DriSteem SINGLE-TUBE Series, MINI-BANK Series, MULTIPLE-TUBE Series, AREA-TYPE Series Installation, Operation And Maintenance Manual

Page 1
READ AND SAVE THESE INSTRUCTIONS
STEAM INJECTION
Humidifiers
Installation, Operation, and Maintenance Manual
For use with steam boilers
Page 2
ATTENTION INSTALLER Read this manual before installing.
Leave manual with product owner.
Where to find more information On our website: The following related documents can be
viewed, printed, or ordered from our website, www.dristeem.com
In Dri-calc Dri-calc is DriSteem’s free sizing and
selection software for calculating load, determining non-wetting distance, and selecting equipment. See Dri-calc on the www.dristeem.com Tools page. Also in Dri-calc:
A comprehensive library of Installation Guide documents, including:
• Recommended placement within a duct or air handler
• Recommended sensor placement
Or call us at 800-328-4447 Obtaining documents from our website or
from Dri-calc is the quickest way to view our literature, or we will be happy to mail literature to you.
®
WARNING
Indicates a hazardous situation that could result in death or serious injury if instructions are not followed.
WARNING
Attention installer
Read this manual before installing, and leave this manual with product owner. This product must be installed by qualified HVAC and electrical contractors and in compliance with local, state, federal, and governing codes. Improper installation can cause property damage, severe personal injury, or death as a result of electric shock, burns, or fire.
DriSteem® technical support: 800-328-4447
Read all warnings and instructions
Read this manual before performing service or maintenance procedures on any part of the system. Failure to follow all warnings and instructions could produce the hazardous situations described, resulting in property damage, personal injury, or death.
Failure to follow the instructions in this manual can cause moisture to accumulate, which can cause bacteria and mold growth or dripping water into building spaces. Dripping water can cause property damage; bacteria and mold growth can cause illness.
mc_011909_1215
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
ii
Hot surfaces and hot water
Steam Injection humidifiers have extremely hot surfaces. Water in steam pipes and dispersion assemblies can be as hot as 212 °F (100 °C). Discharged steam is not visible. Contact with hot surfaces, discharged hot water, or air into which steam has been discharged can cause severe personal injury. To avoid severe burns, allow the system to cool before performing service or maintenance procedures on any part of the system.
Page 3
Table of contents
OVERVIEW.................................................................2
Introduction .............................................2
Available models .........................................3
Basic components ........................................4
Principle of operation ......................................5
Humidifier placement ......................................6
Sensor placement ........................................9
Pressurized steam piping guidelines ..........................10
Condensate drain piping and trapping ........................14
Temperature switches .....................................16
SINGLE-TUBE HUMIDIFIER ....................................................20
Configurations .........................................20
Assembly .............................................21
Installation ............................................22
Piping notes ...........................................23
Field piping ...........................................24
MULTIPLE-TUBE HUMIDIFIER ..................................................28
Field assembly .........................................28
Installation ............................................29
Piping notes ...........................................30
Field piping ...........................................31
WARNING
Hot surface hazard
Steam humidification systems have extremely hot surfaces.
To avoid burns, allow humidifier, steam pipes, and dispersion assemblies to cool before touching any part of the system.
mc_071411_0753
ATTENTION INSTALLER
Read this manual before installing. Leave manual with product owner.
DriSteem technical support
800-328-4447
MAXI-BANK HUMIDIFIER .................................................... 36
Maxi-bank option field assembly and installation .................36
Maxi-bank option piping notes ..............................39
Maxi-bank option field piping ...............................40
Assembly and installation ..................................45
MINI-BANK HUMIDIFIER .....................................................45
Field piping ...........................................47
AREA-TYPE HUMIDIFIER ..................................................... 48
Installation ............................................48
Field piping ...........................................49
Rise, spread, and throw dimensions ..........................50
Humidifier start-up and shut-down ............................51
OPERATION ..............................................................51
Eliminating excess heat from steam jacketed humidifiers ............52
MAINTENANCE ........................................................... 54
Maintenance procedures ..................................54
Troubleshooting .........................................55
TROUBLESHOOTING........................................................ 55
REPLACEMENT PARTS ....................................................... 58
Single-tube and Multiple-tube humidifiers .......................58
Area-type humidifier .....................................60
Mini-bank humidifier .....................................61
WARRANTY .............................................................. 62
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
1
Page 4

OVERVIEW

Introduction

SUITABLE FOR A WIDE RANGE OF APPLICATIONS
Steam Injection humidifiers from DriSteem® use steam from an external source, such as an in-house boiler or a district steam system. DriSteem’s Steam Injection humidifiers are adaptable to virtually any size application, and a wide variety of models accommodate a broad range of steam absorption requirements.
STEAM JACKETED DISPERSION TUBE MODELS FOR DUCTS AND AIR HANDLERS
Single-tube, Mini-bank®, and Multiple-tube humidifiers are designed for ducts and air handlers, and capable of a wide range of guaranteed non-wetting distances.
AREA-TYPE FOR OPEN SPACES
Area-type™ Steam Injection humidifiers are designed for open spaces such as warehouses and manufacturing spaces that do not have a duct system. The steam discharged from the humidifier is quietly dispersed by a fan without introducing water droplets into the air.
FIGURE 2-1: STEAM INJECTION HUMIDIFIERS
Each Single-tube, Mini-bank®, and Multiple-tube humidifier has the same basic components: a stainless steel separator, a steam valve, and one or more jacketed dispersion tubes.
For open spaces, boiler steam can be dispersed by the fan of an Area-type model.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
2
Page 5

Available models

OVERVIEW
FIGURE 3-1: STEAM INJECTION HUMIDIFIER MODELS
SINGLE-TUBE HUMIDIFIER
• Suitable for small- to medium-capacity systems,
1.5 – 525 lbs/hr (0.7 – 238 kg/h)
• Moderate to long non-wetting distance
• Pre-assembled separator/tube assembly
MINI-BANK HUMIDIFIER
• Suitable for small-capacity systems, 1.6 – 84 lbs/ hr (0.7 – 38 kg/h)
• Short to moderate non-wetting distance
• Sized for small ducts
• Pre-engineered and pre-assembled header/tube assembly, ready for mounting and hookup
MULTIPLE-TUBE HUMIDIFIER
• Suitable for small- to large-capacity systems,
6.5 – 3989 lbs/hr (2.3 – 1809 kg/h)
• Sizes to fit small ducts and large air handlers
• Short to moderate non-wetting distance
• Field assembled (with interconnecting piping and header supplied by contractor)
• Maxi-bank™ option: – Pre-assembled, except when either dimension
is 98 inches (2490 mm) or more
– Includes 304 stainless steel header, with
option for 316 stainless steel
– Includes black iron piping, with options for
304 or 316 stainless steel
All Steam Injection humidifiers shown here, except Area-type, are available with options for applications requiring stainless steel steam components.
mc_033111_0500
AREA-TYPE HUMIDIFIER
• Suitable for medium-capacity systems, 1.8 – 286 lbs/hr (0.8 – 130 kg/h)
• Used in open spaces
• Application-dependent non-wetting distances
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
3
Page 6
OVERVIEW

Basic components

FIGURE 4-1: STEAM INJECTION HUMIDIFIER COMPONENTS
Section Y-Y
OM-378
Section X-X
Condensate
Steam
8
X
4
2
OM-376
9
6
5
X
3
Tube profile with insulation
7
Y
Y
Steam-filled jacket
Steam-discharge tubelet
Dispersion tube
Optional PVDF insulation
1. Steam jacket
A chamber that jackets the inner dispersion tube with hot steam to eliminate condensation and dripping
1
OM-1171
Tube profile without insulation
2. Steam separator
Separates steam from condensate
3. Deflector plate
Inside the steam separator, deflects condensate into a circular pattern and toward the drain
4. Multi-baffle plate
Allows only steam to rise into the upper region of the separator
5. Internal drying tube
Excludes any remaining condensate, allowing only dry steam to leave the separator
6. Steam valve
Controls the amount of steam allowed into the dispersion tube
7. Dispersion tube
Provides uniform steam dispersion across the duct width
8. Thermal-resin tubelet
Unique tubelets extend into the dispersion tube center so only the hottest, driest steam is discharged into the air. These tubelets also have an exceptional ability to trap noise generated by the valve, making DriSteem’s Steam Injection humidifiers the quietest in the industry.
9. Steam trap
Allows only condensate to pass to the condensate return system
See Figure 5-1 for a description of how these components operate together.
mc_031611_0805
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
4
Page 7

Principle of operation

FIGURE 5-1: STEAM INJECTION HUMIDIFIER PRINCIPLE OF OPERATION
5
3
1
OVERVIEW
6
OM-1170
2
4
About right-hand and left-hand discharge:
Imagine you are standing in the duct where the Steam Injection humidifier is to be installed, with airflow blowing into your face:
• Specify the humidifier with right-hand discharge if the separator is on your right.
• Specify the humidifier with left-hand discharge if the separator is on your left.
For consistency, humidifier drawings in this catalog are shown with right-hand discharge.
1. Boiler steam enters the humidifier at line pressure and flows through a chamber (jacket) surrounding an inner dispersion tube. The jacket of steam preheats the dispersion tube so that when steam enters the dispersion tube (at Step 5 below) it does not condense as it would if the tube were cold, thereby eliminating condensation and dripping.
2. After flowing through the steam jacket, steam with entrained condensate slows from entering the larger space of the separator and from hitting the perimeter deflector plate, and begins to spin and separate.
3. Separated steam rises through slots in the multi-baffle plate to the separator upper region, and enters the internal drying tube that excludes any remaining condensate, allowing only dry steam to leave the separator.
4. Separated condensate drains from the separator to the steam trap.
5. The steam valve controls the amount of steam allowed into the preheated dispersion tube. The steam valve is typically controlled in one of two ways:
• By a signal from a building automation system
• By a humidity controller connected to the steam valve
6. Steam is discharged uniformly through the tubelets into the airstream.
mc_031611_0808
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
5
Page 8
OVERVIEW
Humidifier placement
USE THESE EXAMPLES AS GUIDELINES
Proper humidifier placement is crucial for successful system operation. Usually, there is no single correct placement for a humidifier. Much depends on system design and application. The following paragraphs and dispersion assembly placement examples are presented as guidelines for common situations.
FIRST, CHECK AVAILABLE ABSORPTION DISTANCE
Available absorption distance affects system choice. Dispersed steam must be absorbed into the airflow before it comes in contact with any duct elbows, fans, vanes, filters, or any object that can cause condensation and dripping.
mc_071911_1516
PLACING A STEAM INJECTION HUMIDIFIER IN AN AHU (SEE FIGURE 6-1)
• Location A is the best choice. Installing downstream from heating and cooling coils provides laminar flow through the dispersion unit; plus, the heated air provides an environment for best absorption. Use a multiple tube dispersion unit to ensure complete absorption of steam vapor before fan entry.
• Location B is the second-best choice. In change-over periods, the cooling coil will eliminate some moisture for humidification.
• Location C is the third-best choice. Air leaving a fan is usually very turbulent and may cause vapor to not absorb at the expected absorption distance. Allow for more absorption distance if installing downstream from a fan.
• Location D is the poorest choice. The cooler air at this location requires an increased absorption distance.
mc_071911_1515
Figure 6-1: Placing a Steam Injection humidifier in an air handling unit (AHU)
Cooling coil
8' to 12' (2.4 m to 3.7 m)
ABD
3' to 5' (1 m to 1.5 m)
8' to 12' (2.4 m to 3.7 m)
Outside air
Exterior building wall
Relief air
Economizer control device
Preheat coil
Motorized air dampers
Filters
Heating coil
Duct high limit humidity control for humidifier locations A, B
Airflow proving switch
Fan
Humidifier discharges against airflow
C
Airflow proving switch
Return airflow
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
6
Supply airflow
Duct high limit humidity control for humidifier location C
DC-1081 mc_071911_1517
Page 9
Humidifier placement
PLACING A STEAM INJECTION HUMIDIFIER NEAR AN ELBOW (SEE FIGURE 7-1)
• Location A is the best choice. Better absorption occurs on the downstream side of an elbow than on the upstream side.
• Location B is the second-best choice. Installing upstream from an elbow can cause wetting at the turning vanes. In cases where it is structurally impossible to avoid Location B, use a multiple tube humidifier to ensure complete absorption. Also, since more air flows along the outside of a turn, better absorption occurs if the humidifier discharges proportionately more steam in that part of the airstream.
• At both locations, discharging steam against or perpendicular to the airstream gives slightly better mixing and absorption than discharging with the airstream.
mc_071911_1518
FIGURE 7-1: PLACING A STEAM INJECTION HUMIDIFIER ASSEMBLY NEAR AN ELBOW
OVERVIEW
Airflow
Duct
B
Less airflow on this side of elbow
Duct high limit humidistat
Mist can collect on vanes
A
(2.4 m to 3.7 m)
DC-1083-1 mc_071911_1519
Airflow
3' to 5'
(1 m to 1.5 m)
8' to 12'
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
7
Page 10
OVERVIEW
Humidifier placement
PLACING A STEAM INJECTION HUMIDIFIER IN A PRIMARY/SECONDARY SYSTEM (SEE FIGURE 8-1)
This type of system is commonly applied to facilities where most of the building requires one humidity level (typically to meet comfort requirements) and part of the building requires additional humidity. In Figure 8-1, the primary humidification system is within the main air handling unit. The secondary humidification system is located close to the point of steam discharge into the secondary area.
FIGURE 8-1: PLACING A STEAM INJECTION HUMIDIFIER IN A PRIMARY/SECONDARY SYSTEM
Exhaust airOutside air
Filter mixing box
Before humidifier: 50 °F (10 °C), 47% RH
Primary humidifier location
After humidifier: 50 °F (10 °C), 60% RH
70 °F (21 °C), 30% RH
Secondary humidifier location
50 °F (10 °C) 60% RH
VAV box
Primary area: 70 °F (21 °C), 30% RH
50 °F (10 °C), 60% RH
Secondary humidified area
Room transmitter: 65 °F (18 °C), 50% RH
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
8
Page 11

