DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
ii
Page 3
Before you begin
Electrical warning label
Location: Front door and electrical
access door
Defi nition: Electrical shock hazard
Important:
This equipment is for use with the
following appliance categories.
Contact your distributor before
converting to another group or supply
pressure.
Table 1-1:
Appliance categories
I2H G20 at 20 mbar
I2E G20 at 20/25 mbar
I
G20/G25 at 20/25 mbar
2E+
I2L G25 at 25 mbar
I
3+(28-30/37)
G31 Propane at 37 mbar
I
3B/P(30)
G31 Propane at 30 mbar
I
3B/P(37)
G31 Propane at 37 mbar
I
3B/P(50)
G31 Propane at 50 mbar
I
3P(30)
I
3P(37)
I
3P(50)
G30 Butane at 28-30 mbar and
G30 Butane and
G30 Butane and
G30 Butane and
G31 Propane at 30 mbar
G31 Propane at 37 mbar
G31 Propane at 50 mbar
An input derate exists when operating
GTS humidifi ers at a high altitude.
Table 1-2:
Input derate for high altitude
Altitude (meters)Input derate %
0 – 6100
611 – 7652
766 – 9154
916 – 10656
1066 – 12208
1221 – 137010
1371 – 152512
1526 – 167514
1676 – 183016
1831 – 198018
1981 – 213520
2136 – 228522
2286 – 244024
2441 – 259026
2591 – 274328
2744 – 289530
2896 – 304832
3049 – 320034
3201 – 335236
3353 – 350538
3506 – 365740
This equipment has been tested by
Intertek to the Low Voltage, Gas
Appliance, and EMC directives and
has been certifi ed by Certigaz for use
in all EU countries.
GTS humidifi ers bearing the CE
mark are authorized for use in the
European countries listed below.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
3P-G31-30 mbar
3P-G31-37 mbar
3P-G31-50 mbar
Average
fl ue
temperature
at 100%
demand
Minimum
draught
requirement
Mass fl ow
rate of
combustion
products
1
Page 4
Safeguards
The GTS humidifi er has a number of safeguards to ensure proper operation:
• When there is a call for humidity, all of the combustion blowers must start. Each combustion
blower sends a signal to the microprocessor relaying its speed. If the speed is outside an
acceptable range, the GTS will not operate.
• The negative-pressure gas valves used on the GTS humidifi er are designed to keep a constant
ratio of air and gas throughout the operating range of the blower. If the blower fails to run, the
GTS humidifi er will shut down due to a blower fault.
• If the fl ue becomes blocked, the blocked fl ue sensor will shut down the humidifi er.
• During operation, the water level in the tank is monitored by a probe system for
tap/softened water humidifi ers and by a low water fl oat switch for humidifi ers with the RO/DI
water option (see Figure 3-1).
These water level monitors tie into the Vapor-logic controller. If the water level drops below a
safe point, the controller turns the burners off and tries to fi ll the tank. If unable to fi ll the tank
within a defi ned time period, an “Excessive refi ll time” alarm appears in the Vapor-logic Alarm
Log. The burners remain off until this alarm is cleared.
• In tap/softened water applications, the water level in the tank is also monitored by a redundant
low-water system that operates independently of the Vapor-logic controller. This system is tied
directly into the power source for the gas valves. If this system detects a low water condition,
the humidifi er shuts down until water is present. A “GTS low water alarm” will be active while
the condition exists.
• There is a temperature sensor near the top of the heat exchanger. If the water level drops too
low and both the main and redundant low water sensors fail to detect it, the temperature sensor
shuts down the humidifi er to prevent an unsafe condition.
• There is a limit-control thermal trip next to the temperature sensor. This thermal trip operates
independently from the Vapor-logic controller. If the water level drops below the heat
exchanger, the thermal trip will directly shut down the gas valves. The thermal trip has a red
button that must be manually reset before the burners are able to fi re again.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
2
Page 5
Product overview
FIGURE 3-1: GTS HUMIDIFIER COMPONENTS AND WATER LEVEL CONTROL TYPES
DI/RO water optionTap/softened water
Humidifi ers using tap or softened water control water levels
electronically using a three-rod probe. A redundant probe is used
as a safety device.
Humidifi ers with the RO/DI water option control water level using a
fl oat valve. A low-water cutoff switch and a redundant low-water cutoff
switch are used as safety devices.
Fill valve closes when water level
rises to this probe.
Fill valve opens when water level
is below this probe.
Controller disables burner if water level
drops below this probe.
Water level probe
(Float-operated low water cutoff switch
if DI/RO water option)
Overflow outlet
Thermal trip
Temperature sensor
Fill valve
Float
Heat exchanger
Steam hose or tubing
Steam outlet
Redundant probe
(Redundant low water cutoff switch
if DI/RO water option)
Flue connection
Blower
Gas valve
Water tempering device
OM-1247
Subpanel/control components
Supply water line
Drain valve
Drain piping
Air gap
Open drain
Tap/softened water
GTS humidifier shown
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
3
Page 6
Finding a location
WARNING
Installation requirements:
Installation must conform to the requirements of local and national directives and regulations for the installation of
gas-fi red equipment.
The humidifi er must be installed by a qualifi ed technician and meet the requirements of all governing codes.
Failure to follow these instructions could cause severe bodily injury or death.
• Provide a level, solid foundation for the humidifi er.
• Locate the humidifi er as near as possible to a chimney or outside wall so that the fl ue pipe from the humidifi er is
short and direct.
• Install the humidifi er where its electrical components are protected from water during operation and service.
• Install the humidifi er in a location away (and protected) from drafts. If installed in a separate room, follow the
instructions concerning combustion and ventilation air.
