DriSteem ultra-sorb MP Installation, Operation And Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS
ULTRA-SORB
Steam Dispersion Panels
®
MODEL MP
Installation, Operation, and Maintenance Manual
For applications using steam from a boiler or from any DriSteem steam generating humidifier.
Table of contents
UNPACKING HIGH-EFFICIENCY TUBES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Ultra-sorb Model MP field assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Ultra-sorb Model MP mechanical specifications . . . . . . . . . . . . . . . . . . . . 4
Selecting the location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Determine humidifier placement . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Placement in an air handling unit . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Mounting and support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation in a cold air stream . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Placement upstream from an elbow or duct split . . . . . . . . . . . . . . . . 8
Installation above valuable equipment . . . . . . . . . . . . . . . . . . . . . . . 8
Panel support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Ultra-sorb Model MP mounting - pressurized steam application . . . . . . . . 10
Ultra-sorb Model MP mounting - nonpressurized steam application . . . . . 11
Mounting in an air handling unit . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mounting in a horizontal duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Supply and drain connections and dimensions . . . . . . . . . . . . . . . . . . . 14
Ultra-sorb Model MP connections and dispersion tube detail . . . . . . . . . 15
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Steam from a Pressurized steam . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Steam from a non-electrode-type evaporative humidifier . . . . . . . . . . 18
Steam from an electrode-type evaporative humidifier . . . . . . . . . . . . 19
WARNING
Hot surface hazard
Steam humidifi cation systems have extremely hot surfaces.
To avoid burns, allow humidifi er, steam pipes, and dispersion assemblies to cool before touching any part of the system.
mc_071411_0753
ATTENTION INSTALLER
Read this manual before installing. Leave manual with product owner.
DriSteem Technical Support
• technical.support@dristeem.com
• 800-328-4447
• dristeem.com/technical-support
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Replacing Ultra-sorb Model MP dispersion tubes . . . . . . . . . . . . . . . . . . 20
Performance data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Inspecting and servicing components . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Steam traps on main steam supply . . . . . . . . . . . . . . . . . . . . . . . . 24
Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
High-Efficiency Tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
ii
Unpacking High-Effi ciency Tubes
UNPACKING HIGH-EFFICIENCY TUBES
NOTE: If you have an Ultra-sorb without High-effi ciency dispersion tubes (non­insulated tubes), please skip to the next page.
UNPACKING
• Remove the dispersion assembly from the shipping container; be careful not to damage the PVDF insulating material on the dispersion tubes.
• Some dispersion panels are shipped unassembled. Do not lay High­Effi ciency Tubes across or under anything that could compress or damage the insulating material. Compressed insulating material has a reduced R-value.
• Before start-up, remove the clear poly fi lm covering the insulation by tearing it along the perforation. Do not use a knife or sharp object to remove the
poly fi lm.
CAUTION
Remove clear poly fi lm; do not remove white PVDF insulation.
High-effi ciency tubes are sleeved in clear poly fi lm for protection during, shipping, and installation. Leave the clear poly fi lm on until installation is complete.
Remove and discard the clear poly fi lm before start-up by tearing it along the perforations. Do not remove the white
PVDF insulation.
Keep fl ame away from the insulation to avoid damage.
PVDF is resistant to UV light. UV-C light from germicidal lamps will not cause the insulating material to degrade.
Do not tighten mounting clamps or fasteners to any part of the dispersion tube.
High-efficiency tube option
Dispersion assemblies with the High-Effi ciency Tube option are designed to produce signifi cantly less dispersion-generated condensate and airstream heat gain, which reduces wasted energy by up to 85%.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
1
INSTALLATION
Ultra-sorb Model MP fi eld assembly
Note: These assembly instructions are for Ultra-sorb Model MP panels shipped
unassembled by request or as required. Panels with overall height more than 98" (2490 mm) are shipped unassembled.
LAY OUT THE PANEL COMPONENTS
Place the panel components on a large, fl at working surface.
ATTACH THE TOP FRAME ASSEMBLY
Span the fl anges with the top frame assembly. Align the locating pins on the fl anges and top frame, and insert screws.
TIGHTEN THE FLANGE LOCKNUTS
Torque the eight fl ange locknuts to 16 ft-lb (22 N-m) at 100 rpm maximum using a 7/16" deep-well socket.
INSTALL THE DISPERSION TUBES
Note: Do not remove the poly fi lm from the dispersion tubes until after the
panel is installed.
