DriSteem SINGLE-TUBE Series, MINI-BANK Series, MULTIPLE-TUBE Series, AREA-TYPE Series Installation, Operation And Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS
STEAM INJECTION
Humidifiers
Installation, Operation, and Maintenance Manual
For use with steam boilers
ATTENTION INSTALLER Read this manual before installing.
Leave manual with product owner.
Where to find more information On our website: The following related documents can be
viewed, printed, or ordered from our website, www.dristeem.com
In Dri-calc Dri-calc is DriSteem’s free sizing and
selection software for calculating load, determining non-wetting distance, and selecting equipment. See Dri-calc on the www.dristeem.com Tools page. Also in Dri-calc:
A comprehensive library of Installation Guide documents, including:
• Recommended placement within a duct or air handler
• Recommended sensor placement
Or call us at 800-328-4447 Obtaining documents from our website or
from Dri-calc is the quickest way to view our literature, or we will be happy to mail literature to you.
®
WARNING
Indicates a hazardous situation that could result in death or serious injury if instructions are not followed.
WARNING
Attention installer
Read this manual before installing, and leave this manual with product owner. This product must be installed by qualified HVAC and electrical contractors and in compliance with local, state, federal, and governing codes. Improper installation can cause property damage, severe personal injury, or death as a result of electric shock, burns, or fire.
DriSteem® technical support: 800-328-4447
Read all warnings and instructions
Read this manual before performing service or maintenance procedures on any part of the system. Failure to follow all warnings and instructions could produce the hazardous situations described, resulting in property damage, personal injury, or death.
Failure to follow the instructions in this manual can cause moisture to accumulate, which can cause bacteria and mold growth or dripping water into building spaces. Dripping water can cause property damage; bacteria and mold growth can cause illness.
mc_011909_1215
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
ii
Hot surfaces and hot water
Steam Injection humidifiers have extremely hot surfaces. Water in steam pipes and dispersion assemblies can be as hot as 212 °F (100 °C). Discharged steam is not visible. Contact with hot surfaces, discharged hot water, or air into which steam has been discharged can cause severe personal injury. To avoid severe burns, allow the system to cool before performing service or maintenance procedures on any part of the system.
Table of contents
OVERVIEW.................................................................2
Introduction .............................................2
Available models .........................................3
Basic components ........................................4
Principle of operation ......................................5
Humidifier placement ......................................6
Sensor placement ........................................9
Pressurized steam piping guidelines ..........................10
Condensate drain piping and trapping ........................14
Temperature switches .....................................16
SINGLE-TUBE HUMIDIFIER ....................................................20
Configurations .........................................20
Assembly .............................................21
Installation ............................................22
Piping notes ...........................................23
Field piping ...........................................24
MULTIPLE-TUBE HUMIDIFIER ..................................................28
Field assembly .........................................28
Installation ............................................29
Piping notes ...........................................30
Field piping ...........................................31
WARNING
Hot surface hazard
Steam humidification systems have extremely hot surfaces.
To avoid burns, allow humidifier, steam pipes, and dispersion assemblies to cool before touching any part of the system.
mc_071411_0753
ATTENTION INSTALLER
Read this manual before installing. Leave manual with product owner.
DriSteem technical support
800-328-4447
MAXI-BANK HUMIDIFIER .................................................... 36
Maxi-bank option field assembly and installation .................36
Maxi-bank option piping notes ..............................39
Maxi-bank option field piping ...............................40
Assembly and installation ..................................45
MINI-BANK HUMIDIFIER .....................................................45
Field piping ...........................................47
AREA-TYPE HUMIDIFIER ..................................................... 48
Installation ............................................48
Field piping ...........................................49
Rise, spread, and throw dimensions ..........................50
Humidifier start-up and shut-down ............................51
OPERATION ..............................................................51
Eliminating excess heat from steam jacketed humidifiers ............52
MAINTENANCE ........................................................... 54
Maintenance procedures ..................................54
Troubleshooting .........................................55
TROUBLESHOOTING........................................................ 55
REPLACEMENT PARTS ....................................................... 58
Single-tube and Multiple-tube humidifiers .......................58
Area-type humidifier .....................................60
Mini-bank humidifier .....................................61
WARRANTY .............................................................. 62
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
1