• Install the humidifi er in an area where leakage from the tank or its connections will not result in damage to the
adjacent structure or to lower fl oors of the structure. When such locations cannot be avoided, install a suitable drain
pan (adequately drained) under the humidifi er. The pan must not restrict combustion airfl ow.
• If located in an insulated space, keep the humidifi er free and clear of insulating materials. Insulating material can be
combustible. Inspect the humidifi er area when the humidifi er is installed or when insulation is added.
FIGURE 4-1: CLEARANCE RECOMMENDATIONS
460 mm
75 mm
760 mm
OM-1222a
Front door:
Burner, blower, gas valve, and plumbing access
• DriSteem recommends 25 mm minimum clearance between back
panel and combustible surfaces.
• These clearance recommendations are provided to provide access
and to prevent property damage from heat. To further safeguard
property, protect heat-sensitive walls and surfaces (wood, plastic,
etc.) with suitable insulation.
Back panel:
No ventilation
louvers
920 mm
Side door:
Electrical access
FIGURE 4-2: OUTDOOR ENCLOSURE RECOMMENDATIONS
Flue piping
Vertical section of fl ue must be at least 1.5 meters or meet all governing
codes, whichever is longer. DriSteem recommends installing a high-wind
vent cap on all GTS humidifi ers.
Clearance required behind outdoor
enclosure for steam outlet
Vent cap
GTS humidifi er
back panel
Outdoor enclosure
back wall
OM-1228LWa
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
4
Page 7
Wiring and supply water piping requirements
WIRING
WARNING
Installation must meet the requirements of governing codes or, in the absence of governing codes, in accordance
with IEE wiring regulations (BS7671). Failure to follow these instructions could cause a fire, resulting in severe
bodily injury, death, or significant property damage.
Follow the instructions below for GTS humidifi er wiring:
• Use only copper wire.
• GTS humidifi ers must be supplied with 230 Vac, 50 Hz, separately fused electrical service.
• The electrical subpanel must have an uninterrupted earth ground to minimize personal injury if an electrical fault
should occur. Install in accordance with existing electrical codes.
• Do not use gas piping as an electrical earth ground.
• All electrical components and wiring must be protected from mechanical damage and water.
• Check the electric current characteristics and capacity requirements against the nameplate. All wiring must be in
accordance with the governing codes listed above and with the GTS wiring diagrams.
SUPPLY WATER PIPING REQUIREMENTS FOR ALL WATER TYPES
Follow the GTS humidifi er supply water piping instructions below for all water types. Install supply water piping in
accordance with locally applicable installation regulations.
• Provide a shutoff valve and union in the supply water line to isolate the humidifi er from the water system while
servicing.
• To minimize electrolytic corrosion, install insulating unions to make connections between copper and other dissimilar
metal fi ttings, such as galvanized steel.
• Humidifi er tank must be full of water — and supply water free to fl ow into the tank — before the ignition sequence
of a newly installed humidifi er is initiated.
• If planning to use heated supply water, disconnect the supply water line from the water tempering device fi ll
manifold/tee. Install a pipe plug in the manifold/tee, and reconnect the water tempering device line to a cold water
supply.
• The supply water pressure range must be 172 kPa minimum with fi ll valve open to 552 kPa maximum with fi ll valve
closed. When using nonmetallic tubing for supply water, it must be rated for 100 °C minimum continuous operating
temperature. DriSteem recommends installing a 1 m piece of noninsulated stainless steel pipe directly off the
humidifi er prior to connecting to the nonmetallic tubing.
• Before connecting piping to the GTS humidifi er, thoroughly fl ush the supply water piping to prevent pipe residue
and stagnant water from getting into the humidifi er tank.
General supply water piping information:
• The end-of-season feature shuts off the supply water and drains the tank when there is no demand for humidity for
72 hours. This is a default setting and is user-adjustable.
• The humidifi er has a 25-mm internal air gap to prevent back siphoning into a potable water system. Some
governing codes may require additional protection, such as a vacuum breaker or backfl ow preventer.
• The supply water assembly has a DN10 pipe thread connection.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
5
Page 8
Supply water piping
TAP/SOFTENED WATER
The primary component of the supply water assembly is a solenoid valve,
which may cause noise during fi ll cycles.
During a fi ll cycle, cold supply water drops the internal tank temperature and
may collapse the boil, which can cause a low rolling sound. To minimize this,
use hot supply water.
In cases where water hammer occurs when the fi ll solenoid closes, a shock
arrester is recommended. Reducing the supply water pressure (minimum
172 kPa with fi ll valve open) or using fl exible tubing (rated for 100 °C
minimum continuous operating temperature) may diminish the noise.
The minimum water conductivity for the GTS tap/softened water model
is 30 µS/cm.
RO/DI WATER OPTION
The water level in GTS humidifi ers with the RO/DI water option is controlled
with a fl oat valve. For models with the end-of-season drain option, a solenoid
valve is installed prior to the fl oat valve.
When using nonmetallic tubing, DriSteem recommends the installer place a
50-mm water seal/loop in the supply water line to isolate steam during RO/DI
water system maintenance.
DriSteem highly recommends installing a strainer in the supply water line
to prevent clogging of the solenoid valve or fl oat valve orifi ce. The strainer
prevents particulate from collecting at the solenoid valve seat.
To minimize RO/DI water waste, disconnect factory piping to the water
tempering device and pipe directly to a tap water source.
WARNING
Fire hazard if using tap/softened supply water with RO/DI water option:
If a GTS humidifier with the RO/DI water option is supplied with
tap/softened fill water, the float valve assembly will become clogged,
and particulate will accumulate on the low water cutoff switch (float
switch). This will cause failure of a critical safety circuit and the potential
for a dry tank fire, which can cause severe property damage, severe
personal injury, or death.
