DriSteem DE-SCALING SOLUTION Usage Instructions

READ AND SAVE THESE INSTRUCTIONS
DE-SCALING SOLUTION
Humidifier De-scaling Solution and Neutralizer
Usage Instructions
Table of contents
ATTENTION INSTALLER
Read this manual before installing. Leave manual with product owner.
DriSteem® Corporation Technical Support
North America: 800-328-4447
Europe: +3211823595
Call us at 800-328-4447
Obtaining documents from our web site or from DriCalc is the quickest way to view our literature, or we will be happy to mail literature to you.
Download DriSteem literature
Most DriSteem product manuals are available on our website: www.dristeem.com
Safety instructions ......................................3
Usage instructions ......................................4
GTS04, STS, and Vaporstream humidifiers ..................5
Vapormist®, CRUV, and VT humidifiers .....................8
GTS LX series and RTS® RX series humidifiers ...............11
Recommended quantity .................................14
DRISTEEM DE-SCALING SOLUTION USER INSTRUCTIONS
2

Safety instructions

INSTRUCTIONS
HUMIDIFIER DE-SCALING SOLUTION
CORROSIVE
8
CAUTION
Humidifier De-scaling Solution contains sulfamic acid and citric acid.
May be harmful if swallowed.
Avoid contact with skin and eyes. Avoid breathing mist.
Use with adequate ventilation.
Keep container closed.
FIRST AID
Eyes: Flush immediately with cool water for 15 minutes. Contact physician immediately.
Skin: Flush immediately with cool water for 15 minutes. Call physician immediately.
Inhalation: Remove to fresh air. If any irritation persists, call physician immediately.
Ingestion: DO NOT INDUCE VOMITING. If conscious, give large amounts of water. Call physician immediately.
STORAGE AND HANDLING INSTRUCTIONS
• Wear all protective equipment.
• Store away from and do not mix with strong bases.
• Use with adequate ventilation.
• Keep container closed when not in use.
• Wash thoroughly after handling product.
• Do not smoke near containers.
• Store away from food.
• Wash contaminated clothing before reuse.
HUMIDIFIER DE-SCALING NEUTRALIZER
CAUTION
Humidifier De-scaling Neutralizer contains soda ash.
Irritates eyes.
Avoid eye or prolonged skin contact.
Avoid breathing dust.
Use with adequate ventilation.
May form caustic when combined with lime in presence of moisture.
May be harmful if ingested.
DriSteem is not responsible for improper handling, any health side effects, or humidifier damage due to use of the de­scaling agent or neutralizer. See the product label and safety data sheet (SDS) for specific directions related to handling, usage, and disposal. Follow all governing codes regarding discharging into drains.
FIRST AID
Skin: Flush with water.
Eyes: Flush with plenty of water for at least 15 minutes and get medical attention.
Ingestion: Drink plenty of water to dilute; DO NOT induce vomiting and get medical attention
Inhalation: Remove to fresh air and get medical attention.
STORAGE AND HANDLING INSTRUCTIONS
• Wear gloves, goggles, and dust mask when handling
• When dissolving, add to stirred water slowly to minimize heat evolution.
• Store in closed drum in dry area away from acid. May absorb moisture from air.
Refer to SDS for additional information.
For industrial use only.
Keep out of reach of children.
KEEP FROM FREEZING
• If frozen, allow slow return to room temperature and mix thoroughly before using.
Refer to SDS for additional information.
For industrial use only.
Keep out of reach of children.
DRISTEEM DE-SCALING SOLUTION USER INSTRUCTIONS
3
INSTRUCTIONS

Usage instructions

FIGURE 4-1: DRISTEEM DE-SCALING SOLUTION RESULTS
Before
Humidifier De-scaling Solution
Humidifier De-scaling Solution
After
The following are instructions for using DriSteem Humidifier De-scaling Solution and DriSteem Humidifier De-scaling Neutralizer to remove scale and other related deposits in industrial and commercial humidifiers.
SAFETY GEAR
Use proper safety gear including the following:
• Rubber or neoprene gloves
• Anti-splash goggles
• Rubber apron
• Rubber boots
• Dust mask when using Humidifier De-scaling Neutralizer
IMPORTANT
Scale buildup on humidifier heaters and heat exchangers acts as an insulator, reducing humidifier performance while increasing energy costs.
Inspect humidifier tanks regularly and perform humidifier de-scaling maintenance as needed to keep humidifiers operating at peak efficiency.
IMPORTANT
These products are not to be used for cleaning DriSteem XT humidifiers. XT humidifiers have disposable evaporative chambers that do not require cleaning.
IMPORTANT
If the humidifier has a normally open drain valve (typical on units installed in outdoor enclosures), the humidifier must remain powered to keep the drain valve closed. To remove from service a humidifier with a normally open drain valve, use the Vapor-logic keypad/display to change the control mode from Auto to Standby.
SUPPLIES REQUIRED
• Humidifier de-scaling solution
• Humidifier de-scaler neutralizer, if required by federal, state or local codes
• pH meter or indicator strips (pH test strips are included with the De-scaling Solution)
• DriSteem humidifier de-scaling solution pump kit
• Humidifier Installation, Operation, and Maintenance manuals (IOMs) for reference
• Tools for servicing
• Additional water source (e.g., plastic bucket or hose)
DE-SCALING PROCESS FOR GTS, STS, VAPORSTREAM HUMIDIFIERS
DRISTEEM DE-SCALING SOLUTION USER INSTRUCTIONS
4

GTS04, STS, and Vaporstream humidifiers

INSTRUCTIONS
See the section titled “De-scaling process for Vapormist, CRUV, Humidi-tech, and VT humidifiers” for instructions regarding these humidifiers.
1. Review SDS sheet for safe handling and proper use of Humidifier De-scaling Solution and Humidifier De-scaling Neutralizer, in addition to instructions provided in this document.
2. Remove the humidifier from service before beginning to clean the humidifier. This can be accomplished by turning off power to the humidifier.
3. Refer to your humidifier IOMs for specific information regarding how to prepare the humidifier for service.
4. Remove the humidifier tank cover. If you have a GTS humidifier, access the tank through the probe plate. Use provided L-bracket to secure pump kit hose when circulating solution.
5. Drain the humidifier and remove loose scale. Test for any draining issues prior to adding Humidifier De-scaling Solution. Use the manual override or ball valve for draining.
FIGURE 5-1: GTS04 HUMIDIFIER DE-SCALING PUMP ASSEMBLY
Return line to tank opening
Remove ¾" plug
Suction line to ¾"
coupling
FIGURE 5-2: STS HUMIDIFIER DE-SCALING PUMP ASSEMBLY
192055-001_GTS_01
6. When draining is complete, close drain valve.
7. If the humidifier is in an air handler, shut down air handler prior to cleaning.
8. Disconnect overflow and drain outlet piping. (For STS
Disconnect drain
Suction to drain outlet
Return to overflow
Return line
Suction
line
192055-001_STS_01
DRISTEEM DE-SCALING SOLUTION USER INSTRUCTIONS
5