FIGURE 2-1: ULTRA-SORB MODEL MP COMPONENTS
Top frame assembly
Locating pins
Left side fl ange
Flange locknut
Dispersion tube
Insulation
Header assembly
OM-7846
Right side fl ange
Table 2-1: Ultra-sorb Model MP components
Component Qty.
Header assembly 1
Dispersion tubes Varies
Top frame assembly 1
Side fl anges 2
Screws Varies
Flange locknuts 8
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
2
Ultra-sorb Model MP fi eld assembly
INSERT DISPERSION TUBES INTO AN UNASSEMBLED ULTRA-SORB PANEL
If the Ultra-sorb Model MP panel was shipped unassembled, the dispersion tubes need to be inserted into the panel.
Note: Use soapy water to lubricate end of tubes where inserted into rubber grommet.
1. Insert tube into rubber grommet at panel header, with open end at bottom. Insert at a slight angle to not interfere with top frame of Ultra-sorb panel.
2. Press downward on tube so to clear stud at top of tube. Align tube with rivet nut on top of the header.
3. Once aligned, turn the tube three full rotations into rivet nut for proper engagement.
4. Turn the tube backwards so that the steam tubelets face the next tube, perpendicular to air flow. Face the lowest tubelet of each tube in the same direction so the facing tubelets are at staggered heights.
INSTALLATION
5. Tighten the locknut down to the top header to 10 in-lbs (1.13 N-m). Note: If the rivet nut pulls through, add a ¼"-20 nut on each side of the top flange to secure the tube.
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
3
INSTALLATION
Ultra-sorb Model MP mechanical specifi cations
FIGURE 4-1: ULTRA-SORB MODEL MP DIMENSIONS
Top view
Connections
side view
4" steam
inlet
G
H
Note: See Table 5-1: Ultra-sorb MP dimensions
All except with 4" steam inlet
G
H
Blank
side view
A
D
B
Header
A’
J
B’
E
F
C
OM-7915_mp
Elevation view
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
4
Table 4-1: Ultra-sorb Model MP unit capacity
Evaporative steam Pressurized steam (2-50 psi)
lbs/hr kg/hr lbs/hr kg/hr
700 318 2720 1235
Table 4-2: Ultra-sorb Model MP tube capacity*
Tubes lbs/hr kg/hr
Uninsulated 40 18.1
1.5" Insulated 43 19.5
Uninsulated 77 34.9
2.0" Insulated 80 36.3
* If face height (B') is <17" (432 mm), consult DriSteem or see DriCalc for the correct calculation.
INSTALLATION
Ultra-sorb Model MP mechanical specifi cations
Table 5-1: Ultra-sorb Model MP dimensions
Dimension Inches (mm)
A Unit width 15" (380 mm) min, 147" (3735 mm) max, in ½" (13 mm) increments
A' Face width 12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments
B Unit height* 19.375" (492 mm) min, 151.375" (3845 mm) max, in ½" (13 mm) increments
B' Face height 12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments
C Frame depth
D Frame enclosure 1.5" (38 mm)
E Header enclosure 5.85" (149 mm)
F Mounting fl ange 1.5" (38 mm)
G Humidifi cation
steam inlet
H Drain port
(internal thread)
J Overall width
* Panels with unit height more than 120" (3048 mm) have two-piece side fl anges and are shipped with brackets for easy fi eld assembly. Panels
with unit height more than 98" (2490 mm) are shipped unassembled.
7.2" (183 mm)
2.3" (58 mm) for side drain port (H) when 4" coupling (DN100) steam inlet
1" or 2" NPT coupling, for pressurized steam
1½" or 2" NPT coupling, for evaporative steam
3" or 4" flange, for evaporative steam
DN25 or DN50 BSPT nipple, for pressurized steam
DN50, DN80, or DN100 BSPT nipple, for evaporative steam
1½" or 2" (DN40 or DN50) hose, for evaporative steam
¾" NPT (DN20) coupling
1" NPT coupling, dimension A + 1/8";
1½" NPT coupling, dimension A + ½";
2" NPT coupling, dimension A + 1"
3" and 4" flange connection, dimension A + 6.5"
DN25, DN50, DN80 BSP nipple, dimension A + 38 mm
DN100 BSP nipple, dimension A + 64 mm
1½" or 2" (DN40 or DN50) hose connection, dimension A + ½" (dimension A + 13 mm)
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
5
INSTALLATION
Selecting the location
DETERMINE HUMIDIFIER PLACEMENT
Dispersed steam must be absorbed into the airfl ow before it comes in contact with duct elbows, fans, vanes, fi lters, or any object that can cause condensation and dripping.