SUPPLY WATER FLOW RATES
The rate of supply water fl ow into the GTS humidifi er tank is determined by the
supply water pressure and the inlet valve. See Table 6-2.
SUPPLY WATER GUIDELINES
Supply water quality is an important
component of humidifier reliability and
maintenance.
Examples:
• Corrosive water can decrease the
service life of the humidifier.
• Excessive water hardness can
increase the humidifier maintenance
requirements.
To maximize humidifier service life
and minimize humidifier maintenance,
DriSteem has established guidelines for
supply water See Table 6-1.
Table 6-1:
DriSteem supply water guidelines
Chlorides*
RO or DI water
Softened water
Tap water
* Damage caused by
chloride corrosion is
not covered by your
DriSteem warranty.
Total hardness
Tap water< 500 ppm
pH
RO, DI, or softened
water
Tap water
Silica< 15 ppm
You may wish to take action to mitigate
potential negative effects to your
humidifi er. Supply water outside of these
guidelines may void your DriSteem
warranty. Please contact your DriSteem
distributor if you need advice.
< 5 ppm
< 25 ppm
< 50 ppm
7 to 8
6.5 to 8.5
Table 6-2:
Supply water flow rates (liters per minute)
Supply
water
pressure
200 kPa7.26.717.0
350 kPa9.08.822.5
450 kPa10.29.925.4
550 kPa11.110.827.6
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
6
Solenoid valve fl ow rates
(tap/softened water)
mc_071912_1545
Float valve fl ow rates (RO/DI water)
Models 100 – 400Models 500 – 800
Page 9
Drain piping
The drain line piped from the humidifi er must be run to an approved sanitary waste or suitable drain. Although the GTS
humidifi er is equipped with integral water tempering, if nonmetallic drain pipe or hose is used, DriSteem recommends it
be rated for 100 °C minimum continuous operating temperature.
• Minimum drain pipe size is DN40 inside diameter. Do not reduce the size of the drain piping. If the length of the
drain piping exceeds 3 m, increase the pipe size. If combining multiple drain lines, ensure proper common pipe
sizing practices are used.
• Do not install the humidifi er directly above a fl oor drain — skim and drain water dumped into the drain will cause
fl ash steam, which will rise and saturate electrical components, adversely affecting their life and performance.
• An open drain with a 25-mm air gap between the drain piping and the drain is required. Locate the air gap only
in spaces with adequate temperature and air movement to absorb fl ash steam; otherwise, condensing on nearby
surfaces may occur.
• Drain piping downstream from the water seal must be pitched a minimum of 1% toward the drain. Governing codes
may require more pitch.
• If the proximity of a drain requires the humidifi er drain and skim water to be lifted, use a water pump with capacity
of at least 45.4 liters per minute. A check valve is required on the discharge of the pump. Electrical power for the
pump is independent of the humidifi er.
• The GTS humidifi er has an auxiliary DN40 drain outlet below the subpanel. This drain outlet can be hard-piped
during installation to enable rapid tank draining before maintenance. Next to this outlet is a cleanout plate that
provides access for removing scale from the tank bottom.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
7
Page 10
Gas piping
Important:
The required supply pressure is 20 or 25 mbar for natural gas and 30, 37, or 50 mbar for propane gas.
WARNING
Fire hazard:
Supply the humidifi er only with the gas type (natural gas or LP gas) listed on the humidifi er name plate. Failure
to supply the humidifi er with the listed gas type could result in burner failure or a fi re, causing property damage,
personal injury, or death.
Follow the GTS humidifi er gas piping instructions below. Conform to local and national directives and regulations for the
installation of gas-fi red equipment.
• After threading and reaming ends of pipes, inspect piping and remove loose dirt and chips.
• Support piping so there are no strains imposed on humidifi er or controls.
• Use two wrenches when connecting piping to humidifi er or controls.
• Provide a drip leg before each humidifi er and in the line where low spots cannot be avoided.
• Take-off to humidifi er should come from top or side of main to avoid trapping condensate.
• Piping that is subject to wide temperature variations should be insulated.
• Pitch piping up toward humidifi er at least 6 mm per 4.5 m of horizontal run.
• Compounds used on threaded joints of gas piping must be resistant to the harmful action of liquefi ed petroleum
gases.
• Install a ground joint union and a manual shutoff valve immediately upstream of the humidifi er.
• Do not use fl exible connectors.
• Allow at least 1.5 m of piping between any high pressure regulator and humidifi er pipe connection.
• Piping installation must conform to the requirements of the authority having jurisdiction or, in the absence of
such requirements, must conform to local and national directives and regulations for the installation of gas-fi red
equipment.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
8
Page 11
Gas piping
• When the specifi c gravity of the gas is other than 0.60 for natural gas or 1.53 for propane, refer to Table 9-1.
• Piping to GTS humidifi ers should conform with local and national requirements for type, volume, and gas handled
and for pressure drop allowed in the line. Refer to the tables on this page to determine the gas fl ow in m3/hr for the
type of gas and size of humidifi er to install. Using this value and the length of pipe necessary, determine the pipe
diameter.
Where several GTS humidifi ers are served by the same main, the total capacity, gas fl ow, and length of main must
be considered. Avoid pipe sizes smaller than DN15. Table 9-2 allows for the usual number of fi ttings with a 0.7
mbar pressure drop.
WARNING
Fire or explosion hazard:
Purge air before lighting humidifi er burners by disconnecting piping at gas control. In no case should line be
purged into heat exchanger. Failure to follow these instructions could cause a fi re or explosion, resulting in bodily
injury, death, or signifi cant property damage.
Gas pressure test gauge
Install a DN6 plugged tapping, accessible for test gauge connection, immediately upstream of the gas supply
connection to the appliance. Use this tap to check pressure with all burners running.