Sensor placement

OVERVIEW
SENSOR LOCATION IS CRITICAL
Sensor location has a significant impact on humidifier performance. See the recommendations below and Figure 9-1.
Note: DriSteem recommends that you do not interchange room and duct
humidity devices. Room humidity devices are calibrated with zero or little airflow, whereas duct humidity devices require air passing across them.
Recommended humidity control (transmitter/humidistat) locations:
A Ideal. Ensures the best uniform mix of dry and moist air with stable
temperature control.
B Acceptable, but room environment can affect controllability, such as
when sensor is too close to air grilles, registers, or heat radiation from room lighting.
C Acceptable. Provides uniform mixture of dry and moist air. If extended
time lag exists between humidity generation and sensing, extend sampling time.
D Acceptable (behind wall or partition) for sampling entire room if sensor
is near an air exhaust return outlet. Typical placement for sampling a critical area.
E Not acceptable. These locations might not represent actual overall
conditions in the space.
F Not acceptable. Do not place sensors near windows, door
passageways, or areas of stagnant airflow.
Other factors affecting humidity control
Humidity control involves more than the controller’s ability to control the system. Other factors that play an important role in overall system control are:
• Size of humidification system relative to load
• Overall system dynamics associated with moisture migration time lags
• Accuracy of humidistats and humidity transmitters and their location
• Dry bulb temperature accuracy in space or duct
• Velocities and airflow patterns in ducts and space environments
• Electrical noise or interference
mc_072011_1656
Recommended safety (airflow and high limit) sensor location:
G Best sensing location for high limit humidistat or humidity sensor and
airflow proving switch.
FIGURE 9-1: RECOMMENDED SENSOR LOCATIONS
8' to 12'
Wall or partition
D
B
(2.4 m to 3.7 m)
min.
F
F
Window
DC-1084
G
Outside air
Relief air
Damper control
Return air
E
A
C
Window
F
Doorway
Air handling
unit
E
High limit humidistat or high limit transmitter (set at 90% RH maximum) for VAV applications
Airflow switch or differential pressure switch (sail type recommended for VAV applications)
Vapor absorption has taken place
Point of vapor absorption
Humidifier dispersion assembly
Turning vanes
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
9
Page 12
OVERVIEW

Pressurized steam piping guidelines

• Size piping in accordance with ASHRAE recommendations.
• Humidifier's steam supply should be taken off top of steam main (not side or bottom) to ensure the driest steam. Main should be dripped and trapped (in accordance with ASHRAE recommendations).
• Humidifier steam trap(s) must drain by gravity to return main having little or no back pressure. If condensate cannot drain by gravity, then it must be elevated to return main (see Figure 12-1 for instructions).
• If steam pressure is less than or equal to 15 psi (103.4 kPa), use float and thermostatic (F&T) traps for the humidifier.
If steam pressure is greater than 15 psi (103.4 kPa), use inverted bucket
traps for the humidifier.
• If lifting condensate, use an inverted bucket trap and check valve regardless of steam pressure. See Figure 12-1 for instructions.
• Condensate from unavoidable heat loss in the distribution system must be removed promptly to eliminate water hammer and degradation of steam quality and heat transfer capability. Install drip legs at all low points and natural drainage points in the system, such as at ends of mains; bottoms of risers; and ahead of pressure regulators, control valves, isolation valves, pipe bends, and expansion joints.
On straight, horizontal runs with no natural drainage points, space drip
legs at the following intervals:
– Not exceeding 300' (91 m) when the pipe is pitched down in the
direction of the steam flow
– At a maximum of 150' (46 m) when the pipe is pitched up, so that
condensate flow is opposite of steam flow.
These distances apply to systems where valves are opened manually to
remove air and excess condensate that forms during warm-up conditions. Reduce these distances by about half in systems that are warmed up automatically.
• Insulate piping well to avoid unnecessary heat loss.
• Pitch return lines downward in the direction of the condensate flow at 1/2" per 10' (0.4%).
mc_051011_1544
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
10
Page 13
Pressurized steam piping guidelines
FIGURE 11-1: FIELD PIPING OVERVIEW
OVERVIEW
Take off branch lines from the top of the steam main, preferably at a 45° angle, although vertical 90° connections are acceptable
Insulate piping
DC-1200M
End of main steam trap by installer
Condensate return
Blowdown valve by installer
45°
Pitch humidifier branch 1/2" per 10' (0.4%) if distance from main to humidifier is less than 10' (3.3 m)
Automatic warm-up: 28" (711 mm) min. Supervised warm-up:
1.5 × pipe diameter, 8" (203 mm) min.
If pipe is 4" (DN100) or larger, size drip for 50% of the condensate load at start-up. If pipe is less than 4" (DN100), size drip for 25% of the condensate load at start-up.
Branch steam trap by installer
Blowdown valve by installer
Branch trap recommended if distance from main to humidifier is greater than 10' (3.3 m)
Condensate return
Pitch main 1/4" per 10' (0.2%)
Piping same size as humidifier inlet strainer
To humidifier. Inlet strainer must be within 3' (1 m) of humidifier
Humidifier isolation valve
Insulate piping
12" (305 mm) min.
4" (100 mm) min.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
11
Page 14
OVERVIEW
Pressurized steam piping guidelines
FIGURE 12-1: ELEVATING CONDENSATE FROM A STEAM INJECTION HUMIDIFIER
Pitch 1/2" per 10' (0.4%)
Elevated condensate return main
1/2" pipe thread (DN15)
5' (1.5 m) maximum
Condensate return flow
Inverted bucket steam trap
Check valve (swing type)
DC-1064
In certain installations, it is not possible to drain the humidifier steam trap by gravity. The condensate must be lifted. Generally, lifting condensate is not recommended, but it can be done successfully by observing the following rules:
Steam pressure. Theoretically, one pound (6.9 kPa) of steam pressure will lift condensate about 2' (0.6 m). But
in practice, because of pipe friction, pressure drop through a steam trap, and back pressure in a return line, we recommend maximum lift of 6" per pound (0.2 m per 6.9 kPa) of steam pressure at the trap. For example, a steam pressure of 5 psi (34.5 kPa) will provide a maximum lift of 2.5' (0.76 m). Lifting condensate more than 5' (1.5 m) should not be attempted.
Steam trap. When lifting condensate, use an inverted bucket steam trap. Float and thermostatic (F&T) traps are
more prone to water hammer damage with a flooded trap, which may occur when lifting condensate.
Pipe size. The size of the vertical portion of the piping should be 1/2" pipe thread (DN15).
Check valve (swing type). A low-pressure differential swing check valve should be installed adjacent to the trap.
This will prevent backflow of condensate into the humidifier during periods of little or no steam pressure. Failure to do so could result in accumulated backflow discharging from the humidifier when steam pressure is resumed. Spring-type check valves are not recommended, as they can reduce pressure available for condensate lifts.
Condensate lifting recommendations:
1. Condensate can be lifted for all steam jacket piping.
2. Condensate could be lifted for connection to separator, but performance could vary based on variable pressure at the separator.
3. Condensate cannot be lifted for connection on headers for Multiple-tube humidifiers (including Maxi-bank option).
mc_051011_1530
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
12
Page 15
Pressurized steam piping guidelines
FIGURE 13-1: MULTIPLE VALVE PLUMBING GUIDELINES
Isolation valve (by others)
From steam source
Install strainer within 3' (1 m) of humidifier (see Note 2)
OVERVIEW
Piping to be same size as strainer
Piping to be same size as valves
Valve
Piping to be same size as separator inlet
Notes:
1. Dashed lines indicate provided by installer.
2. Steam valve and strainer sizes are provided by DriCalc, DriSteem's free sizing and selection software, available at www.dristeem.com.
mc_042811_1450
Separator
Steam trap
Separator
Steam trap
Union
Valve
Union
4" (100 mm)
To Multiple-tube header inlet
To Multiple-tube header inlet
DC-1488
Piping to be same size as separator inlet
12" (305 mm)
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
13
Page 16
OVERVIEW

Condensate drain piping and trapping

FIGURE 14-1: CONDENSATE DRAIN PIPING AND TRAPS FOR STEAM INJECTION HUMIDIFIERS
P-trap dimensions
Condensate outlet
Drop
Lifting condensate
From P-trap or mechanical trap
Condensate pump*
Seal
Check valve
Mechanical trap dimensions
Typical model
Condensate outlet
Drop
Drip
F&T trap (shown) or inverted bucket trap
Notes: * Use condensate pump rated for 212 °F (100 °C) and suitable for lifting 250 gph (16 L/m)
at required head (60 kPa). Stainless steel condensate pump recommended when pumping condensate from systems using optional stainless steel components.
• If wasting condensate to drain, temper condensate to local code to prevent damage to drain plumbing.
• Dashed lines indicate provided by installer.
Stainless steel components model
Condensate outlet
Drip
Cooling
leg
Stainless steel thermostatic trap
mc_050211_1314
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
14
Page 17
Condensate drain piping and trapping
Table 15-1: Condensate drain piping and traps for Steam Injection humidifiers
Single-tube, Mini-bank, and Multiple-tube humidifiers
P-trap water seal
Piping from separator*** Piping from steam jackets Piping from header
Typical
model
Models with optional stainless steel components
Typical
model
Do not use Do not use Do not use Do not use Do not use Do not use
Models with optional
stainless steel
components
Typical
model
Models with optional stainless steel components
OVERVIEW
Area-type humidifier
Piping
from
separator
Use with
minimum:
Drop: 8"
(203 mm)
Seal: 10"
(254 mm)
F&T trap
Inverted bucket trap*
Stainless steel thermostatic trap
Use if steam
pressure is ≤15 psi
(103.4 kPa):
Drop: 12" (305 mm)
Drip: 4" (102 mm)
Use if steam
pressure is >15 psi (103.4 kPa): Drop: 12" (305 mm)
Drip: 4" (102 mm)
Do not use
Do not use
Do not use
Use with stainless
steel
piping with
minimum:
Drip: 4" (102 mm)
Cooling leg: 24"
(610 mm)
Use only if not lifting
condensate and
steam pressure is
≤15 psi (103.4 kPa):
Drop: 12" (305 mm)
Drip: 4" (102 mm)
Use if lifting
condensate or if
steam pressure is
>15 psi (103.4 kPa):
Drop: 12" (305 mm)
Drip: 4" (102 mm)
Do not use
Do not use
Do not use Do not use Do not use Do not use
Use with stainless
steel piping with
minimum:
Drip: 4" (102 mm)
Cooling leg: 24"
(610 mm)
Use with
minimum:
Drop: 12"
(305 mm)
Drip: 4"
(102 mm)
Do not use
Do not use Do not use
Use with stainless
steel piping with
minimum:
Drip: 4" (102 mm)
Do not use
Cooling leg: 24"
(610 mm)
Return condensate to boiler via
Yes Yes Ye s Yes Yes Yes No nonpressurized return line?
Return condensate by condensate
Yes Yes** Yes Yes** Yes Yes** Yes
pump?
Drain condensate to
Yes
Yes
Yes
Yes
Yes
Yes
Recommended
open drain?
Notes: * Trap may require priming after seasonal shutdown. ** DriSteem recommends using a stainless steel condensate pump when pumping condensate from systems using optional stainless steel components. *** During consistent load, there may not be enough steam pressure in the separator to lift condensate from the separator using steam. † If wasting condensate to drain, temper condensate to local code to prevent damage to drain plumbing.
mc_050211_1630
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
15
Page 18
OVERVIEW

