DriSteem ultra-sorb MP Installation, Operation And Maintenance Manual

Page 1
READ AND SAVE THESE INSTRUCTIONS
ULTRA-SORB
Steam Dispersion Panels
®
MODEL MP
Installation, Operation, and Maintenance Manual
For applications using steam from a boiler or from any DriSteem steam generating humidifier.
Page 2
Table of contents
UNPACKING HIGH-EFFICIENCY TUBES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Ultra-sorb Model MP field assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Ultra-sorb Model MP mechanical specifications . . . . . . . . . . . . . . . . . . . . 4
Selecting the location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Determine humidifier placement . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Placement in an air handling unit . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Mounting and support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation in a cold air stream . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Placement upstream from an elbow or duct split . . . . . . . . . . . . . . . . 8
Installation above valuable equipment . . . . . . . . . . . . . . . . . . . . . . . 8
Panel support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Ultra-sorb Model MP mounting - pressurized steam application . . . . . . . . 10
Ultra-sorb Model MP mounting - nonpressurized steam application . . . . . 11
Mounting in an air handling unit . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mounting in a horizontal duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Supply and drain connections and dimensions . . . . . . . . . . . . . . . . . . . 14
Ultra-sorb Model MP connections and dispersion tube detail . . . . . . . . . 15
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Steam from a Pressurized steam . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Steam from a non-electrode-type evaporative humidifier . . . . . . . . . . 18
Steam from an electrode-type evaporative humidifier . . . . . . . . . . . . 19
WARNING
Hot surface hazard
Steam humidifi cation systems have extremely hot surfaces.
To avoid burns, allow humidifi er, steam pipes, and dispersion assemblies to cool before touching any part of the system.
mc_071411_0753
ATTENTION INSTALLER
Read this manual before installing. Leave manual with product owner.
DriSteem Technical Support
• technical.support@dristeem.com
• 800-328-4447
• dristeem.com/technical-support
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Replacing Ultra-sorb Model MP dispersion tubes . . . . . . . . . . . . . . . . . . 20
Performance data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Inspecting and servicing components . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Steam traps on main steam supply . . . . . . . . . . . . . . . . . . . . . . . . 24
Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
High-Efficiency Tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
ii
Page 3
Unpacking High-Effi ciency Tubes
UNPACKING HIGH-EFFICIENCY TUBES
NOTE: If you have an Ultra-sorb without High-effi ciency dispersion tubes (non­insulated tubes), please skip to the next page.
UNPACKING
• Remove the dispersion assembly from the shipping container; be careful not to damage the PVDF insulating material on the dispersion tubes.
• Some dispersion panels are shipped unassembled. Do not lay High­Effi ciency Tubes across or under anything that could compress or damage the insulating material. Compressed insulating material has a reduced R-value.
• Before start-up, remove the clear poly fi lm covering the insulation by tearing it along the perforation. Do not use a knife or sharp object to remove the
poly fi lm.
CAUTION
Remove clear poly fi lm; do not remove white PVDF insulation.
High-effi ciency tubes are sleeved in clear poly fi lm for protection during, shipping, and installation. Leave the clear poly fi lm on until installation is complete.
Remove and discard the clear poly fi lm before start-up by tearing it along the perforations. Do not remove the white
PVDF insulation.
Keep fl ame away from the insulation to avoid damage.
PVDF is resistant to UV light. UV-C light from germicidal lamps will not cause the insulating material to degrade.
Do not tighten mounting clamps or fasteners to any part of the dispersion tube.
High-efficiency tube option
Dispersion assemblies with the High-Effi ciency Tube option are designed to produce signifi cantly less dispersion-generated condensate and airstream heat gain, which reduces wasted energy by up to 85%.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
1
Page 4
INSTALLATION
Ultra-sorb Model MP fi eld assembly
Note: These assembly instructions are for Ultra-sorb Model MP panels shipped
unassembled by request or as required. Panels with overall height more than 98" (2490 mm) are shipped unassembled.
LAY OUT THE PANEL COMPONENTS
Place the panel components on a large, fl at working surface.
ATTACH THE TOP FRAME ASSEMBLY
Span the fl anges with the top frame assembly. Align the locating pins on the fl anges and top frame, and insert screws.
TIGHTEN THE FLANGE LOCKNUTS
Torque the eight fl ange locknuts to 16 ft-lb (22 N-m) at 100 rpm maximum using a 7/16" deep-well socket.
INSTALL THE DISPERSION TUBES
Note: Do not remove the poly fi lm from the dispersion tubes until after the
panel is installed.
FIGURE 2-1: ULTRA-SORB MODEL MP COMPONENTS
Top frame assembly
Locating pins
Left side fl ange
Flange locknut
Dispersion tube
Insulation
Header assembly
OM-7846
Right side fl ange
Table 2-1: Ultra-sorb Model MP components
Component Qty.
Header assembly 1
Dispersion tubes Varies
Top frame assembly 1
Side fl anges 2
Screws Varies
Flange locknuts 8
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
2
Page 5
Ultra-sorb Model MP fi eld assembly
INSERT DISPERSION TUBES INTO AN UNASSEMBLED ULTRA-SORB PANEL
If the Ultra-sorb Model MP panel was shipped unassembled, the dispersion tubes need to be inserted into the panel.
Note: Use soapy water to lubricate end of tubes where inserted into rubber grommet.
1. Insert tube into rubber grommet at panel header, with open end at bottom. Insert at a slight angle to not interfere with top frame of Ultra-sorb panel.
2. Press downward on tube so to clear stud at top of tube. Align tube with rivet nut on top of the header.
3. Once aligned, turn the tube three full rotations into rivet nut for proper engagement.
4. Turn the tube backwards so that the steam tubelets face the next tube, perpendicular to air flow. Face the lowest tubelet of each tube in the same direction so the facing tubelets are at staggered heights.
