If the information in this manual is not
followed exactly, a fire or explosion
may result causing property damage,
personal injury, or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
W H A T T O D O
I F Y O U S M E L L G A S
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier
from an off-site phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
Installation and service must be performed by a qualified installer, service
agency, or the gas supplier.
For toll-free technical support call:
1-800-328-4447
Page 2
ATTENTION INSTALLER
Read this manual before installing.
Leave manual with product owner.
DRI-STEEM technical support
800-328-4447
I m po r ta n t: Troubleshooting information for this humidifier is located
in the Vapor-logic4 Installation and Operation manual shipped with your
humidifier. If you do not have this manual, go to the literature section at
www.dristeem.com to download or order a copy.
Where to find more information
On our Web site:
The following related documents can be
viewed, printed or ordered from our web
site, www.dristeem.com
Dri-calc® is our humidification system
sizing and selection software, which can be
ordered at www.dristeem.com.
Included in Dri-calc:
®
®
manuals:
DRI-STEEM Design Guide
loss tables and general humidification
information)
(includes steam
European models
The DRI-STEEM GTS Gas-to-Steam Humidifier has been certified
for compliance with harmonised European directives concerning
gas appliances, low voltage, and emission (Gas Appliance Directive
90/396/CEE). Testing was carried out by the Canadian Standards
Association; the notifying body is AFNOR in France, which is a
recognized authority by the European bodies and the DTI in the
United Kingdom.
Installation must conform to the requirements of the National Gas
Safety (Installation & Use) Regulations.
• A comprehensive library of installation
guide documents, including:
– Rapid-sorb installation instructions
for vertical airflows
– Recommended dispersion placement
within a duct or air handler
– Recommended sensor placement
Or call us at 800-328-4447
While obtaining documents from our web
site or from Dri-calc is the quickest way to
review our literature, we will also mail to
you any literature you need.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1
Page 4
S a f e t y p r e c a u t i o n s
W A R N I N G !
The humidifier must be installed by
a qualified technician and meet the
requirements of all governing codes. Failure
to follow these instructions could cause
severe bodily injury or death.
W A R N I N G !
If you do not follow the instructions in this manual
exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
For your safety, read this entire manual before
installing or operating the GTS humidifier.
A. This appliance does not have a pilot. It is equipped with an
ignition device which automatically lights the burner.
Do NOT try to light the burner by hand.
B. Before operating, smell all around the appliance area for
gas. Be sure to smell next to the floor because gas can be
heavier than air and settle on the floor.
FOR YOUR SAFETY: WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
C. Do not use this appliance if any part has been under water.
Immediately call a qualified gas appliance service technician
to inspect the appliance and to replace any part of the control
system and any gas control that has been under water.
More safety precautions are on the next page ▶
Pag e 2 • DRI - S TEE M G TS Hu m i difi e r Ins t a llat i on, O p e rat i o n, an d M aint e nanc e M anua l
Page 5
S a f e t y p r e c a u t i o n s ( c o n t i n u e d )
Safe operating instructions
1. STOP! Read the safety information on the previous page.
2. Set the humidistat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device that
automatically lights the burner. Do not try to light the burner
by hand.
5. Remove control access panel.
6. Unplug the black power plug on the gas valve (see
Figure 3-1).
7. Wait five minutes to clear out any gas.
If you then smell gas, STOP! Follow “B” in the safety
information on the previous page.
If you don’t smell gas, go to the next step.
8. Plug the black power plug back into the gas valve.
9. Replace control access panel.
10. Turn on all electric power to the appliance.
To turn off gas to appliance
1. Set the humidistat to lowest setting.
2. Turn off all electric power to the
appliance if service is to be performed.
3. Remove control access panel.
4. Unplug the black power plug on the gas
valve.
5. Replace control access panel.
11. Set humidistat to desired setting.
12. If the appliance will not operate, follow the instructions on this
page titled, “To turn off gas to appliance,” and call your service
technician or gas supplier.
More safety precautions are on the next page ▶
Figure 3-1:
Detail of gas valve
Top view
Gas
valve
Gas valve
power
plug
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 3
Page 6
S a f e t y p r e c a u t i o n s ( c o n t i n u e d )
W A R N I N G !
Improper installation, adjustment, alteration, service, maintenance, or
use can cause carbon monoxide poisoning, explosion, fire, electrical
shock, or other conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency, local gas supplier,
or your distributor or branch for information or assistance. The qualified
installer or agency must use only factory authorized and listed kits
or accessories when modifying this product. A failure to follow this
warning can cause electrical shock, fire, personal injury, or death.
• Inspect humidifier and accessories upon arrival for damaged, missing,
or improper parts. If there is a problem, call DRI-STEEM.
• Application of this humidifier should have special attention given to
vent sizing and material, gas input rate, and unit sizing. Improper
installation or misapplication of the humidifier can cause excessive
servicing or permanent component failure.
• When working on equipment, observe precautions in literature, tags,
and labels attached to or shipped with the unit and observe other
safety precautions that may apply. Wear safety glasses and work
gloves. Have a fire extinguisher available during start-up, adjustment
procedures, and service calls.
• Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any gas
control that has been under water.
• Do not lift humidifier by gas controls, gas manifold, fire box, or
shroud.
• Should overheating occur, or the gas supply fail to shut off, shut
off the manual gas valve to the appliance before shutting off the
electrical supply.
• The evaporating chamber is designed as a non-pressurized vessel.
DO NOT restrict piping where steam exits the humidifier.
Install drain piping and piping that connects the evaporating
chamber to the dispersion assembly only as described in this manual.
DO NOT install a shut-off valve on the piping connecting the
evaporating chamber to the steam outlet.
Pag e 4 • DRI - S TEE M G TS Hu m i difi e r Ins t a llat i on, O p e rat i o n, an d M aint e nanc e M anua l
More safety precautions are on the next page ▶
Page 7
S a f e t y p r e c a u t i o n s ( c o n t i n u e d )
W A R N I N G !
• Installation must conform to the requirements of the authority having
jurisdiction or, in the absence of such requirements, must conform to:
In the United States: The National Fuel Gas Code, ANSI Z223.1
(latest edition).
In Canada: Local plumbing or waste water codes and other
applicable codes and with the current code CAN/CGA-B149.1,
“Installation Code for Natural Gas Burning Appliances and
Equipment,” or CAN/CGA-B149.2, “Installation Code for Propane
Burning Appliances and Equipment.”
In Europe: The National Gas Safety (Installation & Use) Regulations.
• Do not install in potentially explosive or flammable atmospheres
laden with grain dust, sawdust, or similar airborne materials.
• Installation of humidifier in high humidity or salt water atmospheres
causes accelerated corrosion, reducing the normal life-span of the
unit.
• To prevent premature heat exchanger failure, do not locate any gasfired unit in areas where chlorinated, halogenated, or acid vapors are
present in the atmosphere.
• Locate the humidifier in an area clear of combustible materials,
gasoline, and other flammable vapors and liquids.
• With the exception of sealed combustion units, do not locate units
in tightly sealed rooms or small compartments without provision for
adequate combustion air and venting. Room air combustion must be
supplied through a minimum of two permanent openings in the wall,
with at least one near the bottom. See the table and information on
Page 30 for additional information.
• Remove all shipping brackets and materials before operating the
humidifier.
• Do not locate humidifier in a negative pressure space. Combustion
products could be suctioned from the venting.
• Humidifier flue gases must be vented to the outside atmosphere.
• Power supply disconnect switch must be in the off position while
making wiring connections to prevent electrical shock and equipment
damage. All units must be wired in strict accordance with the wiring
diagrams furnished with this unit.
• Turn off all gas while installing the gas piping and manual shutoff
valve for the humidifier.
• The appliance and its individual shut-off valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures exceeding 0.5 psig (3.5 kPa).
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 5
Page 8
Figure 6-1:
GTS standard water model VLC
Steam outlet
Water level probe
Water supply line
P r o d u c t o v e r v i e w
Optional Ultra-sorb dispersion
panel installed in duct
Vapor hose
Flue box
Blower
Gas valve
Notes:
• GTS standard water models can be
converted in the field for use with
deionized/reverse osmosis (DI/RO) water.
GTS-DI models can be converted in the
field for use with potable or softened
water.
• Damage caused by chloride corrosion is
not covered by your DRI-STEEM warranty.
Heat exchanger
Control components
Drain valve
OM-1201
GTS standard water models
GTS standard water gas-fired humidifiers burn either natural
or propane gas to heat potable or softened fill water into steam
for humidification. The unit has from one to four burners that
fire into a heat exchanger submerged in a tank of water. When
there is a call for humidity, the burners fire and generate steam
until the call for humidity ends. A probe monitors water level,
requiring water conductivity to be at least 100 µS/cm to operate
properly. Therefore, GTS standard water models do not operate
with demineralized water (deionized or reverse osmosis treated
water). For demineralized water operation, use the GTS-DI model
(described on next page).
Pag e 6 • DRI - S TEE M G TS Hu m i difi e r Ins t a llat i on, O p e rat i o n, an d M aint e nanc e M anua l
Page 9
P r o d u c t o v e r v i e w ( c o n t i n u e d )
Figure 7-1:
GTS-DI (DI/RO water model)
Blower
Gas valve
Water supply line
Flue connection
Float for water fill valve
Air gap
Open drain
Steam outlet
Redundant low water
cutoff sensor
Float-operated low
water cutoff
Overflow outlet
Drain valve
Drain piping (by installer)
GTS-DI models
GTS-DI humidifiers burn either natural or propane gas to heat
deionized (DI) or reverse osmosis (RO) fill water into steam for
humidification. GTS-DI models control water level using a float
valve.
GTS-DI models are virtually maintenance-free and require very
little or no downtime.
The GTS-DI model is available for use with deionized or reverse
osmosis water. This unit produces chemical-free steam and reliable,
accurate humidification control.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 7
OM-1202
Notes:
• GTS standard water models can be
converted in the field for use with
deionized/reverse osmosis (DI/RO) water.
GTS-DI models can be converted in the
field for use with potable or softened
water.
• Damage caused by chloride corrosion is
not covered by your DRI-STEEM warranty.
Page 10
S p e c i f i c a t i o n s , ca p a c i t i e s , a n d
w e i g h t s
Table 8-1:
GTS specifications, capacities, and weights for North American models only
* Add 15 full load amps for outdoor enclosure heater load on all GTS models
** Add 10% to account for skim and automatic drain/flush features if utilized (standard water units only).
steam
capacity
lbs/hrkg/hMBhkWm3/h
Input
I m po r t an t : See Pages 76-77 for
additional European model specifications
and capacity notes.
Water usage
at maximum
capacity**
gals/hrlitres/
hr
Tank
volume
galslitreslbskglbskglbskglbskg
Operating
weight
Capacity notes
• At sea level, approximately 152 Btu are required to raise the
temperature of one pound of water from 60 °F to 212 °F. (At sea
GTSGTS with outdoor enclosure
Shipping
weight
Operating
weight
Shipping
weight
Full load
amps*
120 V
60 Hz
230 V
50 Hz
level, approximately 352 kJ are required to raise the temperature
Table 8-2:
High altitude derate
Altitude
feetmeters
0–20000–6100
2001–2500610–7652
2501–3000765–9154
3001–3500915–10656
3501–40001065–12208
4001–45001220–137010
4501–50001370–152512
5001–55001525–167514
5501–60001675–183016
6001–65001830–198018
6501–70001980–213520
7001–75002135–228522
7501–80002285–244024
derate %
Input
of one kilogram of water from 16 °C to 100 °C.)
• An additional 970 Btu are required to change the state of one pound
of 212 °F water to vapor. (An additional 2257 kJ are required to
change the state of one kilogram of 100 °C water to vapor.)
• Another factor to consider is condensation steam loss from
piping. Use the following general steam loss guidelines:
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 9
18.0045717.0043217.0043216.25413
14.0035620.5052129.2574335.25895
13.0033013.0033013.0033013.00330
8.752228.752228.752228.75222
Page 12
L o c a t i n g t h e h u m i d i f i e r a n d
c l e a r a n c e r e c o m m e n d a t i o n s
Locating the humidifier
• Provide a level, solid foundation for the humidifier.
• Locate the humidifier as near as possible to a chimney or
outside wall so that the flue pipe from the humidifier is
short and direct.
• Locate the unit so it and its electrical components are
protected from water during humidifier operation and
service.
• Install the humidifier in a location away (and protected)
from drafts. If installed in a separate room, follow the
instructions concerning combustion and ventilation air.
• Locate the humidifier in an area where leakage from the
tank or its connections will not result in damage to the
adjacent structure or to lower floors of the structure.
When such locations cannot be avoided, install a suitable
drain pan (adequately drained) under the humidifier. The
pan must not restrict combustion airflow.
• Do not install the humidifier on carpeting, tile or other
combustible material other than wood flooring (indoor
application only).
• If located in an insulated space, keep the humidifier free
and clear of insulating materials. Insulating material can
be combustible. Inspect the humidifier area when the
humidifier is installed or when insulation is added.
Figure 10-1:
GTS clearance recommendations
18" (457 mm)
36" (914 mm)
30" (762 mm)
OM-1222
Note:
DRI-STEEM recommends a minimum of 1" (25 mm) clearance between hot surfaces and
combustible walls.
Pag e 1 0 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 13
O u t d o o r e n c l o s u r e m o u n t i n g
Outdoor enclosure mounting option
The outdoor enclosure option is used when the GTS is installed
outdoors. The following information is not intended to supersede
any requirements of federal, state, or governing codes having
jurisdiction; prior to locating the unit, authorities having
jurisdiction should be consulted.
Vapor-logic4 keypad shown with optional
cable length. Keypad ships standard with
5' (1.5 m) of cable
OM-1238
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 1
Page 14
O u t d o o r e n c l o s u r e m o u n t i n g
( c o n t i n u e d )
Handling
The GTS outdoor enclosure must be lifted from the bottom base
in a fashion that holds it level and keeps it from tipping, falling, or
twisting. If the unit is severely twisted during handling, permanent
damage can occur. It is the installer’s responsibility to verify the
handling equipment’s capability to safely handle the unit.
Lift the outdoor enclosure by using special lifting lug hooks
installed on the unit. All lifting operations must be accomplished
with a load spreader of sufficient width to ensure that the lifting
cables clear the side of the unit.
Pag e 1 2 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 15
O u t d o o r e n c l o s u r e m o u n t i n g
( c o n t i n u e d )
Location
• The GTS outdoor enclosure must be level and located so there is
enough clearance for opening the access panels.
• Verify that the position of pad or curb properly supports the
unit and that support structure dimensions coincide with unit
dimensions.
• Do not locate unit in areas where the surrounding air has high
levels of particulates, such as some industrial parks or areas near
highways.
• Locate unit so air intakes are not too close to exhaust fan outlets,
gasoline storage, or other contaminants that potentially could
cause dangerous situations. Using and storing gasoline or other
flammable vapors and liquids in open containers in the vicinity of
this appliance is hazardous.