Temperature switches

FIGURE 16-1: PNEUMATIC TEMPERATURE SWITCH STANDARD LOCATION
Pneumatic airflow switch (optional)
Set point controlling humidistat
20 psi (138 kPa) air supply
Duct high limit Required 0.007" (0.18 mm) restrictor
humidistat
(optional)
Separator
12" (305 mm) min.
DC-1190
mc_051011_1650
Steam trap
FIGURE 16-2: PNEUMATIC TEMPERATURE SWITCH ALTERNATE LOCATION
12" (305 mm) min.
Pneumatic temperature switch
DC-1192 mc_051011_1651
Pneumatic temperature switch
Steam trap
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
16
Page 19
Temperature switches
PNEUMATIC TEMPERATURE SWITCH NOTES:
• DriSteem's pneumatic temperature switch, designed for use with a pneumatic control system, prevents condensate discharge from a steam injection humidifier during cold start or if the condensate return main becomes flooded. It accomplishes this by bleeding off the pneumatic signal from the controlling humidistat, preventing the pneumatic humidifier valve from opening until the steam trap has reached operating temperature.
• The pneumatic temperature switch has a self-contained air valve operated by a thermal disc that is normally open, bleeding off control air pressure. When steam comes in contact with the thermal disc, the fluid inside the disc expands, causing the air valve to close, thus allowing the pneumatic control system air pressure to build up and to actuate the steam control valve.
• Install the tee containing the pneumatic temperature switch in the condensate drainage pipe line between the separator and the inlet to the steam trap, as shown in the drawings on Pages 16 and 18.
mc_051011_1652
OVERVIEW
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
17
Page 20
OVERVIEW
Temperature switches
FIGURE 18-1: ELECTRIC MODULATING TEMPERATURE SWITCH LOCATION
120 VAC primary
24 VAC secondary
Duct high limit humidistat (optional)
Airflow proving switch (optional)
Class 2 transformer (by installer) used with 24 VAC coil
Omit transformer when using 120 VAC coil
Steam trap
Electric modulating humidistat (optional) or control signal by others
Normally closed electric modulating valve (120 VAC or 24 VAC)
DC-1227 mc_051011_1653
12" (305 mm) min.
Electric temperature switch
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
18
Page 21
Temperature switches
Electric temperature switches:
• The electric temperature switch prevents condensate discharge from a steam injection humidifier during a cold start or if the condensate return main becomes flooded. DriSteem's electric temperature switch is a temperature­actuated make-break switch designed for use with electric humidity control systems. The temperature at which it switches is adjustable and should be set at 210 °F (99 °C).
• This switch prevents condensate discharge from a steam injection humidifier during a cold start or if the condensate return main becomes flooded.
• Install the sensing element of the device in the condensate return piping on the inlet side of the steam trap (see drawings), including a tee with a ½" pipe thread (DN15) opening to receive the sensing element. When steam surrounds the sensing element, the switch will “make,” allowing the humidifier valve to open.
OVERVIEW
• Install all wiring according to national and local electrical codes, and SIZE TRANSFORMER VA TO LOAD VA.
• When using the temperature switch with an electric modulating valve, use the special wiring instructions furnished with the valve.
mc_051011_1654
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
19
Page 22

SINGLE-TUBE HUMIDIFIER

Configurations
FIGURE 20-1: SINGLE-TUBE HUMIDIFIER INSTALLATION CONFIGURATIONS
Steam inlet
Drain
Horizontal airflow
Horizontal tube/horizontal airflow
Typical configuration. Single-tube humidifiers are shipped this way unless ordered otherwise. See Page 24 for more information about this configuration. This is a right-hand configuration; to change to a left hand configuration, see Figure 20-1.
Vertical tube/horizontal airflow
Use this configuration when there is
Steam inlet
Horizontal airflow
Drain
Steam inlet
no access to side of duct or when duct is tall and narrow, to improve steam absorption. See Page 27 for more information about this configuration.
Horizontal tube/vertical airflow
Use this configuration in vertical airflow ducts. See Page 26 for more information about this configuration.
FIGURE 20-2: CHANGING FROM RIGHT­HAND TO LEFT-HAND CONFIGURATION
Opposite connection
Elbow and union assembly
Union ring
OM-8
It may be necessary to change the steam discharge direction at the job site. To do so, follow these directions:
1. Non-threaded union ring.
2. Remove elbow and nipple assembly from dispersion tube and reinstall on opposite connection.
3. Rotate dispersion tube 180° with respect to separator.
4. Reconnect union halves and tighten union ring.
5. Humidifier now will discharge to opposite side.
Steam inlet
Drain
Steam inlet
Drain
Drain
Vertical airflow
Horizontal airflow
Vertical airflow
Horizontal separator/horizontal airflow
Use this configuration when space is tight, such as when installing above ceilings. This application requires a separator designed for horizontal installation. See Page 25 for more information about this configuration.
Horizontal separator/vertical airflow
Use this configuration in vertical airflow ducts and when space is tight, such as when installing above ceilings. This application requires a separator designed for horizontal installation.
OM-380, 381, 382, 383, 7652
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
20
Page 23

Assembly

FIGURE 21-1: SINGLE-TUBE HUMIDIFIER FIELD ASSEMBLY
SINGLE-TUBE HUMIDIFIER
Single-tube humidifier
Actuator
Valve separator assembly
Steam trap
SINGLE-TUBE HUMIDIFIER FIELD ASSEMBLY
Tube adapter
Teflon® seal ring
Pipe union
Half coupling
O-rings
Hooks of silencer cage
Two-piece escutcheon plate
Strainer
Dispersion tube
Support bracket
Steam discharge tubelets
Detail: Tube adapter single dispersion tube
Tube adapter
Dispersion tube
Automatic valve
O-rings
Silencer cage
Silencer (tubes 48" [1219 mm] and shorter only)
OM-7, OM-14
Small units are shipped assembled; the following applies to larger units that are disassembled for shipment.
1. Unpack shipment and verify receipt of all components with packing list. Report any shortages at once.
2. Match up dispersion tube with its proper valve-separator assembly (tubes and separators are match-tagged). Tubelets should point against the airflow for better steam-air mixing, except if tubes have fiberglass insulated-jacket option, then tubelets should discharge steam with the airflow to prevent condensation from forming on cool jackets. See the installation examples on the following pages before beginning assembly. Note: Before completing Step 3, determine which way (right or left) tubelets should point, and install in appropriate half coupling (see Figure 4-1).
3. Unscrew pipe union, remove elbow and nipple portion, and install in half coupling of tube.
4. Install tube adapter in valve (use pipe dope) and tighten.
5. Lubricate O-rings and install inside tube adapter.
6. Insert tube adapter into dispersion tube. As this is being done, if unit has a silencer, squeeze hooks of silencer cage together and slide them into the tube adapter, allowing them to snap over rear edge of adapter. Complete inserting adapter into tube, being careful not to damage O-rings. Note: Unless special-ordered, silencers are furnished only with Model 60 and Model 70 tubes equal to or shorter than 48" (1219 mm), and only with black iron piping.
7. Tighten pipe union.
8. Thread Teflon seal ring into half coupling.
9. Torque Teflon seal ring to 15 ft-lbs (20.3 N-m). Note: Once tightened, do not attempt to re-tighten the Teflon seal, or the seal could be damaged.
10. Install the assembly in the duct. See “Installation” on the next page.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
21
Page 24
SINGLE-TUBE HUMIDIFIER

Installation

1. Insert a support bolt in one of the support bracket’s three holes (upper, lower or end); cut holes in duct for inserting dispersion tube and support bolt.
2. Secure unit in duct with nut and support bolt. Mount two­piece escutcheon plate around tube and secure into duct with sheet metal screws. Where an airtight seal is required, use a suitable caulk around duct wall penetrations.
3. Install steam strainer and steam trap. Connect to steam and condensate return mains. See the drawings on the following pages and text below for detailed piping instructions.
4. Install control tubing (pneumatic) or wiring (electric) to valve actuator.
5. Install an airflow proving switch to prevent the valve from opening unless air is moving in duct. See “Humidifier placement” on Pages 6 – 8 for location recommendations.
6. Install a duct-mounted high-limit humidistat downstream from the humidifier. Set humidistat at 80-90% RH to prevent condensation forming in duct. Mount this humidistat far enough downstream to ensure that injected steam has been completely absorbed before the humidistat. See “Humidifier placement” on Pages 6 – 8 for location recommendations.
7. Install a temperature switch to prevent possible cold-start dripping when steam pressure to the humidifier is cycled. See “Temperature switches” on Pages 16 – 19 for more information.
8. Install the humidistat and/or sensors according to the recommendations on Page 9.
For more installation information
• See “Humidifier placement” on Pages 6 – 8 for information about choosing an installation location.
• See “Sensor placement” on Page 9.
• See “Pressurized steam piping guidelines” on Pages 10 – 13.
• See “Temperature switches” on Pages 16 – 19.
WARNING
Improper mounting hazard
Mount humidifier per the instructions in this manual and to a structurally stable surface. Improper humidifier mounting can cause the humidifier to fall resulting in severe personal injury or death.
mc_060310_0725
WARNING
Excessive moisture hazard
DriSteem strongly recommends installing a duct airflow proving switch and a duct high limit humidistat. These devices prevent a humidifier from making steam when there is low airflow in the duct or when the RH level in the duct is too high. Failure to install these devices can result in excessive moisture in the duct, which can cause bacteria and mold growth or dripping through the duct.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
22
mc_060310_0725
Page 25

Piping notes

1. Refer to field piping drawings on Pages 24 – 27.
2. To avoid metal fatigue, allow for thermal expansion of dispersion tube.
3. Dashed lines in drawings indicate provided by installer.
Horizontal airflow:
Slightly better mixing with less visible vapor travel occurs when discharged steam blows against the airflow, rather than with the airflow. Therefore, when using noninsulated steam jackets in a horizontal airflow (as shown in the piping drawings on Pages 24 – 27), position tubelets (steam orifices) so they face into the airflow. However, if the dispersion tube has an insulated jacket, the discharged steam must blow with the airflow to avoid condensation that may occur when discharged steam contacts the cooler insulated jacket. When using insulated steam jackets in a horizontal airflow, position tubelets so they discharge steam with the airflow, and add 24" (610 mm) to the non­wetting distance.
SINGLE-TUBE HUMIDIFIER
4. Vertical airflow:
Always position tubelets (steam orifices) pointing up when installing in a vertical airflow. Important: If installing insulated steam jackets in a vertical airflow, install only in an upflow application and add 24" (610 mm) to the non-wetting absorption distance. Do not install insulated steam jackets in a vertical
downflow application.
5. For horizontal tube installations, center tube within duct height. For vertical tube installations, center tube within duct width.
6. If steam pressure is less than or equal to 15 psi (103.4 kPa), use a float and thermostatic (F&T) trap for the humidifier. If steam pressure is greater than 15 psi (103.4 kPa), use an inverted bucket trap for the humidifier. If lifting condensate, use an inverted bucket trap and check valve regardless of steam pressure (see Figure 12-1).
7. See also the “Pressurized steam piping guidelines” on Pages 10 – 13.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
23
Page 26
SINGLE-TUBE HUMIDIFIER