Leak testing
After installation, check fi eld piping and humidifi er gas train for gas leaks.
• Do not use soap solution or open fl ame on humidifi er gas train. A gas leak detector is recommended.
• When leak-testing the gas supply piping system, isolate the humidifi er from the gas supply piping system by closing
its fi eld-installed manual shutoff valve whenever pressure is greater than 60 mbar.
Table 9-1:
Specific gravity conversion factors
Natural gas
Specifi c gravityFactor
0.551.04
0.601.00
0.650.962
Propane gas
Specifi c gravityFactor
1.500.633
1.530.626
1.600.612
Note: Use the above multiplying factor with
Table: 9-2 when the specifi c gravity of
gas is other than 0.60 (natural gas) or
1.53 (propane).
Table 9-2:
Gas pipe capacities for gas pressures of 3.45 kPa or less
Gas fl ow in piping in m3/hr at pressure drop of 0.07 kPa
Length of pipe
DN15DN20DN25DN32DN40
mm
33.77.914.729.745.3
62.65.49.920.731.1
92.14.38.116.725.2
121.83.76.9 14.221.5
151.63.36.112.519.0
181.43.05.511.317.3
211.32.75.110.515.9
241.22.54.89.915.0
271.12.44.59.113.9
301.12.24.28.613.0
3
/hrm3/hrm3/hrm3/hrm3/hr
Nominal iron pipe diameter in inches (DN)
Specifi c gravity = 0.60
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
9
Page 12
Combustion and ventilation air
The GTS humidifi er supports both room air and sealed combustion.
• Do not install the humidifi er in a dusty environment.
• When the GTS humidifi er is installed in an environment with negative pressure or toxic air, it must have sealed
combustion.
ROOM AIR COMBUSTION
WARNING
Air for combustion:
Air for combustion must not be contaminated by halogen compounds, which include fl uoride, chloride, bromide,
and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
Failure to follow these instructions could cause severe bodily injury or death.
• All fuel-burning equipment must be supplied with air for combustion. Suffi cient air must be provided to ensure there
is not a negative pressure in the equipment room or space.
• Do not block or obstruct air openings on the appliance, spaces around the appliance, or air openings to the
appliance area.
• Do not block the fl ow of combustion and ventilation air. To provide necessary oxygen for proper combustion,
openings must be provided to allow outside air to enter the space where the humidifi er is located. Enclosed spaces,
such as equipment rooms, must be vented for combustion air. The size of air openings must be based on all gasburning equipment installed in the space. Table 10-1 outlines four types of locations, and the requirements of each.
Table 10-1:
Location of humidifier and required air openings
Location descriptionRequired air opening
Confi ned space with all air from inside the building; conventional frame, brick or
stone construction with normal infi ltration
Note: this location rarely provides enough air for higher-capacity humidifi ers.
Confi ned space with all air from outside the building through air ductsTwo openings, 2 ducts, 6.5 cm
Confi ned space with all air from outside the building from through-wall openings
only (no ducts)
Unconfi ned space with all air from outside the buildingSame as confi ned space; all air from outside the building
* The minimum dimension of any opening is 76 mm × 76 mm.
Two openings, 6.5 cm
The minimum free area of all openings combined is 645 cm2.
input*
Two openings, 6.5 cm
2
per opening per 293 W input
2
per opening per 586 W
2
per opening per 1172 W input*
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
10
Page 13
Combustion and ventilation air
SEALED COMBUSTION
WARNING
Requirement for manifolding sealed combustion piping runs:
When installing sealed-combustion piping for more than one GTS humidifi er, do not commonly manifold multiple
sealed combustion piping runs without having the manifold sized for the specifi c installation by a licensed
engineer. Failure to follow these instructions could starve the GTS humidifi er of combustion air resulting in either
the burners not being able to light or high carbon monoxide levels, which may cause severe personal injury or
death.
The GTS humidifi er supports sealed combustion using DN100 PVC or CPVC piping. All GTS models have a single-point
connection to the blower inside the front door. See Figure 11-3.
When running PVC or CPVC piping for sealed combustion, the maximum allowable distance to the outdoor air source is
21.3 m including 2.1 m equivalent length for each elbow. The outside air source opening must be covered with a large
mesh screen to prevent the introduction of unwanted materials without restricting airfl ow.
If sealed combustion piping is less than 6 m in length, DriSteem recommends insulating the piping to prevent
condensation.
SEALED COMBUSTION OR OUTDOOR ENCLOSURE
To ensure a supply of clean, fresh air, the GTS humidifi er combustion air must be at least 3 m away from any
mechanical exhaust outlet.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
11
Page 14
Venting
GENERAL VENTING GUIDELINES
WARNING
Installation requirements:
The humidifi er must be installed by a qualifi ed technician and meet the requirements of all governing codes.
Failure to follow these instructions could cause severe bodily injury or death.
• The GTS humidifi er is a Fan Assisted Category I
(natural draft) Appliance. It is a Class B23 appliance,
without a draught diverter, with a combustion
air blower upstream of the heat exchanger. A
GTS humidifi er with the sealed combustion option is
a Class C53 appliance. Installations where the vent
terminates in a side wall of the building, or where the
overall horizontal run exceeds the overall vertical run,
require a power venter.
• Maximum fl ue temperature under normal operating
conditions is 205 °C plus ambient.
• Maximum abnormal-operation fl ue temperature is
348 °C plus ambient.
• Flue draft negative pressure greater than 50 Pa may
cause unacceptable post ignition.
• Vent piping must be approved for a Category I
appliance. Do not use more than one type of venting
per application.
• Vent terminal must be at least 1 m above any forced
air inlet located within 3 m.
• Do not use vent equipment from more than one
manufacturer.