• When located on the roof, the air intakes must be a minimum of
14" (360 mm) off the roof to prevent intake of snow or splashed
rain. The unit should be located so prevailing winds do not blow
into the air intakes.
• An emergency drain is provided. In case of any water leak, water
drains onto the roof through this emergency drain.
• A keypad with standard 5' (1.5 m) cable ships mounted to
the subpanel in the GTS outdoor enclosure. The keypad must
not come in contact with the strip heaters or block the intake
ventilation hood.
• If constant monitoring of the unit is desired, or if the unit is
located in a severe climate, install a remote mount keypad.
Additional cable lengths up to 500' (152 m) are available as an
option for this mounting configuration.
• Curbs (optional) are shipped knocked down for ease of
transporting to the roof. Curbs are manufactured of 14-gauge
galvanized steel and shipped with all hardware for bolt-together
assembly. All holes are matched before leaving the factory. Curb
is to be a minimum of 14" (360 mm) high. A closed-cell curb
gasket with adhesive on one side is supplied with hardware. An
installation drawing also is included. To prevent moisture from
leaking into the building from either driving rain or melting
snow, install the gasket between the top of the curb and the base
surface of the unit.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 3
Page 16
O u t d o o r e n c l o s u r e m o u n t i n g
( c o n t i n u e d )
Before you begin
• Prior to installing the unit, remove all packaging.
• During the transit, unloading, and setting of the unit, bolts and
nuts may become loose. Check that all nuts are tightened as
required.
• There are three knockouts located on the right and left side of the
enclosure. DRI-STEEM recommends running electrical power
into the enclosure at these knockouts.
• When unit is mounted on an outdoor curb, there must be a
gasket between the top of the curb and the base surface of the
unit to prevent moisture from leaking into the building from
either driving rain or melting snow.
• The outdoor enclosure has two available steam distribution
configurations. The standard configuration has a steam outlet
at the back of the outdoor enclosure for connecting to steam
dispersion unit piping. The optional internal steam distribution
configuration routes steam within the outdoor enclosure and
down through the pipe chase into a building. See drawings on
Pages 15 and 16.
I m po r ta n t : A pipe chase is located inside the burner section
of the enclosure. DRI-STEEM recommends using this pipe chase
for both the supply water piping and drain piping. Use insulation
to completely fill the area around the pipes to maintain proper
enclosure pressure and protect unit components from elevated
moisture levels within building; insulation must serve as an
effective vapor barrier. Use the provided pipe chase cover to seal
off the pipe chase. Cut necessary holes and seal after installation.
• The heater package has two thermostat-controlled heaters:
one strip heater is located in the control section, and one strip
heater is located in the burner section to keep the enclosure at
a constant minimum temperature. Once the humidifier tank is
full and up to temperature, the tank will keep the enclosure at an
appropriate temperature. The heaters will turn off.
• Refer to the installation section of this manual for directions
on installing electrical, gas, flue, drain, and water connections.
A separate electrical service connection for the outdoor GTS is
recommended. Insulation and/or heat taping of water piping is
recommended.
Pag e 1 4 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 17
O u t d o o r e n c l o s u r e m o u n t i n g
( c o n t i n u e d )
Piping
• Insulate supply water piping to avoid dripping from
condensation. To ensure that water does not remain in the
fill line and freeze if there is a loss of power, DRI-STEEM
recommends field installing additional valves upstream of the
fill valve in a conditioned space. Power these valves on the same
circuit as the GTS; if the power goes off, water drains out of the
fill line to prevent freezing (see Figure 15-1).
• When pad-mounted or when the pipe chase cannot be used, the
supply water and drain piping can be run through the knockouts,
although preferably on the opposite side from the gas and
electric.
• Install external flue piping shall be provided by installers and
field installed. The flue of the outdoor enclosure exits out the
left side of the unit and a vertical stack must be constructed. The
stack must be a minimum of 5–10 feet (1.5–3.0 m) above the top
of the roof. However, the exact height varies depending on unit
size, climate, etc. Governing codes prevail. A UL or UL/CSA (or
equivalent) listed cap must be used and a drip tee included.
Normally closed
(fail closed) min
3/8" electric valve
(by installer)
Domestic water,
80 psig (582 kPa)
maximum
OM-4045
GTS humidifier in
outdoor enclosure
installed on roof top
Roof decking
Drain line, min. 1½" electric valve
Optional water seal (P-trap)
drain line, min. 1½" (DN40)
Normally open (fail open)
min ½" electric valve
(by installer)
Open drain
Disconnect (by installer); see Detail A
120 V supply (230 V in Europe)
Heated building interior
120 V
(230 V in Europe)
Disconnect
box
Detail A
N
To valves
(by installer)
To GTS humidifier
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 5
Page 18
O u t d o o r e n c l o s u r e m o u n t i n g
( c o n t i n u e d )
Figure 16-1:
GTS outdoor enclosure with standard or optional steam outlet, elevation view
Standard steam outletOptional steam outlet
Flue piping (by installer)
Steam outlet (See Note 1)
Ventilation fans
Combustion
air intake
1½" (38 mm) knockouts
4" (102 mm) o.c.
Pipe chase
Notes:
1. The outdoor enclosure has two available steam distribution configurations. The standard configuration has a steam outlet at the back of the outdoor enclosure
for connecting to steam dispersion unit piping. The optional internal steam distribution configuration routes steam within the outdoor enclosure and down
through the enclosure pipe chase into a building.
2. There are three knockouts located on the right and left side of the enclosure. Run the electrical power and gas piping into the enclosure at these knockouts.
3. Piping from the GTS unit to the steam outlet is stainless steel pipe. Piping from the steam outlet to the dispersion assembly is provided by the installer.
Choose interconnecting steam piping material that is appropriate for the application (e.g., for high-purity steam applications, consider using stainless steel
interconnecting steam piping). See Page 22 for steam outlet sizes.
4. The GTS housed in an outdoor enclosure will operate properly in operating temperature of –40 °F to 122 °F (–40 °C to 50 °C).
Emergency
drain
GTS
humidifier
Power block
OM-1228M
Ventilation fans
Combustion
air intake
1½" (38 mm) knockouts
4" (102 mm) o.c.
Pipe chase
Emergency
drain
Flue piping (by others)
Steam outlet
(See Note 1)
GTS
humidifier
Power block
OM-1227M
Pag e 1 6 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 19
O u t d o o r e n c l o s u r e m o u n t i n g
( c o n t i n u e d )
Exit for optional
steam outlet
(through pipe chase)
Flue
(by installer)
Burner
section
heater
Access panel
door
T
Y
Z
W
U
OM-7430
Control
panel
heater
Access
panel
door
Intake
ventilation
fans
X
V
OM-7432
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 7
Page 20
O u t d o o r e n c l o s u r e o p e r a t i o n
GTS outdoor enclosure sequence of operation
• Power is applied to the outdoor enclosure.
• If the ambient temperature in the enclosure is below
50 °F (10 °C), the strip heaters are powered up. If the enclosure
temperature reaches 35 °F (2 °C), power is allowed to the GTS
subpanel and the GTS unit is enabled. The strip heaters remain
on until the enclosure reaches 50 °F (10 °C) to ensure that
the temperature inside the enclosure does not drop below the
freezing point.
• When the enclosure temperature is at or above 50 °F (10 °C), the
GTS tank heats the enclosure. When there is no call for humidity,
an aquastat maintains tank temperature at the factory default
of 70 °F (21 °C). This temperature can be reset in the field to be
from 40-180 °F (4-82 °C).
• When the ambient temperature in the enclosure reaches 85 °F
(29 °C), two ventilation fans turn on to cool the electronic
components. A high limit is also provided to power down the
GTS if the enclosure temperature reaches 150 °F (66 °C). In a
high limit situation, the ventilation fans continue to run and once
the enclosure temperature falls below 130 °F (54 °C), the GTS
automatically resumes normal operation.
• A normally open drain valve is provided on the GTS outdoor
enclosure to drain the tank in the event of a power loss.
Pag e 1 8 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 21
W i r i n g : E l e c t r i c a l co n n e c t i o n s
W A R N I N G !
Installation must meet the requirements of governing codes or, in the
absence of governing codes, in accordance with the National Electrical
Code, ANSI/NFPA 70, or Canadian Electrical Code, CSA C22.1, or IEE
wiring regulations (BS7671). The electrical subpanel must have an
uninterrupted or unbroken ground to minimize personal injury if an
electrical fault should occur. This ground can consist of electrical wire
or conduit approved for electrical ground when installed in accordance
with existing electrical codes. Do not use gas piping as an electrical
ground.
• GTS humidifiers must be supplied with 120-volt AC, 60 Hz
(North American models) or 230-volt AC, 50 Hz (European
models) separately fused electrical service. The GTS humidifier is
equipped with a transformer to step down the voltage to 24 VAC
control voltage.
• When installed, the GTS humidifier must be electrically
grounded in accordance with governing codes or, in the absence
of governing codes, in accordance with the National Electrical
Code, ANSI/NFPA 70; or Canadian Electrical Code, CSA C22.1;
or IEE wiring regulations (BS7671).
In North America, the electrical conductors shall be Type MTW
(105 °C) AWG #14 (2.5 mm2) wire for 120 V line voltage , with
BLACK WIRE for HOT, WHITE WIRE for NEUTRAL, GREEN
AND YELLOW WIRE for GROUND. Units with outdoor
enclosure must use AWG #12 (4 mm2) for 120 V line voltage.Use
#18 gauge (1 mm2) for control wiring.
In Europe, the electrical conductors shall be Type MTW (105 °C)
2.5 mm2 wire for line voltage (230V), with BLACK WIRE for
LINE, BLUE WIRE for NEUTRAL, GREEN AND YELLOW
WIRE for GROUND, and 2.5 mm2 wire for control wiring.
• All electrical components and wiring must be protected from
mechanical damage and water. The control system requires an
earth ground for proper operation.
• The GTS humidifier is adjusted for correct performance. Only a
qualified gas appliance technician may alter throttle setting.
• Check the electric current characteristics and capacity
requirements against the nameplate. All wiring must be in
accordance with all governing codes and with the GTS wiring
diagrams located inside the control cabinet. See table on Page 8
for information on the various models.
• Refer to the Vapor-logic4 Installation and Operation Manual for
additional information on the controller furnished with this GTS
humidifier.
W A R N I N G !
Do not connect aluminum wire between
disconnect switch and humidifier. Use
only copper wire. Failure to follow these
instructions could cause a fire, resulting in
severe bodily injury, death, or significant
property damage.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 9
Page 22
Figure 20-1:
Field piping overview for GTS standard water models
Optional condensate return piping from dispersion
unit; ¾" pipe thread (DN20) fitting at humidifier
Shock arrester recommended to
reduce water hammer, by installer
Flue size per governing codes.
Do not reduce.
Water supply line; water
pressure range 25 psi to 80 psi
(172 kPa to 582 kPa); water
conductivity minimum 100 µS/cm
G T S p i p i n g , s t a n d a r d w a t e r m o d e l s
Steam hose, pipe or tubing
Install level
Air vent tube
6" (150 mm)
minimum vent height
Flue connection
Offset humidifier from floor
drain to prevent flash steam
from rising into the humidifier
1½" NPT (DN40) drain piping must be
rated for 212 °F (100 °C) (by installer)
1" (25 mm) air gap
Notes:
• Locate air gap only in spaces with adequate
temperature and air movement to absorb flash steam;
otherwise, condensation may form on nearby surfaces.
Refer to governing codes for drain pipe size and
maximum discharge water temperature.
• Dashed lines indicate provided by installer.
• Humidifier flue gases must be vented to the outside
atmosphere.
• The water supply inlet is more than 1" (25 mm) above
the skim/overflow port, eliminating the possibility of
backflow or siphoning from the tank. No additional
backflow prevention is required; however, governing
codes prevail.
• Damage caused by chloride corrosion is not covered by
your DRI-STEEM warranty.
• See the next page for recommended water supply
piping for DI/RO water models.
Air vent height must be equal to
or greater than dimension “H”
(see table below)
Install level
H
Gas inlet connection
Open drain required.
See first note below.
Table 20-1:
Height required to overcome GTS internal pressure (H)
H = Height required to overcome humidifier internal pressure
GTS model
number
inchesmm
100, 20035889
300, 400,
500, 600,
700, 800
411041
OM-1208
Pag e 2 0 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 23
G T S p i p i n g , D I / R O w a t e r m o d e l s
’
Figure 21-1:
Field piping overview for GTS DI/RO water models
Optional condensate return
piping from dispersion unit;
¾" pipe thread (DN20)
fitting at humidifier
Flue size per governing codes.
Do not reduce.
Water supply line; water
pressure range 25 psi to 80 psi
(172 kPa to 582 kPa); first 3'
(1 m) of supply line must be
rated for 212 °F (100 °C)
Steam hose, pipe or tubing
Install level
minimum vent height
Air vent tube
If water piping to humidifier is nonmetallic, we recommend
a 2" (50 mm) water seal in the supply line to isolate steam
during DI/RO water system maintenance.
Inlet strainer by installer
6" (150 mm)
Flue connection
Offset humidifier from floor
drain to prevent flash steam
from rising into the humidifier
1½" (DN40) drain piping must be
rated for 212 °F (100 °C)
1" (25 mm) air gap
Gas inlet connection
Open drain required. See first note below.
Table 21-1:
Height required to overcome GTS-DI internal pressure (H)
H = Height required to overcome humidifier internal pressure
GTS-DI model
number
inchesmm
100, 20035889
300, 400,
500, 600,
700, 800
411041
Install level
Air vent tube height must
be equal to or greater than
dimension “H“ (see table below)
H
OM-1223
Notes:
• Locate air gap only in spaces with adequate
temperature and air movement to absorb flash
steam; otherwise, condensation may form on nearby
surfaces. Refer to governing codes for drain pipe size
and maximum discharge water temperature.
• Dashed lines indicate provided by installer.
• Humidifier flue gases must be vented to the outside
atmosphere.
• The water supply inlet is more than 1" (25 mm)
above the overflow port, eliminating the possibility of
backflow or siphoning from the tank. No additional
backflow prevention is required; however, governing
codes prevail.
• Damage caused by chloride corrosion is not covered
by your DRI-STEEM warranty.
• In order to minimize DI/RO water use, disconnect
factory piping to the water tempering device and pipe
directly to tap water.
• See the previous page for recommended water supply
piping for standard water models.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 2 1
Page 24
S u p p l y w a t e r a n d d r a i n o v e r f l o w
c o n n e c t i o n s
Supply water and drain overflow connections
Regardless of the type of water used, the following general
instructions MUST be followed:
• Make union connections at the humidifier on the make-up water
supply and drain/overflow lines.
• Provide a shutoff valve in the supply water line to isolate the
humidifier from the water system while servicing.
