" (305 mm) centers.
8. Ultra-sorb humidifiers will be assembled, crated, and shipped intact in all sizes up to 98" (2490 mm) wide. Ultra-sorb can be shipped
unassembled, by request, requiring field assembly.
9. Sizes are 12" to 144" (305 mm to 3658 mm) x 12" to 144" (305 mm to 3658 mm) in 1" (25 mm) increments.
Each Ultra-sorb humidifier is furnished with:
1. Type 304 stainless steel header/separator and dispersion tubes when shipped unassembled.
2. Hardware for connection of dispersion tubes to header when shipped unassembled.
3. Tube grommets for connection when shipped unassembled.
*For electrode type humidifi ers pitch towards Ultra-sorb MP steam dispersion panel.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
11
Page 14
INSTALLATION
Mounting and support
MOUNTING IN AN AIR HANDLING UNIT
See placement recommendations in Figure 7-1.
The metal support frame should be anchored to the air handler casing.
Recommended fasteners for mounting the Ultra-sorb to a metal support frame
are 1/4–20 nuts and bolts or #12 self drilling and tapping screws. Due to
the possible forces exerted on this application, DriSteem recommends fastener
spacing not to exceed 6" (150 mm). On larger Ultra-sorb installations, vertical
channels may be required on both the inlet and outlet ends of the humidifi er to
provide proper support. See Figure 12-2.
FIGURE 12-1: ULTRA-SORB MODEL MP INSTALLED INSIDE AN AIR HANDLER
Air handler overall width
Ultra-sorb overall width
Ultra-sorb
overall
Air handler
overall height
See Page 15 for trap dimensions.
FIGURE 12-2: VERTICAL CHANNELS INSIDE AN AIR HANDLER
Ultra-sorb Model
MP, plan view
height
OM-7850_airhandler
Side blank-off
Header
Blanked-off area
Air fl ow
Mounting channel (Typ)
Blank-off plate
Water seal
Floor drain
Dispersion tube
AHU casing
Steam supply
Mounting channel (Typ)
1" (25 mm) air gap
Additional mounting support channels
required on larger Ultra-sorb units
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
12
OM-7851
Air handler casing
Page 15
Mounting and support
INSTALLATION
MOUNTING IN A HORIZONTAL DUCT
The Ultra-sorb panel is contained within a mounting frame.
A mounting fl ange 1½" (38 mm) wide is provided on all four sides of the
unit. The 1½" (38 mm) wide portion of the header enclosure is intended to be
a mounting fl ange. See Figures 13-1 and 13-2. A matching fl ange or metal
frame is required on the ductwork for connection to the Ultra-sorb fl anges.
The recommended fastener is a #12 x 3/4" self-drilling and tapping screw,
spacing not to exceed 12" (305 mm). If an angle-iron frame is provided on the
duct section, a longer screw may be required.
FIGURE 13-2: ULTRA-SORB MODEL MP
Mating fl anges of duct are attached to header enclosures
Mating fl anges of duct are
attached to header enclosures
FIGURE 13-1: ULTRA-SORB MODEL MP
IN DUCT
Side view
Ultra-sorb
OM-7863
1½"
(38 mm)
Mounting
fl ange
Do not puncture
the header
Note: To ensure proper drainage mount the
panel level or slightly pitched towards the
piping end of the panel.
Header
enclosure
1½" (38 mm)
Mounting
fl ange
OM-7864_aa
1½" (38 mm) mounting fl ange on units
up to 72" (1829 mm) face width.
For units wider than 72" (1829 mm)
face dimension, attach bottom edge of
duct work to header cover with #12 x
3/4" self-drilling and tapping screws,
spacing not to exceed 12" (305 mm).
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
13
Page 16
INSTALLATION
Supply and drain connections and dimensions
Table 14-1:
Condensate piping for Ultra-sorb MP steam dispersion panel
Evaporative steamPressurized steam
P-trap water seal
(Figure 14-1)
Inverted bucket trapNoNo
F&T trapNoNo
Condensate to open drainYesYes
Condensate return by
condensate pump
(Figure 14-2)
Condensate return to humidifi er
by gravity
Drop: 2" (50 mm)
Seal: 5" (130 mm)
YesYe s
YesNA
Recommended
method
Drop: 2" (50 mm)
Seal: 10" (255 mm)
FIGURE 14-1:
P-TRAP WATER SEAL DIMENSIONS
Ultra-sorb condensate outlet
3/4” (20 mm)
minimum copper
1” (25 mm)
Drop
FIGURE 14-2: LIFTING CONDENSATE
From P-trap or
mechanical trap
Check valve
Condensate
pump
air gap
Seal
To condensate
return main
FIGURE 14-3: STEAM SUPPLY CONNECTION TO A BOILER
(PRESSURIZED STEAM APPLICATIONS)
Install strainer (same size as valve, or larger
Model MP
Notes:
• See Figure 14-1 for required drain piping.
