This manual will guide you through installation,
operation and maintenance procedures for your new
DRANE-KOOLER. Proper installation and operating
practices will ensure years of trouble-free service.
Technical support: 800-328-4447
If you have questions, review the troubleshooting
guide on Page 10. If you still have questions, call our
customer support group at 800-328-4447. Technicians
are available from 7:30 a.m. to 5:00 p.m. (central
standard time) Monday through Friday, excluding
major holidays.
Visit our web site:
www.dristeem.com
For information about other DRI-STEEM products,
visit our web site, or contact us using the information
listed below.
DRANE-KOOLER is a water tempering device that
mixes cold water with hot water discharged from
various types of equipment, such as a humidifier, to
reduce the discharged water temperature before it
enters a municipal sewer system.
There are two reasons to use a water tempering
device. First, most municipalities prohibit draining
water hotter than 140 °F (60 °C) into their sewer
systems. And second, PVC drain pipes are susceptible
to damage from water that is too hot. When faced
with either of these situations, DRANE-KOOLER is
the solution!
New horizontal design!
A new space-efficient horizontal orientation and side
drain outlet provide enough clearance to allow the
DRANE-KOOLER to be mounted directly
underneath DRI-STEEM humidifiers, saving
footprint space while allowing room for pitched drain
piping.
Reliable, non-electric valve
The temperature-actuated valve is time-tested to be
reliable and maintenance-free. And because it is nonelectric, no wiring is required!
Multiple mounting options
The DRANE-KOOLER can be mounted by attaching
the integral mounting plate to a wall, by attaching the
mounting plate to an adjustable floor stand, or by
using an assembly for suspension mounting. These
multiple mounting options provide capability for the
DRANE-KOOLER to be properly supported and not
secured entirely by piping.
How it works: Hot + cold = tempered!
1.Hot water discharged from a humidifier or other
appliance enters the DRANE-KOOLER through
piping connected to the top threaded connection.
A vacuum breaker prevents backflow into
potable water systems.
2. Cold water enters through the temperature-
actuated valve. The valve and the
DRANE-KOOLER's straightforward design
ensure efficient mixing of hot and cold water.
The valve's sensor, located near the outlet,
ensures that water leaving the
DRANE-KOOLER is 140 °F (60 °C)* or less
before entering the municipal sewer system.
3. Tempered water at 140°F (60°C)* or less exits
through the side outlet for safe discharge into a
municipal sewer system or PVC pipe.
*Please see the capacities table on the next page.
1
2
3
Product overview:
Summary of features
1
Page 6
Product overview
Capacities and connection sizes.
DRANE-KOOLER capacities*DRANE-KOOLER connections
Maximum flo w
rate
U.S.
gpm
Hot water
inflow
Cold water
inflow**
Tempered
water outflow
* This table applies only if one humidifier is connected to
one DRANE-KOOLER, with no more than 10' ( 3 m) of
vertical dimension between the humidifier and the
DRANE-KOOLER. If you wish to connect more than
one humidifier to a DRANE-KOOLER, or if you need more
than 10' (3 m) of vertical dimension, consult the factory.
DRANE-KOOLER does not exceed 6 U.S.
gallons per minute (gpm) (22.7 L/m).
q Note that there are three connections to be made
to the DRANE-KOOLER:
Cold water supply
Hot water inlet (from a humidifier or other
appliance)
Tempered water piping to drain
q Position the DRANE-KOOLER to allow the
most direct path of piping to minimize fittings
(see the piping diagrams on Pages 6-7).
q Position unions on all connections as close to the
DRANE-KOOLER as possible to make cleaning
and maintenance easier.
q Cold water supply connection instructions:
Cold water supply connection on valve is
3/8"(DN10) NPT.
Pipe a 3/8" (DN10) line directly to the
DRANE-KOOLER from the main water
supply line.
TO ENSURE ADEQUATE WATER
PRESSURE TO THE DRANE-KOOLER, DO
NOT CONNECT TO A SUPPLY WATER
LINE THAT IS DEDICATED TO OTHER
APPLIANCES.
q Hot water inlet connection instructions:
Hot water inlet connection is 1" (DN25) NPT.
