Thank you for purchasing our CRUV
you total satisfaction and many years of trouble-free service. Proper installation and operating practices will assure
you of achieving that objective. We therefore urge you to become familiar with the contents of this manual.
(CRUV 6-25 shown, CRUV 2, 4, 30, and 34 not shown)
Probe
Steam outlet
Strainer
Fill
valve
Over
flow
Electric drain
Heater terminal cover
Cover
Cover
bolts
Heater
element
Tank
temperature
sensor
OM-770-1
Figure 3-2: The CRUV-DI Humidifier
(CRUV-DI 6-25 shown, CRUV-DI 2, 4, 30, and 34 not shown)
Float switch
Steam outlet
Water
supply
Over
flow
Heater terminal cover
Cover
Cover
bolts
CRUV Humidifier
This humidifier is designed to be used with either softened or unsoftened water (softened water will greatly
reduce humidifier maintenance and improve overall
system performance). The probe-type level control
system requires water conductivity of at least 100
micromhos/cm (2 grains/gal or 34.2 mg/liter) to function,
and therefore, will not operate with demineralized water.
For humidification using demineralized water, see
CRUV-DI below.
CRUV-DI Humidifiers
The evaporating chamber of this humidifier is
constructed of corrosion-resistant stainless steel alloy
to resist the corrosive effects of mineral-free water.
Since the CRUV-DI humidifier is designed for use with
deionized or RO demineralized water, there is no need to
clean the unit, although an annual inspection of the
evaporating chamber is recommended.
½" SST
ball valve
Heater
element
Tank temperature sensor
OM-770-2
3
Page 4
INSTALLATION
Locate the CRUVTM humidifier near an electric power
source, water supply and a drain. Verify that sufficient
room is provided for a water seal in the drain piping. Refer
to Figure 4-3.
In an Air-Conditioning Unit
When installing a humidifier inside an air conditioning unit,
provide adequate support; allow easy access for removing
and servicing the evaporating chamber, and provide
adequate clearance to install the vapor hose and dispersion tube (see figure 4-1) and water seal. Refer to page 6
for mounting hole locations.
In a Duct
When installing the dispersion tube in a duct, allow for a
continuous pitch of the vapor hose back to the evaporating
chamber. Otherwise, use a water seal and drain (see
examples in figures 4-2 and 5-1). The dispersion tube can
also be placed vertically in the duct with some models
(see figure 5-2).
Place the control cabinet or electrical sub-panel in a
grounded protective metal enclosure and mount in a dry
and accessible location.
Examples of Installation in an Air Stream
Figure 4-1: Installation in an Air-Conditioning Unit
If draining the evaporating chamber by gravity is not
possible, use a small condensate lift pump, rated to pump
212° F/100°C water.
Figure 4-2: Horizontal Dispersion Tube
Duct
Vapor Hose
OM-2006
Figure 4-3: Piping for the CRUV
Water seal must
not be above
bottom of frame
12" (305 mm)
Note: provide 1"
(25 mm) air gap to
eliminate back
siphonage
Floor drain
Sanitary
sewer
OM-2008
OM-2003-1
Horizontal mounting of dispersion tube in a duct, connected
via vapor hose to a wall-mounted CRUV humidifier.
4
Page 5
INSTALLATION
Piping
Water make-up piping should be of corrosion-resistant,
code-approved material (copper, steel, or plastic). The
final connection size is ¼" NPT. In cases where water
hammer is possible, a shock arrestor should be
considered.
Drain piping should be of code approved material
(copper, steel, or plastic rated for 212°F/100°C minimum).
The ¾" O.D. copper sweat connection should not be
reduced in size. (See figure 4-3).
If there is no sewer available for drainage, the unit can
be piped for manual drainage. Consult factory for instructions.
Wiring
The CRUVTM is designed for a single source of electric
power supply. Future tank removal will be easier if plugs or
quick connects and extra long conduits are used to
provide electrical power to components from subpanel.