• When connecting the humidifi er to a gas vent or
chimney, installation must conform to:
– Local and national directives and regulations for
the installation of gas-fi red equipment
– Governing and building codes
– Vent manufacturer’s instructions
• When applying the codes, see also the venting
manufacturer's instructions, the service gas supplier's
regulations, and the specifi c instructions provided in
this manual.
• Inspect for proper and tight construction. Remove any
restrictions or obstructions. An existing chimney may
require cleaning.
• Do not connect this humidifi er to a chimney fl ue
servicing a separate appliance designed to burn solid
fuel.
• Never connect this humidifi er to a chimney serving a
fi replace, unless the fi replace opening is permanently
sealed off.
• Code prohibits venting into an unlined masonry
or concrete chimney. If the humidifi er is connected
to a lined, masonry chimney, the chimney must be
sized and installed according to the provisions of the
governing codes.
• Vent connector serving this appliance shall not be
connected into any portion of mechanical draft
systems operating under positive pressure.
• Add insulation to any roof or wall penetration vent
connector that is exposed to ambient temperatures of
0 °C or less, especially any application using singlewall vent pipe as a connector.
• Do not insulate vent pipe exposed to outdoor weather
conditions (e.g., above roof lines).
• Install vent piping as straight as possible, with a
minimum number of turns or elbows.
• Maintain a minimum upward slope of 2% on all
horizontal runs.
• Rigidly support the vent pipe every 1.5 m or less with
hangers or straps to ensure there is no movement after
installation. The humidifi er vent box should not support
the weight of the vent piping.
• No portion of the vent system should extend into, or
pass through, any circulation air duct or plenum.
• Install and fi re-stop all vent pipe passing through
fl oors, ceilings, and walls with the proper clearances
from combustible material according to local and
national directives and regulations for the installation
of gas-fi red equipment.
• In replacement installation where an existing vent
system may be used, inspect the vent system for
condition, size, type of vent material, and height to
meet the requirements in these instructions.
CAUTION
Flue condensate removal
Install a drip leg or fl ue box condensate drain for startup fl ue condensate removal. Failure to follow these
instructions could cause water to accumulate in the
fl ue box.
OUTDOOR ENCLOSURE VENTING
The vertical section of fl ue must be at least 1.5 meters or
meet all governing codes, whichever is longer. DriSteem
recommends a drip tee directly after the factory-supplied vent
connection. DriSteem recommends a high-wind vent cap on
all GTS humidifi ers. See Figure 4-2.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
12
Page 15
Venting
VERTICAL VENTING REQUIREMENTS
• Do not reduce the vent diameter.
• If turns are required in the vent piping, make
sweeping bends; avoid small-radius turns.
• Use the same size stack as the vent furnished with the
humidifi er.
• Maintain proper support of vent connections and
joints.
• Observe clearances (in accordance with applicable
codes) from all combustible materials and install an
approved cap for the stack outlet.
• The bottom of the cap must be one stack diameter
above the top of the stack.
• Extend chimney or vent at least 1 m above its passage
through a roof and at least 0.6 m above any ridge
within 3 m of the chimney (governing codes apply).
• The vent system must terminate above the roof surface
per the local and national directives and regulations
for the installation of gas-fi red equipment. DriSteem
recommends installing a high-wind vent cap on all
GTS humidifi ers.
• This humidifi er may be commonly vented with other
listed Category I gas-fi red appliances. Total input rates
of all appliances determines the vent size.
HORIZONTAL VENTING REQUIREMENTS
• Contact your DriSteem distributor for all horizontal
venting parts.
• Ensure that distances from vent terminal to adjacent
public walkways, buildings, and openable windows
and building openings are consistent with local and
national directives and regulations for the installation
of gas-fi red equipment.
• In areas accessible to the public, vent terminal must
be at least 2.1 m above ground level to prevent burns
from hot terminal surface.
• The vent terminal and air intake locations must be
at suffi cient height above ground level to prevent
blocking by expected snowfall.
• Maintain minimum horizontal clearance of 1.2 m
from electric meters, gas meters, regulators, and relief
equipment.
• Building materials must be protected from degradation
by fl ue gases.
• Vent box pressure must be –2.5 Pa. Set by adjusting
power venter and barometric damper with all burners
running (see manufacturer's instructions included with
power venter and damper).
WARNING
Horizontal venting with a vertical termination:
For applications where the vent pipe terminates in
a vertical position, the horizontal length must not
exceed the height of the vent unless a power venter
is used. Failure to follow these instructions could
cause fl ue gases to exit the vent piping, causing
severe personal injury or death.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
13
Page 16
Operation
START-UP CHECKLIST
After the system is installed and connected to gas, electrical, water supplies, and controls, check the following items:
☐ Verify that the GTS humidifi er, controls, piping, electrical connections, steam supply, and dispersion units are
installed according to the following:
• Installation instructions in this manual
• Vapor-logic version 5 Installation and Operation Manual (shipped with the humidifi er)
– Installation section
– Installation checklist
• Verify that the gas type supplied to the humidifi er matches the humidifi er nameplate label.
• Verify that all fi eld-installed and humidifi er gas piping has been tested for leaks.
Note: Soap and water are not recommended for leak testing. See “Leak testing” on page 9.
☐Piping (steam, drain, supply water)
Verify that all piping connections have been completed as recommended and that water pressure is available.
☐Electrical
Verify that all wiring connections have been made in accordance with all governing codes and the GTS wiring
diagrams.
☐Control wiring
Verify that all control wiring has been completed as specifi ed and required for correct and safe operation of the
GTS humidifi er.
☐Tank
Verify that the humidifi er tank is:
• Securely installed and level before fi lling with water.
• Level from front to back and from side to side after it is full of water.
START-UP
WARNING
Only qualifi ed electrical and gas personnel should perform start-up.