• For detailed information about steam piping, see
the DriSteem Humidifi cation System Design Guide,
which can be downloaded from the Literature page
of our website: www.dristeem.com.
than control valve) within 3 feet (1 m) of the
Ultra-sorb Model MP dispersion panel.
Steam
control
valve
F&T trap
Note:
The Ultra-sorb Model MP must be installed
with the drain connection at an elevation
that permits gravity drainage. For lifting
condensate, use a condensate pump rated for
your application. Contact your local DriSteem
representative for pump selection.
Steam
supply
OM-7854
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
14
Page 17
Ultra-sorb Model MP connections and dispersion tube detail
INSTALLATION
FIGURE 15-1: ULTRA-SORB MODEL MP STEAM INLET AND
CONDENSATE OUTLET POSITIONS
Airfl ow
Steam inlet
location
¾" (DN20) threaded
condensate drain outlet
FIGURE 15-2: DISPERSION TUBE DETAIL
OM-7841
FIGURE 15-3: ULTRA-SORB MODEL MP
STEAM INLET TYPES
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
15
Page 18
INSTALLATION
Piping
Table 16-1:
Maximum steam carrying capacity and length of interconnecting steam hose or tubing
Steam hose
1
Copper or stainless steel tubing
Hose I.D.Maximum capacity Maximum length
2
Tubing sizeMaximum capacity 3
Maximum developed
length
4
inchesDNlbs/hrkg/hftminchesDNlbs/hrkg/hftm
1½40150681031½4015068206
250250113103250220100309
5
3
80
5
4502048024
4 5 100 575034010030
1. Use DriSteem steam hose for best results. Other hose may have shorter
life and may cause foaming in the evaporating chamber resulting in
condensate discharge at the dispersion assembly. Do not use steam
hose for outdoor applications.
2. Maximum recommended length for steam hose is 10' (3 m). Longer
distances can cause kinking or low spots.
5
5
5
6
3. Insulate tubing to minimize loss of capacity and effi ciency.
4. Developed length of tubing equals measured length plus 50% of
measured length, to account for fi ttings.
Longer tubing lengths are possible at capacities lower than listed
maximums. Consult factory.
5. Requires fl ange connection.
125
150
5
140063510030
5
2300104310030
Note: Capacities and lengths in this table are for steam from a nonpressurized steam humidifi er to a nonpressurized steam dispersion panel, and are
based on total maximum pressure drop in hose or tubing of 5" wc (1250 Pa).
mc_091410_1050-LVLH
Table 16-2:
Steam loss of interconnecting steam hose or tubing
Steam loss
Insulation thickness
Description
Nominal hose or tubing size
NoninsulatedInsulated
inchesDNlbs/hr/ftkg/h/mlbs/hr/ftkg/h/minchesmm
1½400.150.22N/AN/AN/AN/A
Hose
2500.200.30N/AN/AN/AN/A
1½400.110.160.0200.0302.050
2500.140.210.0250.0372.050
3800.200.300.0300.0452.564
Tubing
41000.260.390.0300.0453.076
51250.310.460.0350.0523.076
61500.360.540.0390.0583.076
Note: Data based on an ambient air temperature of 80 °F (27 °C), fi berglass insulation, and copper tubing.
mc_051310_1216
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
16
Page 19
Piping
INSTALLATION
STEAM FROM A PRESSURIZED STEAM
Ultra-sorb panels for pressurized steam have a threaded pipe nipple that
extends outside the framework for a steam supply connection. The steam
supply line should be dripped immediately ahead of the steam valve through a
steam trap. See Figure 14-3.
RECOMMENDED TRAP FOR STEAM MAIN DRIP LEG
Use a fl oat and thermostatic (F&T) trap on the steam supply ≤15 psi and
inverted bucket if > 15 psi.