Field piping

FIGURE 24-1: SINGLE-TUBE HUMIDIFIER WITH HORIZONTAL DISPERSION TUBE AND VERTICAL SEPARATOR INSTALLED IN A HORIZONTAL AIRFLOW
Piping downstream from strainer
Isolation valve (by others)
From steam source
Install strainer within 3' (1 m) of humidifier (see Note 4)
3/4" pipe thread (DN20)
Separator trap (see Note 5)
should be the same size as strainer.
Separator
Condensate drain
Steam valve and actuator (see Note 4)
Airflow
12" (305 mm) min.
4" (100 mm) min.
Drip
Secure and seal escutcheon plates
Level
Dispersion tube with noninsulated steam jacket (see Note 4 on Page 23)
Minimum face height 9" (229 mm)
Secure end of tube to duct using support bracket (0.42" [11 mm] dia. holes in top, bottom, and end of bracket)
DC-1065
mc_050511_1100
NOTES:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. 2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Piping notes” on Page 23, and see Pages 14 and 15 for more information about trap types and trap piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
24
Page 27
Field piping
FIGURE 25-1: SINGLE-TUBE HUMIDIFIER WITH HORIZONTAL DISPERSION TUBE AND HORIZONTAL SEPARATOR INSTALLED IN A HORIZONTAL AIRFLOW
SINGLE-TUBE HUMIDIFIER
From steam source
Piping downstream from strainer should be same size as strainer.
Steam valve and actuator (see Note 4)
Separator
3/4" pipe thread (DN20)
Trap (see Note 7 on Page
23)
Isolation valve (by others)
Install strainer within 3' (1 m) of humidifier (see Note 4)
12" (305 mm) min.
Level
Secure end of tube to duct using support bracket (0.42" [11 mm] dia. holes in top, bottom, and end of bracket)
Duct
Dispersion tube with noninsulated steam jacket (see Note 4 on Page 23)
Airflow
Secure and seal escutcheon plates
Minimum duct width 9" (229 mm)
DC-1066 mc_050911_1600
Condensate drain
4" (100 mm) min.
Drip
NOTES:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Piping notes” on Page 23, and see Pages 14 and 15 for more information about trap types and trap piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
25
Page 28
SINGLE-TUBE HUMIDIFIER
Field piping
FIGURE 26-1: HORIZONTAL DISPERSION TUBE INSTALLED IN A VERTICAL AIRFLOW
From steam source
Piping downstream from strainer should be same size as strainer.
Steam valve and actuator (see Note 4)
Isolation valve (by others)
Secure and seal escutcheon plates
Install strainer within 3' (1 m) of humidifier (see Note 4)
Level
Tubelets (steam orifices) always point up with vertical airflow. Do not install insulated jackets in vertical downflow applications. See Note 5 on Page 23.
Secure end of tube to duct using support bracket (0.421" dia. [11 mm] holes in top, bottom, and end of bracket)
Duct (minimum duct height is 9" [229 mm])
Dispersion tube
DC-1067 mc_051011_0805
NOTES:
3/4" pipe thread (DN20)
Trap (see Note 7 on Page
23)
Condensate drain
Separator
Airflow
12" (305 mm) min.
4" (100 mm) min.
Drip
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Piping notes” on Page 23, and see Pages 14 and 15 for more information about trap types and trap piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
26
Page 29
Field piping
FIGURE 27-1: VERTICAL DISPERSION TUBE INSTALLED IN A HORIZONTAL AIRFLOW
Secure end of tube to duct using support bracket (0.421" dia. [11 mm] holes in both sides and end of bracket)
SINGLE-TUBE HUMIDIFIER
From steam source
Piping downstream from strainer should be same size as strainer.
3/4" pipe thread (DN20)
Trap (see Note 7 on Page 23)
Isolation valve (by others)
Separator
Install strainer within 3' (1 m) of humidifier (see Note 4)
Condensate drain
Drip
12" (305 mm) min.
4" (100 mm) min.
Duct (minimum duct width is 9" [229 mm])
Airflow
DC-1068 mc_051011_0830
Steam valve and actuator (see Note 4)
Dispersion tube with noninsulated steam jacket (see Note 4 on Page 23)
Secure and seal escutcheon plates
NOTES:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Piping notes” on Page 23, and see Pages 14 and 15 for more information about trap types and trap piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
27
Page 30

MULTIPLE-TUBE HUMIDIFIER

Field assembly

Note: For Maxi-bank option, follow the “Maxi-bank option field assembly and
installation” instructions on Page 36.
1. Unpack shipment and verify receipt of all components with packing list. Report any shortages at once.
2. Plan the tube bank. You need to know the required spacing distance between tubes. See Table 29-1. Arrange tubes so steam will discharge against the airflow, unless tubes are insulated (optional), in which case they should blow with the air to prevent condensation on metal jacket covering insulation.
3. Assemble header based on spacings determined in Step 2 above. If header pipe size has not been specified, see Table 28-1. This table is based on a maximum steam velocity of 7,000 to 10,000 fpm (36 to 51 m/s), which will result in lower noise levels and produce uniform steam flow from all tubes. If noise level is not important or a uniform flow is not critical, a smaller header size may be used.
4. Install tube adapter fittings in header tees. (See Figure 28-1.) It usually works best to lay the header on the floor along with the tubes for Steps 5 – 7.
5. Install male pipe thread end of tube adapter into pipe fitting. Dope threads and tighten leak tight sealer.
6. O-rings are installed inside of tube adapter. NOTE: Use synthetic oil to lubricate O-rings before installing.
7. Insert tube adapter into dispersion tube. As this is being done, if unit has a silencer, squeeze hooks of silencer cage together and slide them into tube adapter, allowing them to snap over rear edge of adapter. Complete inserting adapter into tube, being careful not to damage O-rings. NOTE: Unless special-ordered, silencers are furnished only with Model 60 and Model 70 tubes equal to or shorter than 48" (1219 mm), and only with black iron piping.
8. Slide tube into adapter being careful not to damage O-rings.
FIGURE 28-1: TUBE ADAPTER FOR MULTIPLE-TUBE HUMIDIFIERS
Header tee (by installer)
Tube adapter
Use the tube adapter to connect a non-threaded tube to a threaded pipe fitting.
O-rings
Dispersion tube
OM-15
Table 28-1: Multiple-tube humidifier header
sizes
Total capacity Header size
lbs/hr kg/h inches DN
up to 280 up to 127 1.5* 38*
up to 490 up to 222 2.0 50
491 to 980 223 to 444 3.0 80 981 to
1743 1744 to
2752 2753 to
3989 * Non Maxi-bank only
mc_040710_1005
445 to 790 4.0 100
791 to 1248 5.0 125
1249 to 1809 6.0 150
9. Install tubes in adapter fittings, making sure tubelets are pointing in proper direction.
10. Cut to length, thread, and install steam jacket piping. NOTE: When the total tube length of dispersion tubes exceeds 45' (13.7 m), we recommend installing an additional steam inlet to the dispersion tubes and an additional steam jacket trap. One for each additional 45' of total tube length. Divide the tubes into equal groups. See Figures 32-1 and 35-1.
11. Make tube support strut using angle or channel iron, and bolt each tube end in place.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
28
Page 31

Installation

MULTIPLE-TUBE HUMIDIFIER
NOTE: For Maxi-bank option, follow the “Maxi-bank option field assembly and installation” instructions on Page 36.
1. Insert a support bolt in one of the three holes (upper, lower or end) of the support brackets; cut holes in duct for inserting dispersion tube and support bolt.
2. Secure unit in duct with nuts and support bolts. Mount two-piece escutcheon plate around each tube and secure into duct with sheet metal screws. Where an airtight seal is required, use a suitable caulk around duct wall penetrations.
3. Install steam strainer and steam trap. Connect to steam and condensate return mains. See the drawings on the following pages and text on the next for detailed piping instructions.
4. Install control tubing (pneumatic) or wiring (electric) to valve actuator.
5. Install an airflow proving switch to prevent the valve from opening unless air is moving in duct. See “Humidifier placement” on Pages 6 – 8 for location recommendations.
6. Install a duct-mounted high-limit humidistat downstream from the humidifier. Set humidistat at 80-90% RH to prevent condensation forming in duct. Mount this humidistat far enough downstream to ensure that injected steam has been completely absorbed before the humidistat. See “Humidifier placement” on Pages 6 – 8 for location recommendations.
7. Install a temperature switch to prevent possible cold-start dripping when steam pressure to the humidifier is cycled. See “Temperature switches” on Pages 16 – 19 for more information.
8. Install the humidistat and/or sensors according to the recommendations on Page 9.
Table 29-1: Multiple-tube humidifier minimum tube spacing
For more installation information
• See “Humidifier placement” on Pages 6 – 8 for information about choosing an installation location.
• See “Sensor placement” on Page 9.
• See “Pressurized steam piping guidelines” on Pages 10 – 13.
• See “Temperature switches” on Pages 16 – 19.
• See the Maxi-bank option beginning on Page
36.
WARNING
Improper mounting hazard
Mount humidifier per the instructions in this manual and to a structurally stable surface. Improper humidifier mounting can cause the humidifier to fall resulting in severe personal injury or death.
mc_060310_0725
WARNING
Excessive moisture hazard
DriSteem strongly recommends installing a duct airflow proving switch and a duct high limit humidistat. These devices prevent a humidifier from making steam when there is low airflow in the duct or when the RH level in the duct is too high. Failure to install these devices can result in excessive moisture in the duct, which can cause bacteria and mold growth or dripping through the duct.
mc_060310_0725
Tube
model
60 6 152 9 229
70 9 229 9 229
80 9 229 12 305
* See Multiple-tube humidifier drawings on the following pages for center-to-
center distance X.
mc_040710_1030
Minimum tube spacing (X*)
Multiple-tube humidifier
inches mm inches mm
Minimum tube spacing (X*)
Multiple-tube humidifier with op-
tional stainless steel piping
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
29
Page 32
MULTIPLE-TUBE HUMIDIFIER

Piping notes

NOTE: For Maxi-bank option, see the “Maxi-bank option piping notes” on Page
36.
1. Refer to piping drawings on Pages 31 through 35.
2. See also the “Pressurized steam piping guidelines” on Pages 10 through 13.
3. Slightly better mixing with less visible vapor travel occurs when discharged steam
blows against the airflow, rather than with the airflow. Therefore, when using
noninsulated steam jackets in a horizontal airflow (as shown in the drawings),
position dispersion tubelets (steam orifices) so that they face into the airflow. If the dispersion tube has an insulated jacket, the discharged steam must blow with the airflow to avoid condensation that may occur when discharged steam contacts the cooler insulated jacket. Therefore, when using insulated steam jackets in a
horizontal airflow, position dispersion tubelets so that they discharge steam with
the airflow, and also add 24" (610 mm) to the non-wetting absorption distance.
4. Jacket piping size:
• 1/2" pipe thread (DN15) for Model 60 tubes
• 3/4" pipe thread (DN20) for Model 70 tubes
• 1½" pipe thread (DN40) for Model 80 tubes
5. To ensure uniform output from each tube, connect steam supply as close to the middle of the header as possible, but not in direct alignment with a dispersion tube.
For total dispersion tube lengths of more than 45’ (13.7 m), see Step 10 note on Page 28.
6. See header sizing in Table 28-1.
7. After the unit is installed, secure steam jacket piping to the tube header.
8. If steam pressure is less than or equal to 15 psi (103.4 kPa), use float and thermostatic (F&T) traps for the humidifier. If steam pressure is greater than 15 psi (103.4 kPa), use inverted bucket traps for the humidifier. If lifting condensate, use an inverted bucket trap and check valve regardless of steam pressure (Figure 12-1).
9. Due to the pressure drop across the valve, the steam pressure at the header trap is minimal; therefore, you cannot lift condensate or return condensate to a pressurized return by steam pressure from this trap. However, with condensate free steam, no trap is required if load is less than 500 pph, and between 500 and 1000 pph a trap is optional. Above 1000 pph, a trap is recommended.
10. X = distance between tubes, center to center Y = clearance at top and bottom = at least 1/2 of X or 4½" (114 mm), whichever is greater, but not greater than X See the minimum tube spacing in Table 29-1.
11. When installing in a vertical airflow: Always point tubelets (steam orifices) up when installing in a vertical airflow.
Important: If installing insulated steam jackets in a vertical airflow, install only in an upflow application and add 24" (610 mm) to the non-wetting absorption distance. Do not install insulated steam jackets in a vertical downflow application.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
30
Page 33

