DriSteem GTS Installation, Operation And Maintenance Manual

IMPORTANT: Read and save these instructions.
GTS
®
Gas -to -St eam Hum i di f ie r
In st all at io n, O peratio n,
an d M ainte na nc e Manu al
W A R N I N G !
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
W H A T T O D O I F Y O U S M E L L G A S
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from an off-site phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be per­formed by a qualified installer, service agency, or the gas supplier.
For toll-free technical support call: 1-800-328-4447
ATTENTION INSTALLER
Read this manual before installing. Leave manual with product owner.
DRI-STEEM technical support
800-328-4447
I m po r ta n t: Troubleshooting information for this humidifier is located in the Vapor-logic4 Installation and Operation manual shipped with your humidifier. If you do not have this manual, go to the literature section at www.dristeem.com to download or order a copy.
Where to find more information
On our Web site:
The following related documents can be viewed, printed or ordered from our web site, www.dristeem.com
• Catalogs (include dispersion nonwetting distance graphs):
– GTS – Ultra-sorb
• Installation, Operation, and Maintenance
– Ultra-sorb – Vapor-logic4® (includes sensor placement recommendations and troubleshooting information)
In Dri-calc:
Dri-calc® is our humidification system sizing and selection software, which can be ordered at www.dristeem.com.
Included in Dri-calc:
®
®
manuals:
DRI-STEEM Design Guide
loss tables and general humidification information)
(includes steam
European models
The DRI-STEEM GTS Gas-to-Steam Humidifier has been certified for compliance with harmonised European directives concerning gas appliances, low voltage, and emission (Gas Appliance Directive 90/396/CEE). Testing was carried out by the Canadian Standards Association; the notifying body is AFNOR in France, which is a recognized authority by the European bodies and the DTI in the United Kingdom.
Installation must conform to the requirements of the National Gas Safety (Installation & Use) Regulations.
• A comprehensive library of installation guide documents, including:
– Rapid-sorb installation instructions for vertical airflows – Recommended dispersion placement within a duct or air handler – Recommended sensor placement
Or call us at 800-328-4447
While obtaining documents from our web site or from Dri-calc is the quickest way to review our literature, we will also mail to you any literature you need.
Ta b l e o f c o n t e n t s
Overview
Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Specifications and capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation
Locating the humidifier, clearance recommendations . . . . . . 10
Outdoor enclosure mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wiring: Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Piping: Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Piping: Supply water and drain overflow connections . . . . . . . 22
Piping: Water supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Piping: Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Piping: Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Combustion and ventilation air . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Vertical and horizontal venting . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Dispersion: General instructions . . . . . . . . . . . . . . . . . . . . . . . . . 35
Dispersion: Interconnecting piping requirements . . . . . . . . . . 36
Dispersion: Drip tee installation . . . . . . . . . . . . . . . . . . . . . . . . . 38
Dispersion: Single tube and multiple tube . . . . . . . . . . . . . . . . . 39
Dispersion: Rapid-sorb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Dispersion: Area-type fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Operation
Start-up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Safety systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Start-up commissioning checklist . . . . . . . . . . . . . . . . . . . . . . . . 56
Maintenance
For both GTS and GTS-DI models . . . . . . . . . . . . . . . . . . . . . . . 58
Maintenance: GTS standard water models . . . . . . . . . . . . . . . . . 60
Maintenance: GTS-DI models . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Troubleshooting
GTS troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Replacement parts
Replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Electrical replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Outdoor enclosure electrical replacement parts . . . . . . . . . . . . 74
Information for European models only
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76-77
Warranty
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Back cover
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1
S a f e t y p r e c a u t i o n s
W A R N I N G !
The humidifier must be installed by a qualified technician and meet the requirements of all governing codes. Failure to follow these instructions could cause severe bodily injury or death.
W A R N I N G !
If you do not follow the instructions in this manual exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
For your safety, read this entire manual before installing or operating the GTS humidifier.
A. This appliance does not have a pilot. It is equipped with an
ignition device which automatically lights the burner.
Do NOT try to light the burner by hand.
B. Before operating, smell all around the appliance area for
gas. Be sure to smell next to the floor because gas can be heavier than air and settle on the floor.
FOR YOUR SAFETY: WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Do not use this appliance if any part has been under water.
Immediately call a qualified gas appliance service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
More safety precautions are on the next page ▶
Pag e 2 • DRI - S TEE M G TS Hu m i difi e r Ins t a llat i on, O p e rat i o n, an d M aint e nanc e M anua l
S a f e t y p r e c a u t i o n s ( c o n t i n u e d )
Safe operating instructions
1. STOP! Read the safety information on the previous page.
2. Set the humidistat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device that automatically lights the burner. Do not try to light the burner by hand.