• Shock arrester, provided by installer, is recommended to reduce
water hammer.
• A 1" (25 mm) opening is provided in the humidifier tank to
accommodate skim and/or overflow protection. (Note: Follow
governing code requirements regarding size of drain pipe.)
• Use insulating unions or bushings to make connections between
copper and other dissimilar metal fittings, such as galvanized
steel. These insulating fittings are required to minimize
electrolytic corrosion, which results from the direct connection of
dissimilar metals in a water system.
• Before beginning ignition sequence of the humidifier at a new
installation, make sure the humidifier tank is full of water and the
water is free to flow into the tank.
• If planning to use heated supply water, disconnect the water
supply line to the water tempering device at the fill manifold
and reconnect it to a cold water supply. This will ensure that the
water tempering device operates properly.
Table 22-1:
Connection sizes
GTS-100
Description
Gas supply
Sealed combustion
piping (optional)
Flue vent51257180820010250
Water supply to fill valve
and tempering device*
Drain
Steam outlet
Condensate return
(recommended)
Notes:
* In order to minimize DI/RO water use, disconnect factory piping to the water tempering device and pipe directly to tap water.
If planning to use heated supply water, disconnect the water line to the water tempering device at the fill manifold, and reconnect it to a cold water supply.
This will ensure that the water tempering device operates properly.
(pipe thread)
(pipe thread)
(pipe thread)
(pipe thread or
(pipe thread)
GTS-200
inchesDNinchesDNinchesDNinchesDN
½
4100410041004100
3/8
1½
2
hose)
¾
15
10
40
50
20
(pipe thread)
(pipe thread)
(pipe thread)
(pipe thread)
1
3/8
1½
3
(flange)
¾
GTS-300
GTS-400
GTS-500
GTS-600
25
10
40
80
20
1
(pipe thread)
3/8
(pipe thread)
1½
(pipe thread)
4
(flange)
¾
(pipe thread)
25
10
40
100
20
(pipe thread)
(pipe thread)
(pipe thread)
(pipe thread)
1¼
3/8
1½
4
(flange)
¾
GTS-700
GTS-800
32
10
40
100
20
Pag e 2 2 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 25
Wa t e r s u p p l y p i p i n g
Water supply piping general instructions
The GTS humidifier has a 1" (25 mm) internal air gap to prevent
back siphoning into a potable water system. However, some
governing codes may require additional protection such as a
vacuum breaker or backflow preventer.
The supply water pressure range must be 25 psi to 80 psi (172 kPa
to 552 kPa). When nonmetallic water piping is used, it must be
rated to withstand 212 °F (100 °C) or greater temperature. If not,
the final three feet of piping connected to the humidifier should be
metallic and should not be insulated.
GTS (standard water) water supply piping
The water supply assembly has a 3/8" pipe thread (DN10)
connection. Since the primary component of the water supply
assembly is a solenoid valve, there may be noise issues that surface
during a fill cycle.
During a fill cycle, the supply water drops the water temperature in
the tank and may collapse the steam, which can cause a low rolling
sound. To diminish this, adjust the factory-supplied needle valve
(installed prior to the fill valve) to decrease the water fill rate, and/
or use hot supply water.
In cases where water hammer occurs when the fill solenoid closes,
a shock arrester is recommended. Reducing the supply water
pressure (minimum 25 psi [172 kPa]) or using flexible tubing (rated
for 212 °F [100 °C] minimum continuous operating temperature)
may diminish the noise, but installing a shock arrester is the best
solution.
The minimum water conductivity for the GTS standard water
model is 100 µS/cm.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 2 3
Page 26
Wa t e r s u p p l y p i p i n g ( c o n t i n u e d )
I m po r t an t : Damage caused by
chloride corrosion is not covered by your
DRI-STEEM warranty.
GTS-DI water supply piping
GTS-DI models control water level with a float valve, and have
a 3/8" pipe thread (DN10) connection. For DI models with the
end-of-season drain option, a solenoid valve is installed prior to
the float valve. The end-of-season feature shuts off the fill water
supply and drains the tank when there is no demand for humidity
for 72 hours. (This length of time is a default setting and is
user-adjustable. See the Vapor-logic4 Installation and Operation Manual for more information.)
When using nonmetallic tubing for supply water, it must be
rated for 212 °F (100 °C) minimum continuous operating
temperature. DRI-STEEM recommends installing a 3' (1 m) piece
of noninsulated stainless steel pipe directly off the humidifier prior
to connecting to the nonmetallic tubing. When using nonmetallic
tubing, DRI-STEEM recommends the installer place a 2" (50 mm)
water seal/loop in the supply line to isolate steam during DI/RO
water system maintenance. (See Figure 21-1 on page 21.)
DRI-STEEM recommends installing a strainer in the water supply
line to prevent clogging of the solenoid valve or float valve orifice.
A strainer is highly recommended when the humidifier has the
end-of-season drain option. The strainer prevents particulate from
collecting at the solenoid valve seat.
In order to minimize DI/RO water use, disconnect factory piping
to the water tempering device and pipe directly to tap water.
W A R N I N G !
If the GTS-DI humidifier is supplied with tap water, the float valve
assembly will become clogged and particulate will accumulate on the
low water cutoff switch (float switch). This will cause failure of a critical
safety circuit and the potential for a dry tank fire. A dry tank fire can
cause heat exchanger, vapor hose, and wire insulation failure, severe
property damage, severe personal injury, or death.
Pag e 2 4 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 27
D r a i n p i p i n g
The drain line piped from the humidifier must be run to
an approved sanitary waste or suitable drain. Although the
GTS humidifier is equipped with integral water tempering, if
nonmetallic drain pipe or hose is used, DRI-STEEM recommends
it be rated for 212 °F (100 °C) minimum continuous operating
temperature.
Minimum drain pipe size is 1½" (DN40) inside diameter. If the
length of the drain piping exceeds 10' (3 m), increase the pipe size.
Do not locate the humidifier directly above a floor drain — skim
and drain water dumped into the drain will cause flash steam.
This steam will rise and saturate electrical components, adversely
affecting component life and performance.
An open drain with a 1" (25 mm) air gap between the drain piping
and the drain is required. Locate air gap only in spaces with
adequate temperature and air movement to absorb flash steam;
otherwise, condensing on nearby surfaces may occur.
Drain piping after the water seal must be pitched a minimum of
1/8"/ft (1%) toward the drain. Governing codes may require more
pitch.
If the proximity of a drain requires the humidifier drain and skim
water to be lifted, use a water pump with capacity of at least
12 gallons per minute (gpm) or 45.4 litres per minute (L/m).
Contact DRI-STEEM to order a drain pump suitable for your
installation. A check valve is required on the discharge of the pump
(see Figure 25-1). Electrical power for the pump is independent
of the humidifier.
The GTS humidifier has an auxiliary 1½" (DN40) drain outlet
located below the subpanel. This drain outlet can be hardpiped during installation to enable rapid tank draining before
maintenance. This outlet can also provide access for removing scale
from the tank bottom.
Figure 25-1:
Lifting drain water
Discharge
piping, by
Inlet
drain
water
piping,
by installer
installer
Check valve
Integral water tempering chamber
Governing codes may require that the
212 °F (100 °C) drain and skim/overflow
water from the humidifier be tempered
before it is discharged into the building
drain piping. The GTS humidifier has an
integral water tempering chamber that
tempers 6 gpm (22.7 L/m) of 212 °F
(100 °C) water to 140 °F (60 °C). The water
tempering sequence of operation is:
1. Hot water discharged from the humidifier
enters the water tempering chamber
from either the skim/overflow port or the
tank drain.
2. Cold water enters the water tempering
chamber through a temperature-actuated
valve to mix with the hot discharged
water.
3. Tempered water at 140 °F (60 °C)
maximum exits through the water
tempering chamber side outlet for safe
discharge into a municipal sewer system
or PVC pipe.
4. In order to minimize DI/RO water use,
disconnect factory piping to the water
tempering device and pipe directly to tap
water.
5. If planning to use heated supply water,
disconnect the water line to the water
tempering device at the fill manifold,
and reconnect it to a cold water supply.
This will ensure that the water tempering
device operates properly.
Table 25-1:
Integral water tempering
specifications
Water type
Hot water
inflow
Cold water
inflow*
Tempered
water outflow
Maximum
low rate
U.S.
gpm
1245.414060
L/m°F°C
622.7212100
622.77021
Maximum
temperature
Water pump
Note:
Size water pump to handle a minimum of 12 gpm (45.4 L/m).
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 2 5
DC-1117
Note:
* Cold water inflow pressure must be between 25 psi
and 80 psi (172 kPa and 552 kPa).
Page 28
G a s p i p i n g
C a ut i o n! Supply the humidifier only
with the gas type (natural gas or LP gas)
listed on the humidifier name plate or
burner failure will result. To convert the
humidifier to natural gas or LP gas, contact
DRI-STEEM technical support or your
DRI-STEEM representative/distributor.
C a ut i o n! Gas pressure to the
humidifier controls must never exceed
24" wc (6 kPa, 60 mbar) or the gas
valve will become damaged and require
replacement. Install a 1/8" pipe thread
(DN6) plugged tapping, accessible for test
gauge connection, immediately upstream of
the gas supply connection to the appliance.
I m po r t an t : For North American
models, the recommended supply pressure
is 7" wc (1.75 kPa) for natural gas or
11" wc (1.83 kPa) for LP gas.
For European models, the required supply
pressure is 20 or 25 mbar for natural gas
and 30, 37, or 50 mbar for propane gas.
Gas piping guidelines
• After threading and reaming the ends of the pipes, inspect piping
and remove loose dirt and chips.
• Support piping so there are no strains imposed on unit
or controls.
• Use two wrenches when connecting piping to unit or controls.
• Provide a drip pocket before each unit and in the line where low
spots cannot be avoided.
• Takeoff to unit should come from top or side of main to avoid
trapping condensate.
• Piping that is subject to wide temperature variations should be
insulated.
• Pitch piping up toward unit at least ¼" (6 mm) per 15' (4.5 m) of
horizontal run.
• Compounds used on threaded joints of gas piping must be
resistant to the harmful action of liquefied petroleum gases.
W A R N I N G !
Purge air before lighting unit by disconnecting piping at gas control.
In no case should line be purged into heat exchanger. Failure to follow
these instructions could cause an explosion or fire resulting in bodily
injury, death, or significant property damage.
• After installation, check field piping and humidifier gas train for
gas leaks.
• Do not use soap solution or open flame on humidifier gas train.
A gas leak detector is recommended.
• Install a ground joint union and a manual shutoff valve
immediately upstream of the unit. Install a plugged tapping
upstream of the shut-off valve, accessible for test gauge
connection. Pressure tappings for test gauges are located on all
gas valves.
• Allow at least 5' (1.5 m) of piping between any high pressure
regulator and unit pipe connection.
• Piping installation must conform to the requirements of
the authority having jurisdiction or, in the absence of such
requirements, must conform to:
In the United States: The National Fuel Gas Code, ANSI Z223.1
(latest edition).
In Canada: Local plumbing or waste water codes and other
applicable codes and with the current code CAN/CGS-B149.1,
More gas piping instructions on the next page ▶
Pag e 2 6 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 29
G a s p i p i n g ( c o n t i n u e d )
“Installation Code for Natural Gas Burning Appliances and
Equipment,” or CAN/CGA-B149.2, “Installation Code for
Propane Burning Appliances and Equipment.”
In Europe: The National Gas Safety (Installation & Use)
Regulations.
• Do not use flexible connectors.
• Piping to units should conform with local and national
requirements for type, volume, and gas handled and for pressure
drop allowed in the line. Refer to the tables on this page to
determine the gas flow in ft3/hr or m3/hr for the type of gas and
size of unit to install. Using this value and the length of pipe
necessary, determine the pipe diameter. Where several units are
served by the same main, the total capacity, gas flow, and length
of main must be considered. Avoid pipe sizes smaller than ½"
(DN15). Table 27-2 below allows for the usual number of
fittings with a 0.3" wc (0.07 kPa) pressure drop.
• When the specific gravity of the gas is other than 0.60 for natural
gas or 1.53 for propane, use Table 27-1.
Table 27-2:
Gas pipe capacities for gas pressures of 0.5 psig (3.45 kPa) or less
Gas flow in piping in ft3/hr and m3/hr at
pressure drop of 0.3" wc (0.07 kPa)
Length
of pipe
Nominal iron pipe diameter in inches (DN)
Specific gravity = 0.60
Table 27-1:
Specific gravity conversion factors
Natural gas
Specific gravityFactor
0.551.04
0.601.00
0.650.962
Propane gas
Specific gravityFactor
1.500.633
1.530.626
1.600.612
Note:
Use the above multiplying factor with Table: 27-2
when the specific gravity of gas is other than 0.60
(natural gas) or 1.53 (propane).
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 2 7
Page 30
G a s p i p i n g ( c o n t i n u e d )
Gas leak testing
• When leak-testing the gas supply piping
system, disconnect the humidifier and
its gas shutoff valve during any pressure
in excess of 24" wc (6 kPa). Isolate the
humidifier from the gas supply piping
system by closing its field-installed
manual shutoff valve during any pressure
not equal to 24" wc (6 kPa).
• With all burners running, check gas
supply pressure at the inlet pressure tap
of the combination gas control valve.
For North American models, the
recommended supply pressure is
7" wc (1.75 kPa) for natural gas or
11" wc (1.83 kPa) for LP gas. Perform
gas piping purging as described in ANSI
Z223.1 (latest edition) or in Canada, CAN/
CGA-B149 codes. The minimum supply
pressure is 6" wc (1 kPa) for natural gas
or LP gas.
For European models, the required supply
pressure is 20 or 25 mbar for natural gas
and 30, 37, or 50 mbar for propane gas.
Example
For this example, refer to the tables on the previous page.
To determine gas piping size, begin by calculating the cubic
feet/hour (ft3/hr) or m3/hr using the following formula:
Btuh (kW) input
Calorific value of gas
Calorific values are:
• Natural gas: 1025 Btu/ft3 (10.6 kW-hr/m3)
• Propane: 2500 Btu/ft3 (25.9 kW-hr/m3)
For example, if you have a GTS-400 operating on natural gas,
3
calculate the ft
400,000 Btuh
1025 Btu/ft
117.2 kW
10.6 kW-hr/m3
/hr or m3/hr as follows:
= 390 ft3/hr
3
= 11.1 m3/hr
If you need to run your gas piping 60 feet (18 m), see Table 27-2 on
the previous page and look horizontally across the 60 ft (18 m) row
until you locate the next highest value above your calculated ft3/hr
or m3/hr. In this example, you are looking for the next highest value
above 390 ft3/hr (11.05 m3/hr), which is 400 ft3/hr (11.3 m3/hr) and
indicates the use of a 1¼" (DN32) pipe for this application.