• Install the Ultra-sorb panel in a location where discharged water vapor will be absorbed by the airstream.
• Place the Ultra-sorb panel where the air temperature is capable of absorbing discharged steam without causing condensation at or after the unit. This will normally be downstream from the heating coil where the air is warmest.
• Do not place the Ultra-sorb panel in an outside air intake unless the air is tempered with a preheat coil.
• Do not place the Ultra-sorb panel near the entrance of a high-effi ciency fi lter. The fi lter will remove visible moisture and become waterlogged. See the Caution "Installing the Ultra-sorb panel upstream from fi lter media" on page 21.
• Do not place the Ultra-sorb panel where discharged visible mist will impinge directly on a metal surface.
mc_071111_1710
PLACEMENT IN AN AIR HANDLING UNIT
Location A is the best choice. Installing downstream from heating and cooling coils provides laminar fl ow through the dispersion unit; plus, the heated air provides an environment for best absorption.
Location B is the second-best choice. However, conditions when both cooling and humidifi cation is needed, the cooling coil will eliminate some moisture for humidifi cation.
Location C is the third-best choice. Air leaving a fan is usually very turbulent and can cause vapor to not absorb at the expected non-wetting distance. Allow for more distance if installing downstream from a fan.
Location D is the poorest choice. The cooler air at this location requires an increased non-wetting distance.
mc_062111_0715
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
6
Selecting the location
FIGURE 7-1: PLACING A DISPERSION ASSEMBLY IN AN AIR HANDLING UNIT
INSTALLATION
Outside air
Exterior building wall
Relief air
Economizer control device
Preheat coil
Motorized air dampers
Filters
Heating coil
DC-1081 mc_092507_1530
Return airfl ow
Cooling coil
ABD
3' to 5' (1 to 1.5 m)
8' to 12' (2.4 to 3.7 m)
8' to 12' (2.4 to 3.7 m)
Duct high limit humidity control for dispersion locations A, B Airfl ow proving switch
Fan
C
Airfl ow proving switch
Duct high limit humidity control for dispersion location C
Supply airfl ow
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
7
INSTALLATION
Mounting and support
INSTALLATION IN A COLD AIR STREAM
When a humidifi er is installed in a duct that will carry cold air, determine the dew point temperature. If the psychrometric chart reveals that saturation may occur, protection should be provided. A high-limit humidistat or humidity transmitter can be used for this purpose. See Figure 8-1.
PLACEMENT UPSTREAM FROM AN ELBOW OR DUCT SPLIT
Installation upstream from elbows or duct splits can be done. See Figure 8-2 if placed upstream a minimum of the non-wetting distance.
INSTALLATION ABOVE VALUABLE EQUIPMENT
Water piping and humidifi ers should not be installed above expensive equipment. A condensing or leaking water pipe or other accidental water spillage could damage the equipment below. When such an installation cannot be avoided, install a drip pan under the humidifi er piping, valve, etc. to catch and drain away unintended water. See Figure 8-3.
PANEL SUPPORT
The duct or air handler section and Ultra-sorb panel must be properly supported to carry the weight of the assembly. The weight of the piping must be supported by the building structure rather than by the Ultra-sorb unit. Excessive weight on the Ultra-sorb panel may stress the connections, causing them to fracture and leak.
mc_071311_1540
FIGURE 8-1: INSTALLATION IN A COLD AIR STREAM
Extended trails of
Elbow
Non-
wetting
OM-7862
fog may develop
Duct
Cold air fl ow
High limit duct humidistat 10' to 15' (3 to 4.5 m) downstream from Ultra-sorb
OM-197 mc_052411_0830
FIGURE 8-2: UPSTREAM PLACEMENT
Air fl ow
Ultra-sorb
Ultra-sorb
Air fl ow
Ultra-sorb
distance
Duct split
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
8
FIGURE 8-3: INSTALLATION ABOVE VALUABLE EQUIPMENT
Ultra-sorb
Vapor absorption
Air fl ow
Drip pan
Pipe to drain size as required
* This length of duct should have sealed seams
and should be at least three times the height of the Ultra-sorb panel.
OM-198 mc_101410_0955
area
2" (50 mm)
Ceiling line
Loading...
+ 22 hidden pages