OVERVIEW

Introduction

SUITABLE FOR A WIDE RANGE OF APPLICATIONS
Steam Injection humidifiers from DriSteem® use steam from an external source, such as an in-house boiler or a district steam system. DriSteem’s Steam Injection humidifiers are adaptable to virtually any size application, and a wide variety of models accommodate a broad range of steam absorption requirements.
STEAM JACKETED DISPERSION TUBE MODELS FOR DUCTS AND AIR HANDLERS
Single-tube, Mini-bank®, and Multiple-tube humidifiers are designed for ducts and air handlers, and capable of a wide range of guaranteed non-wetting distances.
AREA-TYPE FOR OPEN SPACES
Area-type™ Steam Injection humidifiers are designed for open spaces such as warehouses and manufacturing spaces that do not have a duct system. The steam discharged from the humidifier is quietly dispersed by a fan without introducing water droplets into the air.
FIGURE 2-1: STEAM INJECTION HUMIDIFIERS
Each Single-tube, Mini-bank®, and Multiple-tube humidifier has the same basic components: a stainless steel separator, a steam valve, and one or more jacketed dispersion tubes.
For open spaces, boiler steam can be dispersed by the fan of an Area-type model.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
2

Available models

OVERVIEW
FIGURE 3-1: STEAM INJECTION HUMIDIFIER MODELS
SINGLE-TUBE HUMIDIFIER
• Suitable for small- to medium-capacity systems,
1.5 – 525 lbs/hr (0.7 – 238 kg/h)
• Moderate to long non-wetting distance
• Pre-assembled separator/tube assembly
MINI-BANK HUMIDIFIER
• Suitable for small-capacity systems, 1.6 – 84 lbs/ hr (0.7 – 38 kg/h)
• Short to moderate non-wetting distance
• Sized for small ducts
• Pre-engineered and pre-assembled header/tube assembly, ready for mounting and hookup
MULTIPLE-TUBE HUMIDIFIER
• Suitable for small- to large-capacity systems,
6.5 – 3989 lbs/hr (2.3 – 1809 kg/h)
• Sizes to fit small ducts and large air handlers
• Short to moderate non-wetting distance
• Field assembled (with interconnecting piping and header supplied by contractor)
• Maxi-bank™ option: – Pre-assembled, except when either dimension
is 98 inches (2490 mm) or more
– Includes 304 stainless steel header, with
option for 316 stainless steel
– Includes black iron piping, with options for
304 or 316 stainless steel
All Steam Injection humidifiers shown here, except Area-type, are available with options for applications requiring stainless steel steam components.
mc_033111_0500
AREA-TYPE HUMIDIFIER
• Suitable for medium-capacity systems, 1.8 – 286 lbs/hr (0.8 – 130 kg/h)
• Used in open spaces
• Application-dependent non-wetting distances
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
3
OVERVIEW

Basic components

FIGURE 4-1: STEAM INJECTION HUMIDIFIER COMPONENTS
Section Y-Y
OM-378
Section X-X
Condensate
Steam
8
X
4
2
OM-376
9
6
5
X
3
Tube profile with insulation
7
Y
Y
Steam-filled jacket
Steam-discharge tubelet
Dispersion tube
Optional PVDF insulation
1. Steam jacket
A chamber that jackets the inner dispersion tube with hot steam to eliminate condensation and dripping
1
OM-1171
Tube profile without insulation
2. Steam separator
Separates steam from condensate
3. Deflector plate
Inside the steam separator, deflects condensate into a circular pattern and toward the drain
4. Multi-baffle plate
Allows only steam to rise into the upper region of the separator
5. Internal drying tube
Excludes any remaining condensate, allowing only dry steam to leave the separator
6. Steam valve
Controls the amount of steam allowed into the dispersion tube
7. Dispersion tube
Provides uniform steam dispersion across the duct width
8. Thermal-resin tubelet
Unique tubelets extend into the dispersion tube center so only the hottest, driest steam is discharged into the air. These tubelets also have an exceptional ability to trap noise generated by the valve, making DriSteem’s Steam Injection humidifiers the quietest in the industry.
9. Steam trap
Allows only condensate to pass to the condensate return system
See Figure 5-1 for a description of how these components operate together.
mc_031611_0805
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
4