Using the same example, if the specific gravity of your natural
gas was 0.55 (instead of the 0.60 standard), see Table 27-2 for an
adjustment factor. In this case, the factor would be 1.04, which you
multiply by the 390 ft3/hr (11.05 m3/hr) value. This gives you a new
value of 406 ft3/hr (11.49 m3/hr). Referring again to the gas pipe
capacities table (Table 27-2), you see that for the same 60 ft (18 m)
length, you now need to use 1½" (DN40) pipe due to the change in
the specific gravity of the gas.
More gas piping instructions on the next page ▶
Pag e 2 8 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 31
G a s p i p i n g ( c o n t i n u e d )
Figure 29-1:
GTS gas piping
GTS or GTS-DI models 100, 200
½” pipe thread (DN15) piping
Plugged test
gauge connection
Gas cock
3” (76 mm) min.
GTS or GTS-DI models 300-800
Gas manifold (by DRI-STEEM)
Drip pocket
OM-1236
See Table 22-1 for
pipe size by model
Plugged test
gauge connection
Gas cock
3” (76 mm) min.
Note:
Dashed lines indicate supplied by installer
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 2 9
Drip pocket
OM-1235
Page 32
C o m b u s t i o n a n d v e n t i l a t i o n a i r
W A R N I N G !
Air for combustion must not be
contaminated by halogen compounds, which
include fluoride, chloride, bromide, and
iodide. These elements are found in aerosol
sprays, detergents, bleaches, cleaning
solvents, salts, air fresheners, and other
household products.
When the GTS is located in an environment
with negative pressure or toxic air, it must
have sealed combustion.
Failure to follow these instructions could
cause severe bodily injury or death.
Combustion and ventilation air
The GTS supports both room air and sealed combustion.
Requirements and recommendations for each follow.
Room air combustion
• All fuel burning equipment must be supplied with air for
combustion of the fuel. Sufficient air must be provided to ensure
there is not a negative pressure in the equipment room or space.
• Provide adequate combustion and ventilation air in accordance
with Section 5.3, Air for Combustion and Ventilation, of the
National Fuel Gas Code, ANSI Z223.1 or applicable provisions
of governing codes. Canadian installations must be installed in
accordance with sections 7.2, 7.3, and 7.4 of the CAN/CGA.B149
Installation Codes and all authorities having jurisdiction.
• For proper and safe operation this appliance needs air for
combustion and ventilation. Do not block or obstruct air
openings on the appliance, spaces around the appliance, or air
openings communicating with the appliance area.
• Do not locate in a dusty environment.
• Do not block the flow of combustion and ventilation air. To
provide for necessary oxygen for proper combustion, openings
must be provided to allow outside air to enter the space where the
humidifier is located. Enclosed spaces, such as equipment rooms,
must be vented for combustion air. The size of air openings must
be based on all gas-burning equipment installed in the space
involved. Table 30-1 outlines four types of locations, and the
requirements of each.
Sealed combustion
Table 30-1:
Location of humidifier and required air openings
Location descriptionRequired air opening
Confined space with all air from inside the
building; conventional frame, brick or stone
construction with normal infiltration (Note:
this location rarely provides enough air for
higher capacity units.)
Confined space with all air from outside the
building through air ducts
Confined space with all air from outside the
building from through-wall openings only
(no ducts)
Unconfined space with all air from outside
the building
Note:
* The minimum dimension of any opening is 3" × 3" (76 mm × 76 mm).
Pag e 3 0 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
More instructions on the next page ▶
Two openings, 1 sq. in. (6.5 cm2) per
opening per 1000 Btu/hr (293 W) input
The minimum free area of all openings
combined is 100 sq. in. (645 cm2).
Two openings, 2 ducts, 1 sq. in. (6.5 cm2)
per opening per 2000 Btu/hr (586 W) input*
Two openings, 1 sq. in. (6.5 cm2) per
opening per 4000 Btu/hr (1172 W) input*
Same as confined space; all air from outside
the building
Page 33
C o m b u s t i o n a n d v e n t i l a t i o n a i r
( c o n t i n u e d )
The GTS supports sealed combustion using 4" (DN100) PVC or
CPVC piping (see Figure 31-1). All GTS models have a single
point connection to the blower below the humidifier shroud.
When running PVC or CPVC piping for sealed combustion,
the maximum allowable distance to the outdoor air source is 70'
(21.3 m) including 7' (2.1 m) equivalent length for each elbow.
The outside air source can be either a final connection outside
the building or a connection to an outdoor air plenum within the
building. When the combustion air origination point is outside the
building, the opening must be covered with a large mesh screen to
prevent the introduction of unwanted materials without restricting
airflow.
If sealed combustion piping is less than 20 ft (6 m), we recommend
insulating piping to prevent condensation.
When installing sealed combustion piping
for more than one GTS humidifier, do
not commonly manifold multiple sealed
combustion piping runs without having the
manifold sized for the specific installation by
a licensed engineer. Failure to follow these
instructions could starve the GTS humidifier
of combustion air resulting in either the
unit not being able to light or high carbon
monoxide (CO) levels, which may cause
severe personal injury or death.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 3 1
4" dia. (DN100) PVC
or CPVC combustion
air intake
OM-1225
Page 34
W A R N I N G !
The humidifier must be installed by
a qualified technician and meet the
requirements of all governing codes. Failure
to follow these instructions could cause
severe bodily injury or death.
Note:
For European models, contact your
distributor for horizontal venting parts.
Ve r t i c a l a n d h o r i z o n t a l v e n t i n g
Vertical and horizontal venting guidelines (stack connection)
• The GTS is a Fan Assisted Category I (natural draft) Appliance.
Installations where the vent terminates in a side wall of the
building, or where the overall horizontal run exceeds the overall
vertical run require a power venter. See Page 34.
• Maximum flue temperature is 400 °F (205 °C) + ambient.
• Flue draft negative pressure greater than 0.2" wc (50 Pa) may cause
unacceptable post ignition.
• Vent piping must be UL or UL/CSA listed type B, B-W, or any
other vent type approved for a Category I appliance.
– Type B: Double wall construction, inner wall aluminum, outer
wall galvanized steel
– Type B-W: Same as type B except fabrication in oval shapes only
Do not use more than one type of venting per application Required
clearance for Type B and B-W vent piping is 1" (25 mm).
• Do not use vent equipment from more than one manufacturer.
• When connecting the humidifier to a gas vent or chimney,
installation must be in accordance with Part 7, Venting of
Equipment, of the National Fuel Gas Code, ANSI Z223.1; or
Section 7, Venting Systems and Air Supply Appliances, of the
CAN/CGA B149 Installation Codes; or National Gas Safety Code
(Installation & Use) Regulations (latest revision); governing codes,
and the vent manufacturer’s instructions.
• When applying the codes, reference also the venting
manufacturer's instructions, the service gas supplier's regulations,
and the specific instructions provided in this manual.
C A UT I O N! Install a drip tee or flue box condensate drain for startup flue condensate removal. Failure to follow these instructions could
cause water to accumulate in the flue box.
• The purpose of venting the gas humidifier is to completely remove
all products of combustion and ventilation gases to the outside air.
• For vertical vent pipe terminations only: Do not reduce the vent
diameter and avoid short turns in the vent piping. Use the same
size stack as the vent furnished with the humidifier. Maintain a
minimum upward slope of ¼" per linear foot (2%) on all horizontal
runs. Maintain proper support of vent connections and joints.
Observe clearances (in accordance with applicable codes) from all
combustible materials and install an approved cap for the stack
outlet. The bottom of the cap must be one stack diameter above the
top of the stack.
• Inspect for proper and tight construction. Remove any restrictions
or obstructions. An existing chimney may require cleaning.
• For vertical vent pipe terminations only: Extend chimney or vent at
least 3' (1 m) above its passage through a roof and at least 2' (0.6 m)
above any ridge within 10' (3 m) of the chimney (governing codes
apply).
• Do not connect this humidifier to a chimney flue servicing a
separate appliance designed to burn solid fuel.
Pag e 3 2 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
More instructions on the next page ▶
Page 35
Ve r t i c a l a n d h o r i z o n t a l v e n t i n g
( c o n t i n u e d )
• Never connect this humidifier to a chimney serving a fireplace,
unless the fireplace opening is permanently sealed off.
• Code prohibits venting into an unlined masonry or concrete
chimney.
• If this humidifier is connected to a lined, masonry chimney, the
chimney must be sized and installed according to the provisions
of the National Fuel Gas Code or Canadian CAN/CGA.B149
requirements, or governing codes.
• Vent connector serving this appliance shall not be connected into
any portion of mechanical draft systems operating under positive
pressure.
• Add insulation to any roof or wall penetration vent connector
that is exposed to ambient temperatures of 30 °F (0 °C) or
less, especially any application using single-wall vent pipe as a
connector.
• Do not insulate vent pipe exposed to outdoor weather conditions
(e.g., above roof lines).
• Install vent piping as direct as possible, with a minimum number
of turns or elbows.
• Rigidly support the vent pipe every 5' (1.5 m) or less with hangers
or straps to ensure there is no movement after installation. The
humidifier vent box should not support the weight of the vent
piping.
• No portion of the vent system should extend into, or pass through,
any circulation air duct or plenum.
• The vent system must terminate above the roof surface per the
National Fuel Gas Code, CAN/CGA.B149, or National Gas
Safety Code (Installation & Use) Regulations (latest revision)
requirements or governing codes, and must include a UL or
UL/CSA listed vent cap or roof assembly, unless prohibited by
governing codes.
• For vertical vent pipe terminations only: This humidifier may be
commonly vented with other listed Category I gas-fired appliances.
Total input rates of all appliances determines the vent size.
• Install and fire-stop all vent pipe passing through floors, ceilings,
and walls with the proper clearances from combustible material
according to the National Fuel Gas Code, Canadian Standards
CAN/CGA.B149, the National Gas Safety Code (Installation &
Use) Regulations (latest revision), or governing codes.
• In replacement installation where an existing vent system may
be used, inspect the vent system for condition, size, type of
vent material, and height to meet the requirements in these
instructions. When connecting the humidifier to a gas vent or
chimney, the installation must be in accordance with Part 7,
Venting of Equipment, of the National Fuel Gas Code, ANSI
Z223.1; Section 7, Venting Systems and Air Supply Appliances, of
the CAN/CGA B149 Installation Codes; The National Gas Safety
Code (Installation & Use) Regulations (latest revision), governing
building codes, and the vent manufacturer’s instructions.
W A R N I N G !
For applications where the vent pipe
terminates in a vertical position, the
horizontal length of the vent and vent
connector must not exceed the height of
the vent system unless a power venter is
used. Failure to follow these instructions
could cause flue gases to exit the vent piping
causing severe personal injury or death.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 3 3
Page 36
Ve r t i c a l a n d h o r i z o n t a l v e n t i n g
( c o n t i n u e d )
Table 34-1:
Equipment required for horizontal
venting
Field controls
model number
Item
Power venterPVO-600 (5")PVE-1200 (8")
Barometric
damper
Vent hoodSWH-1-5 (5")SWH-8
Electrical
ratings
Note:
For European models, contact your distributor for
horizontal venting parts.
for GTS or
GTS-DI models
100, 200,
300, 400
MG-1 (5")MG-1 (8")
120 VAC
60 Hz
2.1 A
Field controls
model number
for GTS or
GTS-DI models
500, 600, 700,
and 800
120 VAC
60 Hz
2.5 A
Table 34-2:
Recommended minimum vent sizes
Minimum vent size
Model
Vertical ventHorizontal vent
Special horizontal venting requirements
• Ensure that distances from the vent terminal to adjacent public
walkways, buildings, and openable windows and building
openings are consistent with the National Fuel Gas Code, ANSI
Z223.1, CAN/CGA B149 Installation Codes, National Gas
Safety Code (Installation & Use) Regulations (latest revision), or
governing codes.
• In areas accessible to the public, the vent terminal must be at
least 7' (2.1 m) above ground level to prevent burns from the hot
terminal surface.
• The vent terminal and air intake locations must be at sufficient
height above ground level to prevent blocking by expected
snowfall.
• Building materials must be protected from degradation by flue
gases.
• A minimum horizontal clearance of 4' (1.22 m) from electric
meters, gas meters, regulators, and relief equipment must be
maintained.
• Maximum equivalent length of vent pipe is 100' (30 m).
Minimum equivalent length of vent pipe is 10' (3 m). See power
venter installation manual for equivalent lengths of fittings.
• Vent box pressure must be –0.01" wc (–2.5 Pa). Set by adjusting
power venter and barometric damper, with all burners running
(see manufacturer's instructions included with power venter and
damper).
inchesmminchesmm
GTS-10051305130
GTS-20051305130
GTS-30071805*130
GTS-40071805*130
GTS-50082058205
GTS-60082058205
GTS-700102558*205
GTS-800102558*205
Note:
* For best results, make transition to smaller vent
diameter as close to the power venter as possible.
*
Figure 34-1:
GTS venting
I m po rt a nt : Seal the connection and all other vent
piping joints on the pressure side of the power venter.
Vent hood
Distance**
Air intake
3½' (1.07 m)
min.
Air
intake
Notes:
* Install a tee after the first elbow from the humidifier as shown. Use the open end of
this tee for the location of the barometric damper.
** Required distance between air intake and vent hood is defined by governing codes.
Refer to power venter manual for clearance requirements relative to combustion air
openings.
Power venter
“x”
Recommended value
for “x” approximately
12" (305 mm)
Barometric draft control
installed in tee*
OM-1209
Pag e 3 4 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 37
D i s p e r s i o n : G e n e r a l i n s t r u c t i o n s
Selecting the dispersion assembly location
• For each dispersion device, DRI-STEEM documents distances
required for absorption to occur. If you have questions about
absorption distances, see the absorption tables in the U.S. English
version of the GTS catalog, available for viewing, printing, or
ordering at www.dristeem.com
• It is important that the dispersion assembly is positioned where
the water vapor being discharged is carried off with the airstream
and is absorbed before it can cause condensation or dripping in
the duct.
• In general, the dispersion assembly is best placed where the
air can most readily absorb the moisture being added without
causing condensation at or after the unit. This normally is after
the heating coil or where the air temperature is highest.
• Place the dispersion assembly so that absorption occurs before
the intake of a high efficiency filter. The filter can remove the
visible moisture and become waterlogged.
• Place the dispersion assembly so absorption occurs before coming
in contact with any metal surface.
• Place the dispersion assembly so absorption occurs before fire or
smoke detection devices.
• Place the dispersion assembly so absorption occurs before a split
in the duct. Otherwise, the dispersion assembly may direct more
moisture into one duct than the other.
• When draining dispersion condensate to an open drain, provide
a 1" (25 mm) gap between the condensate drain piping and the
drain. Locate air gap only in spaces with adequate temperature
and air movement to absorb flash steam; otherwise, condensing
on nearby surfaces may occur.
