DriSteem GTS-DI Users/installation Instructions And Maintenance Operations Manual

READ AND SAVE THESE INSTRUCTIONS
This manual must be left with the owner and should be accessible for reference.
DRI-STEEM Models
®
®
GTS and GTS-DI
GAS-TO-STEAM HUMIDIFIERS
User's/Installation Instructions
and
Maintenance Operations Manual
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
• Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from an off-site phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
• Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
For Toll-Free Technical
TABLE OF CONTENTS
TO THE PURCHASER AND THE INSTALLER
Thank you for purchasing DRI-STEEM Model GTS® equipment. We have designed and built this equipment to give you total satisfaction and many years of trouble-free service. Proper installation and operating practices will assure you of achieving that objective. We therefore urge you to become familiar with the contents of this manual.
DRI-STEEM Humidifier Company
GTS Program Code Nomenclature ...................................... 3
Models GTS and GTS-DI Humidifiers .................................. 4
Safety Precautions ................................................................ 5
Installation
Precautions ................................................................ 6
Required Clearance ..................................................... 6
Locating the Humidifier .............................................. 7
Supply Water and Drain Overflow Connections ........ 7
Drain Piping and Material ........................................... 8
Make-up Water Piping and Material .......................... 8
Vapor Hose Piping ..................................................... 8
Gas Piping ................................................................. 9
Gas Leak Testing ....................................................... 9
Electrical .................................................................... 10
Combustion and Ventilation Air .................................. 10
Venting Guidelines (Stack Connection) ..................... 11
Specifications and Capacities ............................................. 13
Dimensions ........................................................................... 14
Piping Diagrams: Gas, Water, and Drain ........................... 15
Mounting the Humidifier ..................................................... 16
Steam Supply Connection Methods ................................... 17
Dispersion Tube Installation ............................................... 18
RAPID-SORB
®
Assembly and Installation
Horizontal Duct Installation .....................................19
Vertical Duct Installation .........................................20
ULTRA-SORB
®
Installation .................................................. 20
AREA-TYPE Application ...................................................... 21
Start-up and Operation ........................................................ 22
Maintenance
GTS (Standard Model Only) ...................................... 23
GTS-DI Model Only ................................................... 23
Both GTS and GTS-DI ............................................... 24
Air Shutter Adjustment Procedure ............................. 25
Replacement Parts ............................................................... 26
Wiring Diagrams ..................................................................28
Caution Labels ..................................................................... 32
Gas Control Valve ................................................................ 33
Maintenance Service Record .............................................. 34
Two-Year Limited Warranty ................................................ 36
2
GTS PROGRAM CODE NOMENCLATURE
GTS PROGRAM CODE NOMENCLATURE
1
How many tanks are in the system
(1-6)
What type of control does the unit have
S - Single staged E - Externally staged Z - Zone valve T - TP X – Slave
M – Master
Does the unit have VAV
V - Yes O - No
Does the unit have temperature compensation
T - Yes O - No
Humidity sensor type
C - 0-135 OHM humidistat Electric D - 6-9 VDC humidistat F - 1-10 VDC humidistat E - 4-20 mA humidistat X - 4-20 mA transmitter S - Slave N - None (On/Off)
P – 0-135 OHM humidstat Pneumatic
O
O
X
7
8A
(Example)
T
Burner size
5-50 MBH 7-75 MBH 1-100 MBH 6-67.5 MBH
Burner quantity
1 - One staged 2 - Two staged 4 - Four staged 5 - One modulating 6 - Two modulating 8 - Four modulating
Water level control
D - DI with manual drain E - DI with auto drain (end of season) M - Probe with manual drain A - Probe with auto drain
3
GTS Gas-to-Steam Humidifier
This humidifier is designed to be used with either softened or unsoftened water. (Softening is recommended to reduce need for cleaning.) The probe-type level control system requires water conductivity of 100 micromhos/cm, this translates to about 2 grains/gal minimum to function, and therefore will not operate on water treated by reverse osmosis or deionization. However, GTS humidifiers are available for use with these water types. The standard humidifier can be converted in the field to a dem­ineralized model. See below.