Principle of operation

FIGURE 5-1: STEAM INJECTION HUMIDIFIER PRINCIPLE OF OPERATION
5
3
1
OVERVIEW
6
OM-1170
2
4
About right-hand and left-hand discharge:
Imagine you are standing in the duct where the Steam Injection humidifier is to be installed, with airflow blowing into your face:
• Specify the humidifier with right-hand discharge if the separator is on your right.
• Specify the humidifier with left-hand discharge if the separator is on your left.
For consistency, humidifier drawings in this catalog are shown with right-hand discharge.
1. Boiler steam enters the humidifier at line pressure and flows through a chamber (jacket) surrounding an inner dispersion tube. The jacket of steam preheats the dispersion tube so that when steam enters the dispersion tube (at Step 5 below) it does not condense as it would if the tube were cold, thereby eliminating condensation and dripping.
2. After flowing through the steam jacket, steam with entrained condensate slows from entering the larger space of the separator and from hitting the perimeter deflector plate, and begins to spin and separate.
3. Separated steam rises through slots in the multi-baffle plate to the separator upper region, and enters the internal drying tube that excludes any remaining condensate, allowing only dry steam to leave the separator.
4. Separated condensate drains from the separator to the steam trap.
5. The steam valve controls the amount of steam allowed into the preheated dispersion tube. The steam valve is typically controlled in one of two ways:
• By a signal from a building automation system
• By a humidity controller connected to the steam valve
6. Steam is discharged uniformly through the tubelets into the airstream.
mc_031611_0808
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
5
OVERVIEW
Humidifier placement
USE THESE EXAMPLES AS GUIDELINES
Proper humidifier placement is crucial for successful system operation. Usually, there is no single correct placement for a humidifier. Much depends on system design and application. The following paragraphs and dispersion assembly placement examples are presented as guidelines for common situations.
FIRST, CHECK AVAILABLE ABSORPTION DISTANCE
Available absorption distance affects system choice. Dispersed steam must be absorbed into the airflow before it comes in contact with any duct elbows, fans, vanes, filters, or any object that can cause condensation and dripping.
mc_071911_1516
PLACING A STEAM INJECTION HUMIDIFIER IN AN AHU (SEE FIGURE 6-1)
• Location A is the best choice. Installing downstream from heating and cooling coils provides laminar flow through the dispersion unit; plus, the heated air provides an environment for best absorption. Use a multiple tube dispersion unit to ensure complete absorption of steam vapor before fan entry.
• Location B is the second-best choice. In change-over periods, the cooling coil will eliminate some moisture for humidification.
• Location C is the third-best choice. Air leaving a fan is usually very turbulent and may cause vapor to not absorb at the expected absorption distance. Allow for more absorption distance if installing downstream from a fan.
• Location D is the poorest choice. The cooler air at this location requires an increased absorption distance.
mc_071911_1515
Figure 6-1: Placing a Steam Injection humidifier in an air handling unit (AHU)
Cooling coil
8' to 12' (2.4 m to 3.7 m)
ABD
3' to 5' (1 m to 1.5 m)
8' to 12' (2.4 m to 3.7 m)
Outside air
Exterior building wall
Relief air
Economizer control device
Preheat coil
Motorized air dampers
Filters
Heating coil
Duct high limit humidity control for humidifier locations A, B
Airflow proving switch
Fan
Humidifier discharges against airflow
C
Airflow proving switch
Return airflow
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
6
Supply airflow
Duct high limit humidity control for humidifier location C
DC-1081 mc_071911_1517
Humidifier placement
PLACING A STEAM INJECTION HUMIDIFIER NEAR AN ELBOW (SEE FIGURE 7-1)
• Location A is the best choice. Better absorption occurs on the downstream side of an elbow than on the upstream side.
• Location B is the second-best choice. Installing upstream from an elbow can cause wetting at the turning vanes. In cases where it is structurally impossible to avoid Location B, use a multiple tube humidifier to ensure complete absorption. Also, since more air flows along the outside of a turn, better absorption occurs if the humidifier discharges proportionately more steam in that part of the airstream.
• At both locations, discharging steam against or perpendicular to the airstream gives slightly better mixing and absorption than discharging with the airstream.
mc_071911_1518
FIGURE 7-1: PLACING A STEAM INJECTION HUMIDIFIER ASSEMBLY NEAR AN ELBOW
OVERVIEW
Airflow
Duct
B
Less airflow on this side of elbow
Duct high limit humidistat
Mist can collect on vanes
A
(2.4 m to 3.7 m)
DC-1083-1 mc_071911_1519
Airflow
3' to 5'
(1 m to 1.5 m)
8' to 12'
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
7
OVERVIEW
Humidifier placement
PLACING A STEAM INJECTION HUMIDIFIER IN A PRIMARY/SECONDARY SYSTEM (SEE FIGURE 8-1)
This type of system is commonly applied to facilities where most of the building requires one humidity level (typically to meet comfort requirements) and part of the building requires additional humidity. In Figure 8-1, the primary humidification system is within the main air handling unit. The secondary humidification system is located close to the point of steam discharge into the secondary area.
FIGURE 8-1: PLACING A STEAM INJECTION HUMIDIFIER IN A PRIMARY/SECONDARY SYSTEM
Exhaust airOutside air
Filter mixing box
Before humidifier: 50 °F (10 °C), 47% RH
Primary humidifier location
After humidifier: 50 °F (10 °C), 60% RH
70 °F (21 °C), 30% RH
Secondary humidifier location
50 °F (10 °C) 60% RH
VAV box
Primary area: 70 °F (21 °C), 30% RH
50 °F (10 °C), 60% RH
Secondary humidified area
Room transmitter: 65 °F (18 °C), 50% RH
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
8