5. Remove control access panel.
6. Unplug the black power plug on the gas valve (see Figure 3-1).
7. Wait five minutes to clear out any gas.
If you then smell gas, STOP! Follow “B” in the safety information on the previous page.
If you don’t smell gas, go to the next step.
8. Plug the black power plug back into the gas valve.
9. Replace control access panel.
10. Turn on all electric power to the appliance.
To turn off gas to appliance
1. Set the humidistat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove control access panel.
4. Unplug the black power plug on the gas valve.
5. Replace control access panel.
11. Set humidistat to desired setting.
12. If the appliance will not operate, follow the instructions on this page titled, “To turn off gas to appliance,” and call your service technician or gas supplier.
More safety precautions are on the next page ▶
Figure 3-1: Detail of gas valve
Top view
Gas valve
Gas valve power plug
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 3
S a f e t y p r e c a u t i o n s ( c o n t i n u e d )
W A R N I N G !
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory authorized and listed kits or accessories when modifying this product. A failure to follow this warning can cause electrical shock, fire, personal injury, or death.
• Inspect humidifier and accessories upon arrival for damaged, missing, or improper parts. If there is a problem, call DRI-STEEM.
• Application of this humidifier should have special attention given to vent sizing and material, gas input rate, and unit sizing. Improper installation or misapplication of the humidifier can cause excessive servicing or permanent component failure.
• When working on equipment, observe precautions in literature, tags, and labels attached to or shipped with the unit and observe other safety precautions that may apply. Wear safety glasses and work gloves. Have a fire extinguisher available during start-up, adjustment procedures, and service calls.
• Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
• Do not lift humidifier by gas controls, gas manifold, fire box, or shroud.
• Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical supply.
• The evaporating chamber is designed as a non-pressurized vessel. DO NOT restrict piping where steam exits the humidifier. Install drain piping and piping that connects the evaporating chamber to the dispersion assembly only as described in this manual. DO NOT install a shut-off valve on the piping connecting the evaporating chamber to the steam outlet.
Pag e 4 • DRI - S TEE M G TS Hu m i difi e r Ins t a llat i on, O p e rat i o n, an d M aint e nanc e M anua l
More safety precautions are on the next page ▶
S a f e t y p r e c a u t i o n s ( c o n t i n u e d )
W A R N I N G !
• Installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, must conform to:
In the United States: The National Fuel Gas Code, ANSI Z223.1
(latest edition).
In Canada: Local plumbing or waste water codes and other
applicable codes and with the current code CAN/CGA-B149.1, “Installation Code for Natural Gas Burning Appliances and Equipment,” or CAN/CGA-B149.2, “Installation Code for Propane Burning Appliances and Equipment.”
In Europe: The National Gas Safety (Installation & Use) Regulations.
• Do not install in potentially explosive or flammable atmospheres laden with grain dust, sawdust, or similar airborne materials.
• Installation of humidifier in high humidity or salt water atmospheres causes accelerated corrosion, reducing the normal life-span of the unit.
• To prevent premature heat exchanger failure, do not locate any gas­fired unit in areas where chlorinated, halogenated, or acid vapors are present in the atmosphere.
• Locate the humidifier in an area clear of combustible materials, gasoline, and other flammable vapors and liquids.
• With the exception of sealed combustion units, do not locate units in tightly sealed rooms or small compartments without provision for adequate combustion air and venting. Room air combustion must be supplied through a minimum of two permanent openings in the wall, with at least one near the bottom. See the table and information on Page 30 for additional information.
• Remove all shipping brackets and materials before operating the humidifier.
• Do not locate humidifier in a negative pressure space. Combustion products could be suctioned from the venting.
• Humidifier flue gases must be vented to the outside atmosphere.
• Power supply disconnect switch must be in the off position while making wiring connections to prevent electrical shock and equipment damage. All units must be wired in strict accordance with the wiring diagrams furnished with this unit.
• Turn off all gas while installing the gas piping and manual shutoff valve for the humidifier.
• The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures exceeding 0.5 psig (3.5 kPa).
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 5
Figure 6-1: GTS standard water model VLC
Steam outlet
Water level probe
Water supply line
P r o d u c t o v e r v i e w
Optional Ultra-sorb dispersion panel installed in duct
Vapor hose
Flue box
Blower
Gas valve
Notes:
• GTS standard water models can be converted in the field for use with deionized/reverse osmosis (DI/RO) water. GTS-DI models can be converted in the field for use with potable or softened water.
• Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty.