Where to find more information
On our Web site:
The following documents can be viewed,
printed or ordered from our web site,
loss tables and general humidification
information)
In Dri-calc:
Dri-calc is our humidification system sizing
and selection software, which can be
ordered at www.dristeem.com.
Included in Dri-calc:
• A comprehensive library of installation
guide documents, including:
– Rapid-sorb installation instructions
for vertical airflows
– Recommended dispersion placement
within a duct or air handler
– Recommended sensor placement
(includes steam
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 3 5
Or call us at 800-328-4447
While obtaining documents from our Web
site or from Dri-calc is the quickest way to
review our literature, we will also mail to
you any literature you need.
Page 38
D i s p e r s i o n : I n t e r c o n n e c t i n g p i p i n g
r e q u i r e m e n t s
W A R N I N G !
The evaporating chamber is designed as a
non-pressurized vessel. DO NOT restrict piping where steam exits the humidifier.
DO NOT install a shut-off valve on the piping
connecting the evaporating chamber to the
steam outlet.
C A UT I O N!
Failure to follow the recommendations in
this section can result in excessive back
pressures on the humidifier. This will result
in unacceptable humidification system
performance such as leaking gaskets, blown
water seals, erratic water level control, and
spitting condensate from the dispersion
tube(s).
Connecting humidifier to dispersion assembly with vapor hose
• Always support vapor hose to prevent sags or low spots and to
maintain a minimum pitch of 2"/ft (15%) back to the humidifier.
• See the maximum steam carrying capacity table on the next page.
• Use DRI-STEEM vapor hose. Other manufacturers of vapor
hose may use unacceptable release agents or material mixes
that can affect humidifier system performance adversely. Using
hose from alternative manufacturers increases the possibility of
tank foaming and accelerated aging. Foaming causes condensate
discharge at the dispersion assembly.
• Do not use vapor hose in outdoor applications.
• Do not insulate vapor hose. Insulation causes accelerated heat
aging, causing the vapor hose to become hard and susceptible to
failure due to cracks.
• The steam outlet on the humidifier is sized to the output of the
humidifier. DO NOT use hose with an inside diameter (ID)
smaller than the humidifier steam outlet.
• If the humidifier must be located above the dispersion assembly,
use the recommended installation as shown on Page 38.
• For single tube applications, see the hose kit sizing table on
Page 39.
Connecting humidifier to dispersion assembly
with tubing or pipe
• See the table on Page 40 for interconnecting tubing and pipe
pitch requirements for single tube and multiple tube applications.
See the table on Page 45 for interconnecting tubing and pipe
pitch requirements for Rapid-sorb applications.
• The steam outlet on the humidifier is sized to the output of the
humidifier. DO NOT use interconnecting tubing or pipe with an
inside diameter (ID) smaller than the humidifier steam outlet.
C A UT I ON ! Reducing the inside diameter of the
interconnecting piping will result in the internal humidifier
system pressure exceeding the parameters for acceptable
performance.
• Steam supply adapters are available from DRI-STEEM. These
adapters convert a tubing outlet on the humidifier to threaded
pipe, allowing a pipe connection.
• 90° elbows are not recommended; use two 45° elbows, 1' (0.3 m)
apart.
• Thin wall tubing heats up faster and causes less start-up loss than
heavy wall pipe.
More on the next page ▶
Pag e 3 6 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 39
D i s p e r s i o n : I n t e r c o n n e c t i n g p i p i n g
r e q u i r e m e n t s ( c o n t i n u e d )
Connecting humidifier to dispersion assembly with tubing or
pipe (continued)
• Insulating hard pipe reduces the loss in output caused by
condensation.
• When using hard pipe, take care to remove ALL traces of
lubricants used to thread the pipe. This minimizes the possibility
of tank foaming. Denatured alcohol or mineral spirits work best
for removing lubricant.
• If the humidifier must be located above the dispersion assembly,
use the recommend installation as shown on Page 38.
• See the maximum steam carrying capacity table below.
Table 37-1:
Maximum steam carrying capacity and length of interconnecting vapor hose, tubing, and pipe*
Vapor hose
Hose I.D.Maximum capacity Maximum length**Tube or pipe size***Maximum capacity
†††
Copper or stainless steel tubing
and Schedule 40 steel pipe
Maximum developed
length
†
inchesDNlbs/hrkg/hftminchesDNlbs/hrkg/hftm
1½40150681031½4015068206
250250113103250220100309
125
150
††
††
††
††
4502048024
75034010030
140063510030
2300104310030
3†† 80
4†† 100
††
5
††
6
* Based on total maximum pressure drop in hose, tubing, or pipe of 5" wc (1244 Pa)
** Maximum recommended length for vapor hose is 10' (3 m). Longer distances can cause kinking or low spots.
*** To minimize loss of capacity and efficiency, insulate tubing and pipe.
†
Developed length equals measured length plus 50% of measured length to account for pipe fittings.
††
Requires flange connection
†††
When using vapor hose, use DRI-STEEM vapor hose for best results. Field-supplied hose may have shorter life and may cause foaming in the evaporating
chamber resulting in condensate discharge at the dispersion assembly. Do not use vapor hose for outdoor applications.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 3 7
Page 40
Figure 38-1:
Drip tee installation (piping over an obstruction)
90° long sweep or
two 45° elbows
D i s p e r s i o n : D r i p t e e i n s t a l l a t i o n
Install a drip tee as shown below
• When the humidifier is mounted higher than the dispersion
assembly
• When interconnecting hose or piping needs to go over an
obstruction
• When interconnecting piping runs are long
I m po r t an t : Vapor hose must be supported to prevent sagging
or low spots.
Pitch
Obstruction
Insulate tubing and hard pipe
to reduce steam loss
To dispersion assembly
Tubing or pipe drip tee, by installer.
6" (150 mm) minimum
8" (200 mm) minimum
1" (25 mm) air gap
Open drain required. See first note below.
Notes:
• Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam, or condensing on nearby surfaces may occur. Refer to
governing codes for drain pipe size and maximum discharge water temperature.
• Support vapor hose so there are no sags or low spots
• Dashed lines indicate provided by installer
DRI-STEEM part numbers for 304 stainless steel in-line tees:
• 1½" diameter (DN40): No. 162710
• 2" diameter (DN50): No. 162712
¾" (DN20)
GTS humidifier
OM-1210
Pag e 3 8 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 41
D i s p e r s i o n : S i n g l e tu b e a n d
m u l t i p l e t u b e
Installation
• See the following pages for detailed drawings and notes for
installing single tube and multiple tube dispersion assemblies.
• See the hose kit sizing table on this page for single tube
applications.
Dispersion tube mounting
• Orient dispersion tube(s) so that tubelets (steam orifices)
point up.
• See the table on the next page for dispersion tube pitch
requirements.
• When mounting the humidifier above the level of the dispersion
tube(s), see the drip tee installation drawing on Page 38.
Condensate drain piping
• Minimum diameter (ID) for draining from one or two dispersion
tubes: ¾" (DN20)
• Minimum diameter (ID) for draining from three or more
dispersion tubes: 1" (DN25)
• Condensate drain piping must be rated for 212 °F (100 °C)
continuous operating temperature.
• Condensate drain line must be piped as shown in the figures
on the following pages. Provide a 6" (152 mm) drop prior to a
5" (127 mm) water seal to:
− Ensure drainage of condensate from the header
− Keep steam from blowing out of the drain line
• After the water seal, run the drain line to an open drain with a 1"
(25 mm) vertical air gap. Cut the drain line at a 45° angle on the
end above the drain to permit a direct stream of water into the
drain pipe while maintaining a 1" (25 mm) air gap. Locate air gap
only in spaces with adequate temperature and air movement to
absorb flash steam, or condensing on nearby surfaces may occur.
• All drain lines must be installed and sized according to governing
codes.
C A UT I O N!
Failure to follow the recommendations in
this section can result in excessive back
pressures on the humidifier. This will result
in unacceptable humidification system
performance such as leaking gaskets, blown
water seals, erratic water level control, and
spitting condensate from the dispersion
tube(s).
Table 39-1:
Hose kit sizing by capacity
Maximum
tube capacity
lbs/hrkg/h
28.4131½" (DN40) without drain
56.825.8
85.238.62" (DN50) with drain
> 85.2>38.6
Notes:
• Assemble multiple dispersion tubes or use a
Rapid-sorb or Ultra-sorb dispersion assembly where
necessary to accommodate maximum humidifier load.
• The smallest GTS humidifier steam outlet is 2"
(DN50). Install an adaptor manifold if using multiple
1½" (DN40) dispersion tubes.
Hose kit
(vapor hose, dispersion tube,
and hardware)
1½" (DN40) with drain
2" (DN50) without drain
These models require multiple
tube assemblies and cannot use
a single hose kit.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 3 9
Page 42
D i s p e r s i o n : S i n g l e tu b e a n d
m u l t i p l e t u b e ( c o n t i n u e d )
Table 40-1:
Pitch of dispersion tube(s) and interconnecting piping for single tube or multiple tube evaporative dispersion units*
Condensate drain
Without drain
With drain
Notes:
* When piping over an obstruction, see the drip tee installation illustration on Page 38.
• Assemble multiple dispersion tubes or use a Rapid-sorb or Ultra-sorb dispersion assembly where necessary to accommodate maximum humidifier load.
• The smallest GTS humidifier steam outlet is 2" (DN50). Install an adaptor manifold if using multiple 1½" (DN40) dispersion tubes. See also Table 37-1.
Type of
interconnecting piping
Vapor hose
Tubing or pipe
Vapor hose
Tubing or pipe
Diameter of
dispersion tube and
interconnecting piping
1½" (DN40)
2" (DN50)
1½" (DN40)
2" (DN50)
1½" (DN40)
2" (DN50)
1½" (DN40)
2" (DN50)
Pitch of
interconnecting piping
2"/ft (15%)
toward humidifier
1/8"/ft (1%)
toward humidifier
2"/ft (15%)
toward humidifier
½"/ft (5%)
toward humidifier
¼"/ft (2%)
toward humidifier
Pitch of
dispersion tube(s)
2"/ft (15%)
toward humidifier
1/8"/ft (1%)
toward
condensate
drain
Pitch of
condensate drain
No drain
¼"/ft (2%)
toward floor drain or
toward humidifier if
humidifier is below
dispersion unit
Pag e 4 0 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 43
D i s p e r s i o n : S i n g l e tu b e a n d
m u l t i p l e t u b e ( c o n t i n u e d )
Figure 41-1:
Single tube dispersion with condensate wasted to floor drain
Vapor hose, tubing or
pipe. Insulate tubing
and hard pipe to reduce
steam loss. Do not
insulate vapor hose.
90° long sweep
or two 45°
elbows
Secure and seal
escutcheon plates
Pitch
(see Notes)
Duct
Maximum capacity of dispersion tube:
• 1½" dia. (DN40): 56.8 lbs/hr
(25.8 kg/h)
• 2" dia. (DN50): 85.2 lbs/hr
(38.6 kg/h)
3/8" (M10)
mounting nut
6" (152 mm)
recommended
GTS humidifier
Notes:
1 Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam, or condensing on nearby surfaces my occur.
Refer to governing codes for drain pipe size and maximum discharge water temperature.
2 Assemble multiple dispersion tubes or use a Rapid-sorb or Ultra-sorb dispersion assembly where necessary to accommodate maximum humidifier load.
3 The smallest GTS humidifier steam outlet is 2" (DN50). Install an adaptor manifold if using multiple 1½" (DN40) dispersion tubes. See also Table 37-1.
4 Pitch vapor hose, tubing or pipe toward humidifier:
– 2"/ft (15%) when using vapor hose
– ½"/ft (5%) when using 1½" tubing or pipe
– ¼"/ft (2%) when using 2" tubing or pipe
5 Dashed lines indicate provided by installer
Water seal
5" (127 mm)
1" (25 mm)
air gap
Table 41-1:
Dispersion tube and condensate drain
escutcheon plate dimensions
Condensate drain tube,
by installer, minimum ¾"
(DN20); must be suitable
for 212 °F (100 °C) water
Open drain required. See Note 1 below.
Figure 41-2:
Dispersion tube and condensate drain
escutcheon plates
Dispersion tube plate
(diameter)
Condensate drain plate
(diameter)
Pitch tube toward
drain 1/8"/ft (1%)
B
A
B
D
C
D
OM-1212a
OM-351c
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 4 1
Page 44
Figure 42-1:
Single tube with condensate returned to humidifier
Vapor hose, tubing,
or pipe
90º long sweep or
two 45° elbows
Secure and seal
escutcheon plates
Pitch (See Notes)
Dispersion tube
D i s p e r s i o n : S i n g l e tu b e a n d
m u l t i p l e t u b e ( c o n t i n u e d )
Maximum capacity of dispersion tube:
• 1½" dia. (DN40): 56.8 lbs/hr
Duct
(25.8 kg/h)
• 2" dia. (DN50): 85.2 lbs/hr
(38.6 kg/h)
Mounting
nut, 3/8"
(M10)
GTS humidifier
½" (13 mm)
air vent
6" (152 mm)
minimum
H (see table, Page 20)
6" (152 mm)
minimum
5" (127 mm)
water seal
Notes:
1 Assemble multiple dispersion tubes or use a Rapid-sorb or Ultra-sorb dispersion
assembly where necessary to accommodate maximum humidifier load.
2 The smallest GTS humidifier steam outlet is 2" (DN50). Install an adaptor manifold
if using multiple 1½" (DN40) dispersion tubes. See also Table 37-1.
3 Pitch vapor hose, tubing or pipe toward humidifier:
– 2"/ft (15%) when using vapor hose
– ½"/ft (5%) when using 1½" (DN40) tubing or pipe
– ¼"/ft (2%) when using 2" (DN50) tubing or pipe
4 Dashed lines indicate provided by installer
Condensate drain tube, by installer, ¾" DN20 minimum. Return line piping material must
be suitable for 212 °F (100 °C) water. Note: Condensate may be returned to the humidifier
or wasted to a drain. See the previous page for piping condensate to a drain.
Figure 42-2:
Single tube dispersion with condensate drain
Thermal-resin tubelets
(steam orifice inserts)
OM-1215b
Pag e 4 2 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
¼" (DN8)
pipe thread
end
Mounting
bracket
½" O.D. (DN15) condensate drain
Movable escutcheon plate.
Plate can be mounted within
limits of 2.5" (64 mm).
OM-351b
Page 45
D i s p e r s i o n : S i n g l e tu b e a n d
m u l t i p l e t u b e ( c o n t i n u e d )
Figure 43-1:
Multiple tubes with condensate wasted to floor drain
Dispersion tube
Vapor hose, tubing,
or pipe
90° long sweep or
two 45° elbows
Secure and seal
escutcheon plates
Pitch (See Notes)
Duct
Pitch
Pitch
Maximum capacity of dispersion tube:
• 1½" dia. (DN40): 56.8 lbs/hr (25.8 kg/h)
• 2" dia. (DN50): 85.2 lbs/hr (38.6 kg/h)
Mounting
nut, 3/8"
(M10)
6"
(152 mm)
GTS humidifier
Notes:
1 Assemble multiple dispersion tubes or use a Rapid-sorb or Ultra-sorb dispersion
assembly where necessary to accommodate maximum humidifier load.