Field piping

FIGURE 31-1: MULTIPLE-TUBE HUMIDIFIER, TOTAL TUBE LENGTH LESS THAN OR EQUAL TO 45' (13.7 M)
MULTIPLE-TUBE HUMIDIFIER
Steam jacket piping (see Note 4 on Page 30)
Isolation valve (by others)
From steam source
Same size as separator inlet
Tube adapter
See header sizes in Table 28-1
Steam valve and actuator (see Note 4)
Separator
3/4" pipe thread (DN20)
12" (305 mm) min.
Separator trap (see Note 8 on Page 30)
4" (100 mm) min.
Header trap by installer (See Note 9 on Page 30)
Steam jacket trap (see Note 8 on Page 30)
Install strainer within 3' (1 m) of humidifier (see Note 4)
Header (see Table 28-1)
4" (100 mm) min.
Level
Escutcheon plate
Dispersion tubes (see Note 3 on Page 30)
See Note 7 on Page 30
Dispersion tube header (insulated)
Secure and seal escutcheon plates
12" (305 mm) min.
Secure end of tube to duct using support bracket (0.421" dia. [11 mm] holes in top, bottom, and end of bracket)
y = 4½" (114 mm) min.
Center assembly in duct. See Note 10 on Page 30.
x
x (See Table 29-1
for minimum tube spacing)
x
x
x
y (see y note above)
DC-1070 mc_040611_1225
Notes:
1. To avoid metal fatigue, allow for thermal expansion of dispersion tubes.
2. Dashed lines indicate provided by installer (see Maxi-bank option beginning on Page 36). Right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
31
Page 34
MULTIPLE-TUBE HUMIDIFIER
Field piping
FIGURE 32-1: MULTIPLE-TUBE HUMIDIFIER, TOTAL TUBE GREATER THAN 45' (13.7 M)
Steam jacket piping (see Note 4 on Page 30)
Isolation valve (by others)
From steam source
Same size as separator inlet
Tube adapter
See Notes 5 and 7 on Page 30
Steam valve and actuator (see Note 4)
Separator
Install strainer within 3' (1 m) of humidifier (see Note 4)
Header (see Table 28-1)
Level
Escutcheon plate
Dispersion tubes (see Note 3 on Page 30)
Secure end of tube to duct using support bracket (0.421" dia. [11 mm] holes in top, bottom, and end of bracket)
y = 4½" (114 mm)
min. Center assembly in duct. See Note 10 .
x
x (See Table
29-1 for minimum tube spacing)
x
3/4" pipe thread (DN20)
Separator trap (see Note 8 on Page 30)
Steam jacket trap (see Note 8 on Page 30)
NOTES:
12" (305 mm) min.
4" (100 mm) min.
Header trap by installer (see Note 9 on Page 30)
4" (100 mm) min.
Second inlet
Dispersion tube header (insulated)
DC-1071
Secure and seal escutcheon plates
12" (305 mm) min.
x
x
y (see y note above)
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer (see Maxi-bank option beginning on Page 36). Right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Piping notes” on Page 30, and see Pages 14 and 15 for more information about trap types and trap piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
32
Page 35
Field piping
FIGURE 33-1: MULTIPLE-TUBE HUMIDIFIER INSTALLED IN A VERTICAL AIRFLOW
MULTIPLE-TUBE HUMIDIFIER
Duct
Secure and seal escutcheon plates
Steam valve and actuator (see Note 4)
See Note 4 on Page 30
Isolation valve (by others)
From steam
source Install strainer within 3' (1 m) of humidifier (see Note 4)
Same size as separator inlet
Separator
Trap
Condensate return
Airflow (see Note 11 on Page 30)
y
Level
See Note 7 on Page 30
See Note 2 on Page 30
See Note 9 on Page 30
Pitch header 1/8"/ft (1%) toward header trap drain
See Table 29-1 for minimum tube spacing (x). See Note 10 on Page 30.
y = 4½" (114 mm) min.
x
x
y
Secure end of tube to duct using support bracket (0.421" dia. [11 mm] holes in sides and end)
Dispersion tube (see Note 11 on Page 30)
Center assembly in duct. See Note 10 on Page
30.
x
DC-1074 mc_051011_0902
Notes:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer (see Maxi-bank option beginning on Page 36). Right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Piping notes” on Page 30, and see Pages 14 and 15 for more information about trap types and trap piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
33
Page 36
MULTIPLE-TUBE HUMIDIFIER
Field piping
FIGURE 34-1: MULTIPLE-TUBE HUMIDIFIER WITH TOTAL TUBE LENGTH LESS THAN OR EQUAL TO 45' (13.7 M) IN A AHU
Steam jacket piping (see Note 4 on Page 30)
Secure end of tube to AHU using support bracket (0.421” dia. [11 mm] holes in top, bottom, and end of bracket)
y = 4½" (114 mm)
min. Center assembly in duct. See Note 10 on Page
x
30.
Isolation valve (by others)
From steam source
Same size as separator inlet
Tube adapter
See Note 5 on Page 30
Install strainer within 3' (1 m) of humidifier (see Note 4)
Level
Steam valve and actuator (see Note 4)
Separator
3/4" pipe thread (DN20)
12" (305 mm) min.
Separator trap (see Note 8 on Page 30)
4" (100 mm) min.
Header trap by installer (see Note 9 on Page 30)
Steam jacket trap (see Note 8 on Page 30)
NOTES:
Dispersion tubes (see Note 3 on Page 30)
See Note 7 on Page 30
Dispersion tube header (insulated) (see Table 28-1)
12” (305 mm) min.
4" (100 mm) min.
DC-1204 mc_050511_1455
x (See Table
29-1 for minimum tube spacing)
x
x
x
y (see y note above)
1. To avoid metal fatigue, allow for thermal expansion of dispersion tubes.
2. Dashed lines indicate provided by installer (see Maxi-bank option beginning on Page 36). Right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See Pages 14 and 15 for more information about trap types and piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
34
Page 37
MULTIPLE-TUBE HUMIDIFIER
Field piping
FIGURE 35-1: MULTIPLE-TUBE HUMIDIFIER WITH TOTAL TUBE LENGTH GREATER THAN 45' (13.7 M) IN A AHU
Steam jacket piping (see Note 4 on Page 30)
Install strainer within 3' (1 m) of humidifier (see Note 4)
Isolation valve (by others)
From steam source
Same size as separator inlet
Tube adaptor
See Note 7 on Page 30
Steam valve and actuator (see Note 4)
Separator
Steam jacket trap (see Note 8 on Page 30)
4" (102 mm) min.
Level
Dispersion tubes (see
Note 3 on Page 30
Secure bracket to duct using 0.375" (9.5 mm) dia. holes in end of bracket
y = 4½" (114 mm)
x
x (See Table
)
x
min. Center assembly in duct. See Note 10 on Page
30.
29-1 for minimum tube spacing)
12" (305 mm) min.
3/4”pipe thread (DN20)
Separator trap (see Note 8 on Page 30)
Header trap (see Note 9 on Page 30)
Steam jacket trap (see Note 8 on Page 30)
NOTES:
4" (102 mm) min.
4" (102 mm) min.
Second inlet
Dispersion tube header (insulated) (see Table 28-1)
12" (305 mm) min.
DC-1205
mc_040711_1705
x
x
y (see y note above)
1. To avoid metal fatigue, allow for thermal expansion of dispersion tubes.
2. Dashed lines indicate provided by installer (see Maxi-bank option beginning on Page 36). Right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See Pages 14 and 15 for more information about trap types and piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
35
Page 38

MAXI-BANK HUMIDIFIER

Maxi-bank option field assembly and installation
The Maxi-bank humidifier’s header piping and steam-jacket piping are provided by DriSteem. The Maxi-bank is factory assembled and shipped intact, except for larger units that are broken down for shipment. If the unit you are installing is already assembled, skip installation steps that do not apply.
1. Unpack shipment and verify receipt of all Maxi-bank components with packing list. Report any shortages at once.
2. To simplify installation, we recommend that dispersion tubes be attached to the Maxi-bank header before dispersion tubes and header are installed in a duct or air handler.
3. Follow the pre-tagged component lettering and match up dispersion tubes (or tube sections) to their proper location on the Maxi-bank header.
4. Install each dispersion tube into its appropriate tube adapter on the header, being sure to lubricate O-rings in the tube adapters.
5. Proceed with the additional tubes. Bring the jacketed union halves together and secure unions by hand.
NOTE: When the total tube length of dispersion tubes
exceeds 45' (13.7 m), we recommend installing an additional steam inlet to the dispersion tubes and an additional steam jacket trap. One for each additional 45' of total tube length. Divide the tubes into equal groups. See Figures 41-1 and 43-1.
6. When all the dispersion tubes are assembled, place the tube assembly into the duct or air handler, securing the assembly and tube ends to the duct or a fabricated structure. Install tubes level.
For more installation information
• See “Humidifier placement” on Pages 6 – 8 for information about choosing an installation location.
• See “Sensor placement” on Page 9.
• See “Pressurized steam piping guidelines” on Pages 10 – 13.
• See “Temperature switches” on Pages 16 – 19.
WARNING
Improper mounting hazard
Mount humidifier per the instructions in this manual and to a structurally stable surface. Improper humidifier mounting can cause the humidifier to fall resulting in severe personal injury or death.
WARNING
Excessive moisture hazard
DriSteem strongly recommends installing a duct airflow proving switch and a duct high limit humidistat. These devices prevent a humidifier from making steam when there is low airflow in the duct or when the RH level in the duct is too high. Failure to install these devices can result in excessive moisture in the duct, which can cause bacteria and mold growth or dripping through the duct.
7. Position and secure header, then tighten interconnecting tube jacket unions. When installing into a duct, use the two-piece escutcheon plates around each tube and secure to duct with sheet metal screws. In duct applications where air tightness is required, seal around tube and bolts with suitable caulk.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
36
Page 39
Maxi-bank option field assembly and installation
8. Locate and install separator/valve assembly to Maxi-bank mating union on header and tighten union.
9. Install strainer and necessary steam traps. Connect assembly to steam and condensate mains.
10. Install control tubing (pneumatic) or wiring (electric) to valve actuator.
11. Install an airflow proving switch to prevent the valve from opening unless air is moving in duct. See “Humidifier placement” on Pages 6 – 8 for location recommendations.
12. Install a duct-mounted high-limit humidistat downstream from the humidifier. Set humidistat at 80-90% RH to prevent condensation forming in the duct. Mount this humidistat far enough downstream to ensure that injected steam has been completely absorbed before the humidistat. See “Humidifier placement” on Pages 6 – 8 for location recommendations.
MAXI-BANK HUMIDIFIER
13. Install a temperature switch to prevent possible cold-start dripping when steam pressure to the humidifier is cycled. See “Temperature switches” on Pages 16 – 19 for more information.
14. Install the humidistat and/or sensors according to the recommendations on Page 9.
15. Pressure test system, and secure fittings as necessary.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
37
Page 40
MAXI-BANK HUMIDIFIER
Maxi-bank option piping notes
1. Refer to piping drawings on Pages 40 – 44.
2. Dashed lines in drawings indicate provided by installer.
3. For total dispersion tube lengths of more than 45' (13.7 m), see Step 5 note Page 36.
4. When installing in a horizontal airflow: Slightly better mixing with less visible vapor travel occurs when discharged steam blows against the airflow, rather than with the airflow. Therefore, when using
noninsulated steam jackets in a horizontal airflow (as
shown in the drawings on Pages 40 – 43), position dispersion tubelets (steam orifices) so that they face into the airflow. If the dispersion tube has an insulated jacket, the discharged steam must blow with the airflow to avoid condensation that may occur when discharged steam contacts the cooler insulated jacket. Therefore, when
using insulated steam jackets in a horizontal airflow,
position dispersion tubelets so that they discharge steam with the airflow, and also add 24" (610 mm) to the non­wetting absorption distance.
5. When installing in a vertical airflow:
Always point tubelets (steam orifices) up with vertical
airflow. Important: If installing insulated steam jackets in a vertical airflow, install only in an upflow application and add 24" (610 mm) to the non-wetting absorption distance. Do not install insulated steam jackets in a vertical downflow application.
6. Jacket piping size:
• 1/2" pipe thread (DN15) for Model 60 tube(s)
• 3/4" pipe thread (DN20) for Model 70 tube(s)
• 1½" pipe thread (DN40) for Model 80 tube(s)
7. After the unit is installed, secure steam jacket piping to the tube header.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
38
Page 41