Heat exchanger
Control components
Drain valve
OM-1201
GTS standard water models
GTS standard water gas-fired humidifiers burn either natural or propane gas to heat potable or softened fill water into steam for humidification. The unit has from one to four burners that fire into a heat exchanger submerged in a tank of water. When there is a call for humidity, the burners fire and generate steam until the call for humidity ends. A probe monitors water level, requiring water conductivity to be at least 100 µS/cm to operate properly. Therefore, GTS standard water models do not operate with demineralized water (deionized or reverse osmosis treated water). For demineralized water operation, use the GTS-DI model (described on next page).
Pag e 6 • DRI - S TEE M G TS Hu m i difi e r Ins t a llat i on, O p e rat i o n, an d M aint e nanc e M anua l
P r o d u c t o v e r v i e w ( c o n t i n u e d )
Figure 7-1: GTS-DI (DI/RO water model)
Blower
Gas valve
Water supply line
Flue connection
Float for water fill valve
Air gap
Open drain
Steam outlet
Redundant low water cutoff sensor
Float-operated low water cutoff
Overflow outlet
Drain valve
Drain piping (by installer)
GTS-DI models
GTS-DI humidifiers burn either natural or propane gas to heat deionized (DI) or reverse osmosis (RO) fill water into steam for humidification. GTS-DI models control water level using a float valve.
GTS-DI models are virtually maintenance-free and require very little or no downtime.
The GTS-DI model is available for use with deionized or reverse osmosis water. This unit produces chemical-free steam and reliable, accurate humidification control.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 7
OM-1202
Notes:
• GTS standard water models can be converted in the field for use with deionized/reverse osmosis (DI/RO) water. GTS-DI models can be converted in the field for use with potable or softened water.
• Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty.
S p e c i f i c a t i o n s , ca p a c i t i e s , a n d w e i g h t s
Table 8-1: GTS specifications, capacities, and weights for North American models only
Maximum
GTS
model
GTS-100 75 34 100 29 2.76 9 34.1 48 181.7 700 320 375 170 800 365 500 230 1.8 2.8
GTS-200 150 68 200 59 5.52 18 68.1 48 181.7 700 320 375 170 800 365 500 230 1.8 2.8
GTS-300 225 102 300 88 8.28 27 102.2 52 196.8 850 385 450 205 1000 455 600 270 3.0 4.0
GTS-400 300 136 400 117 11.04 36 136.3 52 196.8 850 385 450 205 1000 455 600 270 3.0 4.0
GTS-500 375 170 500 147 13.80 45 170.3 76 287.7 1100 500 600 270 1450 660 950 430 4.5 5.5
GTS-600 450 204 600 176 16.56 54 204.4 76 287.7 1100 500 600 270 1450 660 950 430 4.5 5.5
GTS-700 525 238 700 205 19.32 63 238.5 89 336.9 1400 635 700 320 1750 795 1050 475 6.0 7.0
GTS-800 600 272 800 234 22.08 72 272.5 89 336.9 1400 635 700 320 1750 795 1050 475 6.0 7.0
Note:
* Add 15 full load amps for outdoor enclosure heater load on all GTS models ** Add 10% to account for skim and automatic drain/flush features if utilized (standard water units only).
steam
capacity
lbs/hr kg/h MBh kW m3/h
Input
I m po r t an t : See Pages 76-77 for
additional European model specifications and capacity notes.
Water usage at maximum
capacity**
gals/hrlitres/
hr
Tank
volume
gals litres lbs kg lbs kg lbs kg lbs kg
Operating
weight
Capacity notes
• At sea level, approximately 152 Btu are required to raise the temperature of one pound of water from 60 °F to 212 °F. (At sea
GTS GTS with outdoor enclosure
Shipping
weight
Operating
weight
Shipping
weight
Full load
amps*
120 V 60 Hz
230 V 50 Hz
level, approximately 352 kJ are required to raise the temperature
Table 8-2: High altitude derate
Altitude
feet meters
0–2000 0–610 0
2001–2500 610–765 2
2501–3000 765–915 4
3001–3500 915–1065 6
3501–4000 1065–1220 8
4001–4500 1220–1370 10
4501–5000 1370–1525 12
5001–5500 1525–1675 14
5501–6000 1675–1830 16
6001–6500 1830–1980 18
6501–7000 1980–2135 20
7001–7500 2135–2285 22
7501–8000 2285–2440 24
derate %
Input
of one kilogram of water from 16 °C to 100 °C.)
• An additional 970 Btu are required to change the state of one pound of 212 °F water to vapor. (An additional 2257 kJ are required to change the state of one kilogram of 100 °C water to vapor.)