INSTALLATION
5. Tighten the locknut down to the top header to 10 in-lbs (1.13 N-m). Note: If the rivet nut pulls through, add a ¼"-20 nut on each side of the top flange to secure the tube.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
3
Page 6
INSTALLATION
Ultra-sorb Model MP mechanical specifi cations
FIGURE 4-1: ULTRA-SORB MODEL MP DIMENSIONS
Top view
Connections
side view
4" steam
inlet
G
H
Note: See Table 5-1: Ultra-sorb MP dimensions
All except with 4" steam inlet
G
H
Blank
side view
A
D
B
Header
A’
J
B’
E
F
C
OM-7915_mp
Elevation view
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
4
Table 4-1: Ultra-sorb Model MP unit capacity
Evaporative steam Pressurized steam (2-50 psi)
lbs/hr kg/hr lbs/hr kg/hr
700 318 2720 1235
Table 4-2: Ultra-sorb Model MP tube capacity*
Tubes lbs/hr kg/hr
Uninsulated 40 18.1
1.5" Insulated 43 19.5
Uninsulated 77 34.9
2.0" Insulated 80 36.3
* If face height (B') is <17" (432 mm), consult DriSteem or see DriCalc for the correct calculation.
Page 7
INSTALLATION
Ultra-sorb Model MP mechanical specifi cations
Table 5-1: Ultra-sorb Model MP dimensions
Dimension Inches (mm)
A Unit width 15" (380 mm) min, 147" (3735 mm) max, in ½" (13 mm) increments
A' Face width 12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments
B Unit height* 19.375" (492 mm) min, 151.375" (3845 mm) max, in ½" (13 mm) increments
B' Face height 12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments
C Frame depth
D Frame enclosure 1.5" (38 mm)
E Header enclosure 5.85" (149 mm)
F Mounting fl ange 1.5" (38 mm)
G Humidifi cation
steam inlet
H Drain port
(internal thread)
J Overall width
* Panels with unit height more than 120" (3048 mm) have two-piece side fl anges and are shipped with brackets for easy fi eld assembly. Panels
with unit height more than 98" (2490 mm) are shipped unassembled.
7.2" (183 mm)
2.3" (58 mm) for side drain port (H) when 4" coupling (DN100) steam inlet
1" or 2" NPT coupling, for pressurized steam
1½" or 2" NPT coupling, for evaporative steam
3" or 4" flange, for evaporative steam
DN25 or DN50 BSPT nipple, for pressurized steam
DN50, DN80, or DN100 BSPT nipple, for evaporative steam
1½" or 2" (DN40 or DN50) hose, for evaporative steam
¾" NPT (DN20) coupling
1" NPT coupling, dimension A + 1/8";
1½" NPT coupling, dimension A + ½";
2" NPT coupling, dimension A + 1"
3" and 4" flange connection, dimension A + 6.5"
DN25, DN50, DN80 BSP nipple, dimension A + 38 mm
DN100 BSP nipple, dimension A + 64 mm
1½" or 2" (DN40 or DN50) hose connection, dimension A + ½" (dimension A + 13 mm)
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
5
Page 8
INSTALLATION
Selecting the location
DETERMINE HUMIDIFIER PLACEMENT
Dispersed steam must be absorbed into the airfl ow before it comes in contact with duct elbows, fans, vanes, fi lters, or any object that can cause condensation and dripping.
• Install the Ultra-sorb panel in a location where discharged water vapor will be absorbed by the airstream.
• Place the Ultra-sorb panel where the air temperature is capable of absorbing discharged steam without causing condensation at or after the unit. This will normally be downstream from the heating coil where the air is warmest.
• Do not place the Ultra-sorb panel in an outside air intake unless the air is tempered with a preheat coil.
• Do not place the Ultra-sorb panel near the entrance of a high-effi ciency fi lter. The fi lter will remove visible moisture and become waterlogged. See the Caution "Installing the Ultra-sorb panel upstream from fi lter media" on page 21.
• Do not place the Ultra-sorb panel where discharged visible mist will impinge directly on a metal surface.
mc_071111_1710
PLACEMENT IN AN AIR HANDLING UNIT
Location A is the best choice. Installing downstream from heating and cooling coils provides laminar fl ow through the dispersion unit; plus, the heated air provides an environment for best absorption.
Location B is the second-best choice. However, conditions when both cooling and humidifi cation is needed, the cooling coil will eliminate some moisture for humidifi cation.
Location C is the third-best choice. Air leaving a fan is usually very turbulent and can cause vapor to not absorb at the expected non-wetting distance. Allow for more distance if installing downstream from a fan.
Location D is the poorest choice. The cooler air at this location requires an increased non-wetting distance.
mc_062111_0715
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
6
Page 9
Selecting the location
FIGURE 7-1: PLACING A DISPERSION ASSEMBLY IN AN AIR HANDLING UNIT
INSTALLATION
Outside air
Exterior building wall
Relief air
Economizer control device
Preheat coil
Motorized air dampers
Filters
Heating coil
DC-1081 mc_092507_1530
Return airfl ow
Cooling coil
ABD
3' to 5' (1 to 1.5 m)
8' to 12' (2.4 to 3.7 m)
8' to 12' (2.4 to 3.7 m)
Duct high limit humidity control for dispersion locations A, B Airfl ow proving switch
Fan
C
Airfl ow proving switch
Duct high limit humidity control for dispersion location C
Supply airfl ow
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
7
Page 10
INSTALLATION
Mounting and support
INSTALLATION IN A COLD AIR STREAM
When a humidifi er is installed in a duct that will carry cold air, determine the dew point temperature. If the psychrometric chart reveals that saturation may occur, protection should be provided. A high-limit humidistat or humidity transmitter can be used for this purpose. See Figure 8-1.
PLACEMENT UPSTREAM FROM AN ELBOW OR DUCT SPLIT
Installation upstream from elbows or duct splits can be done. See Figure 8-2 if placed upstream a minimum of the non-wetting distance.
INSTALLATION ABOVE VALUABLE EQUIPMENT
Water piping and humidifi ers should not be installed above expensive equipment. A condensing or leaking water pipe or other accidental water spillage could damage the equipment below. When such an installation cannot be avoided, install a drip pan under the humidifi er piping, valve, etc. to catch and drain away unintended water. See Figure 8-3.