Maxi-bank option piping notes

8. If steam pressure is less than or equal to 15 psi (103.4 kPa), use float and thermostatic (F&T) traps for the humidifier. If steam pressure is greater than 15 psi (103.4 kPa), use inverted bucket traps for the humidifier. If lifting condensate, use an inverted bucket trap and check valve regardless of steam pressure (see Figure 12-1).
9. The header trap is required to collect condensate from the header assembly. Due to the pressure drop across the valve, the steam pressure at the header trap is minimal; therefore, you cannot lift condensate by steam pressure, or return condensate to a pressurized return, from this trap. On small headers (2" or less in diameter), this trap may be omitted.
10. X = distance between tubes, center to center Y = clearance at top and bottom = at least ½ X or 4½" (114.3 mm), whichever is greater, but not greater than X See the “Minimum tube spacing distance” table on Page 38.
MAXI-BANK HUMIDIFIER
11. See “Pressurized steam piping guidelines” on Pages 10 – 13.
12. Drawings represent right-hand discharge.
13. See Table 28-1 for header sizing.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
39
Page 42
MAXI-BANK HUMIDIFIER
Maxi-bank option field piping
FIGURE 40-1: MAXI-BANK OPTION, TOTAL TUBE LENGTH LESS THAN OR EQUAL TO 45' (13.7 M)
Secure end of tube to duct using support bracket (0.421" dia. [11 mm] holes in top, bottom, and end of
Isolation valve (by others)
From steam source
Same size as separator inlet
Factory-supplied header and interconnecting piping
See Table 28-1
Steam valve and actuator (see Note 4)
Separator
Install strainer within 3' (1 m) of humidifier (see Note 4)
Mounting bracket
Steam jacket piping (See Note 6 on Page 38)
Level
Escutcheon plate
Dispersion tubes (see Note 4
on Page 38
bracket)
)
y = 4½" (114 mm)
min. Center assembly in duct. See Note
x
10 on Page
39.
x (See Table
29-1 for minimum tube spacing)
x
3/4" pipe thread (DN20)
12" (305 mm) min.
Trap (See Note 8 on Page 39)
4" (100 mm) min.
Header trap by installer (see Note 9 on Page 39)
Steam jacket trap (see Note 8 on Page 39)
NOTES:
4" (100 mm) min.
See Note 7 on Page 38
DC-1072 mc_040611_1550
Secure and seal escutcheon plates
12" (305 mm) min.
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Maxi-bank option piping notes” on Pages 38 and 39, and see Pages 14 and 15 for more information about trap types and trap piping.
x
x
y (see y note above)
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
40
Page 43
Maxi-bank option field piping
FIGURE 41-1: MAXI-BANK OPTION, TOTAL TUBE LENGTH GREATER THAN 45' (13.7 M)
MAXI-BANK HUMIDIFIER
Isolation valve (by others)
From steam source
Same size as separator inlet
Factory-supplied header and interconnecting piping
See Table 28-1
See Note 7 on Page 38
Steam valve and actuator (see Note 4)
Separator
3/4" pipe thread (DN20)
12" (305 mm) min.
Trap (See Note 8 on Page 39)
4" (100 mm) min.
Install strainer within 3' (1 m) of humidifier (see Note 4)
Mounting bracket
Steam jacket piping (See Note 6 on Page 38)
Level
Escutcheon plate
Dispersion tubes (see Note 4 on Page 38)
Second inlet
Secure end of tube to duct using support bracket (0.421" dia. [11 mm] holes in top, bottom, and end of bracket)
y = 4½" (114 mm)
min. Center assembly in duct. See Note
x
10 on Page
39.
x (See Table
29-1 for minimum tube spacing)
x
x
x
y (see y note above)
Header trap by installer (see Note 9 on Page 39)
Steam jacket trap (see Note 8 on Page 39)
NOTES:
4" (100 mm) min.
12" (305 mm) min.
Secure and seal escutcheon plates
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Maxi-bank option piping notes” on Pages 38 and 39, and see Pages 14 and 15 for more information about trap types and trap piping.
DC-1073 mc_051011_1018
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
41
Page 44
MAXI-BANK HUMIDIFIER
Maxi-bank option field piping
FIGURE 42-1: MAXI-BANK OPTION, TOTAL TUBE LENGTH LESS THAN OR EQUAL TO 45' (13.7 M) IN AN AHU
Isolation valve (by others)
From steam source
Same size as separator inlet
Factory-supplied header and interconnecting piping
See Table 28-1
Steam valve and actuator (see Note 4)
Separator
3/4" pipe thread (DN20)
12" (305 mm) min.
Separator trap (See Note 8 on Page 39)
Install strainer within 3' (1 m) of humidifier (see Note 4)
Mounting bracket
Steam jacket piping (See Note 6 on Page 38)
Level
Dispersion tubes (see Note 4
See Note 7 on Page 38
on Page 38
Secure end of tube to AHU using support bracket (0.421" dia. [11 mm] holes in top, bottom, and end of bracket)
y = 4½" (114 mm)
min. Center assembly in duct. See Note 10 on Page 39.
x
x (See Table
29-1 for minimum tube spacing)
)
x
x
x
4" (100 mm) min.
Header trap by installer (see Note 9 on Page 39)
Steam jacket trap (see Note 8 on Page 39)
12" (305 mm) min.4" (100 mm) min.
NOTES:
DC-1207
mc_050511_1456
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Maxi-bank option piping notes” on Pages 38 and 39, and see Pages 14 and 15 for more information about trap types and trap piping.
y (see y note above)
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
42
Page 45
Maxi-bank option field piping
FIGURE 43-1: MAXI-BANK OPTION, TOTAL TUBE LENGTH GREATER THAN 45' (13.7 M) IN AN AHU
Install strainer within 3' (1 m) of humidifier (see Note 4)
Isolation valve (by others)
From steam source
Same size as separator inlet
Factory-supplied header and interconnecting piping
See Table 28-1
Mounting bracket
Steam jacket piping (See Note 6 on Page 38)
Level
MAXI-BANK HUMIDIFIER
Secure end of tube to AHU using support bracket (0.421" dia. [11 mm] holes in top, bottom, and end of bracket)
y = 4½" (114 mm)
min. Center assembly in duct. See Note 10 on Page 39.
x
See Note 7 on Page 38
Steam valve and actuator (see Note 4)
Separator
3/4" pipe thread (DN20)
12" (305 mm) min.
Separator trap (See Note 8 on Page 39)
4" (100 mm) min.
Header trap by installer (see Note 9 on Page 39)
Steam jacket trap (see Note 8 on Page 39)
4" (100 mm) min.
NOTES:
Dispersion tubes (see Note 4 on Page 38)
Second inlet
12" (305 mm) min.
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
DC-1208 mc_050511_1457
x (See Table
29-1 for minimum tube spacing)
x
x
x
y (see y note above)
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Maxi-bank option piping notes” on Pages 38 and 39, and see Pages 14 and 15 for more information about trap types and trap piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
43
Page 46
MAXI-BANK HUMIDIFIER
Maxi-bank option field piping
FIGURE 44-1: MAXI-BANK OPTION INSTALLED IN A DUCT VERTICAL AIRFLOW
See Table 29-1 for minimum tube spacing (x). See Note 10 on Page 39.
y = 4½" (114 mm) min.
Center assembly in duct. See Note 10 on Page 39.
x
x
x
y
See Note 2 on Page 38
Isolation valve (by others)
Pipe size same as inlet to separator
From steam source
Secure end of tube to duct using support bracket (0.421" dia. [11 mm] holes in both sides and end of bracket)
y
x
x
Level
Install strainer within 3' (1 m) of humidifier (see Note 4)
Trap (see Note 8 on Page 39)
Airflow (see Note 5 on Page 38)
Dispersion tube (see Note 5 on Page 38)
Secure and seal escutcheon plates
See Note 2 on Page 38
Header trap (see Note 9 on Page 39)
Valve
Pitch supply header 1/8"/ft (1%) toward drain
Separator
See Note 7 on Page 38
NOTES:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Maxi-bank option piping notes” on Pages 38 and 39, and see Pages 14 and 15 for more information about trap types and trap piping.
mc_040711_1805
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
44
DC-1075
Page 47

Assembly and installation

MINI-BANK HUMIDIFIER

The Mini-bank humidifier is a pre-engineered and pre­assembled header/tube assembly with tubes that are always 3" (76.2 mm) on center. The number of tubes depends upon the duct height. For best mixing, the tubes should span at least 90% (preferably 100%) of the duct width.
1. Unpack shipment and verify receipt of all components with packing list. Two F&T traps and one wye strainer are shipped loose for field installation. Report any shortages at once.
2. The Mini-bank can be configured to discharge steam against or with the airflow: Position the tube bank assembly at the desired orientation, slide the tube bank through the opening in the duct wall, join the tube bank assembly to the separator/valve assembly, and tighten the union.
3. Slightly better mixing with less “fog travel” results when the steam blows against the airflow. If the insulated jacket option has been supplied, the steam must blow with the airflow to avoid steam contacting and condensing on the metal jacket.
For more installation information
• See “Humidifier placement” on Pages 6 – 8 for information about choosing an installation location.
• See “Sensor placement” on Page 9.
• See “Pressurized steam piping guidelines” on Pages 10 – 13.
• See “Temperature switches” on Pages 16 – 19.
WARNING
Improper mounting hazard
Mount humidifier per the instructions in this manual and to a structurally stable surface. Improper humidifier mounting can cause the humidifier to fall resulting in severe personal injury or death.
mc_060310_0725
4. If a field change is necessary, loosen the union, and rotate the tube bank manifold, and tighten the union.
5. Install the Mini-bank humidifier in the duct, positioning the assembly so the tube bank is perpendicular to the top and bottom of the duct and level across the duct. Support the dispersion tube bank out-board end with a No. 10-32 bolt. To secure the Mini-bank escutcheon plate air tight, seal around the plate and fastener with suitable caulk.
6. Install the steam strainer, taking the steam supply to the Mini-bank humidifier off the top of steam main (instead of the side or bottom) to ensure the driest steam. The main should be dripped and trapped. See “Pressurized steam piping guidelines” on Pages 10 – 13.
7. Locate and install the steam traps as necessary. The Mini-bank humidifier steam traps should drain by gravity to return main having little or no back pressure. If condensate cannot drain by gravity, it must be elevated to return main (see Page 11).
Continued
WARNING
Excessive moisture hazard
DriSteem strongly recommends installing a duct airflow proving switch and a duct high limit humidistat. These devices prevent a humidifier from making steam when there is low airflow in the duct or when the RH level in the duct is too high. Failure to install these devices can result in excessive moisture in the duct, which can cause bacteria and mold growth or dripping through the duct.
mc_060310_0725
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
45
Page 48
MINI-BANK HUMIDIFIER
Installation
8. Install control tubing (pneumatic) or wiring (electric) to valve actuator.
9. Install an airflow proving switch to prevent the valve from opening unless air is moving in duct. See “Humidifier placement” on Pages 6 – 8 for location recommendations.
10. Install a duct-mounted high-limit humidistat downstream from the humidifier. Set humidistat at 80-90% RH to prevent condensation forming in the duct. Mount this humidistat far enough downstream to ensure that injected steam has been completely absorbed before the humidistat. See “Humidifier placement” on Pages 6 – 8 for location recommendations.
11. Install a temperature switch to prevent possible cold-start dripping when steam pressure to the humidifier is cycled. See “Temperature switches” on Pages 16 – 19 for more information.
12. Install the humidistat and/or sensors according to the recommendations on Page 9.
Table 46-1: Mini-bank humidifier specifications
Face height
inches mm
6-9 150-230 2
10-12 250-305 3
13-15 330-380 4
16-18 405-460 5
19-21 480-535 6
22-24 560-610 7
Note: See Figure 47-1 for face height and face width.
mc_081108_1455
Required number of tubes Face width Shipping weights
6" to 48" in 1/2" increments (150 mm to 1220 mm in 13-mm increments) For face dimensions larger than 48" × 24" (w x h) (1220 mm x 610 mm), use Multiple-tube humidifier.
Tubes:
0.3 lbs per tube foot (0.4 kg per tube meter) Remaining components (separator, valve, traps, etc.): 8.5 lbs (3.8 kg)
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
46
Page 49

Field piping

FIGURE 47-1: MINI-BANK HUMIDIFIER IN A DUCT HORIZONTAL AIRFLOW
Isolation valve (by others)
From steam source
Install strainer within 3' (1 m) from humidifier. Piping downstream from strainer should be same size as strainer.
Valve
1/2” Pipe thread (DN15) steam jacket inlet
Union
Face width
1.5" (38 mm)
Level
MINI-BANK HUMIDIFIER
10-32 (M5) tapped hole to attach dispersion end to duct
Face height
Separator
1/2" pipe thread (DN15) inlet
12" (305 mm) min.
4" (100 mm) min.
Separator trap
NOTES:
12"
(305 mm)
min.
Condensate returns
3/4" pipe thread (DN20)
4" (100 mm) min.
1/2" pipe thread (DN15)
Steam jacket trap
Dispersion tube
Escutcheon plates fit around tubes. Secure and seal moveable escutcheon plates (plates can be mounted within limits of 1½” [38 mm]).
OM-7480
1. To avoid metal fatigue, allow for thermal expansion of dispersion tubes.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Drawing represents a left-hand discharge.
4. Slightly better mixing with less visible vapor travel occurs when discharged steam blows against the airflow, rather
than with the airflow. Therefore, when using noninsulated steam jackets in a horizontal airflow, position dispersion tubelets (steam orifices) so that they face into the airflow. If the dispersion tube has an insulated jacket, the discharged steam must blow with the airflow to avoid condensation that may occur when discharged steam contacts the cooler insulated jacket. Therefore, when using insulated steam jackets in a horizontal airflow, position dispersion tubelets so that they discharge steam with the airflow, and also add 24" (610 mm) to the non-wetting absorption distance.
5. Center tube assembly within duct height.
6. If steam pressure is less than or equal to 15 psi (103.4 kPa), use float and thermostatic (F&T) traps for the humidifier. If steam pressure is greater than 15 psi (103.4 kPa), use inverted bucket traps for the humidifier. If lifting condensate, use an inverted bucket trap and check valve regardless of steam pressure. (see Figure 12-1)
7. See the previous page for face width and face height dimensions.
8. See “Pressurized steam piping guidelines” on Pages 10 – 13.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
47
Page 50