Sensor placement

OVERVIEW
SENSOR LOCATION IS CRITICAL
Sensor location has a significant impact on humidifier performance. See the recommendations below and Figure 9-1.
Note: DriSteem recommends that you do not interchange room and duct
humidity devices. Room humidity devices are calibrated with zero or little airflow, whereas duct humidity devices require air passing across them.
Recommended humidity control (transmitter/humidistat) locations:
A Ideal. Ensures the best uniform mix of dry and moist air with stable
temperature control.
B Acceptable, but room environment can affect controllability, such as
when sensor is too close to air grilles, registers, or heat radiation from room lighting.
C Acceptable. Provides uniform mixture of dry and moist air. If extended
time lag exists between humidity generation and sensing, extend sampling time.
D Acceptable (behind wall or partition) for sampling entire room if sensor
is near an air exhaust return outlet. Typical placement for sampling a critical area.
E Not acceptable. These locations might not represent actual overall
conditions in the space.
F Not acceptable. Do not place sensors near windows, door
passageways, or areas of stagnant airflow.
Other factors affecting humidity control
Humidity control involves more than the controller’s ability to control the system. Other factors that play an important role in overall system control are:
• Size of humidification system relative to load
• Overall system dynamics associated with moisture migration time lags
• Accuracy of humidistats and humidity transmitters and their location
• Dry bulb temperature accuracy in space or duct
• Velocities and airflow patterns in ducts and space environments
• Electrical noise or interference
mc_072011_1656
Recommended safety (airflow and high limit) sensor location:
G Best sensing location for high limit humidistat or humidity sensor and
airflow proving switch.
FIGURE 9-1: RECOMMENDED SENSOR LOCATIONS
8' to 12'
Wall or partition
D
B
(2.4 m to 3.7 m)
min.
F
F
Window
DC-1084
G
Outside air
Relief air
Damper control
Return air
E
A
C
Window
F
Doorway
Air handling
unit
E
High limit humidistat or high limit transmitter (set at 90% RH maximum) for VAV applications
Airflow switch or differential pressure switch (sail type recommended for VAV applications)
Vapor absorption has taken place
Point of vapor absorption
Humidifier dispersion assembly
Turning vanes
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
9
OVERVIEW