DRIEST STEAM
To ensure driest steam, take humidifi er steam off the top of the steam main (not
the side or bottom).
Table 17-1:
O.D. of pipe and tubing
Nom.
Standard
Dia.
1¼"
(30 mm)
1½"
(38 mm)
(50 mm)
2½"
(65 mm)
Note: Pipe thread and fl ange tubing adapters
are available from DriSteem.
1.6601.375--
1.9001.6251.5001.50
2"
2.3752.1252.0002.00
2.8752.6253.0003.00
pipe
Copper
tubing
SST
tubing
I.D. of
hose
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
17
Page 20
INSTALLATION
Piping
STEAM FROM A NON-ELECTRODE-TYPE EVAPORATIVE HUMIDIFIER
This section provides piping instructions for resistive-element electric, gasto-steam, and steam-to-steam evaporative humidifi ers. For electrode-type
(DriSteem XT Series) humidifi er piping, see Page 19.
TUBING
Standard connections on DriSteem evaporative humidifi ers are 1½" (38 mm)
stainless steel tubing. Two inch tubing connections are available as an option
on higher capacity evaporative units. Hose cuffs are available for connecting
to the tubing connection on the evaporative humidifi er and to the Ultra-sorb
(see Figure 18-2). DriSteem can also provide threaded connections on the
evaporative humidifi er and on the Ultra-sorb. For threading pipe connection
options, see DriSteem’s DriCalc sizing and selection software, available at
www. dristeem.com.
When non-threaded pipe is used, steam hose and clamps can be used for
connections at the humidifi er steam outlet and at the Ultra-sorb. Due to the
difference between the tubing O.D. and the steam hose I.D., multiple hose
clamps may be required.
45° elbows
STEAM HOSE PITCH
recommended
Support steam hose to prevent sags or low spots, and pitch at least 2"/ft (15%)
back to the humidifi er.
TUBING PITCH
• Pitch at least 2"/ft (15%) back to the humidifi er.
FIGURE 18-1: STEAM HOSE
Ultra-sorb
Steam hose
(See Table
16-1)
OM-7855
DriSteem
non-electrode-
type evaporative
humidifi ers
FIGURE 18-2: HOSE CUFF INSTALLATION
Insulated tubing
(See Table 17-1)
Hose and
cuff clamps
Hose
cuff and clamps
Standard 1½" (38 mm)
tubing outlet on cover
DriSteem
non-electrodetype evaporative
humidifi er
Additional
connections can be
provided for multiple
humidifi er connections
Ultra-sorb
OM-7856
• 90° elbows are not recommended. Use two 45° elbows one foot apart (see
Figure 18-2).
Failure to follow the above recommendations may result in excessive back
pressure on the evaporative humidifi er. This may lead to loss of water seal
or leaking gaskets. When the distance between the Ultra-sorb and the
evaporative humidifi er exceeds 20 feet (6 m), consult the factory for special
recommendations.
• Thin wall tubing will heat up with less start up heat loss than heavy wall
pipe.
• Insulate the tubing to reduce the loss in output caused by condensation in
the tubing.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
18
Page 21
Piping
INSTALLATION
STEAM FROM AN ELECTRODE-TYPE EVAPORATIVE HUMIDIFIER
TUBING
Standard steam hose connects to DriSteem electrode steam humidifi er cylinders
(XT series) and to the Ultra-sorb steam inlet directly or with a stainless steel
adaptor. Hose cuffs are also available for connecting tubing. If specifi ed when
ordered, DriSteem can provide a threaded connection on the Ultra-sorb steam
inlet. For threading pipe connection options, see DriSteem’s DriCalc sizing and
selection software, available at www.dristeem.com.
Hose and clamps can be used for connections at the steam cylinder and at the
Ultra-sorb. Due to the difference between the tubing O.D. and the steam hose
I.D., multiple hose clamps may be required.
STEAM HOSE PITCH
Support steam hose to prevent sags or low spots, and pitch at least 2"/ft (15%)
toward the Ultra-sorb panel.
TUBING PITCH
• Pitch at least 1/8" /ft (1%) toward the Ultra-sorb.
• 90° elbows are not recommended. Use two 45° elbows one foot apart as
shown in Figure 19-2.
Condensate drainage for all applications
Since Ultra-sorb panels operate with virtually
zero internal pressure, condensate cannot be
piped directly into a return main. It must be
piped to a fl oor drain or into a condensate
pump and returned to the steam source.