GTS® AND GTS-DI HUMIDIFIERS
®
Low-Water Switch
Control Panel
Blower
ULTRA-SORB
Cover Knob
Cover
Evaporating Chamber
Heat Exchanger
GTS-DI Option
For use with deionized or reverse osmosis water. This unit produces chemical-free steam and reliable, accurate humidification control. It is virtually maintenance-free, with no wasted water, heat, or downtime. The DI unit uses a float valve to control water levels.
Shroud
RAPID-SORB
Control Panel
Blower
Gas Valve
Cover Knob
Flue Box
Blocked Vent Tap
®
Low-Water Switch
Fill Valve
Probes
Manual or Electric Drain Valve
Cover
Evaporating Chamber
OM-730
Shroud
Flue Box Drain Valve
Blocked Vent Tap
Gas Valve
Heat Exchanger
Float Valve
Low-Water Cut-Out
OM-735
4
SAFETY PRECAUTIONS
WARNING:
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, an explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory authorized and listed kits or accessories when modifying this product. A failure to follow this warning can cause electrical shock, fire, personal injury, or death.
• Inspect humidifier and accessories upon arrival for damaged, missing, or improper parts. If there is a problem, call DRI-STEEM.
• Application of this humidifier should have special attention given to vent sizing and material, gas input rate, and unit sizing. Improper installation or misappli­cation of the humidifier can require excessive servicing or cause permanent component failure.
• When working on equipment, observe precautions in this literature, tags, and labels attached to or shipped with the unit and other safety precautions that may apply. Wear safety glasses and work gloves. Have fire extinguisher available during start-up, adjustment procedures, and service calls.
• Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
• Do not lift humidifier by gas controls, gas manifold, fire box, or control shroud.
• Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical supply.
5
INSTALLATION
Precautions
• The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1 (latest edition). In Canada, the installation of this unit must comply with local plumbing or waste water codes and other applicable codes and with the current code CAN/CGS-B149.1 "Installation Code for Natural Gas Burning Appliances and Equipment" or CAN/CGA-B149.2, "Installation Code for Propane Burning Applications and Equipment."
• Do not install in potentially explosive or flammable atmospheres laden with grain dust, sawdust, or similar airborne materials.
• Installation of humidifier in high humidity or salt water atmospheres will cause accelerated corrosion, resulting in a reduction of the normal life-span of the unit.
• To prevent premature heat exchanger failure, do not locate ANY gas-fired unit in areas where chlorinated, halogenated or acid vapors are present in the atmo­sphere.
Required Clearance:
For recommended service and maintenance purposes the following clearances should be maintained:
• Heat exchanger removal - front, 30"
• Burner shroud removal - front, 24"
• Control cabinet - left side, 36"
• Drain valve - right side, 12"
• Clean-out tray - rear, 30" (not applicable with DI/RO systems)
• Cover removal - top, 18"
• Distance from vent box to combustible floor - 30"
GTS clearance recommendations
Control cabinet, 36"
Cover, 18"
Cleanout tray, 30"
• Locate the humidifier in an area clear of combustible materials, gasoline, and other flammable vapors and liquids.
• Do not locate units in tightly sealed rooms or small compartments without provision for adequate combustion air and venting. Combustion air must be supplied to the room through a minimum of two permanent openings in the wall, at least one near the bottom. The openings should provide one square inch of free area per 1000 BTUH input rating of the unit with a minimum of 100 square inches for each opening, whichever is greater. See table 10-1 and information on pages 10 and 11 for additional details.
Burner shroud, 24"
Heat exchanger, 30"
Drain valve, 12"
30"
Floor
6
INSTALLATION
Important:
• Remove all shipping brackets and materials before operating the humidifier.
• Humidifier flue gases must be vented to the outside atmosphere.
• Power supply disconnect switch must be in the off position while making wiring connections to prevent electrical shock and equipment damage. All units must be wired in strict accordance with wiring diagram furnished with this unit.