AREA-TYPE HUMIDIFIER

Installation

ASSEMBLY AND INSTALLATION
Area-type humidifiers are factory assembled and shipped as a complete unit, with steam trap and wye strainer shipped loose. Each humidifier requires a steam supply, condensate return, and electrical supplies to operate the fan.
1. Select a location using Table 50-1.
2. Unpack shipment and verify receipt of all Area-type humidifier components with packing slip. Report any shortages at once.
3. Mount humidifier to supported steam and condensate piping as necessary.
4. Connect fan power as recommended for a minimum 60 lbs/hr (27.2 kg/h) of steam: 120v, 60 hz, below 1 amp. The fan will provide 700 cfm (0.33 m3/s) of air.
WARNING
Improper mounting hazard
Mount humidifier per the instructions in this manual and to a structurally stable surface. Improper humidifier mounting can cause the humidifier to fall resulting in severe personal injury or death.
mc_060310_0725
5. Connect the necessary control signal wiring to steam valve operator.
Note: Recommended maximum steam supply pressure is
15 psi (105 kPa). If pressure is greater than this, consult factory.
6. See components and installation drawing in Figure 39-1.
7. See “Sensor placement” on Page 9.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
48
Page 51

Field piping

AREA-TYPE HUMIDIFIER
FIGURE 49-1: AREA-TYPE HUMIDIFIER COMPONENTS AND INSTALLATION OVERVIEW
Three-speed fan
Strainer (see Note 3)
From steam source
Steam valve and actuator (see Note 3)
Internal baffle plate
Entrained condensate
Steam dispersion port
Humidifier separator drain 3/4" (DN20) pipe thread
8" (203 mm) min.
10"
(254 mm)
min.
DC-1179 mc_050511_0925
Table 49-1: Area-type dispersion fan specifications
120 V
Electric fan motor
Blade diameter 12" (305 mm)
Speeds 3
Control Rotary switch
mc_050511_0924
50/60 Hz
0.75 A
NOTES:
1. Dashed lines indicate provided by installer.
2. Dri-calc is DriSteem’s free sizing and selection software; see Dri-calc on the www.dristeem.com Tools page.
3. Steam valve and strainer sizes are provided by Dri­calc (Note 2).
4. See “Piping notes” on Page 23, and see Pages 14 and 15 for more information about trap types and trap piping.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
49
Page 52
AREA-TYPE HUMIDIFIER

Rise, spread, and throw dimensions

The table below lists the Area-type humidifier's minimum rise, spread and throw non-wetting dimensions. Surfaces cooler
FIGURE 50-1: AREA-TYPE RISE, SPREAD, AND THROW
than ambient temperature, or objects located within this minimum dimension, may cause condensation and dripping.
Rise: Minimum non-wetting height above the steam chute
Spread
Rise
Spread: Minimum non-wetting width from the steam chute Throw: Minimum non-wetting horizontal distance from the steam chute
Throw
The greater the space relative humidity, the higher and farther the discharged steam will carry and rise in the space
mc_041411_1855
DC-5M
until becoming absorbed.
mc_050511_0945
Table 50-1: Area-type humidifier minimum distances for rise, spread, and throw*
Maximum
steam capacity
Rise Spread Throw Rise Spread Throw Rise Spread Throw
lbs/hr kg/h ft m ft m ft m ft m ft m ft m ft m ft m ft m
50 20 1.0 0.3 2.0 0.6 6.0 1.8 1.0 0.3 2.0 0.6 6.0 1.8 1.0 0.3 2.5 0.8 6.0 1.8
75 34 3.0 0.9 3.0 0.9 8.0 2.4 3.0 0.9 3.0 0.9 8.0 2.4 3.0 0.9 4.0 1.2 8.0 2.4
100 45 4.0 1.2 4.0 1.2 10.0 3.1 4.0 1.2 4.0 1.2 10.0 3.1 4.0 1.2 5.0 1.5 10.0 3.1
150 68 6.0 1.8 5.0 1.5 12.0 3.7 6.0 1.8 5.0 1.5 12.0 3.7 6.0 1.8 5.0 1.5 12.0 3.7
200 90 7.0 2.1 7.0 2.1 13.0 4.0 8.0 2.4 7.0 2.1 14.0 4.3 8.0 2.4 7.0 2.1 14.0 4.3
225 102 7.0 2.1 7.0 2.1 13.0 4.0 8.0 2.4 7.0 2.1 14.0 4.3 8.0 2.4 7.0 2.1 14.0 4.3
250 110 8.0 2.4 8.0 2.4 15.0 4.6 9.0 2.7 9.0 2.7 16.0 4.9 9.0 2.7 9.0 2.7 16.0 4.9
285 130 9.0 2.7 9.0 2.7 17.0 5.2 10.0 3.1 10.0 3.1 18.0 5.5 10.0 3.1 10.0 3.1 18.0 5.5
Maximum
steam capacity
Rise Spread Throw Rise Spread Throw Rise Spread Throw
lbs/hr kg/h ft m ft m ft m ft m ft m ft m ft m ft m ft m
50 20 1.0 0.3 1.5 0.5 4.0 1.2 1.0 0.3 2.0 0.6 4.0 1.2 1.0 0.3 2.0 0.6 4.0 1.2
75 34 2.0 0.6 2.0 0.6 6.0 1.8 2.0 0.6 2.5 0.8 6.0 1.8 2.0 0.6 2.5 0.8 6.0 1.8
100 45 3.0 0.9 3.0 0.9 8.0 2.4 3.0 0.9 3.0 0.9 8.0 2.4 3.0 0.9 3.0 0.9 8.0 2.4
30% RH 40% RH 50% RH
30% RH 40% RH 50% RH
60 °F (16 °C)
70 °F (21 °C)
150 68 4.0 1.2 4.0 1.2 10.0 3.1 4.0 1.2 4.0 1.2 11.0 3.4 4.0 1.2 4.0 1.2 11.0 3.4
200 90 5.0 1.5 5.0 1.5 11.0 3.4 5.0 1.5 5.0 1.5 12.0 3.7 5.0 1.5 5.0 1.5 12.0 3.7
225 102 5.0 1.5 5.0 1.5 11.0 3.4 5.0 1.5 5.0 1.5 12.0 3.7 5.0 1.5 5.0 1.5 12.0 3.7
250 110 6.0 1.8 6.0 1.8 12.0 3.7 6.0 1.8 6.0 1.8 13.0 4.0 6.0 1.8 6.0 1.8 14.0 4.3
285 130 7.0 2.1 7.0 2.1 14.0 4.3 7.0 2.1 7.0 2.1 15.0 4.6 7.0 2.1 7.0 2.1 16.0 4.9
* With fan on high speed
mc_030210_0940
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
50
Page 53
Humidifier start-up and shut-down
HUMIDIFIER START-UP
1. Open steam jacketing shut-off valve, if applicable.
2. Inspect steam valve for proper operation. Pneumatic: Inspect to ensure that: (1) the valve closes off steam tight, (2) the stem packing is not leaking steam, and (3) the diaphragm in the actuator is not leaking air. Electric: Inspect to be sure the valve operates freely, closes off steam tightly, and that the stem packing is not leaking.
3. Inspect steam traps and verify all are working properly. A blocked steam trap will be cold. A “blowing” steam trap will be hot and noisy, and the discharge pipe will be hot for a continuous distance up to 30' (9 m). A properly operating steam trap will have about a two­degree temperature drop measured across the trap from inlet to discharge.

OPERATION

4. Verify airflow proving switch and high limit humidistat, if applicable, are working properly.
HUMIDIFIER SHUT-DOWN
Close humidifier steam supply shut-off valve.
See “Maintenance procedures” on Page 54.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
51
Page 54
OPERATION
Eliminating excess heat from steam jacketed humidifiers
FIGURE 52-1: SINGLE HUMIDIFYING STEAM PATH
Humidifier isolation valve (by others)
Modulating control valve
OM-21
mc_051011_1630
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
52
Page 55
Eliminating excess heat from steam jacketed humidifiers
See Figure 52-1.
In some applications with steam-jacketed humidifiers, the heat given off by the steam-heated tube (not the steams sensible heat) may be undesirable. While relatively insignificant in a single-tube unit (usually a rise of less than 2 °F [1 °C]), it can be much greater in a closely-spaced, multiple-tube installation. This can be dealt with in several ways:
1. Manually turn off the steam supply valve after the humidification season.
2. Insulate the tube exterior. Note: Insulation will enlarge the tube profile, causing
additional resistance to airflow.
3. Provide an automatic shut-off valve for the jacketing steam circuit in addition to the modulating control valve. This will eliminate heat gain during the “off” humidification periods only. The jacketing steam valve should be a two-position type, with a minimum Cv of 5, and set to the full-open position prior to opening the modulating valve.
OPERATION
As shown in Figure 52-1, all steam (for jacketing and humidification) must pass through the jacket steam valve. It must do so with little or no pressure drop across the valve, or maximum capacity will be reduced. More importantly, with just one supply source for jacket and humidification steam, the jacket steam temperature may drop below the temperature required to eliminate dripping. Therefore, the valve must be amply sized. This is not significant in a small-capacity humidifier. In a large-capacity humidifier, the required valve size may be quite expensive.
mc_051011_1631
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
53
Page 56

MAINTENANCE

Maintenance procedures

1. Strainer: Inspect the screen at least twice during the first year. If fouled, it should be inspected more frequently and cleaned as needed.
2. Steam trap: At least twice a year, verify that the steam trap is functioning properly. A blocked steam trap will be cold. An improperly operating steam trap with steam exiting the trap will be hot and noisy, and the discharge pipe from it will be hot for a continuous distance up to 30' (9 m). A properly operating steam trap will have about a 2 °F (1 °C) temperature drop measured across the trap from inlet to discharge.
3. Valve (pneumatic): Inspect annually to ensure that: a. The valve tightly closes off steam. b. The stem packing is not leaking steam. c. The diaphragm in the actuator is not leaking air.
Valve (electric modulating): Inspect annually to ensure that: a. The valve operates freely. b. The valve tightly closes off steam. c. The stem packing is not leaking steam.
Valve (solenoid): Inspect annually to verify proper function with steam-tight shutoff.
4. Silencer: Inspect at least annually for cleanliness. Clean or replace as needed.
5. Teflon seal rings: After one year of service, verify that rings are properly functioning. They require replacement if disturbed, since the Teflon can take a “set” and not return to its uncompressed shape.
6. O-rings (dispersion tube adapters): Replace after two or three years of service.
7. Separator: No maintenance required.
8. Dispersion tube: No maintenance required.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
54
Page 57

Troubleshooting

Table 55-1: Steam Injection troubleshooting guide
Problem Possible cause Action
Humidifier discharges water in duct • Steam main overloaded with water
due to boiler discharging water with steam (priming) or improper steam main dripping
• Steam trap not draining properly • Replace trap, repair, or clean as required
• Steam pressure is too low (below 2 psi [14 kPa])
• Condensate is collecting in low, undripped points in steam main
• Steam jacketing of tube not up to proper temperature
• Overloaded condensate return main • Replace with larger piping, or pipe condensate to floor
• Inadequate steam trap capacity • Replace steam trap orifices as necessary.
Humidifier leaks water • Defective O-rings on tube adapter • Replace O-rings
• Locate cause of priming and correct
• Reduce back pressure of condensate return line
• Verify that steam shutoff valves are fully open
• Adjust pressure reducing valve
• Adjust boiler pressure
• Install drips and steam traps as required
• Excessive lifting of condensate. Reroute piping or raise steam pressure.
• Short circuiting inside tube jacketing. Replace tube.
• Improper steam trap location. Relocate and/or add additional trap.
• Condensate return line pressure is too high. Re-pipe.
• Dispersion tube is not level. Reposition.
drain.
• Replace with larger trap.