Locate a union as close to the
DRANE-KOOLER as possible
Run 1" (DN25) pipe as directly as possible
from the hot water appliance (humidifier) to
the DRANE-KOOLER. If the piping to the hot
water inlet has a horizontal run, maintain a
pitch to the DRANE-KOOLER of at least
1/8"/ft (1%).
q Tempered water (to drain) connection
instructions:
Tempered water outlet connection is
2"(DN50) NPT.
Install a union as close to the
DRANE-KOOLER as possible.
Run a 2"(DN50) pipe as directly as possible
from the DRANE-KOOLER to the drain.
Maintain a pitch to drain of at least 1/8"/ft
(1%).
Make sure there is a 1" (25 mm) air gap
between the drain piping and the drain.
If installing the DRANE-KOOLER with a
humidifier, do not branch off the 1/4" (DN8)
cold water supply line to the humidifier.
Verify that the supply water pressure to the
valve is at least 25psi (172kPa) and not more
than 80psi (552kPa).
Install a cold water supply union as close to
the DRANE-KOOLER as possible.
Install a cold water shut-off valve before the
union in the cold water supply line.
Installation:
4
Installation checklist
Page 9
Installation
Mounting options.
Three mounting options
Use one of the mounting options shown on this page
to ensure that the DRANE-KOOLER will be properly
supported and not secured entirely by piping. Floor
stand and suspension mount hanger assembly are
ordered separately.
Wall mount
Suspension mount*
Floor mount
OM-1114
OM-1115
OM-1116
*The suspension mount hanger assembly includes an
L-bracket, two nuts, and two bolts that attach to the
DRANE-KOOLER. Beam clamp assembly and 1/4"
threaded rod are supplied by others.
Installation:
Mounting options
5
Page 10
Installation
DRANE-KOOLER piping.
Cold water supply piping:
3/8" (DN10) NPT
Water pressure must be
between 25 psi and 80 psi
(172 kPa and 552 kPa).
Connect directly to the main
water supply line. TO
ENSURE ADEQUATE
WATER PRESSURE TO
THE DRANE-KOOLER, DO
NOT CONNECT TO A
SUPPLY WATER LINE
THAT IS DEDICATED TO
OTHER APPLIANCES.
Cold
water
supply
shut-off
valve
Cold
water
inlet
service
union:
3/8" (DN10)
NPT
Hot
water
inlet
service
union:
1" (DN25)
NPT
Evaporative humidifier
Installation:
6
Piping
Tempered water drain piping: 2" (DN50) NPT . PIPING MUST BE RUN
1" (25 mm) air gap
before drain
Drain
Tempered water outlet service union: 2" (DN50) NPT
Anchor mounting plate to floor
FULL SIZE TO DRAIN WITH NO REDUCERS.
Recommended minimum pitch: 1/8" per ft (1%)
OM-1120
Page 11
Installation
DRANE-KOOLER piping.
Two examples showing the DRANE-KOOLER mounted directly underneath an evaporative humidifier
Pitch drain piping at least
1/8"/ft (1%) in direction of
arrows.
DRANE-KOOLER
DRANE-KOOLER
OM-1121
Pitch drain piping at least
1/8"/ft (1%) in direction of
arrows.
OM-1122
Installation:
Piping
7
Page 12
Operation
DRANE-KOOLER operation.
How to operate
Once properly installed, to operate simply open the
cold water supply valve.
1
Principle of operation
Temperatureactuated valve
Vacuum breaker
2
Capillary tube
1.Hot water discharged from a humidifier or other
appliance enters the DRANE-KOOLER through
piping connected to the top threaded connection.
The vacuum breaker prevents backflow into
potable water systems.
Sensor
3
OM-1114-2
2. Cold water enters through the temperature-
actuated valve. The valve and the
DRANE-KOOLER's straightforward design
ensure efficient mixing of hot and cold water. The
valve's sensor, located near the outlet, ensures
that water leaving the DRANE-KOOLER is less
than 140 °F (60 °C)* before entering the
municipal sewer system.
Operation:
8
Start-up and operation
3. Tempered water at 140°F (60°C)* or less exits
through the side outlet for safe discharge into a
municipal sewer system or PVC pipe.
*Please see the capacities table on Page 2.
Page 13
Maintenance
DRANE-KOOLER maintenance.
Step-by-step maintenance instructions
q Shut off cold water supply.
q Disconnect service unions at:
Cold water supply inlet
Hot water inlet
Tempered water drain outlet
q Remove the DRANE-KOOLER from piping
and take to a service sink. Add water and,
with pipe caps or hands covering the hot water
inlet and tempered water outlet, shake the
DRANE-KOOLER to dislodge mineral deposits.