• Turn off all gas while installing the run-out and manual shut-off valve for the humidifier.
Locating the Humidifier
• Provide a level, solid foundation for the humidifier. Locate the humidifier as near as possible to chimney or outside wall so that the flue pipe from the humidifier is short and direct. The location should also be such that the gas ignition system components are protected from water during humidifier operation and service.
Supply Water and Drain Overflow Connections
IMPORTANT: The humidifier is shipped with the auto­matic drain valve locked in the manual open position. This position reduces the possibility of damaging the valve seat from the heat of sweating the drain connection during installation. After the drain connection has been completed the "manual open" lever position must be reset to the auto position. Failure to close the drain valve will not allow the tank to fill.
Regardless of the type of water used, the following general instructions must be followed:
• Union connections must be made at the humidifier on the cold water supply and drain/overflow lines.
• A shut-off valve should be provided in the supply water line to isolate the humidifier from the water system while servicing.
• If the water pressure is above 60 psi and/or water hammer would be objectionable, a pressure reducing valve or shock arrester should be installed.
• The humidifier should be installed in a location away from drafts and properly protected. If installed in a separate room, follow the instructions concerning combustion and ventilation air.
• The humidifier should be located in an area where leakage from the tank or its connections will not result in damage to the adjacent structure or to lower floors of the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the humidifier. The pan must not restrict combustion air flow.
• The humidifier must not be installed on carpeting, tile, or other combustible material other than wood flooring (indoor application only).
• Install humidifier so electrical components are pro­tected from water.
• The appliance must be kept free and clear of insulat­ing materials when located in an insulated space. Insulating material may be combustible. Inspection of the appliance area must be performed when the appli­ance is installed, or when insulation is added.
• A 3/4” opening is provided in the humidifier tank to accommodate skim and/or overflow protection. A water seal is required on the drain/overflow connection and a 1” air gap should be provided prior to a building drain. (Note: Follow local code requirements regarding size of drain pipe.) The water seal must be piped to hold steam in the humidifier and also provide a pressure relief if the steam outlet becomes clogged. (See diagram on page 15)
• Insulating unions or bushings must be used to make connections between copper and other dissimilar metal fittings, such as galvanized steel. These insulating fittings are required to minimize electrolytic corrosion, which results from the direct connection of dissimilar metals in a water system.
• Before beginning ignition sequence of the humidifier at a new installation, be sure the humidifier tank is full of water and the water is free to flow into the tank.
7
INSTALLATION
Drain Piping and Material
Drain piping diagrams are provided on page 15. If non­metallic pipe or hose is used, it must be capable of withstanding temperatures up to 212°F.
To prevent steam from escaping out the drain line, a water seal must be provided in the drain line of sufficient height to contain the pressure developed within the humidifier and steam dispersion system. To determine the proper height of the water seal, see table 15-1 on page 15.
Make-up Water Piping and Material
Make-up water piping diagrams are provided on page 15. Minimum make-up water pressure must be 25 psig. When non-metallic water piping is used, it must be rated to withstand 212°F or greater temperature. If not, the final 3 feet connected to the humidifier should be metallic and should not be insulated.
As part of the fill valve assembly, the needle valve restricts the rush of cold water entering the evaporating chamber during the fill cycle. Adjusting the supply water flow with the needle valve will reduce fill cycle noise from the collapsing steam head in the humidifier. Ad­justing the needle valve will also reduce the drop in output during a fill cycle. Care must be taken to not reduce the fill rate below the humidifier's capacity, this it will cause a low-water shutdown.
Vapor Hose Piping
When a vapor hose and stainless steel dispersion tubes are used, they should be pitched back to the humidifier. A minimum slope of 2" per foot (with no “low spots”) is recommended. When this is not possible due to duct elevation or an obstruction, alternate arrange­ments may be used as shown in figures 8-1 and 8-2 below.
Any condensate that forms in the vapor hose must be removed. Preferably, it should be returned to an open drain with a water seal of sufficient height to contain the duct static pressure, as shown in figure 8-1.