2 The smallest GTS humidifier steam outlet is 2" (DN50). Install an adaptor manifold
if using multiple 1½" (DN40) dispersion tubes. See also Table 37-1.
3 Pitch vapor hose, tubing or pipe toward humidifier:
– 2"/ft (15%) when using vapor hose
– ½"/ft (5%) when using 1½" (DN40) tubing or pipe
– ¼"/ft (2%) when using 2" (DN50) tubing or pipe
4 Dashed lines indicate provided by installer
Water seal
5" (127 mm)
1" (25 mm)
air gap
¼" (DN8)
pipe thread
Condensate drain tube provided by installer,
¾" (DN20) minimum
Open drain required.
Locate air gap only in spaces with adequate
temperature and air movement to absorb flash
steam, or condensing on nearby surfaces may
occur. Refer to governing codes for drain pipe
size and maximum discharge water temperature.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 4 3
Page 46
D i s p e r s i o n : R a p i d - s o r b
C A UT I O N!
Failure to follow the recommendations in
this section can result in excessive back
pressures on the humidifier. This will result
in unacceptable humidification system
performance such as leaking gaskets, blown
water seals, erratic water level control, and
spitting condensate from the dispersion
tube(s).
Table 44-1:
Rapid-sorb dispersion tube capacities
Tube capacityTube diameter
lbs/hrkg/hinchesDN
≤ 35≤ 161½40
36-7017-32250
Table 44-2:
Rapid-sorb header capacities
Header capacityHeader diameter
lbs/hrkg/hinchesDN
≤ 250≤ 113250
251-500114-227380
501-800228-3634100
General Rapid-sorb installation instructions
• Before you begin installation, read all dispersion instructions in
this manual.
• Before you begin installation, unpack shipment and verify receipt
of all Rapid-sorb components with packing list. Report any
shortages to DRI-STEEM factory immediately. The components
typically include the following:
– Multiple dispersion tubes
– Header
– ¾" × 2" (19 mm × 51 mm) L-bracket
– A single duct escutcheon plate the size of the header
– Slip couplings or hose cuffs and clamps.
– Accessories such as duct plates, slip couplings, or hose cuffs are
in a plastic bag.
– The bolts and washers for mounting the dispersion tubes to the
bracket will be in the end of the tubes or packaged in a bag with
the other accessories.
– The tubes, header, and L-bracket are tagged with the customer
requested identification number written on each component.
• When choosing a location for installation, select a location that
provides necessary access in and around the ductwork or air
handler.
• The Rapid-sorb typically is installed centered side to side in a
duct, or is installed across the face of a coil in an air handler.
• The center line of the outer dispersion tubes should never be
closer than 4.5" (114 mm) from the side of the ductwork or air
handler wall.
• Rapid-sorbs are provided with an L-bracket for installation:
– L-brackets that are 50" (1270 mm) or less in length have a hole
4" (102 mm) in from each end to mount the L-bracket to the
duct or air handler wall.
– L-brackets that are greater than 50" (1270 mm) in length have
an additional hole in the center of the L-bracket.
– I m p or t an t : Before marking and drilling holes in the duct or
air handler, refer to ALL pitch requirements for the Rapid-sorb
assembly you received (see the table on
Page 45). The size, quantity, and location of penetrations are
determined by the specific dimensions and configuration of the
Rapid-sorb assembly you received.
– Note: The hardware for mounting the L-bracket to the duct
or air handler wall and the hardware for the header support
bracket is not provided.
• The Rapid-sorb instructions that follow are for the most
typical Rapid-sorb installations — installed in a duct horizontal
airflow with Rapid-sorb header either inside or outside the
duct. See the Dri-calc Installation Guides library or contact
your representative/distributor or DRI-STEEM for installation
instructions for air handler or vertical airflow applications.
Pag e 4 4 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 47
D i s p e r s i o n : R a p i d - s o r b ( c o n t i n u e d )
Rapid-sorb pitch requirements
• When installing Rapid-sorb with the header outside a horizontal
airflow duct, consider the following pitch issues:
– For 1½" (DN40) dispersion tubes, use a fastener of sufficient
length to accommodate the 1/8"/ft (1%) pitch requirements
toward the ¾" pipe thread (DN20) header drain fitting.
– For 2" (DN50) dispersion tubes, the bracket can be mounted
flush to the ductwork. The 1/8"/ft (1%) pitch typically can be
accomplished in the length of the hose cuffs used to connect
the tubes to the header.
• See the table below and the drawings on the following pages for
pitch requirements.
Table 45-1:
Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb evaporative dispersion units
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 4 5
Page 48
D i s p e r s i o n : R a p i d - s o r b ( c o n t i n u e d )
Figure 46-1:
Rapid-sorb installed in a horizontal airflow with header outside the duct
Position L-bracket so that flange is upstream of
dispersion tubes. This drawing shows the L-bracket
positioned for airflow back to front
Dispersion tube
Point tubelets (steam orifices)
perpendicular to airflow
90° long sweep or
two 45° elbows
Vapor hose,
tubing, or pipe
Note:
* Pitch vapor hose, tubing, or
pipe toward Rapid-sorb:
– 2"/ft (15%) when using
vapor hose
– 1/8"/ft (1%) when using
tubing or pipe
Slip coupling or hose cuff
Pitch*
Pitch header toward drain
1/8"/ft (1%)
GTS humidifier
(DN20) condensate drain
¾" (DN20) copper
1" (25 mm) air gap
Open drain required.
Locate air gap only in spaces with adequate
temperature and air movement to absorb flash
steam, or condensing on nearby surfaces may
occur. Refer to governing codes for drain pipe
size and maximum discharge water temperature.
Stainless Steel Support
by DRI-STEEM
¾" pipe thread
Airflow
Duct
Secure and seal
escutcheon plates
5" (127 mm)
Support bracket
6" (152 mm)
OM-1214
Assembly and installation instructions for a Rapid-sorb installed
with header outside the duct (horizontal airflow)
1. Locate and cut the holes in the ductwork for the dispersion
tubes. Use the L-bracket as a template to locate the holes on the
duct floor.
2. Temporarily, loosely suspend or support the header below the
final location — the vertical balance point of the dispersion
tube length dictates where the header should be suspended or
supported temporarily.
3. Mount the dispersion tubes to the header with the provided
connector, either a slip coupling or a hose cuff.
• When installing slip couplings for 1½" (DN40) dispersion
tubes, take care not to shear the O-rings.
• Set the slip coupling on the header stub or dispersion tube so
the O-ring is resting on the face of the tubing.
• Rotate the slip coupling as you push it on to the tubing.
• The O-rings are lubricated at the factory. If additional
lubrication is necessary, DO NOT use a petroleum-based
lubricant.
4. Position the flange of the L-bracket so it is upstream of the
tubes when the assembly is raised and fastened into position.
Fasten the L-bracket to the end of the dispersion tubes with the
provided bolt, lock washer, and flat washer.
More on next page ▶
Pag e 4 6 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 49
D i s p e r s i o n : R a p i d - s o r b ( c o n t i n u e d )
Assembly and installation instructions for a Rapid-sorb installed
with header outside the duct (continued)
5. Before tightening the L-bracket bolts to the dispersion tubes
follow these instructions:
• For 1½" (DN40) dispersion tubes:
– The dispersion tube will rotate in the slip
coupling. Verify that the dispersion tube orifices are
directed perpendicular to the airflow.
– The dispersion tube and slip coupling must be fully
engaged on to the header stub for the O-rings to provide a
seal.
• For 2" (DN50) dispersion tubes:
– Before securing the hose cuff in place with the hose clamps
on the dispersion tube and the header stub, verify that the
dispersion tube orifices are directed perpendicular to the
airflow.
6. Slide the assembly up until the L-bracket aligns with the
mounting holes in the duct.
• For 1½" (DN40) dispersion tubes:
– The header pitch is duplicated in the L-bracket.
– The dispersion tube and slip coupling must be fully
engaged on to the header stub for the O-rings to provide a
seal.
– The high end of the L-bracket can be fastened tight to the
duct or air handler.
– On the low end of the L-bracket, the fastener must be long
enough to compensate for the pitch, and a nut should be
provided and secured on both sides of the L-bracket and
the duct or air handler for stability.
• For 2" (DN50) dispersion tubes:
– Fasten the bracket to the top of the duct and use the hose
cuffs to compensate for the pitch of the header.
– Before securing the hose cuff in place with the hose clamps
on the dispersion tube and the header stub, verify that the
header pitch, 1/8"/ft (1%) toward drain, is maintained.
Note:
See Page 46 for steam supply and
condensate drain line connection
instructions.
7. Permanently secure both ends of the header and verify that the
header pitch, 1/8"/ft (1%) toward drain, is maintained.
8. Verify that all fasteners are secure:
• L-bracket to duct
• Dispersion tubes to L-bracket
• Hose clamps on 2" (DN50) tubes
9. Secure and seal the dispersion tube escutcheon plate and
condensate drain tube escutcheon plate around the respective
tubes, if applicable.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 4 7
Page 50
D i s p e r s i o n : R a p i d - s o r b ( c o n t i n u e d )
Figure 48-1:
Rapid-sorb installed in a horizontal airflow with header inside the duct
Position L-bracket so that flange is upstream
of dispersion tubes. This drawing shows the
L-bracket positioned for airflow back to front
Dispersion tube
Point tubelets (steam orifices)
perpendicular to airflow
90° long sweep or
two 45° elbows
Vapor hose,
tubing, or pipe
Note:
* Pitch vapor hose, tubing,
or pipe toward Rapid-sorb:
– 2"/ft (15%) when
using vapor hose
– 1/8"/ft (1%) when
using tubing or pipe
Slip coupling or hose cuff
Pitch*
Secure and seal
escutcheon plate
Pitch header
toward drain
1/8"/ft (1%)
GTS humidifier
Stainless Steel Support
by DRI-STEEM
Airflow
Duct
¾" pipe thread
(DN20) drain
¾" (DN20) copper
1" (25 mm) air gap
Open drain required.
Locate air gap only in spaces with adequate
temperature and air movement to absorb flash
steam, or condensing on nearby surfaces may
occur. Refer to governing codes for drain pipe
size and maximum discharge water temperature.
5" (127 mm)
6" (152 mm)
Support bracket
OM-1213
Assembly and installation instructions for a Rapid-sorb installed
with header inside the duct (horizontal airflow)
1. Locate and cut the holes in ductwork or air handler for steam
header penetration, condensate drain piping, and header support
bracket fastener. Allow 1/8"/ft (1%) header pitch toward the
support bracket when you drill the hole for the header support
bracket fastener.
2. Loosely fasten the header in place.
3. Rotate the header 90° so the header stubs point horizontally in
the duct.
• When installing in an air handler, the rotation of the header
is often less than 90°. Typically, due to the condensate drain
piping requirements, the header can be set on the floor of the
air handler, assembled in the vertical position, and then raised
and mounted in place.
4. Mount the dispersion tubes on the header with the slip
couplings or hose cuffs.
• When installing slip couplings for 1½" (DN40) dispersion
tubes, take care not to shear the O-rings.
• Set the slip coupling on the header stub or dispersion tube so
the O-ring is resting on the face of the tubing.
More on next page ▶
Pag e 4 8 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 51
D i s p e r s i o n : R a p i d - s o r b ( c o n t i n u e d )
Assembly and installation instructions for a Rapid-sorb installed
with header inside the duct (continued)
• Rotate the slip coupling as you push it on to the tubing.
• The O-rings are lubricated at the factory. If additional
lubrication is necessary, DO NOT use a petroleum-based
lubricant.
5. Allow the dispersion tubes to rest against the bottom of the duct.
6. Position the flange of the L-bracket so it is upstream of the tubes
when the assembly is rotated into position. Fasten the L-bracket
to the end of the dispersion tubes with the provided bolt, lock
washer, and flat washer.
7. Rotate the assembly up until the L-bracket aligns with the
mounting holes in the duct or air handler.
• 1½'' (DN40) dispersion tubes
– The header pitch is duplicated in the L-bracket.
– The dispersion tube and slip coupling must be fully
engaged on to the header stub for the O-rings to provide a
seal.
– The high end of the L-bracket can be fastened tight to the
duct or air handler.
– On the low end of the L-bracket, the fastener must be long
enough to compensate for the pitch, and a nut should be
provided and secured on both sides of the L-bracket and
the duct or air handler for stability.
• 2" (DN50) dispersion tubes
– Fasten the bracket to the top of the duct or air handler and
use the hose cuffs to compensate for the pitch of the header.
– Before securing the hose cuff in place, with the hose clamps
on the dispersion tube and the header stub, verify that the
dispersion tube orifices are directed perpendicular to the
airflow.
8. Verify that all fasteners are secure:
• L-bracket to duct
• Dispersion tubes to L-bracket
• Hose clamps on 2" (DN50) tubes
• Header support bracket fastener
9. Secure and seal the header escutcheon plate around the header.
10. See page 48 for steam supply and condensate drain line
connection instructions.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 4 9
Page 52
D i s p e r s i o n : R a p i d - s o r b ( c o n t i n u e d )
Steam supply connections to the Rapid-sorb header
1. Connect the steam supply interconnecting piping from the
humidifier to the Rapid-sorb. The steam supply piping requires
a minimum of 1/8"/ft (1%) pitch toward the header.
2. If multiple humidifiers are supplying one Rapid-sorb, a multiple
steam supply connector is provided.
• Typically, the multiple steam supply connector attaches to the
Rapid-sorb header supply end with hose cuff and clamps.
• Route the necessary number of steam supplies from the
humidifier tanks to the steam supply connector.
• Position the steam supply connector to accept the steam
supplies while maintaining the necessary pitch.
• Make sure the hose clamps on the steam supply connector
and header are tight.
Condensate drain connections to the Rapid-sorb header
1. Piping must be minimum ¾" I.D. (DN20) and rated for 212 °F
(100 °C) minimum continuous operating temperature.
2. Condensate drain line must be piped as shown in the figures
on the previous pages. Provide a 6" (152 mm) drop prior to a
5" (127 mm) water seal to:
• Ensure drainage of condensate from the header
• Keep steam from blowing out of the drain line
3. After the water seal, run the drain line to an open drain with a 1"
(25 mm) vertical air gap. Cut the drain line at a 45° angle on the
end above the drain to permit a direct stream of water into the
drain pipe while maintaining a 1" (25 mm) air gap. Locate air
gap only in spaces with adequate temperature and air movement
to absorb flash steam, or condensing on nearby surfaces may
occur.