Wiring must meet all electrical codes, the current characteristics, and capacity requirements should be checked
against the nameplates. The electrical subpanel should be
mounted in a location convenient for service. Wiring must
be in accordance with all governing codes, and with the
humidifier wiring diagram. The wiring diagram(s) are
shipped loose with the unit. The wiring between the control
cabinet and humidifier must be rated at 105°C, 600V.
Caution: Only qualified electrical personnel
should perform installation procedures.
Figure 5-2: Vertical Dispersion Tube
Duct
OM-775-1
The dispersion tube can be mounted vertically in the duct.
Note: When dispersion tube is more than 10' (3 m) from unit,
insulated, 1½" (38 mm) diameter minimum rigid tubing or
pipe should be used instead of vapor hose. This application
is not recommended for CRUV-10 through CRUV-34.
Figure 5-3: RAPID-SORB® Rapid Absorption Tube
Bank
Duct
Figure 5-1: Horizontal Dispersion Tube Lower Than
Humidifier
Duct
6" (152 mm)
Tee
8"
(200 mm)
Water Seal
When horizontally mounting the dispersion tube in an air
stream that is located lower than the CRUV humidifier a water
seal (to prevent steam from escaping at the open drain) must
be provided in the drain line and line extended to open drain,
as shown, to drain the condensate. A multiple dispersion
tube bank must be used with a CRUV-30 or CRUV-34
because of its high output (see figure 5-3).
OM-774-1
OM-831-1
When rapid absorption is extremely critical, a RAPID-SORB
multiple-tube bank can provide 100% steam absorption within
three feet or less - at any duct temperature. A multiple tube or
RAPID-SORB dispersion system is required for CRUV-30 or
CRUV-34.
For complete information on calculating the number of
dispersion tubes required to satisfy steam absorption
distance requirements, consult your sales representative,
the DRI-STEEM factory, or use DRI-STEEM's DRI-CALC
Humidification Sizing and Selection Software.
5
®
Page 6
SPECIFICATIONS, CAPACITIES, AND DIMENSIONS
CRUVTM Mechanical/Electrical Specifications
Top view
OM-2004
End Elevation
OM-2002
15.0
G4.25
H
E
G
4.25
C
A
Side Elevation
(CRUV 25, 30, 34)
A
F
D
OM-759-1
0.250
Table 6-1: CRUV Dimensions (in inches)
ledoMABCDEFGH
4&2-ID-VURC/VURC
F
01&8,6-ID-VURC/VURC
61&21-ID-VURC/VURC
NOTE: Charts shown here can be used for CRUV-DI sizing.
.ni53.4105.5100.988.705.1144.1183.26.6
mm46349392200229219233.067.761
.ni53.4100.6183.4188.888.6149.2150.53.9
mm46360456352292492372.8212.632
.ni53.4100.6183.4186.0188.6157.4150.53.9
mm46360456317292457372.8212.632
.ni53.4100.6183.4152.2188.6152.6150.53.9
43&03,52,12-ID-VURC/VURC
mm46360456311392431472.8212.632
Table 6-2: CRUV Mechanical/Electrical Specifications and Capacities
* Add 9 lbs (4 kg) to total weight for models with pre-wired subpanel.
** For wire sizing, highest leg draw is due to current unbalance in some cases.
*** Output capacity and kW derate of 7%.
6
4-VURC
4-ID-VURC
6-VURC
6-ID-VURC
8-VURC
8-ID-VURC
01-VURC
01-ID-VURC
21-VURC
21-ID-VURC
41-VURC
41-ID-VURC
61-VURC
61-ID-VURC
12-VURC
12-ID-VURC
52-VURC
52-ID-VURC
03-VURC
03-ID-VURC
43-VURC
43-ID-VURC
Page 7
START-UP AND OPERATION
Start-up and Checkout Procedures
After the system has been properly installed and connected to both electrical and water supplies, it may then
be started.
Mounting
Check mounting to see that the unit is level and securely
supported before filling with water. Refer to page 6 for
mounting hole locations.