Pressurized steam piping guidelines

• Size piping in accordance with ASHRAE recommendations.
• Humidifier's steam supply should be taken off top of steam main (not side or bottom) to ensure the driest steam. Main should be dripped and trapped (in accordance with ASHRAE recommendations).
• Humidifier steam trap(s) must drain by gravity to return main having little or no back pressure. If condensate cannot drain by gravity, then it must be elevated to return main (see Figure 12-1 for instructions).
• If steam pressure is less than or equal to 15 psi (103.4 kPa), use float and thermostatic (F&T) traps for the humidifier.
If steam pressure is greater than 15 psi (103.4 kPa), use inverted bucket
traps for the humidifier.
• If lifting condensate, use an inverted bucket trap and check valve regardless of steam pressure. See Figure 12-1 for instructions.
• Condensate from unavoidable heat loss in the distribution system must be removed promptly to eliminate water hammer and degradation of steam quality and heat transfer capability. Install drip legs at all low points and natural drainage points in the system, such as at ends of mains; bottoms of risers; and ahead of pressure regulators, control valves, isolation valves, pipe bends, and expansion joints.
On straight, horizontal runs with no natural drainage points, space drip
legs at the following intervals:
– Not exceeding 300' (91 m) when the pipe is pitched down in the
direction of the steam flow
– At a maximum of 150' (46 m) when the pipe is pitched up, so that
condensate flow is opposite of steam flow.
These distances apply to systems where valves are opened manually to
remove air and excess condensate that forms during warm-up conditions. Reduce these distances by about half in systems that are warmed up automatically.
• Insulate piping well to avoid unnecessary heat loss.
• Pitch return lines downward in the direction of the condensate flow at 1/2" per 10' (0.4%).
mc_051011_1544
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
10
Pressurized steam piping guidelines
FIGURE 11-1: FIELD PIPING OVERVIEW
OVERVIEW
Take off branch lines from the top of the steam main, preferably at a 45° angle, although vertical 90° connections are acceptable
Insulate piping
DC-1200M
End of main steam trap by installer
Condensate return
Blowdown valve by installer
45°
Pitch humidifier branch 1/2" per 10' (0.4%) if distance from main to humidifier is less than 10' (3.3 m)
Automatic warm-up: 28" (711 mm) min. Supervised warm-up:
1.5 × pipe diameter, 8" (203 mm) min.
If pipe is 4" (DN100) or larger, size drip for 50% of the condensate load at start-up. If pipe is less than 4" (DN100), size drip for 25% of the condensate load at start-up.
Branch steam trap by installer
Blowdown valve by installer
Branch trap recommended if distance from main to humidifier is greater than 10' (3.3 m)
Condensate return
Pitch main 1/4" per 10' (0.2%)
Piping same size as humidifier inlet strainer
To humidifier. Inlet strainer must be within 3' (1 m) of humidifier
Humidifier isolation valve