• Another factor to consider is condensation steam loss from piping. Use the following general steam loss guidelines:
– Vapor hose: 0.15 lbs/hr/ft (0.22 kg/h/m) – Insulated pipe: 0.05 lbs/hr/ft (0.07 kg/h/m) – Hard pipe and dispersion tubes: 0.50 lbs/hr/ft (0.7 kg/h/m) – High-eciency dispersion tubes: 0.20 lbs/hr/ (0.298 kg/h/m)
For more detailed information about condensation steam loss, see the DRI-STEEM Design Guide or our software program, Dri-calc.
LP gas
All models operate at rated input.
High altitude
An input derate exists when operating units at a high altitude. See Table 8-2 for high altitude derate information.
Pag e 8 • DRI - S TEE M G TS Hu m i difi e r Ins t a llat i on, O p e rat i o n, an d M aint e nanc e M anua l
D i m e n s i o n s
Figure 9-1: Dimensions
Side viewFront viewTop view
F
D
E
Table 9-1: Dimensions
Description
G
C
J
L
M
B
GTS-100 GTS-200
inches mm inches mm inches mm inches mm
GTS-300 GTS-400
K
A
GTS-500 GTS-600
H
5" (127 mm)
OM-1203
GTS-700 GTS-800
A Overall length 54.35 1380 54.35 1380 54.35 1380 54.35 1380
B Overall width 26.38 670 32.38 822 42.38 1076 48.38 1229
C Shroud height 41.00 1040 41.00 1040 41.00 1040 41.00 1040
D
Flue position
E 13.00 330 15.63 397 18.63 475 21.00 533
F Flue diameter 5.00 127 7.00 178 8.00 203 10.00 254
G
Steam outlet position
H 11.63 295 11.63 295 11.63 295 11.63 295
J
Fill valve connection position
K 13.00 330 13.00 330 13.00 330 13.00 330
L
Drain position
M 8.00 203 8.00 203 8.00 203 8.00 203
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 9
18.00 457 17.00 432 17.00 432 16.25 413
14.00 356 20.50 521 29.25 743 35.25 895
13.00 330 13.00 330 13.00 330 13.00 330
8.75 222 8.75 222 8.75 222 8.75 222
L o c a t i n g t h e h u m i d i f i e r a n d c l e a r a n c e r e c o m m e n d a t i o n s
Locating the humidifier
• Provide a level, solid foundation for the humidifier.
• Locate the humidifier as near as possible to a chimney or outside wall so that the flue pipe from the humidifier is short and direct.
• Locate the unit so it and its electrical components are protected from water during humidifier operation and service.
• Install the humidifier in a location away (and protected) from drafts. If installed in a separate room, follow the instructions concerning combustion and ventilation air.
• Locate the humidifier in an area where leakage from the tank or its connections will not result in damage to the adjacent structure or to lower floors of the structure. When such locations cannot be avoided, install a suitable drain pan (adequately drained) under the humidifier. The pan must not restrict combustion airflow.
• Do not install the humidifier on carpeting, tile or other combustible material other than wood flooring (indoor application only).
• If located in an insulated space, keep the humidifier free and clear of insulating materials. Insulating material can be combustible. Inspect the humidifier area when the humidifier is installed or when insulation is added.
Figure 10-1: GTS clearance recommendations
18" (457 mm)
36" (914 mm)
30" (762 mm)
OM-1222
Note:
DRI-STEEM recommends a minimum of 1" (25 mm) clearance between hot surfaces and combustible walls.
Pag e 1 0 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
O u t d o o r e n c l o s u r e m o u n t i n g
Outdoor enclosure mounting option
The outdoor enclosure option is used when the GTS is installed outdoors. The following information is not intended to supersede any requirements of federal, state, or governing codes having jurisdiction; prior to locating the unit, authorities having jurisdiction should be consulted.
Figure 11-1: Outdoor enclosure typical installation overview
Steam piping
GTS humidifier in outdoor enclosure
Roof surface
Flue
Curb
Drain piping
Water piping
Electrical connections
Gas piping
Vapor-logic4 keypad shown with optional cable length. Keypad ships standard with 5' (1.5 m) of cable
OM-1238
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 1
O u t d o o r e n c l o s u r e m o u n t i n g ( c o n t i n u e d )
Handling
The GTS outdoor enclosure must be lifted from the bottom base in a fashion that holds it level and keeps it from tipping, falling, or twisting. If the unit is severely twisted during handling, permanent damage can occur. It is the installer’s responsibility to verify the handling equipment’s capability to safely handle the unit.
Lift the outdoor enclosure by using special lifting lug hooks installed on the unit. All lifting operations must be accomplished with a load spreader of sufficient width to ensure that the lifting cables clear the side of the unit.