Piping
Verify that all piping connections have been completed as
recommended and that water pressure is available. Refer
to page 5.
Electrical
Verify that all wiring connections have been made in
accordance with all governing codes and the enclosed
wiring diagram. Refer to page 5.
Caution: Only qualified personnel should
perform start-up procedure.
LW417 Electronic Water Level Control Module
When the power is activated, the solenoid-operated water
fill valve will open, filling the evaporating chamber. Filling
will continue until water reaches level A (figure 8-1), at
which time the fill valve will close. To ensure that a water
seal is created in the field-installed water seal, disconnect
probe plug and cable from probe rod assembly (located
on the top of the tank), allowing the fill valve to reenergize and overfill humidifier tank. This process will
take only seconds; probe plug and cable must then be
reconnected. A call for humidity will then energize the
heating element.
Water Refill
During operation, when the water line drops below level B
the fill valve opens, and remains open until the water line
returns to level A (figure 7-1).
Heater Protection
Should the water line ever drop below level C, the heaters
are de-energized and remain OFF until the water line has
been restored to level C. This feature provides heater
protection in the event of a low-water condition.
Figure 7-1: Electronic
Probe Control for
Maintaining Proper
Water Level (CRUVTM)
A
B
C
OM-211-2
A simple three-probe conductivity sensor cycles a
solenoid-operated water fill valve to maintain the proper
water levels.
The CRUVTM humidifier is available with either the
standard LW 417 Electronic Water Level Control Module
or the optional VAPOR-LOGIC
system. If your system is equipped with the
VAPOR-LOGIC3 system, see the
Operations and Maintenance Manual
Then continue reading this manual beginning at the
maintenance section on page 9.
®
microprocessor control
3
VAPOR-LOGIC
3
for more information.
Drain/Flush Feature
This control module contains an integral electronic timer
which tracks the humidifying time of the unit. When this
accumulated time reaches what has been set in the
timer, the drain/flush cycle is activated.
Upon activation, the following sequence occurs:
1. The drain valve opens and begins to drain surface
water and minerals from the evaporating chamber.
2. When the height of the water drops below level "C",
this will allow the flush cycle to start.
3. Once the flush period starts the drain and fill valves
will remain open 1-3 minutes, flushing the chamber.
4. After 10 minute Drain/Flush feature, the drain valve
then closes, the chamber refills, and the fill valve
closes. The timer resets and the unit resumes normal
operation.
The electronic timer comes factory-set for drainage after
40 hours of operation. Alternate settings of 20 hours and
80 hours are available. See wiring diagram(s) attached to
unit for timer board location and instructions for changing
the timer setting.
7
Page 8
START-UP AND OPERATION
Test Cycling the Drain/Flush System
The level control board incorporates a set of slide
switches which are marked 1 through 8. To test:
1. Place "SWI" slide switches 1,2 and 3 to off position.
2. Set the humidistat high enough so that unit will remain
“on call” for at least 15 minutes.
3. After about 2 minutes of operation, activation will
take place, causing the drain valve to open. The
water level will then drop to level C (see figure 7-1 on
page 7) and allow the fill valve to open. Both valves
will remain open for the remainder of Auto/Flush period.
4. The drain valve will then close, and the water level
will rise to level A (see figure 7-1 on page 7), causing
the fill valve to close.
5. Once the test cycle is complete, return slide switches
back to the desired operating mode. Failure to do so
will result in a drain/flush cycle every 2 minutes.
CRUVTM Make-up Water Piping
If the water pressure is above 60 psi (414 kPa) and/or
water hammer would be objectionable, a pressurereducing valve or shock arrester should be installed.
Even though the humidifier has an internal 1" (25 mm) air
gap, some local codes may require a vacuum breaker.
Important: Minimum water supply pressure is 25 psi (170
kPa). Maximum water supply pressure is 80 psi (552 kPa).
CRUV-DI Water Level Control System
The basic float valve water level system and float switch
circuit for heater protection in the event of a low-water
condition is common to all DI humidifiers and can be
found in the wiring diagram shipped with the unit.
