DriSteem Vapormist, Humidi-tech, CRUV Service Kit Manual

Humidi-tech
Electric Humidifiers,
Standard Water
Service Kit Manual
®
, and CRUV
®
,
®
WARNING
Indicates a hazardous situation that could result in death or serious injury if instructions are not followed.
Read all warnings and instructions
This page provides important safety instructions; it is intended to supplement — not replace — the humidifier's Installation, Operation, and Maintenance Manual (IOM). Read the IOM that was provided with the humidifier before performing service or maintenance procedures on any part of the system. Failure to follow all warnings and instructions could produce the hazardous situations described here and in the IOM, resulting in property damage, personal injury, or death.
If the IOM is missing, go to http://www.dristeem.com/ds_lit.jsp to download a replacement. mc_071608_0910
Hot surfaces and hot water
Steam humidification systems have extremely hot surfaces, and water in tanks, electrode cylinders, steam pipes, and dispersion assemblies can be as hot as 212 °F (100 °C). To avoid severe burns, allow the entire humidification system to cool.
Follow the cool-down procedure in the humidifier's IOM before performing service or maintenance procedures on any part of the system.
mc_071608_0911
Shut down the energy source
Before performing service or maintenance procedures on any part of the humidification system, verify that all energy sources are off. Energy sources can be electricity, gas, steam, or hot liquid. Failure to shut down the energy source could result in carbon monoxide poisoning, fire, explosion, electrical shock, and other hazardous conditions. These hazardous conditions could cause property damage, personal injury, or death.
Contact with energized circuits can cause property damage, severe personal injury or death as a result of electrical shock or fire. Do not remove the shroud/cover, electrical panel cover/door, access panels, or heater terminal cover until electrical power is disconnected.
Follow the shutdown procedure in the humidifier's IOM before performing service or maintenance procedures on any part of the system. mc_050808_1551
CAUTION
Indicates a hazardous situation that could result in damage to or destruction of property if instructions are not followed.
WARNING
mc_051508_1145
Electrical shock hazard
If the humidifier starts up at a call for humidity during maintenance, severe bodily injury or death from electrical shock could occur. To prevent such start-up, follow the procedure below before performing service or maintenance procedures on this humidifier (after the tank has cooled down and drained):
1. Use the Vapor-logic®3 or Vapor-logic4 keypad to change the control mode to Standby.
2. Shut off all electrical power to the humidifier using the field-installed fused disconnect, and lock all power disconnect switches in the OFF position.
3. Close the field-installed manual water supply and gas shut-off valves. mc_050808_1530
Damage from hot discharge water
Discharge water can be as hot as 212 °F (100 °C) and can damage the drain plumbing. If the humidifier is equipped with a water tempering device such as a DRI-STEEM Drane-kooler™, it needs fresh make-up water in order to function
properly. Make sure the water supply to the Drane-kooler remains open during draining. If the humidifier is not equipped with a water tempering device, allow the tank to cool before opening the drain valve. mc_111308_1345
Parts in this service kit are for VM99, HT99, and CRUV99 humidifiers (August 1999 to present). Parts are listed on page 2.
CAUTION
Vapormist/Humidi-tech/CRUV, standard water, service kit parts
VM99 / HT99 / CRUV99, standard water, 2 to 4 kW Service Kit No. 900100-001
No. Part Description Part No. Qty.
1 Probe tool (see Probe Tool inset) 406201 1
2 Silicone, clear (not shown) 320000 1
3 Sediment screen (see Fill Valve inset) 300051 1
4 Cover gasket 160695-001 1
5 Probe gasket 309750-004 1
6 Bulkhead drain gasket (Vapormist/Humidi-tech only) 309750-005 1
7 Probe rod assembly 406303-005 1
8 Probe housing 308500 1
VM99 / HT99 / CRUV99, standard water, 6 to 34 kW Service Kit No. 900100-002
No. Part Description Part No. Qty.