Pag e 1 2 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
O u t d o o r e n c l o s u r e m o u n t i n g ( c o n t i n u e d )
Location
• The GTS outdoor enclosure must be level and located so there is enough clearance for opening the access panels.
• Verify that the position of pad or curb properly supports the unit and that support structure dimensions coincide with unit dimensions.
• Do not locate unit in areas where the surrounding air has high levels of particulates, such as some industrial parks or areas near highways.
• Locate unit so air intakes are not too close to exhaust fan outlets, gasoline storage, or other contaminants that potentially could cause dangerous situations. Using and storing gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
• When located on the roof, the air intakes must be a minimum of 14" (360 mm) off the roof to prevent intake of snow or splashed rain. The unit should be located so prevailing winds do not blow into the air intakes.
• An emergency drain is provided. In case of any water leak, water drains onto the roof through this emergency drain.
• A keypad with standard 5' (1.5 m) cable ships mounted to the subpanel in the GTS outdoor enclosure. The keypad must not come in contact with the strip heaters or block the intake ventilation hood.
• If constant monitoring of the unit is desired, or if the unit is located in a severe climate, install a remote mount keypad. Additional cable lengths up to 500' (152 m) are available as an option for this mounting configuration.
• Curbs (optional) are shipped knocked down for ease of transporting to the roof. Curbs are manufactured of 14-gauge galvanized steel and shipped with all hardware for bolt-together assembly. All holes are matched before leaving the factory. Curb is to be a minimum of 14" (360 mm) high. A closed-cell curb gasket with adhesive on one side is supplied with hardware. An installation drawing also is included. To prevent moisture from leaking into the building from either driving rain or melting snow, install the gasket between the top of the curb and the base surface of the unit.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 3
O u t d o o r e n c l o s u r e m o u n t i n g ( c o n t i n u e d )
Before you begin
• Prior to installing the unit, remove all packaging.
• During the transit, unloading, and setting of the unit, bolts and nuts may become loose. Check that all nuts are tightened as required.
• There are three knockouts located on the right and left side of the enclosure. DRI-STEEM recommends running electrical power into the enclosure at these knockouts.
• When unit is mounted on an outdoor curb, there must be a gasket between the top of the curb and the base surface of the unit to prevent moisture from leaking into the building from either driving rain or melting snow.
• The outdoor enclosure has two available steam distribution configurations. The standard configuration has a steam outlet at the back of the outdoor enclosure for connecting to steam dispersion unit piping. The optional internal steam distribution configuration routes steam within the outdoor enclosure and down through the pipe chase into a building. See drawings on Pages 15 and 16.
I m po r ta n t : A pipe chase is located inside the burner section
of the enclosure. DRI-STEEM recommends using this pipe chase for both the supply water piping and drain piping. Use insulation to completely fill the area around the pipes to maintain proper enclosure pressure and protect unit components from elevated moisture levels within building; insulation must serve as an effective vapor barrier. Use the provided pipe chase cover to seal off the pipe chase. Cut necessary holes and seal after installation.
• The heater package has two thermostat-controlled heaters: one strip heater is located in the control section, and one strip heater is located in the burner section to keep the enclosure at a constant minimum temperature. Once the humidifier tank is full and up to temperature, the tank will keep the enclosure at an appropriate temperature. The heaters will turn off.
• Refer to the installation section of this manual for directions on installing electrical, gas, flue, drain, and water connections. A separate electrical service connection for the outdoor GTS is recommended. Insulation and/or heat taping of water piping is recommended.
Pag e 1 4 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
O u t d o o r e n c l o s u r e m o u n t i n g ( c o n t i n u e d )
Piping
• Insulate supply water piping to avoid dripping from condensation. To ensure that water does not remain in the fill line and freeze if there is a loss of power, DRI-STEEM recommends field installing additional valves upstream of the fill valve in a conditioned space. Power these valves on the same circuit as the GTS; if the power goes off, water drains out of the fill line to prevent freezing (see Figure 15-1).
• When pad-mounted or when the pipe chase cannot be used, the supply water and drain piping can be run through the knockouts, although preferably on the opposite side from the gas and electric.
• Install external flue piping shall be provided by installers and field installed. The flue of the outdoor enclosure exits out the left side of the unit and a vertical stack must be constructed. The stack must be a minimum of 5–10 feet (1.5–3.0 m) above the top of the roof. However, the exact height varies depending on unit size, climate, etc. Governing codes prevail. A UL or UL/CSA (or equivalent) listed cap must be used and a drip tee included.