Dump mineral deposits and rinse.
q If severe mineral accumulation has occurred,
remove the thermal sensor from the
DRANE-KOOLER chamber and gently clean
the sensor with an abrasive pad. Do not twist the
capillary tube during removal or cleaning.
q Reconnect service unions and open cold water
supply valve to resume operation.
Maintenance:
Maintenance instructions
9
Page 14
Maintenance
Troubleshooting guide.
Problem
number
Problem
Possible cause
Action
1
Water leaving the
DRANE-KOOLER is
hotter than 140°F
(60°C)
Mineral accumulation in
mixing chamber
Mineral accumulation
on thermal sensor
Valve malfunction
Steam is entering the
DRANE-KOOLER
Remove the DRANE-KOOLER and
dislodge mineral accumulation.
Remove thermal sensor from
DRANE-KOOLER and gently remove
mineral accumulation with an abrasive
pad. Do not twist capillary tubing
during removal or cleaning.
Valve is not working properly.
Replace. Note: This valve is factoryset and should not need adjustment.
The DRANE-KOOLER is designed to
handle hot water and hot condensate. If
a large amount of steam enters the
DRANE-KOOLER it is likely that
discharge water temperatures will be
greater than 140°F (60°C). Check
P-traps on humidifier or other
appliance to ensure that the P-traps
have the proper depth and are working
properly to prevent steam from
entering the DRANE-KOOLER.
2
Maintenance:
10
Troubleshooting guide
Makes a loud popping
or crackling noise
Steam is entering the
DRANE-KOOLER
If steam is entering the
DRANE-KOOLER, the introduction of
cold water through the valve will cause
the steam to collapse and make a
popping or crackling sound. Check
P-traps on humidifier or other
appliance to ensure that the P-traps
have the proper depth and are working
properly.
DRI-STEEM Humidifier Company (DRI-STEEM)
warrants to the original user that its products will be
free from defects in materials and workmanship for a
period of two (2) years after installation or twentyseven (27) months from the date DRI-STEEM ships
such product, whichever date is the earlier.
If any DRI-STEEM product is found to be defective
in material or workmanship during the applicable
warranty period, DRI-STEEMs entire liability, and
the purchasers sole and exclusive remedy, shall be
the repair or replacement of the defective product, or
the refund of the purchase price, at DRI-STEEMs
election. DRI-STEEM shall not be liable for any
costs or expenses, whether direct or indirect,
associated with the installation, removal or
reinstallation of any defective product.
DRI-STEEMs limited warranty shall not be effective
or actionable unless there is compliance with all
installation and operating instructions furnished by
DRI-STEEM, or if the products have been modified
or altered without the written consent of
DRI-STEEM, or if such products have been subject
to accident, misuse, mishandling, tampering,
negligence or improper maintenance. Any warranty
claim must be submitted to DRI-STEEM in writing
within the stated warranty period.
DRI-STEEMs limited warranty is made in lieu of,
and DRI-STEEM disclaims all other warranties,
whether express or implied, including but not limited
to any IMPLIED WARRANTY OF MERCHANTABILITY, ANY IMPLIED WARRANTY OF
FITNESS FOR A PARTICULAR PURPOSE, any
implied warranty arising out of a course of dealing or
of performance, custom or usage of trade.
DRI-STEEM SHALL NOT, UNDER ANY
CIRCUMSTANCES BE LIABLE FOR ANY
DIRECT, INDIRECT, INCIDENTAL, SPECIAL OR
CONSEQUENTIAL DAMAGES (INCLUDING,
BUT NOT LIMITED TO, LOSS OF PROFITS,
REVENUE OR BUSINESS) OR DAMAGE OR
INJURY TO PERSONS OR PROPERTY IN ANY
WAY RELATED TO THE MANUFACTURE OR
THE USE OF ITS PRODUCTS. The exclusion
applies regardless of whether such damages are
sought based on breach of warranty, breach of
contract, negligence, strict liability in tort, or any
other legal theory, even if DRI-STEEM has notice of
the possibility of such damages.
By purchasing DRI-STEEMs products, the purchaser
agrees to the terms and conditions of this limited
warranty.