CRUV-DI Start-Up Procedure
a) Adjust humidistat to "call" setting.
b) Open shut-off valve on water supply line. Unit should
begin filling with water through the fill valve.
c) Shortly before the fill valve shuts off, the float
operated heater cut-off switch will "make." When
this switch makes, the heating element contactor(s)
will be actuated. A time delay relay circuit prevents
contactor chatter due to bouncing of heater cut-off
float.
d) Check heater cut-off circuit.
1. Close manual valve on water supply.
2. Open drain valve and start draining unit.
3. When water level drops past switching level on
the heater cut-off float, the heating element
contactor(s) will drop out.
4. When step 3 has been satisfactorily completed,
close drain valve.
e) Check function of field-installed safety controls,
such as the fan proving switch. Contactor(s) should
drop out when the proving switch is "open."
f)Check heater draw by testing and recording voltage
and amperage in each phase. Readings should
match name plate readings; name plate is located on
the humidifier housing.
g) Inspect installations for steam or air leaks while
operating the humidifier. Any leaks should be
sealed.
Inspect after first three months of duty. The best way to
determine how often your particular system will need
maintenance is to remove the cover and inspect it after
its first three months of duty. Potable water carries a
variety of minerals and other materials in a mix that varies
from location to location. This variation in water quality,
combined with the hours of operation and duty cycle, will
determine your own unique maintenance schedule.
Water quality makes a difference
1. Light to moderately hard water (2 to 10 grains/gallon
or 34.2 to 171 mg/1 hardness)
•annual cleaning
2. High mineral content water (more than 10 grains/
gallon or 171 mg/1 hardness)
•cleaning frequency determined by use and water
quality
•periodic drain and flush cycles
3. DI/RO water (Model VMDI)
•no regular cleaning required (although regular
inspections are advised)
•no drain and flush cycles required
•the presence of chlorides in DI water will
eventually cause pitting and failure of the tank
and its components
4. To dramatically reduce mineral accumulation inside
the evaporating chamber, softening of the makeup water
recommended. (Solids like silica are not removed in the
the softening process.)
8
Page 9
MAINTENANCE
CRUVTM Humidifier
(Non-DI humidifiers with either the LW 417 or
VAPOR-LOGIC
Mineral Precipitate
As evaporation takes place in the CRUV humidifier, some
of the minerals dissolved in the water precipitate out and
float on the water surface. The minerals not removed by
the skimmer will settle to the bottom of the evaporating
chamber.
Cleaning the Evaporating Chamber
The heating element itself is self-cleaning. The mineral
buildup on the element flakes off after reaching a thickness of about 1/16" (2 mm), and settles to the bottom of
the chamber.
Long heater element life can be expected when the
operation of the humidifier is observed for a few weeks
following initial start-up. By observing the mineral build-up
rate, the frequency of both drain/flush use and manual
cleaning can be determined and adjustments made.
CAUTION: Before this mineral scale builds up on the
underside of the heating element, it must be removed.
Failure to do so may result in premature heater burnout.
The CRUV humidifier is designed for convenient cleaning
and maintenance.
To Inspect and Service:
1. Shut off all eletrical power to humidifier. Drain
evaporating chamber by manually opening DRAIN
valve. Do this by moving lever on valve to MANUAL
position and lock in place. If the tank is hot, cool it
down by opening the manual valve on the side of the
tank. The float valve will open allowing cool water to
run into the tank until it is cool enough to handle.
2. Unscrew probe-rod assembly. Scale should flake off
easily. Build-up on tips should be scraped off to
remove any mineral residue.
3. Remove the tank cover and wet vac minerals out of
tank (recommended).
4. To remove tank for cleaning, disconnect drain line
union, fill valve supply line, electrical connections to
drain, (disconnecting field wiring in conduit is NOT
recommended,) thermal trip, heaters, fill valve, and
probe. Disconnect steam hose from top of tank and
remove mounting bracket fasteners.
5. Remove evaporating chamber and clean.
6. Install the probe and probe plug assembly. Verify
that ground wire is connected.