1 Probe tool (see Probe Tool inset) 406201 1
2 Silicone, clear (not shown) 320000 1
3 Sediment screen (see Fill Valve inset) 300051 1
4 Cover gasket (Vapormist/Humidi-tech only) 160695-002 1
5 Probe gasket 309750-004 1
6 Bulkhead drain gasket 309750-005 1
7 Probe rod assembly 406303-006 1
8 Probe housing 308500 1
Page 2 • DRI-STEEM Vapormist/Humidi-tech/CRUV, Standard Water, Service Kit Manual
Vapormist/Humidi-tech/CRUV, standard water, service kit parts
This service kit contains the replacement parts called out in the parts drawing to keep your DRI‑STEEM humidifier operating at peak performance. This Service Kit Manual provides important safety and service instructions; it is intended to supplement — not replace — the humidifier's Installation, Operation, and Maintenance Manual. Please see Read all warnings and instructions on page 1.
While performing service and maintenance procedures, replace existing parts with the new parts provided in the service kit.
mc_052808_1400
Enclosure Screw Cap
(Vapormist/Humidi-tech)
Note: Components may by oriented
differently than shown in drawing.
OM-778-3
Probe Tool
Torque probe assembly to 10 ft-lbs (13.6 N-m).
3/8" drive
1
OM-7395X
mc_051508_1320
Fill Valve
3
Sediment screen (3)
inside of Tee
TANKASM-VM2-4X
Apply clear silicone (2) to both sides of gasket.
See Fill Valve inset.
Vapormist/Humidi-tech only
6
4
7
5
8
OM-768X
DRI-STEEM Vapormist/Humidi-tech/CRUV, Standard Water, Service Kit Manual • Page 3
Vapormist/Humidi-tech/CRUV, standard water, service instructions
Inspection and maintenance
Cool down humidifier
Before performing service or maintenance procedures, allow the tank to cool down. Insulated and uninsulated tanks will have hot surfaces
Note: Fresh make‑up water is used to speed up cooling. Do
not close the manual water supply before cooling down the humidifier; otherwise the tank could stay hot for several hours.
1. Verify that there is no call for humidity and that the aquastat set point (adjusted using the keypad/display Setup screens) is less than room temperature (default setting is 40 °F [4 °C]) so that the heaters do not energize while cooling down the tank.
2. Verify that the tank is in Auto mode so it will fill after draining begins.
3. Drain the tank: a. Manually open the drain valve by moving the valve
lever located on the back of the drain valve to the manual open position. The fill valve will open after enough water has drained out of the tank.
b. Let the fill water run until the tank is cooled; then shut
off the field‑installed manual supply water shut‑off valve.
c. Let the tank drain; then manually close the drain valve.
mc_052708_1145
Shut down humidifier
Follow the procedure below before performing service or maintenance procedures (after the tank has cooled down and drained):
1. If the humidifier is equipped with a Vapor‑logic3 controller, use the keypad to change the control mode to Standby.
2. Shut off all electrical power to the humidifier using the field‑installed fused disconnect, and lock all power disconnect switches in the OFF position.
3. Close the field‑installed manual water supply shut‑off valve.
mc_060208_0945
Annually (also recommended when maintenance is performed)
1. All safety devices in the control circuit should be cycled on and off to verify they are functioning. These include:
• Highlimitswitch
• Airflowprovingswitch
• Lowwaterlevelprobe.Pulloutprobeplug;fillvalve
should energize.
2. Measure current draw of heaters and verify amp values per stage by comparing to the wiring diagram located inside the subpanel cover. This identifies any burned out heaters. Only qualified electrical personnel should perform this task.
3. Inspect tank and gaskets for leaks.
mc_060208_1005
Seasonally (or as required, depending on water quality)
Clean the evaporating chamber. See the facing page of this Service Kit manual for Vapormist instructions; see the back page for CRUV instructions.
Off-season maintenance
Perform complete inspection and cleaning of the following:
• Heaters
• Proberods
• Skimmerportandwaterseal
• Humidifiertank
After cleaning, the humidifier should remain empty until humidification is required.
mc_052708_1210
Note: Steps 4 and 7 below apply only to Vapormist humidifiers.