PANEL SUPPORT
The duct or air handler section and Ultra-sorb panel must be properly supported to carry the weight of the assembly. The weight of the piping must be supported by the building structure rather than by the Ultra-sorb unit. Excessive weight on the Ultra-sorb panel may stress the connections, causing them to fracture and leak.
mc_071311_1540
FIGURE 8-1: INSTALLATION IN A COLD AIR STREAM
Extended trails of
Elbow
Non-
wetting
OM-7862
fog may develop
Duct
Cold air fl ow
High limit duct humidistat 10' to 15' (3 to 4.5 m) downstream from Ultra-sorb
OM-197 mc_052411_0830
FIGURE 8-2: UPSTREAM PLACEMENT
Air fl ow
Ultra-sorb
Ultra-sorb
Air fl ow
Ultra-sorb
distance
Duct split
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
8
FIGURE 8-3: INSTALLATION ABOVE VALUABLE EQUIPMENT
Ultra-sorb
Vapor absorption
Air fl ow
Drip pan
Pipe to drain size as required
* This length of duct should have sealed seams
and should be at least three times the height of the Ultra-sorb panel.
OM-198 mc_101410_0955
area
2" (50 mm)
Ceiling line
Page 11
Mounting and support
INSTALLATION
The Ultra-sorb panel can operate with air fl ow in either direction. The steam supply and condensate drain connections must be connected to the header assembly. To locate connections, the panel may be rotated 180º to the preferred side of the AHU or duct.
Once installed, verify that all steam discharge tubelets are pointed perpendicular to the airstream (see Figure 9-1). Loosen the jam nut at the top of the tube to allow rotation of the dispersion tubes for proper tubelet orientation.
When removing and installing the dispersion tubes, verify that the replacement grommets are seated in their grooves and lubricated. When sliding the dispersion tube into the grommet, be careful not to cut the grommet.
Note: To prevent leakage, use HVAC caulking or a similar weather sealant to
seal all places where the Ultra-sorb installation hardware and fi ttings penetrate the wall of the duct.
FIGURE 9-1: DISPERSION TUBE ORIENTATION
Airfl ow
Dispersion tube
Airfl ow
Tubelet
OM-150a
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
9
Page 12
INSTALLATION
Ultra-sorb Model MP mounting - pressurized steam application
FIGURE 10-1: MOUNTING ULTRA-SORB MODEL MP (PRESSURIZED STEAM APPLICATION SHOWN)
Install strainer within 3' (1 m) of Ultra-sorb
1½" (38 mm) fl ange
Tubelets perpendicular to airfl ow
Condensate header
Blanked-off area
Water seal
(see Note 5)
Face width
AHU width
Notes:
1. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
2. Dashed lines indicate provided by installer.
3. Steam supply line to unit and piping are not included.
4. Mount the Ultra-sorb Model MP vertically (for horizontal airflow only).
5. For pressurized steam applications provide a 10" (255 mm) minimum water seal.
6. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
7. When mounting an Ultra-sorb in a duct, headers and flanges are mounted outside the duct.
8. 100% of the airflow must pass through the Ultra-sorb, which means that any openings surrounding it must be sealed. The blanked-off area below the Ultra-sorb provides clearance height for water seals, and condensate piping connections.
9. Due to the pressure drop across the valve, the steam pressure at the header traps is minimal. Condensate must be drained.
10. Dispersion tubes are available at : 3" (76 mm), 4" (102 mm; for 2" diameter only), 6" (152 mm), 9" (228 mm), 12" (305 mm) centers.
11. Ultra-sorb humidifiers will be assembled, crated, and shipped intact in all sizes up to 98" (2490 mm) tall. Ultra-sorb can be shipped unassembled, by request, requiring field assembly.
12. Sizes are 12" to 144" (305 mm to 3658 mm) x 12" to 144" (305 mm to 3658 mm) in 1" (25 mm) increments.
Valve
Face height
≥ 2" (51 mm)
¾" (DN20) pipe thread
Open drain 1" (25 mm) air gap (see Note 1)
AHU/ Overall height
From pressurized steam source
OM-7839
Each Ultra-sorb humidifier is furnished with:
1. Type 304 stainless steel header/separator and dispersion tubes when shipped unassembled.
2. Hardware for connection of dispersion tubes to header when shipped unassembled.
3. Tube grommets for connection when shipped unassembled.
Each Ultra-sorb humidifier used with boiler steam is also furnished with:
1. One 3/4" NPT float and thermostatic trap (≤15 psi steam source) or an inverted bucket trap for steam main drip leg use (>15 psi).
2. Inlet "Y" strainer.
3. Normally closed steam valve with stainless steel parabolic plug and seat.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
10
Page 13
INSTALLATION
Ultra-sorb Model MP mounting - nonpressurized steam application
FIGURE 11-1: MOUNTING ULTRA-SORB MODEL MP (NONPRESSURIZED STEAM APPLICATION SHOWN)
1½" (38 mm) fl ange
Depending on humidifi cation load, interconnecting piping may be hose, tubing, or hard pipe
90˚ long sweep or two 45˚ elbows
Insulate tubing and hard pipe to reduce steam loss
Typical evaporative
humidifi er
Position tubelets perpendicular to airfl ow
Condensate header
Blanked-off area
Water seal (see Note 4)
Face width
AHU width
Face height
AHU/Overall height
≥ 2" (51 mm)
¾" (DN20) pipe thread
Open drain 1" (25 mm) air gap: (see Note 1)
*Pitch 1/8"/ft (1%)
OM-7840
Notes:
1. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on
nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
2. When mounting an Ultra-sorb in a duct, headers and flanges are mounted outside the duct.
3. Mount the Ultra-sorb Model MP vertically (for horizontal airflow only).
4. For non-pressurized steam, provide a 5" (127 mm) minimum water seal with a 2" (51 mm) minimum drop from the header connection.
5. 100% of the airflow must pass through the Ultra-sorb, which means that any openings surrounding it must be sealed. The blanked-off area below the Ultra-sorb provides clearance height for water seals and condensate piping connections.
6. Condensate must be drained.
7. Dispersion tubes are available at: 3" (76 mm), 4" (102 mm; for 2" diameter only), 6" (152 mm), 9" (228 mm), 12" (305 mm) centers.
8. Ultra-sorb humidifiers will be assembled, crated, and shipped intact in all sizes up to 98" (2490 mm) wide. Ultra-sorb can be shipped unassembled, by request, requiring field assembly.