To prevent steam from escaping down the drain
line, install a water seal or steam trap in the
drain line. The water seal must be of suffi cient
height to contain the pressure in the humidifi er.
FIGURE 19-1: CONDENSATE DRAINAGE
Failure to follow the above recommendations may result in faults at the
electrode-type humidifi er. This may lead to erratic or stopped operation. When
the distance between the Ultra-sorb and the evaporative humidifi er exceeds 20
feet (6 m), consult the factory for special recommendations.
• Thin wall tubing will heat up with less start up heat loss than heavy wall
pipe.
• Insulate the tubing to reduce the loss in output caused by condensation in
the tubing.
FIGURE 19-2: ULTRA-SORB MODEL MP IN A HORIZONTAL AIRFLOW WITH
ELECTRODE-TYPE HUMIDIFIER
Pitch toward Ultra-sorb*
90° long sweep or two 45° elbows
Steam hose, tubing, or pipe
Electrode-type humidifi er
OM-7587
* Pitch steam hose, tubing, or pipe
toward Ultra-sorb:
2"/ft (15%) when using steam hose.
1/8"/ft (1%) when using tubing or pipe.
See trap
dimensions
in Table 14-1
3/4" pipe
thread (DN20)
drain
3/4" (DN20) copper
1" (25 mm) air gap
Open drain required.
Locate air gap only in spaces with adequate
temperature and air movement to absorb fl ash
steam; otherwise, condensation may form on
nearby surfaces. Refer to governing codes for
drain pipe size and maximum discharge water
temperature.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
19
Page 22
OPERATION
Replacing Ultra-sorb Model MP dispersion tubes
REMOVING A DISPERSION TUBE FROM AN ULTRA-SORB PANEL
A dispersion tube may need to be removed for access to an adjacent coil, or
because of tube damage or upgrade to an insulated tube. See page 3 for
how to install a dispersion tube.
1. Apply soapy water around the tube grommet to ease turning and removal
of the dispersion tube.
2. Loosen the jam nut from the tube nut at top of the tube. Rotate the tube off
the top frame assembly bolt (about 4 rotations of the tube).
3. Press downward on the tube so to clear bolt at top of frame.
4. Move the tube to a slight angle so that it does not interfere with top frame
of Ultra-sorb Model MP panel.
5. Pull the tube out from the rubber grommet.
6. If the grommet shows any sign of wear or damage, replace it before
reinstalling the dispersion tube. See Table 29-1 for replacement parts.
Note: Grommets are provided with replacement tubes.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
20
Page 23
Performance data
OPERATION
NON-WETTING DISTANCE
Non-wetting distance is the distance downstream from the leaving side of
the steam dispersion assembly to the point where wetting will not occur.
This distance is dependent on several application parameters. To determine
your dispersion assembly’s non-wetting distance, consult your system’s
design engineer or project documentation. Non-wetting distance can also be
calculated using DriSteem’s DriCalc sizing and selection application, available
at www. dristeem.com. Note that your current design conditions may vary from
conditions used for system design.
• Note that the rise in relative humidity (ΔRH) between entering and leaving
air has a direct bearing on the non-wetting distance.
As the change in relative humidity (ΔRH) increases, the
non-wetting distance increases.
• Uneven airfl ow over the Ultra-sorb panel cross-section
may result in nonuniform mixing of steam with air,
which may adversely affect absorption distance.
Table 21-1:
Ultra-sorb air pressure loss
Duct air velocity
(55 ˚F at sea level)
• A small amount of duct air pressure loss will be present
downstream from the Ultra-sorb panel, depending
on air density, velocity, and tube spacing. See Table
21-1.
mc_071211_1515
fpmm/swcPawcPa
5002.540.0205.10.0041.1
10005.080.08220.50.0174.2
CAUTION
Installing the Ultra-sorb panel upstream
from fi lter media
Non-wetting distances described
here do not apply when installing an
Ultra-sorb panel upstream from fi lter
media. If you must install upstream
from fi lter media, consult DriSteem or
your local DriSteem representative for
recommendations.
mc_071211_1505
Tube spacing
3"75 mm6"150 mm
Uninsulated tubes
15007.620.17543.80.0389.5
fpmm/swcPawcPa
5002.540.0338.30.0051.3
10005.080.12130.20.0205.1
15007.620.23759.20.04611.5
High-efficiency tubes
Notes:
• Ultra-sorb panels with 9" (225 mm) or 12" (300 mm) tube spacings
have no measurable air pressure loss.