Off-season shut-down procedure
1. If the tank is hot, cool it down first. See cool‑down instructions at left.
2. Drain evaporating chamber.
3. Switch off electrical power.
4. Remove enclosure.
5. Shut off water supply to makeup valve.
6. Examine the evaporating chamber (see facing page of this Service Kit manual), and clean if necessary.
7. Replace enclosure.
8. Leave chamber dry, power off, and the water shut‑off valve closed until the next humidification season.
mc_060208_1030
Page 4 • DRI-STEEM Vapormist/Humidi-tech/CRUV, Standard Water, Service Kit Manual
Vapormist/Humidi-tech/CRUV, standard water, service instructions
Vapormist service
1. Remove the evaporating chamber: a. Remove the two fasteners on each side of the cover
enclosure (see Enclosure Screw Cap inset on page 3)
b. Remove the enclosure.
WARNING!
Do not remove the humidifier electrical panel cover or the heater terminal cover until electrical power is disconnected. Contact with energized circuits can cause property damage, severe personal injury or death as a result of electrical shock.
c. If the Vapormist has an SDU mounted directly above it,
the SDU cover must be removed before removing the humidifier cover.
d. If the tank is hot, cool it down first (see cool‑down
instructions on facing page). e. Shut off the water supply. f. Allow the tank to drain completely. g. Shut off the electrical supply. h. Disconnect the fill line at the supply side of the fill
valve. i. Disconnect the electrical plugs between the tank
components and the back of the electrical panel
(includes: power plug, fill plug, drain plug, water level
control plug, tank temperature sensor plug and thermal
trip plug). Important: Disconnect by pulling on plug
housing. Do not disconnect by pulling on cord or
wires. j. Disconnect the drain union on the back left corner of
the frame. k. Disconnect the steam supply hose from the top of the
tank. l. Lift the tank foot above the frame flange and slide the
tank assembly forward to remove.
2. Loosen the four cover bolts and remove the cover assembly from the tank.
3. Clean the tank interior using a putty knife or similar flat instrument.
4. Clean the probes: a. Unplug probe plug assembly. Leave ground wire
connected to tank.
b. Unscrew the probe rod assembly using the probe tool
connected to a 3/8" square drive.
c. Inspect the probe housing and clean, ensuring that all
the housing passageways are clear. Remove the housing from the holding bracket by sliding the housing horizontally toward the open end of the bracket.
• Thescaleshouldflakeoffeasilyfromtheprobe
assembly rods.
• Thebottom3/8"(10mm)ofeachrodisthesensing
portion; clean these areas with a wire brush, abrasive pad, or steel wool.
d. Inspect the composite plastic probe rod assembly for
any signs of cracking, roughness, or deterioration. If found, replace probe assembly.
e. Reassemble and install the probe and probe plug
assembly. Verify ground wire is solidly connected to tank.
5. Secure the chamber cover, making sure the cover gasket is seated and the chamber is sealed.
6. Re‑install the evaporating chamber: a. Reconnect the fill line. b. Reconnect the electrical plugs (plugs are color coded). c. Reconnect the drain union. d. Reconnect the vapor hose.
7. Verify electrical connections: a. Verify that all DIN rail‑mounted components are
securely fastened to DIN rail.
b. Verify that all power terminal screws and lugs are tight
from power block to heaters. See the table below for torque specifications.
Table 5-1: Vapormist torque specifications
Screw or lug location
Power block 16 1.8 Contactor 16 1.8
Heater nut
Heater wire lug
8-32 (8.5 mm) nut 20 2.2 10-32 (9.5 mm) nut 25 2.8 6 gauge (10 mm2) wire 35 4.0 8 gauge (6 mm2) wire 25 2.8 10-14 gauge (<6 mm2) wire 20 2.2
Torque
inch - lbs N-m
c. Verify that all plugs located under the humidifier cover
are completely plugged in.