7. Replace tank cover, making sure tank is sealed tight.
®
Control Systems)
3
8. Reconnect drain line union, fill valve supply line,
electrical connections to drain, thermal trip, heaters,
fill valve, and probe. Connect steam hose to top of
tank.
9. Verify drain valve lever is in AUTO position.
10. The CRUV humidifier is again ready to humidify.
Off-Season Shutdown
1. Switch off power.
2. Turn off water supply to make-up valve.
3. Drain evaporating chamber and clean if necessary
(see steps 1 through 9 above).
4. Leave chamber dry, power OFF and water shut-off
valve closed until the next humidification season.
CRUV-DI Humidifier
To Service
1.Manually open drain valve.
2.Allow time for the evaporating chamber to cool. If the
tank is hot, cool it down by moving the valve lever
located on the back of the drain valve to the manual
open position – the fill valve will eventually open
allowing cool water to run through the tank until it is
cool enough to handle.
3.Shut off electrical power to unit.
4.Shut off water supply to make-up valve.
5.Make sure evaporating chamber is drained.
6.Unscrew four cover bolts and remove cover.
7.Check operation of float valve and low-water cut-out.
8.Inspect heating elements.
9.Inspect evaporating chamber and clean if necessary.
10. Inspect cover gasket, and replace if necessary.
11. Replace chamber cover.
12. Verify drain valve is in the closed position.
13. Open water supply valve and turn on electric power.
14. CRUV-DI humidifier is again ready to humidify.
15. If necessary, remove tank as follows:
Remove flexible vapor hose from tank. Close drain
valve. Disconnect unit from drain and supply water
lines. DO NOT DISCONNECT ANY OF THE
ELECTRICAL CONDUITS.
Off-Season Shutdown Procedure
1.Switch off electrical power to unit.
2.Check overall appearance of unit.
3.Shut off water supply to make-up valve.
4.Drain evaporating chamber by manually opening
drain valve.*
5.Visually check electrical components of subpanel.
6.Leave chamber dry, power off, and water shut-off
valve closed until the next humidification season.
* With VAPOR-LOGIC3 option, the evaporating chamber is automatically drained after 72 hours without a call for humidity when the endof-season drain option is ordered.
9
Page 10
CRUVTM TROUBLE-SHOOTING GUIDE (LW417 Electronic Water Level System Only)*
MODULE INDICATING
LIGHTS
PROBLEM FULL READYDRAIN POSSIBLE CAUSE RECOMMENDED ACTION
WATER
Humidifier willOffOffOffControl transformerVerify control voltage across secondary
not heatleads of transformer. Reset transformer
circuit breaker.
OnOnOffHumidistat is not callingSet humidistat to call. Inspect for faulty
Safety controls openCheck safety controls, air flow switch, high
Faulty control boardVerify control voltage between terminals.
Probe head deterioration**Replace probe head.
Humidifier willOffOffOffNo water pressure at valve.Check water supply/shut off valves.
not fill
Faulty water fill valveVerify action of fill water solenoid valve by
Plugged strainerCheck strainer.
Plugged valveCheck valve.
Faulty control boardVerify control voltage across input terminals
Humidifier doesOffOffOffLack of tank to probesJumper wires violet, orange then brown to
not stop fillingelectrical continuity. Waterground. If water stops, verify tank ground;
conductivity 100check water supply conductivity; then
microSiemens/cm (2 gr/gal) min. consult factory.
humidistat.
limit humidistat, etc.
turning control module switch from standby
to normal op. Audible click should be
heard as solenoid operates.
"B&W"
OffOffOnAuto-drain mode10 Minute must complete first.
Low outputOnOnOffElectric drain valve notCorrect cause of leakage or replace valve.
OnOnOffFill valve is stuck openCheck valve for foreign matter.