• Use DriSteem’s DriCalc sizing and selection application to calculate
your specifi c air pressure loss.
mc_100907_0830
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
21
Page 24
OPERATION
VDC
T STEAM
VALVE
VDC SIGNAL
Controls
AIRFLOW PROVING SWITCH
An air fl ow proving switch should be used to prevent the steam valve from
opening if air is not moving in the duct.
HIGH LIMIT HUMIDISTAT
To prevent over saturation when duct air is cooler than 70 °F (21 °C), use a
high limit (duct mounted) humidistat (Figure 10-1). Mount it 10' to 15' (3 to
4.5 m) downstream from the Ultra-sorb panel, and set it at 80 to 90% RH.
FIGURE 22-1: ULTRA-SORB MODEL MP TYPICAL CONTROL WIRING
-10
OR HUMIDISTA
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
22
-10
Page 25
Startup
1. Turn on humidification steam to the Ultra-sorb supply header:
• Pressurized steam: Open the modulating steam valve.
• Evaporative humidifi er: Follow the startup instructions in the humidifi er's
Installation, Operation, and Maintenance Manual.
2. Check for piping leaks.
3. See “Steam traps” on page 24.
4. Check the dispersion tubes for leaks.
5. Ensure that the dispersion tubes are oriented with the tubelets at a right
angle to the airflow. See Figure 9-1.
6. Check for any other leaks from steam and drain connections.
7. Ensure that the P-traps are operating.
• At the beginning of the season, ensure there is a stream of water from
condensate drain when operating.
1. If not, verify P-trap is not blocked.
2. If steam is blowing out of the P-trap, it needs to be primed.
3. Verify the P-trap is tall enough to contain panel operating pressure
(see page 10 or 11).
4. Duct static pressure > 2.5" ( 63.5 mm) wc may require a taller
P-trap.
OPERATION
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
23
Page 26
MAINTENANCE
Inspecting and servicing components
STRAINER
Inspect the strainer screen at least twice during the fi rst year. If fouled, inspect it
more frequently.
STEAM TRAPS ON MAIN STEAM SUPPLY
At least twice a year verify that steam traps are functioning properly. A
blocked steam trap is cold. A "blowing" steam trap is hot and noisy, and the
discharge pipe from it is hot for 30 feet. A properly operating steam trap is hot
and makes noise at intervals, and the discharge pipe is progressively cooler
beginning at the trap.
VALVES
• Electric modulating:
Inspect annually to be sure that the valve operates freely and closes off
steam tightly and the stem packing is not leaking.
• Pneumatic:
Inspect annually to be sure the valve closes off steam tightly, the stem
packing is not leaking steam, and the diaphragm in the actuator is not
leaking air.
HIGH-EFFICIENCY TUBES
• If the insulating material gets dirty or smudged, gently clean it with a damp
cloth and a solution of soapy water or diluted non-toxic, biodegradable
cleaner/degreaser.
• Do not clean the insulating material with a pressure washer. The direct
spray could cause damage.
• If using a torch in the vicinity of the dispersion panel, keep the fl ame away
from the insulating material to avoid damage.
• PVDF is inherently resistant to UV light. Indirect, low-intensity UV-C light from
germicidal lamps will not cause the insulating material to degrade.
• Do not tighten mounting clamps or fasteners to any part of the dispersion
tube.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
24
Page 27
Troubleshooting
Table 25-1:
Ultra-sorb Model MP troubleshooting
ProblemPossible causeAction
Humidifi er discharges
water in duct
Humidity exceeds
setting of humidistat
• Steam main overloaded with water due
to boiler discharging water with steam
(priming)
• P- trap not draining properly• Replace or clean trap as required.
• Humidifi er improperly piped• Correct the piping as shown on Page 14. Steam inlet
• Surges of condensate in steam supply due
to condensate collecting at low, undripped
point in steam main
• Inadequate main steam trap capacity• Replace with larger trap.
• Control valve not fully closing• Foreign matter holding valve open; clean valve.
• Faulty or inaccurately placed humidity
controller
• Poor location of control components• Relocate per catalog recommendations.
• Incompatible control components• Replace per specifi ed recommendations.