4. All drain lines must be installed and sized according to
governing codes.
Pag e 5 0 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 53
D i s p e r s i o n : A r e a - t y p e f a n
Area-type™ fan dispersion
The table on the following page lists the Area-type steam minimum
rise, spread, and throw nonwetting dimensions. Surfaces or objects
located within this minimum dimension can cause condensation
and dripping.
• Rise: The minimum nonwetting height above the steam chute
• Spread: The minimum nonwetting width from the steam chute
• Throw: The minimum nonwetting horizontal distance from the
steam chute
The greater the space relative humidity, the higher and farther the
discharged steam will carry and rise in the space until becoming
absorbed.
The Area-type fan, brackets, and wiring are factory installed on the
humidifier.
Table 51-1:
Area-type electric fan specifications
Motor120 V, 50/60 Hz
Blade diameter18" (457 mm)
Speeds3
ControlRotary switch
cfm (high speed)5350
m3/s (high speed)2.52
rpm (high speed)1500
Amps (high speed)1.52
Note:
For European models, contact your
distributor for Area-type parts.
Figure 51-1:
Area-type rise, spread, throw
OM-1230
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 5 1
Page 54
D i s p e r s i o n : A r e a - t y p e f a n
( c o n t i n u e d )
* With fan on high speed
Rise: Minimum non-wetting height above the steam chute
Spread: Minimum non-wetting width from the steam chute
Throw: Minimum non-wetting horizontal distance from the steam chute
Pag e 5 2 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 55
S t a r t - u p p r o c e d u r e
After the system is installed and connected to gas, electrical, water
supplies, and controls, you can begin start-up procedures.
1. Verify that the GTS humidifier, controls, piping, electrical
connections, steam supply, and dispersion unit(s) are installed
according to the following:
2. Piping (gas)—Verify that all field and humidifier gas
piping has been tested for leaks. (Soap and water are not
recommended near gas valves.)
Piping (steam, drain, water supply)—Verify that all piping
connections have been completed as recommended and that
water pressure is available.
3. Electrical—Verify that all wiring connections have been made
in accordance with all governing codes and the GTS wiring
diagrams.
4. Controls—Before proceeding with start-up and operation,
verify that all control wiring has been completed as specified
and required for correct and safe operation of the GTS
humidifier. Refer to the Vapor-logic4 manual that was enclosed
with the product shipment.
W A R N I N G !
Only qualified electrical and gas personnel
should perform the start-up procedure.
Note:
The
Vapor-logic4 Installation and Operation
Manual
manual. Refer to it for information regarding
the following features:
• Keypad display setup and menu
• Control input signals and functions
• Drain, flush, and skim features
• Safety features
• Alarm screens and fault messages
The Vapor-logic4 manual was shipped
with your humidifier. Additional copies
can be viewed, printed, or ordered at
www.dristeem.com
is a comprehensive operation
information
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 5 3
More on the next page ▶
Page 56
S t a r t - u p p r o c e d u r e ( c o n t i n u e d )
5. Verify that the humidifier tank is securely installed and level
before filling with water (see the operating weights table in this
manual).
6. Verify that the humidifier tank is level front to back and side to
side after it is full of water.
7. Refer to the following sections in the Vapor-logic4 Installation
and Operation Manual:
• Operation section
• Start-up checklist (it is critical that the installer follow this
checklist)
8. During start-up, do not leave the humidifier unattended.
9. Monitor humidifier operation through multiple fill cycles. The
humidifier operating status appears on the keypad/display.
10. On standard water units, water skims from the humidifier
after every fill cycle. Adjust the amount of skim by increasing
or decreasing the skim time (see the Vapor‑logic4 Installation and Operation Manual). However, at start-up, DRI-STEEM
recommends initially running the humidifier with the factory
default setting for skim time. (See the operation information
section in this manual.)
Pag e 5 4 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 57
O p e r a t i o n : S a f e t y s y s t e m s
Safety systems
The GTS humidifier has a number of systems and safeguards to
ensure proper operation.
• When there is a call for humidity, all of the combustion blowers
must start. Each combustion blower sends a signal to the
microprocessor relaying its current speed. If this actual speed is
outside an acceptable range, the GTS will not operate.
• The negative pressure gas valves used on the GTS are designed
to keep a constant ratio of air and gas throughout the operating
range of the blower. If the flue becomes blocked or the
blower fails to run, the blocked flue sensor will shut down the
humidifier.
• During operation, the water level in the tank is monitored by a
probe system for standard water units and by a low water float
for DI/RO units. These water monitors tie into the Vapor-logic4
controller. If the water level drops below a safe point, the
controller turns heaters off and tries to fill. If humidifier is unable
to fill within a defined time period, an “Excessive refill time”
alarm appears in the Vapor-logic4 Alarm Log. The heaters will
remain off until this alarm is cleared. (For more about alarms, see
the Vapor-logic4 Installation and Operation manual.)
• In standard water applications, the water level in the tank is
also monitored by a redundant low-water system that runs
independently of the Vapor-logic4. This system is tied directly
into the power source for the gas valves. If this system detects
a low water condition, the humidifier shuts down until water is
present or until the a “GTS low water” alarm is cleared from the
Vapor-logic4 Alarm Log.
• In addition to monitoring the water level, there is a temperature
sensor located near the top of the heat exchanger. If the water
level drops too low and both the main and redundant low water
sensors fail to detect it, the temperature sensor shuts down the
humidifier before an unsafe condition occurs.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 5 5
Page 58
O p e r a t i o n : S t a r t - u p c o m m i s s i o n i n g
c h e c k l i s t
Visit date_____________________________________
Model #______________________________________
Serial #______________________________________
Tag #________________________________________
I m po r t an t : Troubleshooting information for this
humidifier is located in the Vapor-logic4 Installation and
Operation manual shipped with your humidifier. If you
do not have this manual, go to the literature section at
www.dristeem.com to download or order a copy.
Supply water
☐ DI
☐ RO
☐ Soft
☐ Potable
Grains hardness ____________________________
☐ Hot*
☐ Cold
Water pressure ________________ psi
(must be between 25 and 80 psi
[172 and 582 kPa])
☐ Water supply piping is 3/8" pipe thread (DN10) minimum
Float adjustments (DI system)
_________________________________________
Note: *If using heated supply water, disconnect the water supply line to the water tempering device at the fill manifold and
reconnect it to a cold water supply. This will ensure that the water
tempering device operates properly.
Flue piping
Class _____________________________________
Size ______________________________________
Rise ______________________________________
Run ______________________________________
☐ Slight pitch toward drip tee
☐ Termination point capped and covered
Power venter location ________________________
Barometric damper location ___________________
Pag e 5 6 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Steam pipe
Outlet size _________________________________
☐ Flange
☐ Hard pipe
☐ Insulated
☐ Vapor hose (do not insulate)
Rise ______________________________________
Run _____________________________________
☐ Pitched back to humidifier
☐ 45° angles used in piping
More checklist on next page ...
Page 59
O p e r a t i o n : S t a r t - u p c o m m i s s i o n i n g
c h e c k l i s t ( c o n t i n u e d )
Dispersion
☐ Ultra-sorb
☐ Rapid-sorb
☐ Single tube
☐ Single tube with drain
☐ Area-type fan
Condensate/drain piping
Water seal height of dispersion system
______________________________
☐ Air gap
☐ Condensate return to tank
☐ Drane-kooler
Cold-start burner ignition
Burner 1 lights after: ☐ First try
☐ Second try
☐ Third try
Burner 1 color after 15 minutes:
☐ Blue
☐ Orange
☐ Red-orange
Safety testing to verify function
Low water test ______________________________
High humidity limit test _______________________
Airflow test ________________________________
Aquastat test _______________________________
Additional comments
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
Burner 2 lights after: ☐ First try
☐ Second try
☐ Third try
Burner 2 color after 15 minutes:
☐ Blue
☐ Orange
☐ Red-orange
Burner 3 lights after: ☐ First try
☐ Second try
☐ Third try
Burner 3 color after 15 minutes:
☐ Blue
☐ Orange
☐ Red-orange
Burner 4 lights after: ☐ First try
☐ Second try
☐ Third try
Burner 4 color after 15 minutes:
☐ Blue
☐ Orange
☐ Red-orange
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
____________________________________________
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 5 7
Page 60
M a i n t e n a n c e : F o r b o t h GT S a n d
G T S - D I m o d e l s
Table 58-1:
GTS products of combustion guidelines
(at 100% demand)
CO
CO2 %
O2 %4-10%
Flue
temperature
Burner
efficiency
Less than 40 ppm; 0 or low single
digits is typical
8-10%; 9% is typical for natural gas,
10% is typical for LP gas
Less than 400 °F plus room temp.
(Less than 204.4 °C plus room temp.)
Greater than 80%
Both GTS and GTS-DI models
Inspection recommendations:
• User inspection every 30 days.
• Appliance system inspected once a year by a qualified service
person.
During inspection, verify the following:
• Proper field operation of burner. Measure CO, CO2%, O2%,
flue temperature, and burner efficiency at 100% demand. Verify
that measurements are within the guidelines described in Table
58-1; if not, consult DRI-STEEM.
• Flue passageways external to the appliance, such as vent
connector and chimney, are clear and free of obstructions.
• Vent connector is in place, sloping upward and is physically
sound without holes or excessive corrosion.
• Physical support of the appliance is sound without sagging cracks
or gaps between floor stand legs or tank flanges.
• There are no obvious signs of deterioration of the appliance.
• Burner flame is blue or orange in color — up to a ¼"
(6 mm) from the surface of the burner.
• See “Clean the probes” and “Clean low water cutout probe” on
Page 62 and 63.
Inspecting burner assemblies and heat exchanger tubes
This is not a regular maintenance item, but if the heat exchanger
tubes contain carbon deposits, soot, or other residue, clean as
follows:
• Turn off gas, electrical power, and water supply.
• Remove gas train shroud.
• Disconnect wiring to blowers, flame sensors, gas valves, and
ignition controllers and remove burner assemblies (each assembly
is mounted with four bolts).
• Remove vent box.
• Use a 6" (150 mm) flue brush with a 24" (600 mm) extension
and reversible drill. Work brush in and out of all combustion
chambers. Note: Disconnecting components from one burner
assembly at a time and then cleaning the corresponding
combustion chamber and burner will ease reassembly.
More on next page ▶
Pag e 5 8 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 61
M a i n t e n a n c e : b o t h G T S an d G T S - D I
m o d e l s ( c o n t i n u e d )
• Remove loose deposits and residue that falls into rear header with
a vacuum cleaner and hose extension.
• Inspect 1½" (DN40) return tubes and clean if necessary.
• Run thin brush between turbulator and tube wall on all four
sides.
• Reinstall burner assemblies and gaskets; vent box and
gasket; all electrical wiring; gas train shroud; and pressure switch
connections.
Burner maintenance
Under normal use conditions, the burner(s) should not need
cleaning for a minimum of five years. However, depending on
the operating environment, the burner(s) may require periodic
cleaning to remove accumulated materials. Failure to clean burners
can result in reduced unit capacity. Use sealed combustion in dirty
environments. See burner maintenance instructions below.
Burner maintenance instructions
To service the burner system, clean both the blower and the burner.
Remove the blower(s) from the system and clean dust from the
wheel. Remove the burner(s) for cleaning. Removing and cleaning
one burner at a time eases reassembly. To dislodge particulate
matter from the burner surface matrix, use compressed air
(100 psig [700 kPa] maximum). Keep the air nozzle about 2"
(50 mm) from the burner’s surface, blowing air perpendicular
to the burner surface while moving the nozzle back and forth
lengthwise. This dislodges particles trapped in the matrix, pushing
them back inside the burner. Avoid blowing air across the surface,
which tends to have a destructive effect on the burner surface.
Allow particulate matter to fall from the burner through the air/gas
inlet. To assist in removing the particulate matter, use a vacuum at
the burner’s air/gas inlet.
Note:
Soot and carbon deposits may indicate
a combustion problem that needs to be
corrected. Consult the factory.
W A R N I N G !
When cleaning burners with compressed
air, wear appropriate respiratory protection.
Failure to do so may cause severe bodily
injury.
Replacement parts
When servicing or repairing this equipment, use only DRI-STEEM
approved service replacement parts. Complete replacement part
lists are on Pages 68–77. Refer to the rating plate on the unit for
complete unit model number, serial number, and company address.
Any substitution of parts or controls not approved by DRI-STEEM
will be at owner’s risk and will void the warranty.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 5 9
Page 62
M a i n t e n a n c e : G T S s t a n d a r d w a t e r
m o d e l s
GTS standard water quality recommendations
The best way to determine how often your particular system needs
maintenance is to remove the probe plate and inspect it for mineral
deposits after three months of duty. Potable water carries a variety
of minerals and other materials in a mix that varies from location
to location. This variation in water quality, combined with the
hours of operation and duty cycle, will determine your own unique
maintenance schedule.
Water quality makes a difference
• Light to moderately hard water (2 to 10 grains hardness per
gallon [35 mg/L to 170 mg/L]) requires:
– Annual cleaning
– Regular skimming
• High mineral content water (more than 10 grains hardness per
gallon [more than 170 mg/L]) requires:
– Cleaning frequency determined by use and water quality
– Regular skimming
– Periodic drain and flush cycles
• Softened water dramatically reduces mineral accumulation inside
standard water models.
(Note: Solids, like silica, are not removed in the softening
process.)
Adjusting skim duration
The skim time duration determines the quantity of water skimmed
with each fill cycle. Skim time is field adjustable using the
Vapor-logic4 keypad.
Each time the GTS refills, it fills to an elevation near the lip of the
skim/overflow fitting. A portion of the refill water then flows to the
drain carrying most of the minerals left by the previous evaporating
cycle. This reduces the mineral concentration, thereby reducing the
frequency of cleaning needed.
The heated water that flows to the drain is an operational cost.
Cleaning the humidifier also is an operational cost. Therefore, DRISTEEM recommends that the user observe and adjust the skimming
quantity to achieve a balance between minimizing mineral buildup
and conserving heated water.
Pag e 6 0 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 63
M a i n t e n a n c e : G T S s t a n d a r d w a t e r
m o d e l s ( c o n t i n u e d )
Cool down humidifier before beginning maintenance
Before performing any maintenance, allow the tank to cool down.
• Insulated and uninsulated tanks will have hot surfaces.
• Verify that there is no call for humidity and that the aquastat set
point (adjusted using the keypad/display Set Up screens) is less
than room temperature (default setting is 40 °F [4 °C]) so that the
heaters do not energize while cooling down the tank.
• For models with a standard drain valve:
– Manually open the drain valve by moving the valve lever
located on the back of the drain valve to the manual open
position.
– The fill valve eventually opens.
– Let the fill water run until the tank is cooled; then shut off the
field-installed manual supply water shut-off valve.
– Let the tank drain; then manually close the drain valve.