Unit short cycles
Reduced or noOnOnOffHeater malfunctioningVerify that proper voltage is being applied to
output evenheaters. Check heater (amp draw and
though watercompare to wiring diagram ratings).
is at the proper
level
*For VAPOR-LOGIC3 trouble-shooting, see the VAPOR-LOGIC3 Operations and Maintenance Manual.
**Probe rod corrosion or probe head material aging may cause level control system failure. This generally does not occur in the first two years of operation.
10
On & Off
OnOffProbes may be incorrectlyConfirm that unit is wired per diagram.
Fill valve is stuck openCheck valve for foreign matter.
Drain Valve not closedCheck for correct water flow through valve
Fill valve installed backwardnote arrow.
seating
wired or need cleaningClean probe rod tips with steel wool.
not allowing system to operate (dust humidistat, air flow proving switch, etc.). Reset,
replace or calibrate as required. Faulty or
inaccurate humidistat, replace or calibrate.
Page 11
CRUVTM-DI TROUBLE-SHOOTING GUIDE
PROBLEMPOSSIBLE CAUSERECOMMENDED ACTION
Humidifier will
not heat
Humidifier will
not fill
Water fl o at valve
does not close
Control transformerVerify control voltage across secondary leads of
transformer. Reset transformer circuit breaker.
Humidistat is not callingSet humidistat to call. Inspect for faulty humidistat.
Safety controls openCheck safety control. (Air flow switch, high limit
humidistat, etc.)
Low water float switchVerify control voltage from float switch and transformer
secondary common.
No water pressure at valveC heck manual water supply. Valve, minimum 25 psi
wa te r pres s u re.
Malfunctioning water float valveCheck to make sure that valve float & stem moves
freely.
Plugged float valveCheck float valve seat.
Open drain valveObstruction in drain valve wil l not all ow complete
closure, clean or replace valve.
Manual drain valve not closedClose drain valve.
Malfunctioning float valveFloat ball has water leak. Float valve seat defective,
replace.
Reduced or no
output even
though water is at
the proper level
Water passing into overflow
stand pipe
Float valve stuckObstruction will not allow float valve to seat properly,
Heater malfunctioningVerify that proper voltage is being applied to heaters.
Malfunctioning control systemHeater contactor not functioning, replace. Service
Time delay/interlock relaysRelay delay on time is 10-15 seconds. Check relays.
Low water cut-off switchCheck for proper operation.
Readjust float valve rod, so water level reaches 1/4-
3/8" from overflow edge when water is at ambient or
cold state. Excessive water pressure, 80 psi maximum.
clean or replace with new seat.
Check heaters (amp draw and compare to wire
diagram rati ngs).
fuses blown. A uxil i ary limit controls not allowi ng
system to operate (duct humidi stat, air flow proving
switch, etc.). R eset, replace, or calibrate as required.
Faulty or inaccurate humidistat, replace or calibrate.
11
Page 12
CRUVTM TROUBLE-SHOOTING GUIDE (VAPOR-LOGIC
®
only)
3
PROBLEMPOSSIBLE CAUSERECOMMENDED ACTION
Humidifi er does not heat.
Humidifier will not fill.
Incorrect or nonexistent supply
voltage to unit
Incorrect or nonexistent control
voltag e
Humidistat not callingSet humidistat to call. Inspect for faulty humidistat.
Safety controls openCheck safety controls, air flow swi tch, and high limit humidistat.
No water pressure at valveCheck w ater supply/shut-off valves.
Faulty water fill valveCheck for 24 volts at the fill valve.
Plugged strainerCheck strainer.
Plugged valveCheck valve.
Faulty control boardVeri fy control voltage across the fill valve output.
Check main line safety switch.
Check main line fuses.
Check for proper supply voltage.
Reset control transformer circuit breaker.
Check for 24 VAC control circuit voltage at T-1 and T-2 on the
control board.
Humidifier does not stop
filling.
Low output
Unit short-cycles.
Reduced or no output even
Lack of tank to probe electrical
continuity. Water conductivity must
be 100 microSiemens/cm (2 gr/gal)
Fill valve stuck openC heck valve for foreign matter.