• Automatic valve is hunting• Humidifi er capacity is oversized; change to smaller valve.
• Excessive outside air volume• Check fans, dampers, VAV, etc. See formula below.
MAINTENANCE
• Locate cause of priming and correct.
• If condensate return main is overloaded, fi nd an
alternative method for draining.
should be at center off the header and condensate outlet
at the bottom of the assembly.
• Install drips and steam traps as required. See Page 14.
• Check signal and power to valve.
• Valve steam packing too tight; loosen and/or replace
packing.
• Steam pressure exceeds close-off rating of valve spring;
replace actuator or valve spring with one that is
compatible with the higher steam pressure.
• Valve installed backwards; re-install.
• Adjust valve linkage.
• Replace controller or relocate per catalog
recommendations.
• Pressure reducing valve is not accurately controlling steam
pressure; repair or replace.
• Boiler pressure is swinging too widely; adjust.
Mixed Air Inlet formula: (% outside air x moisture content)
+ (% return air x moisture content)
= mixed air inlet in lbs/100 cfm
(kg/100 m3/h)
Continued
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
25
Page 28
MAINTENANCE
Troubleshooting
Table 25-1:
Ultra-sorb Model MP troubleshooting
ProblemPossible causeAction
Control system
malfunctioning
Air cannot absorb
steam quantity being
discharged
Humidifi er is noisy• Steam pressure too high• Reduce pressure.
• Incorrect control voltage• Replace transformer.
• Incorrect control signal• Replace components.
• Improper wiring connections• Rewire.
• Incorrect humidity sensor• Replace.
• Humidity controller out of calibration• Recalibrate.
• Humidifi er operates when blower is off• Provide interlock.
• Valve is hunting• See above.
• Air temperature in duct too low for steam
quantity being emitted
• Raise duct air temperature.
Continued
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
26
Page 29
Troubleshooting
Table 25-1:
Ultra-sorb Model MP troubleshooting (continued)
ProblemPossible causeAction
Space humidity will not
rise to humidistat set
point
Condensate in duct• Foreign matter preventing valve from closing • Clean or replace valve.
• Steam pressure too low• Increase.
• Manual steam valve partially closed• Open.
• Strainer screen partially clogged• Clean.
• Boiler pressure too low• Adjust control.
• Pressure reducing valve not accurately
controlling steam pressure
• Boiler pressure swinging too widely• Adjust controls.
• Incorrect piping• Repipe. See Page 14.
• Undersized steam piping• Replace.
• Undersized humidifi er• Replace valve with larger capacity valve.
• Automatic steam valve not fully opening• Valve packing is adjusted too tightly, loosen and/or
• Electric control system malfunctioning• Change transformer.
• Incorrect control circuit voltage• Replace component(s) to make all components compatible.
• Incorrect control signal• Replace components.
• Improper wiring• Rewire.
• Incorrect humidity sensor• Replace sensor.
• Humidity controller out of calibration or
malfunctioning
• Malfunctioning humidifi er temperature switch
not allowing humidifi er valve to open
• Pneumatic control system malfunctioning• Repair or replace.
• Obstructed air line• Remove obstruction.
• Malfunctioning pneumatic temperature
switch
• Air leak in actuator• Repair or replace diaphragm.
• Compressed air pressure is too low• Adjust pressure.
• Humidifi er is mounted too close to internal
devices (dampers, turning vanes, etc.) in
duct
• Non-insulated duct passing through
unheated area (duct surface temperature too
low)
• Repair or replace.
• Replace with larger humidifi er.
• Add additional humidifi er.
replace packing.
• Adjust valve linkage.
• Recalibrate humidistat.
• Repair or replace.
• Replace or readjust.
• Replace switch.
• Move humidifi er tubes to a point further upstream from
internal devices.
• Add more dispersion tubes for shorter non-wetting
distance. Consult DriSteem to determine the total number
of tubes required.
• Insulate ductwork.
MAINTENANCE
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
27
Page 30
MAINTENANCE
Replacement parts
FIGURE 28-1: ULTRA-SORB MODEL MP REPLACEMENT PARTS
7
5
4
8
6
2
OM-7890
1
3
11
10
9
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
28
OM-7854_rightside
Page 31
Replacement parts
Note:
Consult factory for Ultra-sorb Model MP replacement parts.