Figure 15-1: Outdoor enclosure installation detail
Normally closed fill valve (by factory)
Make-up water supply piping (by installer)
Open to drain
Vent with check valve (by installer)
120 V (230 V in Europe)
from unit disconnect or
other source
Normally closed (fail closed) min 3/8" electric valve (by installer)
Domestic water, 80 psig (582 kPa) maximum
OM-4045
GTS humidifier in outdoor enclosure installed on roof top
Roof decking
Drain line, min. 1½" electric valve
Optional water seal (P-trap) drain line, min. 1½" (DN40)
Normally open (fail open) min ½" electric valve (by installer)
Open drain
Disconnect (by installer); see Detail A
120 V supply (230 V in Europe)
Heated building interior
120 V (230 V in Europe)
Disconnect box
Detail A
N
To valves (by installer)
To GTS humidifier
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 5
O u t d o o r e n c l o s u r e m o u n t i n g ( c o n t i n u e d )
Figure 16-1: GTS outdoor enclosure with standard or optional steam outlet, elevation view
Standard steam outlet Optional steam outlet
Flue piping (by installer)
Steam outlet (See Note 1)
Ventilation fans
Combustion
air intake
1½" (38 mm) knockouts
4" (102 mm) o.c.
Pipe chase
Notes:
1. The outdoor enclosure has two available steam distribution configurations. The standard configuration has a steam outlet at the back of the outdoor enclosure for connecting to steam dispersion unit piping. The optional internal steam distribution configuration routes steam within the outdoor enclosure and down through the enclosure pipe chase into a building.
2. There are three knockouts located on the right and left side of the enclosure. Run the electrical power and gas piping into the enclosure at these knockouts.
3. Piping from the GTS unit to the steam outlet is stainless steel pipe. Piping from the steam outlet to the dispersion assembly is provided by the installer. Choose interconnecting steam piping material that is appropriate for the application (e.g., for high-purity steam applications, consider using stainless steel interconnecting steam piping). See Page 22 for steam outlet sizes.
4. The GTS housed in an outdoor enclosure will operate properly in operating temperature of –40 °F to 122 °F (–40 °C to 50 °C).
Emergency drain
GTS humidifier
Power block
OM-1228M
Ventilation fans
Combustion
air intake
1½" (38 mm) knockouts
4" (102 mm) o.c.
Pipe chase
Emergency drain
Flue piping (by others)
Steam outlet (See Note 1)
GTS humidifier
Power block
OM-1227M
Pag e 1 6 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
O u t d o o r e n c l o s u r e m o u n t i n g ( c o n t i n u e d )
Table 17-1: Outdoor enclosure dimensions
GTS-100
Description
A Enclosure height 54.63 1388 54.63 1388 54.63 1388 54.63 1388
B Enclosure width 26.00 660 32.00 813 42.00 1067 48.00 1219
C Enclosure length 57.25 1454 57.25 1454 57.25 1454 57.25 1454
GTS-200
inches mm inches mm inches mm inches mm
GTS-300 GTS-400
GTS-500 GTS-600
GTS-700 GTS-800
Figure 17-1: Outdoor enclosure mounted on a curb
14"
(356 mm)
B
C
OM-7431
Table 17-2: Outdoor enclosure top view dimensions
GTS-100
Description
Enclosure
T
width
U
Pipe chase position
V 3.00 76 3.00 76 3.00 76 3.00 76
W
Pipe chase size
X 11.00 279 11.00 279 11.00 279 11.00 279
Y
Steam pipe position
Z 21.00 533 27.00 686 37.00 940 43.00 109
GTS-200
inches mm inches mm inches mm inches mm
26.00 660 32.00 813 42.00 1067 48.00 1219
3.00 76 3.00 76 3.00 76 3.00 76
16.00 406 16.00 406 16.00 406 16.00 406
14.12 359 20.12 511 30.12 765 36.12 917
GTS-300 GTS-400
GTS-500 GTS-600
GTS-700 GTS-800
Figure 17-2: Outdoor enclosure mounted flush
A
B
C
Figure 17-3: Outdoor enclosure top view
Exit for standard steam outlet
GTS humidifier
Exit for optional steam outlet (through pipe chase)
Flue (by installer)
Burner section heater
Access panel door
T
Y
Z
W
U
OM-7430
Control panel heater
Access panel door
Intake ventilation fans
X
V
OM-7432
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 7
O u t d o o r e n c l o s u r e o p e r a t i o n
GTS outdoor enclosure sequence of operation
• Power is applied to the outdoor enclosure.