Figure 8-1: Piping method recommended when obstruction prevents dispersion tube from being continuously pitched back to humidifier
Inline Tee
(1½" Dia. - Part # 162710) (2" Dia. - Part # 162712)
Duct
5" Min.
4" Min.
Funnel or
OM-749
Notes:
• The GTS typically requires multiple dispersion tubes. * Refer to local codes for drain pipe size requirements.
Floor Drain*
Obstruction
GTS
¾" Tubing
Figure 8-2: Piping method recommended when humidifier must be mounted higher than the duct
Duct
GTS
Inline Tee
(1½" Dia. - Part # 162710) (2" Dia. - Part # 162712)
OM-750
8
INSTALLATION
Gas Piping
(See "Gas Piping" diagram on page 15.)
CAUTION: Gas pressure to humidifier controls must never exceed 14” W.C. (1/2 psi). A 1/8" inch NPT plugged tapping, accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to the appliance.
• Piping installation must be in accordance with local codes, and ANSI Z233.1, “National Fuel Gas Code,” or CAN/CGA-B149 in Canada. Do not use flexible connec­tors.
• Piping to units should conform with local and national requirements for type and volume and gas handled, and pressure drop allowed in the line. Refer to table 9-1 and 9-2 to determine the cubic feet per hour (cfh) for the type of gas and size of unit to be installed. Using this value and the length of pipe necessary, determine the pipe diameter. Where several units are served by the same main, the total capacity, gas flow (cfh), and length of main must be considered. Avoid pipe sizes smaller than 1/2”. Table 9-1 allows for the usual number of fittings with a 0.3” W.C. pressure drop.
• After threading and reaming the ends, inspect piping and remove loose dirt and chips.
• Support piping so that no strains are imposed on unit or controls.
• Use two wrenches when connecting piping to unit controls.
• Provide a drip pocket before each unit and in the line where low spots cannot be avoided.
• Take-off to unit should come from top or side of main to avoid trapping conden­sate.
• Piping subject to wide temperature variations should be insulated.
• Pitch piping up toward unit at least 1/4” per 15’ of horizontal run.
• Compounds used on threaded joints of gas piping must be resistant to the harmful action of liquefied petroleum gases.
• Purge air before lighting unit by disconnecting piping at gas control. In
no case should line be purged into heat exchanger.
• After installation, check field piping and humidifier gas train for gas leaks.
Table 9-1: Gas Pipe Capacities for Gas Pressures of .5 PSIG or Less
Length of Pipe
Feet
1/2 3/4 1 1-1/4 1-1/2
10 132 278 520 1050 1600
20 92 190 350 730 1100
30 73 152 285 590 890
40 63 130 245 500 760
50 56 115 215 440 670
60 50 105 195 400 610
70 46 96 180 370 560
80 43 90 170 350 530
90 40 84 160 320 490
100 38 79 150 305 460
• Do not use soap solution, or open flame on humidifier gas train. A gas leak detector is recommended.
• Install a ground joint union and a manual shut-off valve immediately upstream of the unit including a 1/8” NPT plugged tapping accessible for test gauge connection. Plugged tappings for test gauges are located on all gas valves.
• Allow at least 5 feet of piping between any high pressure regulator and unit pipe connection.
Gas Leak Testing
• When leak testing the gas supply piping system, the humidifier and its gas shut-off valve must be disconnected during any pressure testing in excess of 14” W.C. (½ psi). The humidifier must be isolated from the gas supply piping system by closing its field-installed manual shut-off valve during any pressure testing equal to or greater than 14" W.C. (½ psi).
• Check gas supply pressure with all burners running at inlet pressure tap of combination gas control. (See page
33) The recommended supply pressure should be 7" W.C. on natural gas or 11" W.C. on LP gas. Purging of gas piping should be performed as described in ANSI Z223.1 (latest edition) or, in Canada, in CAN/CGA-B149 codes.
• Minimum supply pressure. Natural - 4½" W.C. LP - 10" W.C.