9. Sizes are 12" to 144" (305 mm to 3658 mm) x 12" to 144" (305 mm to 3658 mm) in 1" (25 mm) increments.
Each Ultra-sorb humidifier is furnished with:
1. Type 304 stainless steel header/separator and dispersion tubes when shipped unassembled.
2. Hardware for connection of dispersion tubes to header when shipped unassembled.
3. Tube grommets for connection when shipped unassembled.
*For electrode type humidifi ers pitch towards Ultra-sorb MP steam dispersion panel.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
11
Page 14
INSTALLATION
Mounting and support
MOUNTING IN AN AIR HANDLING UNIT
See placement recommendations in Figure 7-1.
The metal support frame should be anchored to the air handler casing. Recommended fasteners for mounting the Ultra-sorb to a metal support frame are 1/4–20 nuts and bolts or #12 self drilling and tapping screws. Due to the possible forces exerted on this application, DriSteem recommends fastener spacing not to exceed 6" (150 mm). On larger Ultra-sorb installations, vertical channels may be required on both the inlet and outlet ends of the humidifi er to provide proper support. See Figure 12-2.
FIGURE 12-1: ULTRA-SORB MODEL MP INSTALLED INSIDE AN AIR HANDLER
Air handler overall width
Ultra-sorb overall width
Ultra-sorb
overall
Air handler
overall height
See Page 15 for trap dimensions.
FIGURE 12-2: VERTICAL CHANNELS INSIDE AN AIR HANDLER
Ultra-sorb Model MP, plan view
height
OM-7850_airhandler
Side blank-off
Header
Blanked-off area
Air fl ow
Mounting channel (Typ)
Blank-off plate
Water seal
Floor drain
Dispersion tube
AHU casing
Steam supply
Mounting channel (Typ)
1" (25 mm) air gap
Additional mounting support channels required on larger Ultra-sorb units
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
12
OM-7851
Air handler casing
Page 15
Mounting and support
INSTALLATION
MOUNTING IN A HORIZONTAL DUCT
The Ultra-sorb panel is contained within a mounting frame. A mounting fl ange 1½" (38 mm) wide is provided on all four sides of the unit. The 1½" (38 mm) wide portion of the header enclosure is intended to be a mounting fl ange. See Figures 13-1 and 13-2. A matching fl ange or metal frame is required on the ductwork for connection to the Ultra-sorb fl anges. The recommended fastener is a #12 x 3/4" self-drilling and tapping screw, spacing not to exceed 12" (305 mm). If an angle-iron frame is provided on the duct section, a longer screw may be required.
FIGURE 13-2: ULTRA-SORB MODEL MP
Mating fl anges of duct are attached to header enclosures
Mating fl anges of duct are attached to header enclosures
FIGURE 13-1: ULTRA-SORB MODEL MP IN DUCT
Side view
Ultra-sorb
OM-7863
1½"
(38 mm)
Mounting
fl ange
Do not puncture
the header
Note: To ensure proper drainage mount the panel level or slightly pitched towards the piping end of the panel.
Header enclosure
1½" (38 mm) Mounting fl ange
OM-7864_aa
1½" (38 mm) mounting fl ange on units up to 72" (1829 mm) face width.
For units wider than 72" (1829 mm) face dimension, attach bottom edge of duct work to header cover with #12 x 3/4" self-drilling and tapping screws, spacing not to exceed 12" (305 mm).
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
13
Page 16
INSTALLATION
Supply and drain connections and dimensions
Table 14-1: Condensate piping for Ultra-sorb MP steam dispersion panel
Evaporative steam Pressurized steam
P-trap water seal (Figure 14-1)
Inverted bucket trap No No
F&T trap No No
Condensate to open drain Yes Yes
Condensate return by condensate pump (Figure 14-2)
Condensate return to humidifi er by gravity
Drop: 2" (50 mm)
Seal: 5" (130 mm)
Yes Ye s
Yes NA
Recommended
method
Drop: 2" (50 mm)
Seal: 10" (255 mm)
FIGURE 14-1: P-TRAP WATER SEAL DIMENSIONS
Ultra-sorb condensate outlet
3/4” (20 mm) minimum copper
1” (25 mm)
Drop
FIGURE 14-2: LIFTING CONDENSATE
From P-trap or mechanical trap
Check valve
Condensate
pump
air gap
Seal
To condensate return main
FIGURE 14-3: STEAM SUPPLY CONNECTION TO A BOILER (PRESSURIZED STEAM APPLICATIONS)
Install strainer (same size as valve, or larger
Model MP
Notes:
• See Figure 14-1 for required drain piping.
• For detailed information about steam piping, see the DriSteem Humidifi cation System Design Guide, which can be downloaded from the Literature page of our website: www.dristeem.com.
than control valve) within 3 feet (1 m) of the Ultra-sorb Model MP dispersion panel.
Steam control valve
F&T trap
Note: The Ultra-sorb Model MP must be installed with the drain connection at an elevation that permits gravity drainage. For lifting condensate, use a condensate pump rated for your application. Contact your local DriSteem representative for pump selection.
Steam supply
OM-7854
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
14
Page 17
Ultra-sorb Model MP connections and dispersion tube detail
INSTALLATION
FIGURE 15-1: ULTRA-SORB MODEL MP STEAM INLET AND CONDENSATE OUTLET POSITIONS
Airfl ow
Steam inlet location
¾" (DN20) threaded condensate drain outlet
FIGURE 15-2: DISPERSION TUBE DETAIL
OM-7841
FIGURE 15-3: ULTRA-SORB MODEL MP STEAM INLET TYPES
Flange
OM-607-1b
Hose
OM-607-1a
Coupling
OM-607-2
Nipple
OM-7842
Orifi ce tubelet
1½” (Typ)
1½ or 2" Dia. dispersion tube
¾” Offset (Typ)
Grommet
FIGURE 15-4: INSULATED TUBE DETAIL (HIGH-EFFICIENCY TUBE OPTION)
Tubelets
Steam supply header separator
Steam
Dispersion tube insulation
Dispersion tubes
Grommet
OM-7843
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
15
Page 18
INSTALLATION
Piping
Table 16-1: Maximum steam carrying capacity and length of interconnecting steam hose or tubing
Steam hose
1
Copper or stainless steel tubing
Hose I.D. Maximum capacity Maximum length
2
Tubing size Maximum capacity 3
Maximum developed
length
4
inches DN lbs/hr kg/h ft m inches DN lbs/hr kg/h ft m
40 150 68 10 3 40 150 68 20 6
2 50 250 113 10 3 2 50 220 100 30 9
5
3
80
5
450 204 80 24
4 5 100 5750 340 100 30
1. Use DriSteem steam hose for best results. Other hose may have shorter life and may cause foaming in the evaporating chamber resulting in condensate discharge at the dispersion assembly. Do not use steam hose for outdoor applications.