Drain valve not closed
Fill valve installed backward
Autodrain modeHumidifier may be in periodic drain and flush. Check controller
Electric drain valve not seatingCorrect the cause of leakage or replace valve.
Fill valve stuck openC heck valve for foreign matter.
Controller cycle rate set too lowReview controller cycle set point.
Heater malfunctioningVerify that proper voltage is being appli ed to heaters. Check heater
though water is at the
proper level
Malfunctioning control systemReplace heater contactor if not functioning. Verify auxiliary limit
*Probe rod corrosion or probe head material aging may cause level control system failure. This generally does not occur in the first
two years of operation.
12
Add salt to the tank. If this solves the problem, consult factory for
further advice.
Check for correct water flow through valvee by noting arrow.
display.
amp draw and compare to wiring diag ram ratings.
controls (humidistat, air flow proving swi tch, etc.) and reset,
replace or calibrate as needed.
* Specify humidifier model and serial numbers when ordering.
®
option
3
OM-1017C
cruvpnlasm-1
OM-1017B
18
Page 19
MAINTENANCE SERVICE RECORD
DATE INSPECTEDPERSONNELOBSERVATIONACTIONS PERFORMED
19
Page 20
TWO-YEAR LIMITED WARRANTY
DRI-STEEM Humidifier Company (“DRI-STEEM”) warrants to the original user that its products will be free
from defects in materials and workmanship for a period of two (2) years after installation or twenty-seven (27)
months from the date DRI-STEEM ships such product, whichever date is the earlier.
If any DRI-STEEM product is found to be defective in material or workmanship during the applicable warranty
period, DRI-STEEM’s entire liability, and the purchaser’s sole and exclusive remedy, shall be the repair or
replacement of the defective product, or the refund of the purchase price, at DRI-STEEM’s election. DRISTEEM shall not be liable for any costs or expenses, whether direct or indirect, associated with the installation, removal or reinstallation of any defective product.
DRI-STEEM’s limited warranty shall not be effective or actionable unless there is compliance with all installation and operating instructions furnished by DRI-STEEM, or if the products have been modified or altered
without the written consent of DRI-STEEM, or if such products have been subject to accident, misuse,
mishandling, tampering, negligence or improper maintenance. Any warranty claim must be submitted to
DRI-STEEM in writing within the stated warranty period.
DRI-STEEM’s limited warranty is made in lieu of, and DRI-STEEM disclaims all other warranties, whether
express or implied, including but not limited to any IMPLIED WARRANTY OF MERCHANTABILITY, ANY
IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, any implied warranty arising out of a
course of dealing or of performance, custom or usage of trade.
DRI-STEEM SHALL NOT, UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY DIRECT, INDIRECT,
INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, LOSS OF
PROFITS, REVENUE OR BUSINESS) OR DAMAGE OR INJURY TO PERSONS OR PROPERTY IN ANY
WAY RELATED TO THE MANUFACTURE OR THE USE OF ITS PRODUCTS. The exclusion applies regardless of whether such damages are sought based on breach of warranty, breach of contract, negligence, strict
liability in tort, or any other legal theory, even if DRI-STEEM has notice of the possibility of such damages.
By purchasing DRI-STEEM’s products, the purchaser agrees to the terms and conditions of this limited
warranty.
U.S. Headquarters:
14949 Technology Drive • Eden Prairie, MN 55344
Phone: (800)328-4447 • (952) 949-2415 • Fax: (952) 229-3200
E-Mail: sales@dristeem.com • Web: www.dristeem.com
Europe Office:
Bell Place, Bell Lane • Syresham, Brackley • NN13 5HP, U.K.
Phone: +44 1280 850122 • Fax: +44 1280 850124
E-Mail: 106277.1443@compuserve.com
Continuous product improvement is a policy of DRI-STEEM Humidifier Company;
therefore, product features and specifications are subject to change without notice.
DRI-STEEM, CRU, RAPID-SORB and VAPOR-LOGIC3 are registered trademarks of the DRI-STEEM Humidifier Company.