• Single stage gas valves GTS™-300, 150, and 75 outlet pressure (manifold) should be factory set at 3 1/2" w.c. for natural, 9" w.c. for L.P. This pressure can be checked on the combination gas valve at the out pressure tap (see page 33).
Table 9-2: Specific
Gas Flow in Piping (Cu. Ft. per Hr.)
(At pressure drop of 0.3 in. water.
Specific gravity = 0.60)
Iron Pipe Size (NPT) Inches
Gravity Conversion Factors
Multiplying factor to be used with table 9-1 when the specific gravity of gas is other than 0.60.
Natural Gas
Specific
Gravity
0.55 1.04
0.60 1.00
0.65 0.962
Propane Gas
Specific
Gravity
1.50 0.633
1.53 0.626
1.60 0.612
Factor
Factor
9
INSTALLATION
• Two stage gas valves (used on GTS® 400, 200 and 100) have a 10 second high fire stage and then drop to a normal fire stage. Factory settings for natural gas are 5" w.c. high, 3 1/2" w.c. normal. Factory settings for L.P. gas are 8" w.c. high, 6" w.c. low. These pressures can be checked on the combination gas valve at the out pressure tap (see page 33).
Electrical
CAUTION: Do not connect aluminum wire between disconnect switch and humidifier. Use only copper wire.
WARNING:
The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/NFPA 70 and Canadian Electrical Code, CSA C22.1, or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground.
• GTS Humidifiers should be supplied with 120-volt AC, 60-Hz, 15-amp separately fused electrical service. The GTS humidifier is equipped with a transformer to step down the voltage to 24 VAC control voltage.
• When installed, the GTS humidifier must be electrically grounded in accordance with local codes or, in the ab­sence of local codes, with the National Electrical Code ANSI/NFPA No. 70-1987. The electrical conductors shall be Type MTW (105°C) AWG #14 wire for line voltage (120V), with BLACK WIRE for HOT; WHITE WIRE for NEUTRAL, GREEN WIRE for GROUND; and #18 gauge for control wiring. All electrical components and wiring must be protected from mechanical damage and water. The control system requires an earth ground for proper operation.
• The humidifier is adjusted for correct performance. Do not alter fan or operate motors at reduced speed.
Combustion and Ventilation Air
CAUTION: Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning sol­vents, salts, air fresheners, and other household products.
CAUTION: The operation of exhaust fans, kitchen ventilation fans, clothes dryers, or fireplaces could create a negative pressure condition at the humidifier. Make­up air must be provided for the ventilation devices, in addition to that required by the humidifier.
• All fuel burning equipment must be supplied with air for combustion of the fuel. Sufficient air MUST be provided to ensure there will not be a negative pressure in the equipment room or space.
• Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1-1988, or applicable provisions of the local building codes. Canadian installations must be installed in accordance with sections 7.2, 7.3, and 7.4 of the CAN/CGA.B149 Installation Codes, and all authorities having jurisdiction.
Table 10-1: Location of Humidifier and Required Air Openings to Confined Space
Confined Space - All air from inside the building; conventional frame. Brick or stone construction with normal infiltration. (Can only be rarely used with larger input units.)
Two openings, 1 square inch per opening per
1000 BTU/hr. input.*
The minimum free area of opening is 100 square inches.
• The current characteristics, and capacity requirements should be checked against the nameplates. All wiring must be in accordance with all governing codes, and with GTS wiring diagram located inside the control cabinet. See table 13-1 for information on the various models.
• See page 14 for recommended knockout locations for the electrical power supply and control wiring connections on the control cabinet.
• See separate publication for the specific controller furnished with this specific GTS humidifier.
10
Confined Space - All air from outside the building through air ducts.
Confined Space - All air from outside the building, through wall openings only (no ducts.)
Unconfined Space - All air from outside the building.
Two openings, 2 ducts, 1 square inch per opening per 2000 BTU/hr. input.*
Two openings, 1 square inch per opening per 4000 BTU/hr. input.*
Same as confined space, all air from outside the building.*
*Note the minimum dimension of any opening is three inches.