2. Maximum recommended length for steam hose is 10' (3 m). Longer distances can cause kinking or low spots.
5
5
5
6
3. Insulate tubing to minimize loss of capacity and effi ciency.
4. Developed length of tubing equals measured length plus 50% of measured length, to account for fi ttings.
Longer tubing lengths are possible at capacities lower than listed
maximums. Consult factory.
5. Requires fl ange connection.
125
150
5
1400 635 100 30
5
2300 1043 100 30
Note: Capacities and lengths in this table are for steam from a nonpressurized steam humidifi er to a nonpressurized steam dispersion panel, and are
based on total maximum pressure drop in hose or tubing of 5" wc (1250 Pa).
mc_091410_1050-LVLH
Table 16-2: Steam loss of interconnecting steam hose or tubing
Steam loss
Insulation thickness
Description
Nominal hose or tubing size
Noninsulated Insulated
inches DN lbs/hr/ft kg/h/m lbs/hr/ft kg/h/m inches mm
40 0.15 0.22 N/A N/A N/A N/A
Hose
2 50 0.20 0.30 N/A N/A N/A N/A
40 0.11 0.16 0.020 0.030 2.0 50
2 50 0.14 0.21 0.025 0.037 2.0 50
3 80 0.20 0.30 0.030 0.045 2.5 64
Tubing
4 100 0.26 0.39 0.030 0.045 3.0 76
5 125 0.31 0.46 0.035 0.052 3.0 76
6 150 0.36 0.54 0.039 0.058 3.0 76
Note: Data based on an ambient air temperature of 80 °F (27 °C), fi berglass insulation, and copper tubing.
mc_051310_1216
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
16
Page 19
Piping
INSTALLATION
STEAM FROM A PRESSURIZED STEAM
Ultra-sorb panels for pressurized steam have a threaded pipe nipple that extends outside the framework for a steam supply connection. The steam supply line should be dripped immediately ahead of the steam valve through a steam trap. See Figure 14-3.
RECOMMENDED TRAP FOR STEAM MAIN DRIP LEG
Use a fl oat and thermostatic (F&T) trap on the steam supply ≤15 psi and inverted bucket if > 15 psi.
DRIEST STEAM
To ensure driest steam, take humidifi er steam off the top of the steam main (not the side or bottom).
Table 17-1: O.D. of pipe and tubing
Nom.
Standard
Dia.
1¼"
(30 mm)
1½"
(38 mm)
(50 mm)
2½"
(65 mm)
Note: Pipe thread and fl ange tubing adapters are available from DriSteem.
1.660 1.375 - -
1.900 1.625 1.500 1.50
2"
2.375 2.125 2.000 2.00
2.875 2.625 3.000 3.00
pipe
Copper
tubing
SST
tubing
I.D. of
hose
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
17
Page 20
INSTALLATION
Piping
STEAM FROM A NON-ELECTRODE-TYPE EVAPORATIVE HUMIDIFIER
This section provides piping instructions for resistive-element electric, gas­to-steam, and steam-to-steam evaporative humidifi ers. For electrode-type (DriSteem XT Series) humidifi er piping, see Page 19.
TUBING
Standard connections on DriSteem evaporative humidifi ers are 1½" (38 mm) stainless steel tubing. Two inch tubing connections are available as an option on higher capacity evaporative units. Hose cuffs are available for connecting to the tubing connection on the evaporative humidifi er and to the Ultra-sorb (see Figure 18-2). DriSteem can also provide threaded connections on the evaporative humidifi er and on the Ultra-sorb. For threading pipe connection options, see DriSteem’s DriCalc sizing and selection software, available at www. dristeem.com.
When non-threaded pipe is used, steam hose and clamps can be used for connections at the humidifi er steam outlet and at the Ultra-sorb. Due to the difference between the tubing O.D. and the steam hose I.D., multiple hose clamps may be required.
45° elbows
STEAM HOSE PITCH
recommended
Support steam hose to prevent sags or low spots, and pitch at least 2"/ft (15%) back to the humidifi er.
TUBING PITCH
• Pitch at least 2"/ft (15%) back to the humidifi er.
FIGURE 18-1: STEAM HOSE
Ultra-sorb
Steam hose (See Table 16-1)
OM-7855
DriSteem
non-electrode-
type evaporative
humidifi ers
FIGURE 18-2: HOSE CUFF INSTALLATION
Insulated tubing (See Table 17-1)
Hose and cuff clamps
Hose cuff and clamps
Standard 1½" (38 mm)
tubing outlet on cover DriSteem non-electrode­type evaporative humidifi er
Additional connections can be provided for multiple humidifi er connections
Ultra-sorb
OM-7856
• 90° elbows are not recommended. Use two 45° elbows one foot apart (see Figure 18-2).
Failure to follow the above recommendations may result in excessive back pressure on the evaporative humidifi er. This may lead to loss of water seal or leaking gaskets. When the distance between the Ultra-sorb and the evaporative humidifi er exceeds 20 feet (6 m), consult the factory for special recommendations.
• Thin wall tubing will heat up with less start up heat loss than heavy wall pipe.
• Insulate the tubing to reduce the loss in output caused by condensation in the tubing.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
18
Page 21
Piping
INSTALLATION
STEAM FROM AN ELECTRODE-TYPE EVAPORATIVE HUMIDIFIER
TUBING
Standard steam hose connects to DriSteem electrode steam humidifi er cylinders (XT series) and to the Ultra-sorb steam inlet directly or with a stainless steel adaptor. Hose cuffs are also available for connecting tubing. If specifi ed when ordered, DriSteem can provide a threaded connection on the Ultra-sorb steam inlet. For threading pipe connection options, see DriSteem’s DriCalc sizing and selection software, available at www.dristeem.com.
Hose and clamps can be used for connections at the steam cylinder and at the Ultra-sorb. Due to the difference between the tubing O.D. and the steam hose I.D., multiple hose clamps may be required.