Insulate piping
12" (305 mm) min.
4" (100 mm) min.
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
11
OVERVIEW
Pressurized steam piping guidelines
FIGURE 12-1: ELEVATING CONDENSATE FROM A STEAM INJECTION HUMIDIFIER
Pitch 1/2" per 10' (0.4%)
Elevated condensate return main
1/2" pipe thread (DN15)
5' (1.5 m) maximum
Condensate return flow
Inverted bucket steam trap
Check valve (swing type)
DC-1064
In certain installations, it is not possible to drain the humidifier steam trap by gravity. The condensate must be lifted. Generally, lifting condensate is not recommended, but it can be done successfully by observing the following rules:
Steam pressure. Theoretically, one pound (6.9 kPa) of steam pressure will lift condensate about 2' (0.6 m). But
in practice, because of pipe friction, pressure drop through a steam trap, and back pressure in a return line, we recommend maximum lift of 6" per pound (0.2 m per 6.9 kPa) of steam pressure at the trap. For example, a steam pressure of 5 psi (34.5 kPa) will provide a maximum lift of 2.5' (0.76 m). Lifting condensate more than 5' (1.5 m) should not be attempted.
Steam trap. When lifting condensate, use an inverted bucket steam trap. Float and thermostatic (F&T) traps are
more prone to water hammer damage with a flooded trap, which may occur when lifting condensate.
Pipe size. The size of the vertical portion of the piping should be 1/2" pipe thread (DN15).
Check valve (swing type). A low-pressure differential swing check valve should be installed adjacent to the trap.
This will prevent backflow of condensate into the humidifier during periods of little or no steam pressure. Failure to do so could result in accumulated backflow discharging from the humidifier when steam pressure is resumed. Spring-type check valves are not recommended, as they can reduce pressure available for condensate lifts.
Condensate lifting recommendations:
1. Condensate can be lifted for all steam jacket piping.
2. Condensate could be lifted for connection to separator, but performance could vary based on variable pressure at the separator.
3. Condensate cannot be lifted for connection on headers for Multiple-tube humidifiers (including Maxi-bank option).
mc_051011_1530
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
12
Pressurized steam piping guidelines
FIGURE 13-1: MULTIPLE VALVE PLUMBING GUIDELINES
Isolation valve (by others)
From steam source
Install strainer within 3' (1 m) of humidifier (see Note 2)
OVERVIEW
Piping to be same size as strainer
Piping to be same size as valves
Valve
Piping to be same size as separator inlet
Notes:
1. Dashed lines indicate provided by installer.
2. Steam valve and strainer sizes are provided by DriCalc, DriSteem's free sizing and selection software, available at www.dristeem.com.
mc_042811_1450
Separator
Steam trap
Separator
Steam trap
Union
Valve
Union
4" (100 mm)
To Multiple-tube header inlet
To Multiple-tube header inlet
DC-1488
Piping to be same size as separator inlet
12" (305 mm)
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
13
OVERVIEW