INSTALLATION
• For proper and safe operation this appliance needs air for combustion and ventilation. DO NOT block or obstruct air openings on the appliance, spaces around the appliance, or air openings communicating with the appli­ance area.
• DO NOT block the flow of combustion and ventilation air. To provide for necessary oxygen for proper combus­tion, opening must be provided to allow outside air to enter the space in which the heater is located. Enclosed spaces, such as equipment rooms, must be vented at the blower for combustion air. The size of air openings must be based on all gas-burning equipment installed in the space involved. Four types of locations, and the require­ments of each, are outlined in table 10-1, on page 10.
Vertical and Horizontal Venting Guidelines (Stack Connection)
• The GTS® is a fan assisted category 1 appliance.
• The purpose of venting the gas humidifier is to com­pletely remove all products of combustion and ventilation gases to the outside air, without condensation in the stack.
• When connecting the humidifier to a gas vent or chim­ney, the installation shall be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1, or Section 7, Venting Systems and Air Supply Appliances, of the CAN/CGA B149 Installation Codes, the local building codes, and the vent manufacturer's instructions.
• Do not reduce the vent diameter, and avoid short turns in the vent piping. Use the same size stack as the vent furnished with the humidifier. Maintain a minimum upward slope of 1/4-inch-per-linear foot on all horizontal runs. Maintain proper support of vent connections and joints. Observe clearances (in accordance with appli­cable codes) from all combustible materials, and obtain an approved cap for the stack outlet. The bottom of the cap must be one stack diameter above the top of the stack.
• Inspect for proper and tight construction. Any restric­tions or obstructions must be removed. An existing chimney may require cleaning.
• Chimney or vent must extend at least 3 feet above its passage through a roof and at least 2 feet above any ridge within 10 feet of the chimney. (Local codes apply.)
• Minimum clearance from the vent connector to combus­tible material is 6 inches unless the combustible materials are protected in accordance with applicable codes. The recommended vent system for the GTS-400, 200 and 100 humidifiers is constructed of Type C single wall vent pipe (UL or CUL listed). Type C vent requires varying
levels of insulation when penetrating a combustible wall depending on vent temperatures.
• This humidifier must not be connected to a chimney flue servicing a separate appliance designed to burn solid fuel.
• Never connect this humidifier to a chimney serving a fireplace, unless the fireplace opening is permanently sealed off.
• The recommended vent system for the GTS-300, 150, and 75 humidifier is constructed of Type B double-wall vent pipe (UL or CUL listed). Type B vent is rated for 400°F plus ambient temperature. A minimum 1-inch clearance is required between Type B vent and combus­tible materials. Field expertise has shown that venting through a properly sized Type B vent significantly reduces the occurrence of vent condensation.
• It may be necessary to add insulation to Type B double­wall vent and to single-wall vent connector, if allowed by local codes, in some applications. When insulation is required, it must be at least 1-inch thick fiberglass with foil backing. Using permanent foil tape, attach insulation to vent pipe. Both the foil tape and fiberglass insulation must be suitable for temperatures up to 450°F.
• Insulation must be added to any vent connector which will be exposed to ambient temperatures of 30°F or less, especially any application using single-wall vent pipe as a connector.
• Do not insulate vent pipe exposed to outdoor weather conditions (i.e. above roof lines).
• Venting into an unlined masonry or concrete chimney is prohibited by code.
• If this humidifier is connected to a lined, masonry chimney, the chimney must be sized and installed accord­ing to the provisions of the National Fuel Gas Code, or Canadian CAN/CGA.B149 requirements. Vent connectors from the humidifier to the chimney should be made with insulated Type C single-wall vent pipe or Type B vent pipe for GTS-300, 150, and 75. The GTS-400, 200 and 100 is approved for single wall vent only.
• Installation of the vent pipe should be as directly as possible, with a minimum number of turns or elbows.
• Rigidly support the vent pipe every 5 feet or less with hangers or straps to ensure that there will be no move­ment after installation. The humidifier vent box should not be supporting the weight of the vent piping.
11
Loading...
+ 25 hidden pages