STEAM HOSE PITCH
Support steam hose to prevent sags or low spots, and pitch at least 2"/ft (15%) toward the Ultra-sorb panel.
TUBING PITCH
• Pitch at least 1/8" /ft (1%) toward the Ultra-sorb.
• 90° elbows are not recommended. Use two 45° elbows one foot apart as shown in Figure 19-2.
Condensate drainage for all applications
Since Ultra-sorb panels operate with virtually zero internal pressure, condensate cannot be piped directly into a return main. It must be piped to a fl oor drain or into a condensate pump and returned to the steam source.
To prevent steam from escaping down the drain line, install a water seal or steam trap in the drain line. The water seal must be of suffi cient height to contain the pressure in the humidifi er.
FIGURE 19-1: CONDENSATE DRAINAGE
Failure to follow the above recommendations may result in faults at the electrode-type humidifi er. This may lead to erratic or stopped operation. When the distance between the Ultra-sorb and the evaporative humidifi er exceeds 20 feet (6 m), consult the factory for special recommendations.
• Thin wall tubing will heat up with less start up heat loss than heavy wall pipe.
• Insulate the tubing to reduce the loss in output caused by condensation in the tubing.
FIGURE 19-2: ULTRA-SORB MODEL MP IN A HORIZONTAL AIRFLOW WITH ELECTRODE-TYPE HUMIDIFIER
Pitch toward Ultra-sorb*
90° long sweep or two 45° elbows
Steam hose, tubing, or pipe
Electrode-type humidifi er
OM-7587
* Pitch steam hose, tubing, or pipe
toward Ultra-sorb: 2"/ft (15%) when using steam hose. 1/8"/ft (1%) when using tubing or pipe.
See trap dimensions in Table 14-1
3/4" pipe thread (DN20) drain
3/4" (DN20) copper
1" (25 mm) air gap
Open drain required. Locate air gap only in spaces with adequate temperature and air movement to absorb fl ash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
19
Page 22
OPERATION
Replacing Ultra-sorb Model MP dispersion tubes
REMOVING A DISPERSION TUBE FROM AN ULTRA-SORB PANEL
A dispersion tube may need to be removed for access to an adjacent coil, or because of tube damage or upgrade to an insulated tube. See page 3 for how to install a dispersion tube.
1. Apply soapy water around the tube grommet to ease turning and removal of the dispersion tube.
2. Loosen the jam nut from the tube nut at top of the tube. Rotate the tube off the top frame assembly bolt (about 4 rotations of the tube).
3. Press downward on the tube so to clear bolt at top of frame.
4. Move the tube to a slight angle so that it does not interfere with top frame of Ultra-sorb Model MP panel.
5. Pull the tube out from the rubber grommet.
6. If the grommet shows any sign of wear or damage, replace it before reinstalling the dispersion tube. See Table 29-1 for replacement parts. Note: Grommets are provided with replacement tubes.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
20
Page 23
Performance data
OPERATION
NON-WETTING DISTANCE
Non-wetting distance is the distance downstream from the leaving side of the steam dispersion assembly to the point where wetting will not occur. This distance is dependent on several application parameters. To determine your dispersion assembly’s non-wetting distance, consult your system’s design engineer or project documentation. Non-wetting distance can also be calculated using DriSteem’s DriCalc sizing and selection application, available at www. dristeem.com. Note that your current design conditions may vary from conditions used for system design.
• Note that the rise in relative humidity (ΔRH) between entering and leaving air has a direct bearing on the non-wetting distance. As the change in relative humidity (ΔRH) increases, the non-wetting distance increases.
• Uneven airfl ow over the Ultra-sorb panel cross-section may result in nonuniform mixing of steam with air, which may adversely affect absorption distance.
Table 21-1: Ultra-sorb air pressure loss
Duct air velocity
(55 ˚F at sea level)
• A small amount of duct air pressure loss will be present downstream from the Ultra-sorb panel, depending on air density, velocity, and tube spacing. See Table 21-1.
mc_071211_1515
fpm m/s wc Pa wc Pa
500 2.54 0.020 5.1 0.004 1.1
1000 5.08 0.082 20.5 0.017 4.2
CAUTION
Installing the Ultra-sorb panel upstream from fi lter media
Non-wetting distances described here do not apply when installing an Ultra-sorb panel upstream from fi lter media. If you must install upstream from fi lter media, consult DriSteem or your local DriSteem representative for recommendations.
mc_071211_1505
Tube spacing
3" 75 mm 6" 150 mm
Uninsulated tubes
1500 7.62 0.175 43.8 0.038 9.5
fpm m/s wc Pa wc Pa
500 2.54 0.033 8.3 0.005 1.3
1000 5.08 0.121 30.2 0.020 5.1
1500 7.62 0.237 59.2 0.046 11.5
High-efficiency tubes
Notes:
• Ultra-sorb panels with 9" (225 mm) or 12" (300 mm) tube spacings have no measurable air pressure loss.
• Use DriSteem’s DriCalc sizing and selection application to calculate your specifi c air pressure loss.
mc_100907_0830
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
21
Page 24
OPERATION
VDC
T STEAM
VALVE
VDC SIGNAL
Controls
AIRFLOW PROVING SWITCH
An air fl ow proving switch should be used to prevent the steam valve from opening if air is not moving in the duct.
HIGH LIMIT HUMIDISTAT
To prevent over saturation when duct air is cooler than 70 °F (21 °C), use a high limit (duct mounted) humidistat (Figure 10-1). Mount it 10' to 15' (3 to
4.5 m) downstream from the Ultra-sorb panel, and set it at 80 to 90% RH.
FIGURE 22-1: ULTRA-SORB MODEL MP TYPICAL CONTROL WIRING
-10
OR HUMIDISTA
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
22
-10
Page 25
Startup
1. Turn on humidification steam to the Ultra-sorb supply header:
• Pressurized steam: Open the modulating steam valve.
• Evaporative humidifi er: Follow the startup instructions in the humidifi er's Installation, Operation, and Maintenance Manual.