• For models with optional drain valves:
– For drain valves without the manual open lever, use the keypad
to perform the cool down process.
– Go to the Home screen and change mode to Drain.
– Allow approximately half the water to drain out of the tank.
– Go to the Home screen and change mode to Auto; the fill valve
opens and the humidifier cools down.
– When the fill valve closes, select Manual Drain in the Control
Modes screen and let the tank drain dry. The humidifier should
be cool enough to work on.
– For more information about using the Vapor-logic4 keypad
or web browser interface, see the Vapor-logic4 Installation and
Operation Manual.
W A R N I N G !
When performing maintenance on the GTS
humidifier, always change the control mode
to Standby, place all power disconnects in
OFF position and lock in OFF position, close
the field installed manual water supply and
gas shut-off valves. Failure to follow these
instructions may cause severe bodily injury
or death from electric shock.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 6 1
Page 64
M a i n t e n a n c e : G T S s t a n d a r d w a t e r
m o d e l s ( c o n t i n u e d )
Inspection and maintenance
1. Annually (also recommended when maintenance is performed)
• Inspect tank, piping, and gaskets for water and gas leaks.
• All safety devices in the control circuit should be cycled on
and off to verify they are functioning. These include:
– High limit switch
– Airflow proving switch
– Low water level probe. Pull out probe plugs; valve should
de-energize.
2. Seasonally (or as required, depending on water quality)
• Clean tank
– Remove cleanout plate and dispose of any loose scale that
has collected in the tank. Do this before the scale buildup
reaches the bottom of the heat exchanger.
– Inspect the area inside the tank in front of the drain valve
fitting and thoroughly clean all scale and mineral buildup
from that area.
• Dismantle and clean drain valve and associated piping
• Clean the probes
– Access the probe assembly either from the electrical panel
or by removing the roof panel above the electrical area.
– Disconnect the probe plug and cable assembly and unscrew
the probe rod assembly from the humidifier probe housing.
– Inspect the probe housing and clean, ensuring that all the
housing passageways are clear. Remove the housing from
the tank by removing the cover plate from the tank.
– The scale should flake off easily from the probe assembly
rods.
– The bottom 3/8" (10 mm) of each rod is the sensing
portion; clean these areas with a wire brush, abrasive pad,
or steel wool.
– Inspect the composite plastic probe rod assembly for any
signs of cracking, roughness, or deterioration. If found,
replace probe assembly.
– Reassemble the probe assembly.
More on next page ▶
Pag e 6 2 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 65
M a i n t e n a n c e : G T S s t a n d a r d w a t e r
m o d e l s ( c o n t i n u e d )
Inspection and maintenance (continued)
• Clean the skim/overflow port
– Water should drain from the skimmer drain pipe after
each fill cycle. This should be verified visually by a weekly
inspection.
– Loosen deposits in and around the skimmer/overflow port
with a long tool such as a screwdriver.
– If flow through the water seal/P-trap is diminished due to
mineral accumulation:
• Remove the water seal piping from the humidifier and
flush out.
• Replace the water seal with new piping if the minerals
have hardened in the water seal.
• Clean low water cutout probe — Remove the shroud cover
and inspect the probe rod for mineral accumulation. The rod
is located on the top of the tank near the back. Use stainless
steel wool to clean the probe .
• Inspect blower motor — A lubrication port is not provided,
therefore lubrication is not required.
• Remove dust — Using a vacuum, remove all dust from areas
around the motor, vent fan(s), and louvers that allow air to
the shrouded area.
More on next page ▶
W A R N I N G !
When performing maintenance on the GTS
humidifier, always change the control mode
to Standby, place all power disconnects in
OFF position and lock in OFF position, close
the field installed manual water supply and
gas shut-off valves. Failure to follow these
instructions may cause severe bodily injury
or death from electric shock.
I m po r t an t :
Minimum water supply pressure is 25 psi
(172 kPa).
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 6 3
Page 66
M a i n t e n a n c e : G T S s t a n d a r d w a t e r
m o d e l s ( c o n t i n u e d )
• When the maintenance requirements are complete:
– Replace cleanout plate and tighten the nuts on the plate.
– Verify that the probe rod holder is secure and that the
probe plug and cable assembly are plugged into the probe
rod holder.
– Verify that the drain valve assembly is in the closed
position.
– Replace and secure all covers and doors.
– Turn on the water supply.
– Turn on the electrical power.
– Turn on gas.
– Do not leave humidifier unattended. Allow the humidifier
to cycle through multiple fill cycles and verify that the
humidifier cover, cleanout plate, and probe holder gasket
are not leaking.
3. Off-season maintenance
• Perform complete inspection and cleaning of the following:
– Probe rods
– Skimmer port and water seal
– Humidifier tank
– Heat exchanger
• After cleaning, the humidifier should remain empty until
humidification is required.
Pag e 6 4 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 67
M a i n t e n a n c e : G T S - D I m o d e l s
GTS-DI models DI water quality recommendations
• Verify regularly that water processing equipment is operating
correctly. The presence of chlorides in improperly processed
DI water can cause pitting and failure of the tank and heat
exchanger. Your DRI-STEEM warranty does not cover damage
caused by chloride corrosion.
• GTS-DI models do not require regular cleaning, although regular
inspections are advised.
• GTS-DI models do not require skimming or draining and
flushing to remove precipitated minerals. However, at the end
of a humidification season, drain all DI humidifiers either
by manually opening the drain valve or by programming the
humidifier to automatically drain at end-of-season (electric fill
and drain valve required).
Cool down humidifier before beginning maintenance
Before performing any maintenance, allow the tank to cool down.
• Tanks will have hot surfaces.
• Verify that there is no call for humidity and that the aquastat set
point (adjusted using the keypad/display Set Up screens) is less
than room temperature (default setting is 40 °F [4 °C]) so the unit
does not fire-up while cooling down the tank.
• For models with a standard drain valve:
– Manually open the drain valve.
– The float valve opens.
– Let the fill water run until the tank is cooled; then shut off the
field-installed manual supply water shut-off valve.
– Let the tank drain; then manually close the drain valve.
• For models with end-of-season drain option:
– Use the keypad to perform the cool down process.
– Go to the Home screen and change mode to Drain.
– Allow approximately half the water to drain out of the tank.
– Go to the Home screen and change mode to Auto; the fill valve
opens and the humidifier cools down.
– When the fill valve closes, select Manual Drain in the control
modes screen and allow the tank to drain completely dry. The
humidifier should be cool enough to work on.
– For more information about using the Vapor-logic4 keypad
or web browser interface, see the Vapor-logic4 Installation and
Operation Manual.
W A R N I N G !
When performing maintenance on the GTS
humidifier, always change the control mode
to Standby, place all power disconnects in
OFF position and lock in OFF position, close
the field installed manual water supply and
gas shut-off valves. Failure to follow these
instructions may cause severe bodily injury
or death from electric shock.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 6 5
Page 68
W A R N I N G !
When servicing controls, before
disconnecting, label all areas. Wiring errors
can cause explosion or fire, resulting in
severe bodily injury, death, or significant
property damage.
M a i n t e n a n c e : G T S - D I m o d e l s
( c o n t i n u e d )
Inspection
1. Annually (also recommended when maintenance is performed)
• Inspect tank and gaskets for leaks.
• All safety devices in the control circuit should be cycled on
and off to verify they are functioning. These include:
– High limit switch
– Airflow proving switch
– Low water cutoff switch
• Verify that the float valve is closing off. If the float valve will
not shut off, there may be particulate on the valve seat, or the
stopper may be worn and need replacing.
• As long as mineral-free water is used in the GTS, no cleaning
or flushing of the humidifier should be necessary.
2. Seasonally (or as required, depending on water quality)
• Inspect blower motor. Since a lubrication port is not provided,
lubrication is not required.
• Remove dust — Using a vacuum, remove all dust from areas
around the motor, vent fan(s), and louvers that allow air to
the shaded area.
3. Off-season maintenance
• Perform a complete inspection of the following:
– Float valve
– Low water cutoff switch
– Humidifier tank and gaskets
– Heat exchanger
• Drain humidifier tank and rinse.
• After inspection, the humidifier should remain empty until
humidification is required.
Pag e 6 6 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Page 69
G T S t r o u b l e s h o o t i n g
The Vapor-logic4 Installation and Operation Manual that shipped
with your humidifier is a comprehensive operation manual. Refer
to it for troubleshooting information.
Download DRI-STEEM literature
Most DRI-STEEM product manuals can be
downloaded, printed and ordered from our
web site: www.dristeem.com
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 6 7
Page 70
•
Figure 68-1:
GTS replacement parts
G T S r e p l a c e m e n t p a r t s
Pag e 6 8 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 7 3
Page 76
Figure 74-1:
Outdoor enclosure electrical replacement parts
O u t d o o r e n c l o s u r e e l e c t r i c a l
r e p l a c e m e n t p a r t s
Note:
For European models, refer to Fisair diagrams
Pag e 7 4 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
Not shown
OM-7471
Page 77
O u t d o o r e n c l o s u r e e l e c t r i c a l
r e p l a c e m e n t p a r t s
Table 75-1:
Outdoor enclosure electrical replacement parts
No.Description Part no.
1Vapor-logic4 display with back
Fan assembly (for North America)185110-001
2
Fan assembly (for Europe)185110-002
3High limit stat405800-065
Fan stat (for North America)405800-067
4
Fan stat (for Europe)405871-002
Heater stat (for North America)405800-066
5
Heater stat (for Europe)405871-001
6Ground wire lug409250-003
7Power block408300-002
8Circuit breaker406775-005
9Relays, sockets, time delayConsult factory
10Heater assembly, 500W *Consult factory
11Heater assembly, 1100W *Consult factory
12DIN-rail end bracket408252-006
Note:
* Not shown
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 7 5
Page 78
I n f o r m a t i o n f o r E u r o p e a n m o d e l s
o n l y
Electrical warning label
Location: Control cover, shroud
Definition: Electrical shock hazard
Important:
This equipment is for use with second family
(G20, G25) natural gases; and third family
(G30, G31) propane gas. Contact your
distributor before converting to another
group or supply pressure.
This equipment has been tested by the Canadian Standards
Association International to the Low Voltage, Gas Appliance, and
EMC directives and has been certified by AFNOR for use in all EU
countries.
Authorized countries of destination
The GTS and GTS-DI humidifiers bearing the CE mark are
authorized for use in the European countries listed below.
* The maximum steam capacities listed may be as much as 10% lower than the given values due to local variations in the Wobbe index of G20 and G25 gases.
Capacity notes
• At sea level, 402 kJ are required to raise the temperature of one
kilogram of water from 4 °C to 100 °C.
• An additional 2257 kJ are required to change the state of one
kilogram of 100 °C water to vapor.
• Another factor to consider is condensation steam loss from hoses
and tubes. Use the following steam loss guidelines:
humidifier controls must never exceed
6 kPa (60 mbar) or the gas valve will
become damaged and require replacement.
Immediately install a DN6 pipe thread
plugged tapping, accessible for test gauge
connection, upstream of the gas supply
connection to the appliance.
Full load
amps
Operating characteristics
• Unit is capable of operating in ambient conditions of 5 °C to
40 °C.
• Unit is capable of operating in ambient conditions between 30%
RH and 95% RH (noncondensing).
• NOx class 5
Gas supply pressure
• 20 or 25 mbar for natural gas (depending on gas group), and 30,
37 or 50 mbar for propane gas (depending on gas group)
PMS (all units)
• 7.0 bar
Electric supply
• 230V, 667W to 2415W (see data plate)
Max inlet water temperature
• 90 °C
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 7 7
Page 80
Expect quality from the industry leader
For more than 40 years, DRI-STEEM has
been leading the industry with creative and
reliable humidification solutions. Our focus
on quality is evident in the construction of
the GTS, which features cleanable, stainless
steel construction, and an industry-leading
two year warranty that covers all parts.
For more information
www.dristeem.com
sales@dristeem.com
DRI-STEEM Corporation
An ISO 9001:2000 certified corporation
Continuous product improvement is a
policy of DRI-STEEM Corporation; therefore,
product features and specifications are
subject to change without notice.
U.S. Headquarters:
14949 Technology Drive
Eden Prairie, MN 55344
800-328-4447
952-949-2415
952-229-3200 (fax)
European office:
Marc Briers
Grote Hellekensstraat 54 b
B-3520 Zonhoven
Belgium
+3211823595 (voice)
+3211817948 (fax)
E-mail: marc.briers@dristeem.com
DRI-STEEM, Area-type, Drane-kooler,
Dri-calc, Rapid-sorb, Ultra-sorb, and
Vapor-logic are registered trademarks or
trademarks of DRI-STEEM Corporation
and are filed for trademark registration in
Canada and the European community.
Two-year limited warranty
DRI-STEEM Corporation (“DRI-STEEM”) warrants to the original
user that its products will be free from defects in materials and
workmanship for a period of two (2) years after installation or
twenty-seven (27) months from the date DRI-STEEM ships such
product, whichever date is the earlier.
If any DRI-STEEM product is found to be defective in material or
workmanship during the applicable warranty period, DRI-STEEM’s
entire liability, and the purchaser’s sole and exclusive remedy, shall
be the repair or replacement of the defective product, or the refund
of the purchase price, at DRI-STEEM’s election. DRI-STEEM shall
not be liable for any costs or expenses, whether direct or indirect,
associated with the installation, removal or reinstallation of any
defective product.
DRI-STEEM’s limited warranty shall not be effective or actionable
unless there is compliance with all installation and operating
instructions furnished by DRI-STEEM, or if the products have been
modified or altered without the written consent of DRI-STEEM,
or if such products have been subject to accident, misuse,
mishandling, tampering, negligence or improper maintenance. Any
warranty claim must be submitted to DRI-STEEM in writing within
the stated warranty period.
DRI-STEEM’s limited warranty is made in lieu of, and DRI-STEEM
disclaims all other warranties, whether express or implied,
including but not limited to any IMPLIED WARRANTY OF
MERCHANTABILITY, ANY IMPLIED WARRANTY OF FITNESS
FOR A PARTICULAR PURPOSE, any implied warranty arising out
of a course of dealing or of performance, custom or usage of trade.
DRI-STEEM SHALL NOT, UNDER ANY CIRCUMSTANCES BE
LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL
OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT
LIMITED TO, LOSS OF PROFITS, REVENUE OR BUSINESS)
OR DAMAGE OR INJURY TO PERSONS OR PROPERTY IN
ANY WAY RELATED TO THE MANUFACTURE OR THE USE
OF ITS PRODUCTS. The exclusion applies regardless of whether
such damages are sought based on breach of warranty, breach of
contract, negligence, strict liability in tort, or any other legal theory,
even if DRI-STEEM has notice of the possibility of such damages.
By purchasing DRI-STEEM’s products, the purchaser agrees to the
terms and conditions of this limited warranty.