• If the ambient temperature in the enclosure is below 50 °F (10 °C), the strip heaters are powered up. If the enclosure
temperature reaches 35 °F (2 °C), power is allowed to the GTS subpanel and the GTS unit is enabled. The strip heaters remain on until the enclosure reaches 50 °F (10 °C) to ensure that the temperature inside the enclosure does not drop below the freezing point.
• When the enclosure temperature is at or above 50 °F (10 °C), the GTS tank heats the enclosure. When there is no call for humidity, an aquastat maintains tank temperature at the factory default of 70 °F (21 °C). This temperature can be reset in the field to be from 40-180 °F (4-82 °C).
• When the ambient temperature in the enclosure reaches 85 °F (29 °C), two ventilation fans turn on to cool the electronic components. A high limit is also provided to power down the GTS if the enclosure temperature reaches 150 °F (66 °C). In a high limit situation, the ventilation fans continue to run and once the enclosure temperature falls below 130 °F (54 °C), the GTS automatically resumes normal operation.
• A normally open drain valve is provided on the GTS outdoor enclosure to drain the tank in the event of a power loss.
Pag e 1 8 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
W i r i n g : E l e c t r i c a l co n n e c t i o n s
W A R N I N G !
Installation must meet the requirements of governing codes or, in the absence of governing codes, in accordance with the National Electrical Code, ANSI/NFPA 70, or Canadian Electrical Code, CSA C22.1, or IEE wiring regulations (BS7671). The electrical subpanel must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. This ground can consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground.
• GTS humidifiers must be supplied with 120-volt AC, 60 Hz (North American models) or 230-volt AC, 50 Hz (European models) separately fused electrical service. The GTS humidifier is equipped with a transformer to step down the voltage to 24 VAC control voltage.
• When installed, the GTS humidifier must be electrically grounded in accordance with governing codes or, in the absence of governing codes, in accordance with the National Electrical Code, ANSI/NFPA 70; or Canadian Electrical Code, CSA C22.1; or IEE wiring regulations (BS7671).
In North America, the electrical conductors shall be Type MTW
(105 °C) AWG #14 (2.5 mm2) wire for 120 V line voltage , with BLACK WIRE for HOT, WHITE WIRE for NEUTRAL, GREEN AND YELLOW WIRE for GROUND. Units with outdoor enclosure must use AWG #12 (4 mm2) for 120 V line voltage.Use #18 gauge (1 mm2) for control wiring.
In Europe, the electrical conductors shall be Type MTW (105 °C)
2.5 mm2 wire for line voltage (230V), with BLACK WIRE for LINE, BLUE WIRE for NEUTRAL, GREEN AND YELLOW WIRE for GROUND, and 2.5 mm2 wire for control wiring.
• All electrical components and wiring must be protected from mechanical damage and water. The control system requires an earth ground for proper operation.
• The GTS humidifier is adjusted for correct performance. Only a qualified gas appliance technician may alter throttle setting.
• Check the electric current characteristics and capacity requirements against the nameplate. All wiring must be in accordance with all governing codes and with the GTS wiring diagrams located inside the control cabinet. See table on Page 8 for information on the various models.
• Refer to the Vapor-logic4 Installation and Operation Manual for additional information on the controller furnished with this GTS humidifier.
W A R N I N G !
Do not connect aluminum wire between disconnect switch and humidifier. Use only copper wire. Failure to follow these instructions could cause a fire, resulting in severe bodily injury, death, or significant property damage.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 1 9
Figure 20-1: Field piping overview for GTS standard water models
Optional condensate return piping from dispersion
unit; ¾" pipe thread (DN20) fitting at humidifier
Shock arrester recommended to reduce water hammer, by installer
Flue size per governing codes. Do not reduce.
Water supply line; water
pressure range 25 psi to 80 psi
(172 kPa to 582 kPa); water
conductivity minimum 100 µS/cm
G T S p i p i n g , s t a n d a r d w a t e r m o d e l s
Steam hose, pipe or tubing
Install level
Air vent tube
6" (150 mm)
minimum vent height
Flue connection
Offset humidifier from floor drain to prevent flash steam from rising into the humidifier
1½" NPT (DN40) drain piping must be rated for 212 °F (100 °C) (by installer)
1" (25 mm) air gap
Notes:
• Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
• Dashed lines indicate provided by installer.
• Humidifier flue gases must be vented to the outside atmosphere.
• The water supply inlet is more than 1" (25 mm) above the skim/overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required; however, governing codes prevail.
• Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty.
• See the next page for recommended water supply piping for DI/RO water models.
Air vent height must be equal to or greater than dimension “H” (see table below)
Install level
H
Gas inlet connection
Open drain required. See first note below.