2. Check for piping leaks.
3. See “Steam traps” on page 24.
4. Check the dispersion tubes for leaks.
5. Ensure that the dispersion tubes are oriented with the tubelets at a right angle to the airflow. See Figure 9-1.
6. Check for any other leaks from steam and drain connections.
7. Ensure that the P-traps are operating.
• At the beginning of the season, ensure there is a stream of water from
condensate drain when operating.
1. If not, verify P-trap is not blocked.
2. If steam is blowing out of the P-trap, it needs to be primed.
3. Verify the P-trap is tall enough to contain panel operating pressure (see page 10 or 11).
4. Duct static pressure > 2.5" ( 63.5 mm) wc may require a taller P-trap.
OPERATION
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
23
Page 26
MAINTENANCE
Inspecting and servicing components
STRAINER
Inspect the strainer screen at least twice during the fi rst year. If fouled, inspect it more frequently.
STEAM TRAPS ON MAIN STEAM SUPPLY
At least twice a year verify that steam traps are functioning properly. A blocked steam trap is cold. A "blowing" steam trap is hot and noisy, and the discharge pipe from it is hot for 30 feet. A properly operating steam trap is hot and makes noise at intervals, and the discharge pipe is progressively cooler beginning at the trap.
VALVES
• Electric modulating:
Inspect annually to be sure that the valve operates freely and closes off
steam tightly and the stem packing is not leaking.
• Pneumatic:
Inspect annually to be sure the valve closes off steam tightly, the stem
packing is not leaking steam, and the diaphragm in the actuator is not leaking air.
HIGH-EFFICIENCY TUBES
• If the insulating material gets dirty or smudged, gently clean it with a damp cloth and a solution of soapy water or diluted non-toxic, biodegradable cleaner/degreaser.
• Do not clean the insulating material with a pressure washer. The direct spray could cause damage.
• If using a torch in the vicinity of the dispersion panel, keep the fl ame away from the insulating material to avoid damage.
• PVDF is inherently resistant to UV light. Indirect, low-intensity UV-C light from germicidal lamps will not cause the insulating material to degrade.
• Do not tighten mounting clamps or fasteners to any part of the dispersion tube.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
24
Page 27
Troubleshooting
Table 25-1: Ultra-sorb Model MP troubleshooting
Problem Possible cause Action
Humidifi er discharges water in duct
Humidity exceeds setting of humidistat
• Steam main overloaded with water due to boiler discharging water with steam (priming)
• P- trap not draining properly • Replace or clean trap as required.
• Humidifi er improperly piped • Correct the piping as shown on Page 14. Steam inlet
• Surges of condensate in steam supply due to condensate collecting at low, undripped point in steam main
• Inadequate main steam trap capacity • Replace with larger trap.
• Control valve not fully closing • Foreign matter holding valve open; clean valve.
• Faulty or inaccurately placed humidity controller
• Poor location of control components • Relocate per catalog recommendations.
• Incompatible control components • Replace per specifi ed recommendations.
• Automatic valve is hunting • Humidifi er capacity is oversized; change to smaller valve.
• Excessive outside air volume • Check fans, dampers, VAV, etc. See formula below.
MAINTENANCE
• Locate cause of priming and correct.
• If condensate return main is overloaded, fi nd an alternative method for draining.
should be at center off the header and condensate outlet at the bottom of the assembly.
• Install drips and steam traps as required. See Page 14.
• Check signal and power to valve.
• Valve steam packing too tight; loosen and/or replace packing.
• Steam pressure exceeds close-off rating of valve spring; replace actuator or valve spring with one that is compatible with the higher steam pressure.
• Valve installed backwards; re-install.
• Adjust valve linkage.
• Replace controller or relocate per catalog recommendations.
• Pressure reducing valve is not accurately controlling steam pressure; repair or replace.
• Boiler pressure is swinging too widely; adjust.
Mixed Air Inlet formula: (% outside air x moisture content) + (% return air x moisture content) = mixed air inlet in lbs/100 cfm (kg/100 m3/h)
Continued
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
25
Page 28
MAINTENANCE
Troubleshooting
Table 25-1: Ultra-sorb Model MP troubleshooting
Problem Possible cause Action
Control system malfunctioning
Air cannot absorb steam quantity being discharged
Humidifi er is noisy • Steam pressure too high • Reduce pressure.
• Incorrect control voltage • Replace transformer.
• Incorrect control signal • Replace components.
• Improper wiring connections • Rewire.
• Incorrect humidity sensor • Replace.
• Humidity controller out of calibration • Recalibrate.
• Humidifi er operates when blower is off • Provide interlock.
• Valve is hunting • See above.
• Air temperature in duct too low for steam quantity being emitted
• Raise duct air temperature.
Continued
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
26
Page 29
Troubleshooting
Table 25-1: Ultra-sorb Model MP troubleshooting (continued)
Problem Possible cause Action
Space humidity will not rise to humidistat set point
Condensate in duct • Foreign matter preventing valve from closing • Clean or replace valve.
• Steam pressure too low • Increase.
• Manual steam valve partially closed • Open.
• Strainer screen partially clogged • Clean.
• Boiler pressure too low • Adjust control.
• Pressure reducing valve not accurately controlling steam pressure
• Boiler pressure swinging too widely • Adjust controls.
• Incorrect piping • Repipe. See Page 14.
• Undersized steam piping • Replace.
• Undersized humidifi er • Replace valve with larger capacity valve.
• Automatic steam valve not fully opening • Valve packing is adjusted too tightly, loosen and/or
• Electric control system malfunctioning • Change transformer.
• Incorrect control circuit voltage • Replace component(s) to make all components compatible.
• Incorrect control signal • Replace components.
• Improper wiring • Rewire.
• Incorrect humidity sensor • Replace sensor.
• Humidity controller out of calibration or malfunctioning
• Malfunctioning humidifi er temperature switch not allowing humidifi er valve to open
• Pneumatic control system malfunctioning • Repair or replace.
• Obstructed air line • Remove obstruction.
• Malfunctioning pneumatic temperature switch
• Air leak in actuator • Repair or replace diaphragm.
• Compressed air pressure is too low • Adjust pressure.
• Humidifi er is mounted too close to internal devices (dampers, turning vanes, etc.) in duct
• Non-insulated duct passing through unheated area (duct surface temperature too low)
• Repair or replace.
• Replace with larger humidifi er.
• Add additional humidifi er.
replace packing.