Condensate drain piping and trapping

FIGURE 14-1: CONDENSATE DRAIN PIPING AND TRAPS FOR STEAM INJECTION HUMIDIFIERS
P-trap dimensions
Condensate outlet
Drop
Lifting condensate
From P-trap or mechanical trap
Condensate pump*
Seal
Check valve
Mechanical trap dimensions
Typical model
Condensate outlet
Drop
Drip
F&T trap (shown) or inverted bucket trap
Notes: * Use condensate pump rated for 212 °F (100 °C) and suitable for lifting 250 gph (16 L/m)
at required head (60 kPa). Stainless steel condensate pump recommended when pumping condensate from systems using optional stainless steel components.
• If wasting condensate to drain, temper condensate to local code to prevent damage to drain plumbing.
• Dashed lines indicate provided by installer.
Stainless steel components model
Condensate outlet
Drip
Cooling
leg
Stainless steel thermostatic trap
mc_050211_1314
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
14
Condensate drain piping and trapping
Table 15-1: Condensate drain piping and traps for Steam Injection humidifiers
Single-tube, Mini-bank, and Multiple-tube humidifiers
P-trap water seal
Piping from separator*** Piping from steam jackets Piping from header
Typical
model
Models with optional stainless steel components
Typical
model
Do not use Do not use Do not use Do not use Do not use Do not use
Models with optional
stainless steel
components
Typical
model
Models with optional stainless steel components
OVERVIEW
Area-type humidifier
Piping
from
separator
Use with
minimum:
Drop: 8"
(203 mm)
Seal: 10"
(254 mm)
F&T trap
Inverted bucket trap*
Stainless steel thermostatic trap
Use if steam
pressure is ≤15 psi
(103.4 kPa):
Drop: 12" (305 mm)
Drip: 4" (102 mm)
Use if steam
pressure is >15 psi (103.4 kPa): Drop: 12" (305 mm)
Drip: 4" (102 mm)
Do not use
Do not use
Do not use
Use with stainless
steel
piping with
minimum:
Drip: 4" (102 mm)
Cooling leg: 24"
(610 mm)
Use only if not lifting
condensate and
steam pressure is
≤15 psi (103.4 kPa):
Drop: 12" (305 mm)
Drip: 4" (102 mm)
Use if lifting
condensate or if
steam pressure is
>15 psi (103.4 kPa):
Drop: 12" (305 mm)
Drip: 4" (102 mm)
Do not use
Do not use
Do not use Do not use Do not use Do not use
Use with stainless
steel piping with
minimum:
Drip: 4" (102 mm)
Cooling leg: 24"
(610 mm)
Use with
minimum:
Drop: 12"
(305 mm)
Drip: 4"
(102 mm)
Do not use
Do not use Do not use
Use with stainless
steel piping with
minimum:
Drip: 4" (102 mm)
Do not use
Cooling leg: 24"
(610 mm)
Return condensate to boiler via
Yes Yes Ye s Yes Yes Yes No nonpressurized return line?
Return condensate by condensate
Yes Yes** Yes Yes** Yes Yes** Yes
pump?
Drain condensate to
Yes
Yes
Yes
Yes
Yes
Yes
Recommended
open drain?
Notes: * Trap may require priming after seasonal shutdown. ** DriSteem recommends using a stainless steel condensate pump when pumping condensate from systems using optional stainless steel components. *** During consistent load, there may not be enough steam pressure in the separator to lift condensate from the separator using steam. † If wasting condensate to drain, temper condensate to local code to prevent damage to drain plumbing.
mc_050211_1630
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
15
OVERVIEW

Temperature switches

FIGURE 16-1: PNEUMATIC TEMPERATURE SWITCH STANDARD LOCATION
Pneumatic airflow switch (optional)
Set point controlling humidistat
20 psi (138 kPa) air supply
Duct high limit Required 0.007" (0.18 mm) restrictor
humidistat
(optional)
Separator
12" (305 mm) min.
DC-1190
mc_051011_1650
Steam trap
FIGURE 16-2: PNEUMATIC TEMPERATURE SWITCH ALTERNATE LOCATION
12" (305 mm) min.
Pneumatic temperature switch
DC-1192 mc_051011_1651
Pneumatic temperature switch
Steam trap
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
16
Temperature switches
PNEUMATIC TEMPERATURE SWITCH NOTES:
• DriSteem's pneumatic temperature switch, designed for use with a pneumatic control system, prevents condensate discharge from a steam injection humidifier during cold start or if the condensate return main becomes flooded. It accomplishes this by bleeding off the pneumatic signal from the controlling humidistat, preventing the pneumatic humidifier valve from opening until the steam trap has reached operating temperature.
• The pneumatic temperature switch has a self-contained air valve operated by a thermal disc that is normally open, bleeding off control air pressure. When steam comes in contact with the thermal disc, the fluid inside the disc expands, causing the air valve to close, thus allowing the pneumatic control system air pressure to build up and to actuate the steam control valve.
• Install the tee containing the pneumatic temperature switch in the condensate drainage pipe line between the separator and the inlet to the steam trap, as shown in the drawings on Pages 16 and 18.
mc_051011_1652
OVERVIEW
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
17
OVERVIEW
Temperature switches
FIGURE 18-1: ELECTRIC MODULATING TEMPERATURE SWITCH LOCATION
120 VAC primary
24 VAC secondary
Duct high limit humidistat (optional)
Airflow proving switch (optional)
Class 2 transformer (by installer) used with 24 VAC coil
Omit transformer when using 120 VAC coil
Steam trap
Electric modulating humidistat (optional) or control signal by others
Normally closed electric modulating valve (120 VAC or 24 VAC)
DC-1227 mc_051011_1653
12" (305 mm) min.
Electric temperature switch
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
18
Loading...
+ 44 hidden pages