TROUBLESHOOTING

Humidity exceeds setting of humidistat
Continued
• Steam leak in outer jacket of dispersion tube
• Automatic valve not fully closing • Foreign matter is holding valve open. Clean valve; check
• Control system is malfunctioning • Incorrect control voltage. Verify and correct.
• Leak in steam piping inside duct • Repair leak.
• Repair leak, or replace tube. Note: Check installation to ensure tubes are not rigidly anchored in place. Tubes must be allowed to flex in response to thermal expansion.
line strainer.
• Valve spring is broken. Replace spring.
• Valve stem packing is adjusted too tightly. Loosen and/or replace packing.
• Steam pressure exceeds close-off rating of valve spring. Replace actuator or valve spring with one that is compatible with the higher steam pressure.
• Valve is installed backers. Remount.
• Adjust valve linkage.
• Incorrect control signal. Verify and correct.
• Improper wiring. Verify and correct.
• Incorrect humidity sensor. Verify and correct.
• Humidity controller out of calibration. Calibrate.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
55
Page 58
TROUBLESHOOTING
Troubleshooting
Table 55-1: Steam Injection troubleshooting guide (continued)
Problem Possible cause Action
Hunting: Humidity swings above and below desired set point
Space humidity will not rise to humidistat set point
Continued
• Control system is malfunctioning. • Faulty or inaccurate humidity controller. Calibrate or replace.
• Automatic valve is hunting. • Humidifier is oversized. Change to a smaller valve.
• Excessive outside air volume • Check fans, dampers, VAV, etc.
• Steam pressure is too low. • Manual steam valve is partially closed. Open.
• Humidifier is undersized. • Replace valve with larger capacity valve.
• Automatic steam valve is not opening fully.
• Control system is malfunctioning. Electric:
• Poor location of control components. Relocate.
• Incompatible control component(s). Change component(s).
• Pressure-reducing valve is not accurately controlling steam pressure. Repair or replace.
• Boiler pressure is swinging too widely. Adjust.
• Strainer screen is partially clogged. Clean.
• Boiler pressure is too low. Adjust.
• Pressure reducing valve is not accurately controlling steam pressure. Repair or replace.
• Boiler pressure is swinging too widely. Adjust.
• Check fans, dampers, VAV, etc.
• Piped incorrectly. Re-pipe.
• Steam piping is undersized.
• Replace with larger humidifier.
• Add additional humidifier.
• Valve packing is adjusted too tightly. Loosen and/or replace packing.
• Adjust valve linkage.
• Check pilot positioner settings.
• Incorrect control circuit voltage. Change transformer.
• Incorrect control signal. Replace component(s) to make all components compatible.
• Improperly wired. Rewire.
• Incorrect humidity sensor (Barber-Colman units only). Replace.
• Humidity controller is out of calibration or is malfunctioning. Repair or replace.
• Malfunctioning humidifier temperature switch is not allowing humidifier valve to open. Replace or readjust.
Pneumatic:
• Humidity controller is out of calibration or is malfunctioning. Repair or replace.
• Obstructed air line. Clean.
• Malfunctioning pneumatic temperature switch. Replace.
• Air leak in actuator. Repair or replace.
• Compressed air pressure is too low. Adjust.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
56
Page 59
Troubleshooting
Table 55-1: Steam Injection troubleshooting guide (continued)
Problem Possible cause Action
Space humidity will not rise to humidistat set point (continued)
• Foreign matter is preventing valve from opening.
• Excessive outside air volume. • Reduce air volume.
TROUBLESHOOTING
• Clean or replace valve.
Condensate in duct • Humidifier is mounted too close to
internal devices (dampers, turning vanes, etc.) in duct.
• A noninsulated duct is passing through an unheated area (duct surface temperature is too low).
• Air cannot absorb steam quantity being discharged.
• Steam pressure is too high, causing excess capacity.
Humidifier is noisy • Tube silencer is missing. • Install silencer.
• Check fan, dampers, VAV, etc.
• Move humidifier tubes to a point farther upstream from internal devices.
• Add dispersion tubes for shorter absorption distance. consult DriSteem to determine the total number of tubes required.
• Insulate ductwork.
• Humidifier is operating when blower is off. Install airflow proving switch.
• Valve is hunting. See previous page for instructions.
• Air temperature in duct is too low for steam quantity being supplied.
• Air cfm in duct is too low for steam quantity being supplied.
• Reduce steam pressure.
Note: Unless special-ordered, silencers are furnished only with
Model 60 and Model 70 tubes equal to or shorter than 48” (1219 mm), and only with black iron piping.
• Dispersion tube output is excessively high.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
• Install additional tubes.
57
Page 60

REPLACEMENT PARTS

Single-tube and Multiple-tube humidifiers
FIGURE 58-1: SINGLE-TUBE AND MULTIPLE-TUBE HUMIDIFIER REPLACEMENT PARTS
OM-23
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
58
Page 61
Single-tube and Multiple-tube humidifiers
Table 59-1: Single-tube and Multiple-tube humidifier replacement parts
No. Description Part No.
1 Separator (vertical separator shown) Consult factory
Valve/actuator assembly (refer to specific order)
2
Valve/actuator assembly or actuator alone are available as replacement parts. Valve body alone is not available as a replacement part.
3 Actuator Consult factory
4 Tube adapter Consult factory
O-ring, 1" I.D., black EPDM, for Model 60 and Model 70 tubes (not shown)
5
O-ring, 1½” I.D., black EPDM, for Model 80 tubes (not shown)
6 Silencer holder, stainless steel (not shown) 183100
7 Medium grit stainless steel wool (not shown) 300210
8 Replacement tube Consult factory
Seal ring, brass, 1/2" (DN15), for Model 60 tube 306360-001
Seal ring, brass, 3/4" (DN20), for Model 70 tube 306360-002
Seal ring, brass, 1½" (DN40), for Model 80 tube 306360-003
9
Seal ring, 316 stainless steel, 1/2" (DN15), for Model 60 tube 306360-007
Seal ring, 316 stainless steel, 3/4" (DN20), for Model 70 tube 306360-004
Seal ring, 316 stainless steel, 1½" (DN40), for Model 80 tube 306360-006
10 Nipple Consult factory
11 Elbow Consult factory
12 Union Consult factory
13 Tubelet Consult factory
14 Y-strainer Consult factory
Steam trap, float and thermostatic (F&T) (shown), cast iron, 3/4" (DN20), for ≤15 psi (103.4 kPa)
15
Steam trap, inverted bucket, cast iron, 3/4" (DN20), for >15 psi (103.4 kPa) or lifting condensate
Steam trap, thermostatic, 316 stainless steel, 3/4" (DN20) 300025
Temperature switch, electric 400260-001
16
Temperature switch, pneumatic 307076
Consult factory
300400-007
300400-006
300000-DB
300010
REPLACEMENT PARTS
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
59
Page 62
REPLACEMENT PARTS
Area-type humidifier
Table 60-1: Area-type humidifier with electric fan replacement parts
No. Description Part No.
1 Separator (with 3/4" NPT [DN20] supply) Consult factory
2 Fan, three-speed 400010
3 Valve actuator Consult factory
Valve, 1/2" NPT (DN15) pneumatic with operator
Valve, 3/4" NPT (DN20) pneumatic with operator
Valve, 1" NPT (DN25) pneumatic with
4
operator
Valve, 1/2" NPT (DN15) electric 510030
Valve, 3/4" NPT (DN20) electric 510031
Valve, 1" NPT (DN25) electric 510032
510060
510061
510063
FIGURE 60-1: AREA-TYPE HUMIDIFIER WITH ELECTRIC FAN
2
3
4
DC-6M
1
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
60
Page 63
Mini-bank humidifier
REPLACEMENT PARTS
Table 61-1: Mini-bank humidifier replacement parts
No. Description Part No.
1 5" (127 mm) separator 162520
Valve, 1/2" (DN15)) pneumatic with operator 510060
2
Valve, 1/2" (DN15) electric 510030
3 Orifice, brass (not shown)* 203450
4 Trap, float and thermostatic (F&T) (not shown)** 300000
5 Y-strainer, 1/2" (DN15) (not shown)** 300100-001
6 Valve actuator Consult factory
NOTES: * Varies with each order ** Shipped loose
FIGURE 61-1: MINI-BANK HUMIDIFIER REPLACEMENT PARTS
6
1
2
OM-7479
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
61
Page 64

WARRANTY

Expect quality from the industry leader
For more than 45 years, DriSteem has been leading the industry with creative and reliable humidification solutions. Our focus on quality is evident in the construction of our Steam Injection humidifiers, which feature cleanable stainless steel construction. DriSteem also leads the industry with a Two-year Limited Warranty and optional extended warranty.
For more information
www.dristeem.com sales@dristeem.com
For the most recent product information visit our Web site: www.dristeem.com
DRI-STEEM Corporation a subsidiary of Research Products Corporation DriSteem U.S. operations are ISO 9001:2015 certified
U.S. Headquarters: 14949 Technology Drive Eden Prairie, MN 55344 800-328-4447 or 952-949-2415 952-229-3200 (fax)
Two-year Limited Warranty
DRI-STEEM Corporation (“DriSteem”) warrants to the original user that its products will be free from defects in materials and workmanship for a period of two (2) years after installation or twenty­seven (27) months from the date DriSteem ships such product, whichever date is the earlier.
If any DriSteem product is found to be defective in material or workmanship during the applicable warranty period, DriSteem’s entire liability, and the purchaser’s sole and exclusive remedy, shall be the repair or replacement of the defective product, or the refund of the purchase price, at DriSteem’s election. DriSteem shall not be liable for any costs or expenses, whether direct or indirect, associated with the installation, removal or reinstallation of any defective product. The Limited Warranty does not include cylinder replacement for electrode steam humidifiers.
DriSteem’s Limited Warranty shall not be effective or actionable unless there is compliance with all installation and operating instructions furnished by DriSteem, or if the products have been modified or altered without the written consent of DriSteem, or if such products have been subject to accident, misuse, mishandling, tampering, negligence or improper maintenance. Any warranty claim must be submitted to DriSteem in writing within the stated warranty period. Defective parts may be required to be returned to DriSteem.
DriSteem’s Limited Warranty is made in lieu of, and DriSteem disclaims all other warranties, whether express or implied, including but not limited to any IMPLIED WARRANTY OF MERCHANTABILITY, ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, any implied warranty arising out of a course of dealing or of performance, custom or usage of trade.
DriSteem SHALL NOT, UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, LOSS OF PROFITS, REVENUE OR BUSINESS) OR DAMAGE OR INJURY TO PERSONS OR PROPERTY IN ANY WAY RELATED TO THE MANUFACTURE OR THE USE OF ITS PRODUCTS. The exclusion applies regardless of whether such damages are sought based on breach of warranty, breach of contract, negligence, strict liability in tort, or any other legal theory, even if DriSteem has notice of the possibility of such damages.
By purchasing DriSteem’s products, the purchaser agrees to the terms and conditions of this Limited Warranty.
European office: Marc Briers Grote Hellekensstraat 54 b B-3520 Zonhoven Belgium +3211823595 (voice) +3211817948 (fax) E-mail: marc.briers@dristeem.com
Continuous product improvement is a policy of DriSteem Corporation; therefore, product features and specifications are subject to change without notice.
DriSteem, DriCalc and Mini-bank are registered trademarks of Research Products Corporation and are filed for trademark registration in Canada and the European community.
Area-type and Maxi-bank and trademarks of Research Products Corporation.
Product and corporate names used in this document may be trademarks or registered trademarks. They are used for explanation only without intent to infringe.
© 2015 Research Products Corporation
Extended warranty
The original user may extend the term of the DriSteem Limited Warranty for a limited number of months past the initial applicable warranty period and term provided in the first paragraph of this Limited Warranty. All the terms and conditions of the Limited Warranty during the initial applicable warranty period and term shall apply during any extended term. An extended warranty term of an additional twelve (12) months or twenty four (24) months of coverage may be purchased. The extended warranty term may be purchased until eighteen (18) months after the product is shipped, after which time no extended warranties are available.
Any extension of the Limited Warranty under this program must be in writing, signed by DriSteem, and paid for in full by the purchaser.
mc_051308_0630
Form No. DS-IOM-0115 Part No. 890000-401 Rev F
Loading...