Table 20-1: Height required to overcome GTS internal pressure (H)
H = Height required to overcome humidifier internal pressure
GTS model
number
inches mm
100, 200 35 889
300, 400, 500, 600,
700, 800
41 1041
OM-1208
Pag e 2 0 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l
G T S p i p i n g , D I / R O w a t e r m o d e l s
Figure 21-1: Field piping overview for GTS DI/RO water models
Optional condensate return piping from dispersion unit;
¾" pipe thread (DN20)
fitting at humidifier
Flue size per governing codes. Do not reduce.
Water supply line; water
pressure range 25 psi to 80 psi
(172 kPa to 582 kPa); first 3'
(1 m) of supply line must be
rated for 212 °F (100 °C)
Steam hose, pipe or tubing
Install level
minimum vent height
Air vent tube If water piping to humidifier is nonmetallic, we recommend
a 2" (50 mm) water seal in the supply line to isolate steam during DI/RO water system maintenance.
Inlet strainer by installer
6" (150 mm)
Flue connection
Offset humidifier from floor
drain to prevent flash steam
from rising into the humidifier
1½" (DN40) drain piping must be rated for 212 °F (100 °C)
1" (25 mm) air gap
Gas inlet connection
Open drain required. See first note below.
Table 21-1: Height required to overcome GTS-DI internal pressure (H)
H = Height required to overcome humidifier internal pressure
GTS-DI model
number
inches mm
100, 200 35 889
300, 400, 500, 600, 700, 800
41 1041
Install level
Air vent tube height must be equal to or greater than dimension “H“ (see table below)
H
OM-1223
Notes:
• Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
• Dashed lines indicate provided by installer.
• Humidifier flue gases must be vented to the outside atmosphere.
• The water supply inlet is more than 1" (25 mm) above the overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional backflow prevention is required; however, governing codes prevail.
• Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty.
• In order to minimize DI/RO water use, disconnect factory piping to the water tempering device and pipe directly to tap water.
• See the previous page for recommended water supply piping for standard water models.
DRI - STEE M G TS Hu m idif i e r Ins t alla t i on, O p erat i o n, and Main t e nanc e Manu a l • Pag e 2 1
S u p p l y w a t e r a n d d r a i n o v e r f l o w c o n n e c t i o n s
Supply water and drain overflow connections
Regardless of the type of water used, the following general instructions MUST be followed:
• Make union connections at the humidifier on the make-up water supply and drain/overflow lines.
• Provide a shutoff valve in the supply water line to isolate the humidifier from the water system while servicing.
• Shock arrester, provided by installer, is recommended to reduce water hammer.
• A 1" (25 mm) opening is provided in the humidifier tank to accommodate skim and/or overflow protection. (Note: Follow governing code requirements regarding size of drain pipe.)
• Use insulating unions or bushings to make connections between copper and other dissimilar metal fittings, such as galvanized steel. These insulating fittings are required to minimize electrolytic corrosion, which results from the direct connection of dissimilar metals in a water system.
• Before beginning ignition sequence of the humidifier at a new installation, make sure the humidifier tank is full of water and the water is free to flow into the tank.
• If planning to use heated supply water, disconnect the water supply line to the water tempering device at the fill manifold and reconnect it to a cold water supply. This will ensure that the water tempering device operates properly.
Table 22-1: Connection sizes
GTS-100
Description
Gas supply
Sealed combustion piping (optional)
Flue vent 5 125 7 180 8 200 10 250
Water supply to fill valve and tempering device*
Drain
Steam outlet
Condensate return (recommended)
Notes:
* In order to minimize DI/RO water use, disconnect factory piping to the water tempering device and pipe directly to tap water.
If planning to use heated supply water, disconnect the water line to the water tempering device at the fill manifold, and reconnect it to a cold water supply. This will ensure that the water tempering device operates properly.
(pipe thread)
(pipe thread)
(pipe thread)
(pipe thread or
(pipe thread)
GTS-200
inches DN inches DN inches DN inches DN
½
4 100 4 100 4 100 4 100
3/8
2
hose)
¾
15
10
40
50
20
(pipe thread)
(pipe thread)
(pipe thread)
(pipe thread)
1
3/8
3
(flange)
¾
GTS-300 GTS-400
GTS-500 GTS-600
25
10
40
80
20
1
(pipe thread)
3/8
(pipe thread)
(pipe thread)
4
(flange)
¾
(pipe thread)
25
10
40
100
20
(pipe thread)
(pipe thread)
(pipe thread)
(pipe thread)
3/8
4
(flange)
¾
GTS-700 GTS-800
32
10
40
100
20
Pag e 2 2 • DR I - STE E M GTS H u m idif i er In s t alla t ion, O p era t i on, a n d Main t enan c e Manu a l