8. Move the drain valve lever back to the auto position.
9. Turn on the water supply.
10. Turn on the electrical power.
mc_060208_1055
DRI-STEEM Vapormist/Humidi-tech/CRUV, Standard Water, Service Kit Manual • Page 5
Vapormist/Humidi-tech/CRUV, standard water, service instructions
Humidifier De-scaling Solution
Scale buildup on humidifier heaters acts as an insulator, reducing humidifier performance while increasing energy costs. To keep humidifiers operating as efficiently as possible, remove scale with DRI-STEEM's Humidifier De-scaling Solution, available for purchase from your DRI-STEEM representative or distributor.
The De-scaling Solution cleans without risk of corroding humidifier tanks or welds. The De-scaling Solution also cleans surfaces unreachable by hand scraping.
DRI-STEEM's Humidifier De-scaling Solution is the only approved cleaner/de-scaler for use with DRI-STEEM humidifiers. Use of other cleaners/de-scalers may void your DRI-STEEM warranty.
mc_021908_1410-elec
DRI-STEEM Corporation
An ISO 9001: 2000 certified corporation U.S. Headquarters:
14949 Technology Drive Eden Prairie, MN 55344 800-328-4447 or 952-949-2415 952-229-3200 (fax)
European office: Marc Briers Grote Hellekensstraat 54 b B-3520 Zonhoven Belgium +3211823595 (voice) +3211817948 (fax) E-mail: marc.briers@dristeem.com
Continuous product improvement is a policy of DRI-STEEM Corporation; therefore, product features and specifications are subject to change without notice.
DRI-STEEM, Vapormist, Humidi-tech, CRUV, and Vapor-logic are registered trademarks of DRI-STEEM Corporation and are filed for trademark registration in Canada and the European community.
Drane-kooler is a trademark of DRI-STEEM Corporation.
CRUV Service
1. Drain the tank. See Step 3 on page 4.
2. Clean the probes. See Step 4 on page 5.
3. Remove the tank cover and wet vac minerals out of tank (recommended).
4. To remove tank for cleaning, disconnect drain line union, fill valve supply line, electrical connections to drain, (disconnecting field wiring in conduit is NOT recommended,) thermal trip, heaters, fill valve, and probe. Disconnect steam hose from top of tank and remove mounting bracket fasteners.
5. Remove evaporating chamber and clean.
6. Install the probe and probe plug assembly. Verify that ground wire is connected.
7. Replace tank cover, making sure tank is sealed tight.
8. Reconnect drain line union, fill valve supply line, electrical connections to drain, thermal trip, heaters, fill valve, and probe. Connect steam hose to top of tank.
9. Verify drain valve lever is in AUTO position.
The CRUV humidifier is again ready to humidify.
mc_060208_1100
Mineral precipitate
As evaporation takes place in the humidifier, some of the minerals dissolved in the water precipitate out and float on the water surface. The minerals not removed by the skimmer will settle to the bottom of the evaporating chamber.
Cleaning the evaporating chamber
The heating element is self‑cleaning. The mineral buildup on the element flakes off after reaching a thickness of about 1/16" (2 mm), and settles to the bottom of the chamber.
Long heater element life can be expected when the operation of the humidifier is observed for a few weeks following initial start‑up. By observing the mineral build‑up rate, the frequency of both drain/flush
use and manual cleaning can be determined and adjustments made.
CAUTION
Before this mineral scale builds up on the underside of the heating element, it must be removed. Failure to do so could result in premature
heater burnout. The humidifier is designed for convenient cleaning and maintenance.
mc_052708_1130
Start-up
Perform the Annual safety checks in the Inspection and maintenance section on page 4.
If resuming operation after service, do not leave the humidifier unattended; allow it to cycle through multiple fill cycles to verify that all serviced parts are functioning properly. See the humidifier's Installation, Operation, and Maintenance manual for start‑up details.
mc_052908_1005
© 2011 DRI-STEEM Corporation
Form No. VM/CRUV-standard-SKM-0711
Page 6 DRI-STEEM Vapormist/Humidi-tech/CRUV, Standard Water, Service Kit Manual
Part No. 891000-001 Rev C
DRI-STEEM products are warranted according to the terms and conditions of the standard two-year Limited Warranty effective when the humidifier was purchased. See the literature that was shipped with the humidifier for warranty information.
mc_081308_1405
Loading...
+ 12 hidden pages