Refer to the Vapor-logic version 5 Installation and Operation Manual for
details about commissioning, menu navigation, fi rmware updates, humidifi er
troubleshooting, and more.
During start-up and operation, the humidifi er operating status appears on
the Vapor-logic keypad/display Home screen (Figure 14-1). Do not leave
the humidifi er unattended during initial start-up; monitor operation through
multiple fi ll cycles.
To change Mode or Set point:
1. Press Up or Down arrow to highlight Set point or Mode, then press Enter
to confi rm selection.
2. Press Up or Down arrow to increase or decrease highlighted value, then
press Enter to confi rm.
Note: For example, to create a call for humidity, increase SET PT to an RH
that is higher than the displayed SPACE RH.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
14
FIGURE 14-1: HOME SCREEN
Press this softkey
to access Status,
Diagnostics,
Alarms, and Setup.
Press arrow keys
to navigate or to
change values.
Press Enter to
confi rm selections.
Mode and set point can be changed from the
Home screen. Other parameters displayed here
can be changed in the Setup menu.
Page 17
Maintenance
COOL-DOWN PROCEDURE
Before performing these maintenance procedures, allow
the tank to cool down as described here.
NOTE: Insulated and uninsulated tanks will have hot
surfaces.
Verify that there is no call for humidity and that the
aquastat set point (adjusted using the keypad/display
Setup screens) is less than room temperature (default
setting is 4 °C) so the burners do not energize.
• GTS models with RO/DI water option and a ball valve
drain:
1. Manually open the ball valve, and allow
approximately half of the water to drain out of the
tank.
The fl oat valve opens after the water level in the
tank begins to drop.
2. Let the fi ll water run until the tank is cooled; then
shut off the fi eld-installed manual supply water shutoff valve.
3. Let the tank drain; then manually close the drain
valve.
• GTS models with tap/softened water and any model
with end-of-season drain:
1. From the Main menu, enter the Tank Status
submenu.
2. Change mode to Drain, and allow approximately
half the water to drain out of the tank.
3. Change the mode back to Auto; the fi ll valve opens
and the humidifi er cools down.
4. When the fi ll valve closes, go back into Drain
mode, and allow the tank to drain completely. The
humidifi er should be cool enough to work on.
WARNING
Shutdown procedure:
To prevent severe personal injury or death from
electrical shock, fi re, or explosion, follow this
shutdown procedure before performing the
following service or maintenance procedures on this
humidifi er.
1. Use Vapor-logic keypad/display, change the
control mode to Standby.
2. Place all power disconnects in OFF position and
lock in OFF position.
3. Close fi eld-installed manual supply water shut-off
valve.
4. Close gas shut-off valves.
INSPECTION AND MAINTENANCE
1. Annually (also recommended when maintenance is
performed)
• Inspect tank, piping, and gaskets for water and
gas leaks.
• All safety devices in the control circuit should be
cycled on and off to verify they are functioning.
These include:
– High limit switch
– Airfl ow proving switch
• Tap/softened water humidifi ers only:
– Low water level probe. Pull out probe plug; fi ll
valve should energize.
– Redundant low water level probe
• Humidifi ers with the RO/DI water option only:
– Verify that the fl oat valve is closing off. If the
fl oat valve will not shut off, there may be
particulate on the valve seat, or the seat may
be worn and in need of replacement.
– NOTE: As long as mineral-free water is used
in the GTS, no cleaning or fl ushing of the
humidifi er should be necessary.
2. Seasonally (or as required, depending on water
quality)
Tap/softened water humidifi ers only:
• Clean tank:
– Remove cleanout plate, and dispose of any
loose scale that has collected in the tank.
Do this before the scale buildup reaches the
bottom of the heat exchanger.
– Inspect the area inside the tank in front of the
drain valve fi tting, and thoroughly clean all
scale and mineral buildup from that area.
• Dismantle and clean drain valve and associated
piping.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
15
Page 18
Maintenance
Seasonally (continued)
• Clean the probes
– Access the probe assembly either from the
electrical panel or by removing the roof panel
above the electrical area.
– Disconnect the probe plug and cable assembly,
and unscrew the probe rod assembly from the
humidifi er probe housing.
– Clean the probe housing, ensuring that all the
housing passageways are clear. Remove the
housing from the tank by removing the cover
plate from the tank.
Note: The scale should fl ake off easily from the
probe assembly rods.
– The bottom 10 mm of each rod is the sensing
portion; clean these areas with a wire brush,
emery cloth, or steel wool.
– Inspect the composite plastic probe rod
assembly for any signs of cracking, roughness,
or deterioration. If found, replace probe
assembly.
– Reassemble the probe assembly.
• Clean the skim/overfl ow port
– Water should drain from the skimmer drain
pipe after each fi ll cycle. This should be verifi ed
visually by a weekly inspection.
– Loosen deposits in and around the skimmer/
overfl ow port with a screwdriver or similar tool.
– If fl ow through the water seal/P-trap is
diminished due to mineral accumulation:
- Remove the water seal piping from the
humidifi er, and fl ush it out.
- Replace the water seal with new piping if the
minerals have hardened in the water seal.
• Clean the low water cutout probe:
Remove the electrical access panel, and inspect the
probe rod for mineral accumulation. The probe rod
is located on the top of the tank near the back. Use
a wire brush, emery cloth, or steel wool to clean
the probe rod.
• Inspect blower motor. Lubrication is not required.
• Remove dust with a vacuum:
Remove all dust from areas around the motor, vent
fan(s), and louvers that allow air to the shrouded
area.
• When the maintenance requirements are complete:
– Replace cleanout plate, and tighten the nuts.
Torque nuts to 25 to 35 in-lb (2.8 to 4.0 N-m).