• Adjust valve linkage.
• Recalibrate humidistat.
• Repair or replace.
• Replace or readjust.
• Replace switch.
• Move humidifi er tubes to a point further upstream from internal devices.
• Add more dispersion tubes for shorter non-wetting distance. Consult DriSteem to determine the total number of tubes required.
• Insulate ductwork.
MAINTENANCE
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
27
Page 30
MAINTENANCE
Replacement parts
FIGURE 28-1: ULTRA-SORB MODEL MP REPLACEMENT PARTS
7
5
4
8
6
2
OM-7890
1
3
11
10
9
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
28
OM-7854_rightside
Page 31
Replacement parts
Note: Consult factory for Ultra-sorb Model MP replacement parts.
Table 29-1: Ultra-sorb Model MP replacement parts
No. Description Part number
1 Ultra-sorb Model MP header Consult factory
2 Flange side Ultra-sorb Model MP Consult factory
Nut lock ¼" 20 UNC Hex Nylock SST 191172-010
3
Nut lock ¼" 20 UNC Hex Nylock plated 191170-035
1½" (38 mm) high-effi ciency insulated dispersion tube Consult factory
1½" (38 mm) high-effi ciency non-insulated dispersion tube Consult factory
4
2" (50 mm) high-effi ciency insulated dispersion tube Consult factory
MAINTENANCE
2" (50 mm) high-effi ciency non-insulated dispersion tube Consult factory
Screw #8 32 x 3/8" PHL PNHD DRV Type F stainless steel (SST) 191172-015
5
Screw #8 32 x 3/8" PHL PNHD Type F 191172-020
Grommet for 1½" (38 mm) dispersion tube 405895-150
6
Grommet for 2" (50 mm) dispersion tube 405895-200
Frame top, Ultra-sorb Model MP, split over, 144" (3658 mm) width Consult factory
7
Frame top, Ultra-sorb Model MP, to 144" (3658 mm) width Consult factory
8 Tubelet Consult factory
9 Steam trap Consult factory
10 Steam valve Consult factory
11 Strainer Consult factory
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
29
Page 32
W
ARRANTY
Expect quality from the industry leader
Since 1965, DriSteem has led the industry with innovative methods for humidifying and cooling air with precise control. Our focus on ease of ownership is evident in the design of the Ultra--sorb steam dispersion panels, which feature cleanable, stainless steel construction. DriSteem also leads the industry with a Two-year Limited Warranty and optional extended warranty.
For more information
www.dristeem.com sales@dristeem.com
For the most recent product information visit our website: www.dristeem.com
DRI-STEEM Corporation
a subsidiary of Research Products Corporation DriSteem is an ISO 9001:2008 certifi ed company
U.S. Headquarters: 14949 Technology Drive Eden Prairie, MN 55344 800-328-4447 or 952-949-2415 952-229-3200 (fax)
European offi ce: Grote Hellekensstraat 54 b B-3520 Zonhoven Belgium +3211823595 E-mail: dristeem-europe@dristeem.com
Two-year Limited Warranty
DRI-STEEM Corporation (“DriSteem”) warrants to the original user that its products will be free from defects in materials and workmanship for a period of two (2) years after installation or twenty­seven (27) months from the date DriSteem ships such product, whichever date is the earlier.
If any DriSteem product is found to be defective in material or workmanship during the applicable warranty period, DriSteem’s entire liability, and the purchaser’s sole and exclusive remedy, shall be the repair or replacement of the defective product, or the refund of the purchase price, at DriSteem’s election. DriSteem shall not be liable for any costs or expenses, whether direct or indirect, associated with the installation, removal or reinstallation of any defective product. The Limited Warranty does not include cylinder replacement for electrode steam humidifi ers.
DriSteem’s Limited Warranty shall not be effective or actionable unless there is compliance with all installation and operating instructions furnished by DriSteem, or if the products have been modifi ed or altered without the written consent of DriSteem, or if such products have been subject to accident, misuse, mishandling, tampering, negligence or improper maintenance. Any warranty claim must be submitted to DriSteem in writing within the stated warranty period. Defective parts may be required to be returned to DriSteem. Excluded from the Limited Warranty are all consumable and wear and tear items such as cylinders, membranes, fi lters, or media replacements. These items are subject to usual wear and tear during usage.
DriSteem’s Limited Warranty is made in lieu of, and DriSteem disclaims all other warranties, whether express or implied, including but not limited to any IMPLIED WARRANTY OF MERCHANTABILITY, ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, any implied warranty arising out of a course of dealing or of performance, custom or usage of trade.
DriSteem SHALL NOT, UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, LOSS OF PROFITS, REVENUE OR BUSINESS) OR DAMAGE OR INJURY TO PERSONS OR PROPERTY IN ANY WAY RELATED TO THE MANUFACTURE OR THE USE OF ITS PRODUCTS. The exclusion applies regardless of whether such damages are sought based on breach of warranty, breach of contract, negligence, strict liability in tort, or any other legal theory, even if DriSteem has notice of the possibility of such damages.
By purchasing DriSteem’s products, the purchaser agrees to the terms and conditions of this Limited Warranty.
Extended warranty
The original user may extend the term of the DriSteem Limited Warranty for a limited number of months past the initial applicable warranty period and term provided in the fi rst paragraph of this Limited Warranty. All the terms and conditions of the Limited Warranty during the initial applicable warranty period and term shall apply during any extended term. An extended warranty term of an additional twelve (12) months or twenty four (24) months of coverage may be purchased. The extended warranty term may be purchased until eighteen (18) months after the product is shipped, after which time no extended warranties are available. When a Dristeem humidifi er is purchased with a DriSteem RO system, an extended twenty-four (24) month coverage is included.
Continuous product improvement is a policy of DriSteem; therefore, product features and specifi cations are subject to change without notice.
DriSteem and Ultra-sorb are registered trademarks of Research Products Corporation and are fi led for trademark registration in Canada and the European community.
Product and corporate names used in this document may be trademarks or registered trademarks. They are used for explanation only without intent to infringe.
© 2018 Research Products Corporation
Form No. US-MP-IOM-EN-0818 Part No. 890000-611 Rev E
Any extension of the Limited Warranty under this program must be in writing, signed by DriSteem, and paid for in full by the purchaser.