Frame top, Ultra-sorb Model MP, to 144" (3658 mm) widthConsult factory
8TubeletConsult factory
9Steam trapConsult factory
10Steam valveConsult factory
11StrainerConsult factory
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
29
Page 32
W
ARRANTY
Expect quality from the industry leader
Since 1965, DriSteem has led the industry
with innovative methods for humidifying and
cooling air with precise control. Our focus
on ease of ownership is evident in the design
of the Ultra--sorb steam dispersion panels,
which feature cleanable, stainless steel
construction. DriSteem also leads the industry
with a Two-year Limited Warranty and optional
extended warranty.
For more information
www.dristeem.com
sales@dristeem.com
For the most recent product information
visit our website: www.dristeem.com
DRI-STEEM Corporation
a subsidiary of Research Products Corporation
DriSteem is an ISO 9001:2008 certifi ed company
U.S. Headquarters:
14949 Technology Drive
Eden Prairie, MN 55344
800-328-4447 or 952-949-2415
952-229-3200 (fax)
European offi ce:
Grote Hellekensstraat 54 b
B-3520 Zonhoven
Belgium
+3211823595
E-mail: dristeem-europe@dristeem.com
Two-year Limited Warranty
DRI-STEEM Corporation (“DriSteem”) warrants to the original user that its products will be free from
defects in materials and workmanship for a period of two (2) years after installation or twentyseven (27) months from the date DriSteem ships such product, whichever date is the earlier.
If any DriSteem product is found to be defective in material or workmanship during the applicable
warranty period, DriSteem’s entire liability, and the purchaser’s sole and exclusive remedy, shall
be the repair or replacement of the defective product, or the refund of the purchase price, at
DriSteem’s election. DriSteem shall not be liable for any costs or expenses, whether direct or
indirect, associated with the installation, removal or reinstallation of any defective product. The
Limited Warranty does not include cylinder replacement for electrode steam humidifi ers.
DriSteem’s Limited Warranty shall not be effective or actionable unless there is compliance with
all installation and operating instructions furnished by DriSteem, or if the products have been
modifi ed or altered without the written consent of DriSteem, or if such products have been subject
to accident, misuse, mishandling, tampering, negligence or improper maintenance. Any warranty
claim must be submitted to DriSteem in writing within the stated warranty period. Defective
parts may be required to be returned to DriSteem. Excluded from the Limited Warranty are all
consumable and wear and tear items such as cylinders, membranes, fi lters, or media replacements.
These items are subject to usual wear and tear during usage.
DriSteem’s Limited Warranty is made in lieu of, and DriSteem disclaims all other warranties,
whether express or implied, including but not limited to any IMPLIED WARRANTY OF
MERCHANTABILITY, ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, any
implied warranty arising out of a course of dealing or of performance, custom or usage of trade.
DriSteem SHALL NOT, UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY DIRECT, INDIRECT,
INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED
TO, LOSS OF PROFITS, REVENUE OR BUSINESS) OR DAMAGE OR INJURY TO PERSONS OR
PROPERTY IN ANY WAY RELATED TO THE MANUFACTURE OR THE USE OF ITS PRODUCTS. The
exclusion applies regardless of whether such damages are sought based on breach of warranty,
breach of contract, negligence, strict liability in tort, or any other legal theory, even if DriSteem has
notice of the possibility of such damages.
By purchasing DriSteem’s products, the purchaser agrees to the terms and conditions of this Limited
Warranty.
Extended warranty
The original user may extend the term of the DriSteem Limited Warranty for a limited number of
months past the initial applicable warranty period and term provided in the fi rst paragraph of this
Limited Warranty. All the terms and conditions of the Limited Warranty during the initial applicable
warranty period and term shall apply during any extended term. An extended warranty term of
an additional twelve (12) months or twenty four (24) months of coverage may be purchased. The
extended warranty term may be purchased until eighteen (18) months after the product is shipped,
after which time no extended warranties are available. When a Dristeem humidifi er is purchased
with a DriSteem RO system, an extended twenty-four (24) month coverage is included.
Continuous product improvement is a policy of
DriSteem; therefore, product features and
specifi cations are subject to change without
notice.
DriSteem and Ultra-sorb are registered
trademarks of Research Products Corporation
and are fi led for trademark registration in
Canada and the European community.
Product and corporate names used in this
document may be trademarks or registered
trademarks. They are used for explanation only
without intent to infringe.