– Verify that the probe rod holder is secure and
that the probe plug and cable assembly are
plugged into the probe rod holder.
– Verify that the drain valve assembly is in the
closed position.
– Replace and secure all covers and doors.
– Turn on water supply.
– Turn on electrical power.
– Turn on gas.
– Do not leave humidifi er unattended. Allow
humidifi er to cycle through multiple fi ll cycles,
and verify that humidifi er cover, cleanout plate,
and probe holder gasket are not leaking.
3. Off-season maintenance
• Tap/softened water humidifi ers:
Inspect and clean the following:
– Probe rods
– Skimmer port and water seal
– Humidifi er tank and gaskets
– Heat exchanger
After cleaning, the humidifi er should remain empty
until humidifi cation is required.
• Humidifi ers with the RO/DI water option:
Inspect the following:
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
16
Page 19
Inspection recommendations
RO/DI WATER QUALITY RECOMMENDATIONS
• Verify regularly that water processing equipment is operating correctly. The presence of chlorides in improperly
processed DI water can cause pitting and failure of the tank and heat exchanger.
• GTS humidifi ers with the RO/DI water option do not require regular cleaning, although regular inspections are
advised.
• GTS humidifi ers with the RO/DI water option do not require skimming or draining and fl ushing to remove
precipitated minerals. However, at the end of a humidifi cation season, drain the humidifi er either by manually
opening the drain valve. If the humidifi er was purchased with end-of-season drain, it is already programmed to
drain.
INSPECTION INTERVALS
• By the user every 30 days.
• Appliance system inspected once a year by a qualifi ed service person.
INSPECTION ITEMS
• Proper fi eld operation of burner. Measure CO ppm, CO2%, O2%, fl ue temperature, and burner effi ciency at 100%
demand with the tank at a boil. Verify that measurements are within the guidelines described in burner tuning.
• Burner fl ame is blue or orange in color — up to 6 mm from the surface of the burner.
WARNING
Shutdown procedure:
Perform the shutdown procedure on page 15 before proceeding.
• Inspect fl ue passageways external to the appliance, such as vent connector and chimney. Make sure they are clear
and free of obstructions.
• Ensure that vent connector is in place, sloping upward, and physically sound without holes or excessive corrosion.
• Ensure that physical support of the humidifi er is sound without sagging, cracks, or gaps between fl oor stand or tank
fl anges.
• Ensure that there are no obvious signs of deterioration of the humidifi er.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
17
Page 20
Inspection recommendations
BURNER ASSEMBLIES AND HEAT EXCHANGER TUBES
This is not a regular maintenance item, but if the heat exchanger tubes contain carbon deposits, soot, or other residue,
clean as follows:
1. Follow shutdown procedure on page 15.
2. Remove front door of humidifier.
3. Disconnect wiring to blowers, flame sensors, gas valves, and ignition controllers. Remove burner assemblies (each
assembly is mounted with four bolts).
4. Remove vent box.
5. Use a 150 mm flue brush with a 600 mm extension and reversible drill. Work brush in and out of all combustion
chambers.
NOTE: To ease reassembly, disconnect components from one burner assembly at a time, and clean each
corresponding combustion chamber individually.
6. Remove loose deposits and residue that falls into rear header with vacuum cleaner and hose extension.
7. Inspect DN40 return tubes. Clean if necessary.
8. Run thin brush between turbulator and tube wall on all four sides.
9. Reinstall burner assemblies and gaskets, vent box and gasket, all electrical wiring, humidifier front door, and
pressure switch connections.
BURNER MAINTENANCE FREQUENCY
Under normal use conditions, the burner(s) should not need cleaning for a minimum of fi ve years. However, depending
on the operating environment, the burner(s) may require periodic cleaning to remove accumulated materials. Failure
to clean burners can result in reduced humidifi er capacity. Use sealed combustion in dirty environments. See burner
maintenance instructions below.
BURNER MAINTENANCE INSTRUCTIONS
To service the burner assembly, clean both the blower and the burner. Remove the blower(s) from the system, and clean
dust from the wheel.
Remove the burner(s) for cleaning.
Removing and cleaning one burner at a time eases reassembly.
To dislodge particulate matter from the burner surface matrix, use compressed air (700 kPa maximum). Keep the air
nozzle about 50 mm from the burner’s surface, blowing air perpendicular to the burner surface while moving the nozzle
back and forth lengthwise. This dislodges particles trapped in the matrix, pushing them back inside the burner.
NOTE: Avoid blowing air across the surface, which tends to have a destructive effect on the burner surface. Allow
particulate matter to fall from the burner through the air/gas inlet. To assist in removing the particulate matter, use
a vacuum at the burner’s air/gas inlet.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
18
Page 21
Burner tuning
NOTE: The GTS humidifi er is adjusted for correct performance. Only a qualifi ed gas appliance technician should alter
the throttle setting.
Follow these instructions closely to ensure proper combustion and the most effi cient burner setting. For humidifi ers with
multiple burners, tune all burners (individual burners can be tuned while other burners are running).
1. Ensure there are no gas leaks in the gas piping and
that all wiring and gas connections are complete.
2. Check for proper gas supply pressure. See the
humidifier nameplate label.
3. Apply power and gas to the humidifier.
4. Generate a call for humidity.
The Vapor-logic controller has a Test Run capability to
confi rm system functionality. This capability allows a
technician to simulate a demand for steam production
when there is not demand (such as when performing
routine maintenance).
To confi rm functionality:
a. Go to the Test Run section of the Diagnostics
menu.
b. Set system demand percent, and set Test Run time
duration.
c. Push the Start button.
The humidifi er mode changes to Test.
The burners will light and ramp up to 100% until
the humidifi er is producing steam. At this point,
they will modulate to meet the demand.
5. If the burners do not light, refer to the Troubleshooting
guide in the Vapor-logic version 5 Installation and Operation Manual (shipped with the humidifier).
Note: This manual is also available on the Literature
tab at www.dristeem.com .
6. After the water temperature reaches 100 °C and
the tank is at a boil, use a combustion analyzer
to determine the combustion characteristics of the
burners. Guidelines for products of combustion are:
• CO less than 40 ppm (low single digits is the
norm)
• CO2 from 8% to 10%, preferably 9%
• O2 between 4% and 7%
• Flue Temperature less than 204 °C plus room
temperature
• Burner effi ciency greater than 80%
• Orange color fl ame
7. Locate the throttle screw on the gas valve assembly.
See Figure 19-1.
FIGURE 19-1: THROTTLE SCREW
Remove cap. Throttle screw is inside of housing.
8. If temperature or CO percentage are higher than the
ranges in step 6, turn the throttle screw clockwise
1/4 turn at a time until the readings are acceptable.
If CO percentage and/or burner efficiency are lower
than the ranges in step 6, turn the throttle screw
counterclockwise 1/4 turn at a time until readings are
acceptable.
Note: If the humidifi er has multiple burners, adjust
them all an equal amount before retesting with
the combustion analyzer.
9. If the humidifier has a dedicated gas meter, use it
to ensure that gas flow rate is not greater than the
nameplate label on the humidifier. Code dictates that
flue temperature must be below 204 °C plus room
temperature, and CO level must be below 40 ppm.
10. Reset the humidifier to the desired set point and leave
the humidifier in operation.
DRISTEEM GTS HUMIDIFIER INSTALLATION AND OPERATION MANUAL
19
Page 22
Warranty
Expect quality from the industry leader
Since 1965, DriSteem has led the industry with
innovative methods for humidifying and cooling
air with precise control. Our focus on ease of
ownership is evident in the design of the GTS
humidifi er, which features cleanable, stainless
steel construction. DriSteem also leads the
industry with a Two-year Limited Warranty and
optional extended warranty.
For more information
www.dristeem.com
sales@dristeem.com
For the most recent product information
visit our website: www.dristeem.com
Two-year Limited Warranty
DRI-STEEM Corporation (“DriSteem”) warrants to the original user that its products will be free from
defects in materials and workmanship for a period of two (2) years after installation or twentyseven (27) months from the date DriSteem ships such product, whichever date is the earlier.
If any DriSteem product is found to be defective in material or workmanship during the applicable
warranty period, DriSteem’s entire liability, and the purchaser’s sole and exclusive remedy, shall
be the repair or replacement of the defective product, or the refund of the purchase price, at
DriSteem’s election. DriSteem shall not be liable for any costs or expenses, whether direct or
indirect, associated with the installation, removal or reinstallation of any defective product. The
Limited Warranty does not include cylinder replacement for electrode steam humidifi ers.
DriSteem’s Limited Warranty shall not be effective or actionable unless there is compliance with
all installation and operating instructions furnished by DriSteem, or if the products have been
modifi ed or altered without the written consent of DriSteem, or if such products have been subject
to accident, misuse, mishandling, tampering, negligence or improper maintenance. Any warranty
claim must be submitted to DriSteem in writing within the stated warranty period. Defective parts
may be required to be returned to DriSteem.
DriSteem’s Limited Warranty is made in lieu of, and DriSteem disclaims all other warranties,
whether express or implied, including but not limited to any IMPLIED WARRANTY OF
MERCHANTABILITY, ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, any
implied warranty arising out of a course of dealing or of performance, custom or usage of trade.
DriSteem SHALL NOT, UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY DIRECT, INDIRECT,
INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED
TO, LOSS OF PROFITS, REVENUE OR BUSINESS) OR DAMAGE OR INJURY TO PERSONS OR
PROPERTY IN ANY WAY RELATED TO THE MANUFACTURE OR THE USE OF ITS PRODUCTS. The
exclusion applies regardless of whether such damages are sought based on breach of warranty,
breach of contract, negligence, strict liability in tort, or any other legal theory, even if DriSteem has
notice of the possibility of such damages.
By purchasing DriSteem’s products, the purchaser agrees to the terms and conditions of this Limited
Warranty.
DRI-STEEM Corporation
a subsidiary of Research Products Corporation
DriSteem is an ISO 9001:2000 certifi ed company
U.S. Headquarters:
14949 Technology Drive
Eden Prairie, MN 55344
800-328-4447 or 952-949-2415
952-229-3200 (fax)
European offi ce:
Grote Hellekensstraat 54 b
B-3520 Zonhoven
Belgium
+3211823595
E-mail: dristeem-europe@dristeem.com
Continuous product improvement is a policy of
DriSteem; therefore, product features and
specifi cations are subject to change without
notice.
DriSteem, GTS, and Vapor-logic are registered
trademarks of Research Products Corporation
and are fi led for trademark registration in
Canada and the European community.
Product and corporate names used in this
document may be trademarks or registered
trademarks. They are used for explanation only
without intent to infringe.
The original user may extend the term of the DriSteem Limited Warranty for a limited number of
months past the initial applicable warranty period and term provided in the fi rst paragraph of this
Limited Warranty. All the terms and conditions of the Limited Warranty during the initial applicable
warranty period and term shall apply during any extended term. An extended warranty term of
an additional twelve (12) months or twenty four (24) months of coverage may be purchased. The
extended warranty term may be purchased until eighteen (18) months after the product is shipped,
after which time no extended warranties are available.
Any extension of the Limited Warranty under this program must be in writing, signed by DriSteem,
and paid for in full by the purchaser.
mc_051308_0630
Form No. GTS-IO-EN-0815
Part No. 890000-106 Rev B
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.