The EB1400 is a portable cooling, heating and dehumidification system. The unit may be
ducted for directing cooled or heated air into specific spaces.
READ AND SAVE THESE INSTRUCTIONS
Read and understand manual before operating.
ELECTRIC SHOCK HAZARD
WARNING! Unit must be grounded.
• Use indoors only.
• Keep out of water.
• Keep electrical components dry. If they get wet, allow
them to dry before using the EB1400.
• Insert three-prong plug on power cord into a matching
electrically grounded outlet. Never cut off third prong.
FIRE HAZARD
• Keep air intakes clear of obstructions and dirt. Reduced
airflow can cause motor to overheat. Keep away from
draperies or other material that could block air intakes.
See maintenance instructions.
• Keep air filter clean. Keep filter clear of clogging, oil,
grease or other contaminants that can be drawn into the
EB1400.
SAFETY INSTRUCTIONS
WARNING! Unplug unit before opening housing for
cleaning or servicing.
• Turn off unit and unplug before lifting or moving.
• Handle the unit carefully. Always operate the unit on a
stable, level surface. Do not drop, throw, or place where it
could fall. Rough treatment can damage the unit, and may
create a hazardous condition or void the warranty.
• Inspect the power cord before use. If cord is damaged, do
not use. Replace with a cord of the same type and
amperage rating. Protect cord from damage by turning off
unit before unplugging. Always grasp the plug (not pulling
on the cord) to unplug.
• The unit is designed to operate on 115V/60 Hz. Make sure
that the electrical outlet is grounded.
ARNING
EnviroBoss™ 1400 (115V)
DRI-EAZ PRODUCTS, INC.
15180 Josh Wilson Road, Burlington, WA 98233
www.dri-eaz.com
• Secure during transport to prevent sliding and possible
injury to vehicle occupants.
• Keep children away from unit. Be sure unit is inaccessible
to children when unattended.
• Do not attempt to disassemble or repair the unit. For
Authorized Service Centers, go to
www.dri-eaz.com/howtobuy or call Dri-Eaz Service at
800-932-3030.
INTRODUCTION
The EB1400 is a versatile unit providing dehumidification, 1-ton
cooling with 470 CFM across the evaporator and 750 CFM
across the condenser, plus focused heating and ventilation.
The unit can be ducted for spot cooling and directing
conditioned air or heat into specific spaces while filtering room
air and pumping out condensate.
FEATURES:
• Ducts to and from unit for heating and cooling. Note: Duct
adapters for condenser inlet and outlet and evaporator
outlet. No duct adapter for evaporator inlet.
• Refrigeration system that dehumidifies while it heats or
cools
• Uniform 8" ducting size for all outlets
• Digital temperature control
• Durable rotomolded duct rings and housing
• Wheel casters and handle for ease of transport
07-01626B 2008-05 Copyright 2007 Dri-Eaz Products, Inc. 1
PARTS IDENTIFICATION (Shown, below)
(
)
Condenser
Duct C:
Process air
outlet (cool)
Front filter
Air Inlet
Drain Hose
pocket
Wheel casters
Rotomolded
shell
Front (Intake) Filter View
Touchpad
temperature
controls
Duct B:
Process air
heat recovery
outlet
Duct A (Heat inlet back of unit)
Duct A:
Process air
heat recovery
inlet
Cord
pocket
Back View
SETUP
Place dehumidifier upright. When transporting the EB1400 in a
horizontal position is necessary, set upright (vertically) for at
least 30 minutes before operation. When machine is placed in
a horizontal position, oil from the compressor flows into the
refrigerant coils reducing the ability of the EB1400 to function.
OPERATING INSTRUCTIONS
GETTING STARTED
PLACEMENT:
For cooling or heating, place at least one EB1400 per room.
1. Place the unit on a level surface.
2. Make sure the System switch is set to Off then plug power
cord into a standard 115V grounded outlet.
3. Set the digital temperature controls needed to function
(see below).
4. Check for proper operation before leaving the unit
unattended. Do not move or carry the EB1400 when it is
running or plugged in.
OPERATING RANGE
Recommended operating range is between 60° and 105°F (16°
and 46°C). The EB1400 will not function properly when
operating in an environment with temperatures outside this
range.
CYCLE TIMES AND COMPRESSOR PROTECTION
The EB1400 thermostat includes an automatic compressor
protection feature to avoid potential damage to the cooling
system from short cycling. This thermostat automatically
provides a five minute delay after turning off the cooling system
output to protect the compressor. This protection is also
present while operating the unit in heating applications.
Important Notes:
• If unit loses power or gets unplugged during operation,
operator MUST wait five minutes before plugging unit back
in or risk damaging the compressor or tripping the circuit
breaker in the facility.
• Always turn the System switch to OFF before unplugging.
• If the System setting is adjusted during operation the unit
will automatically delay five minutes before start-up.
• When switching unit from cooling to heating or heating to
cooling operator must adjust set point temperature.
TESTING AND PROGRAMMING THERMOSTAT
DIGITAL CONTROLS
Up Down
Heat Cool Off
Digital display
Auto
Reset
Fan
control
On
TO TEST THERMOSTAT:
1. Move the system switch from OFF to the HEAT position.
Press the ^ button on the keypad until the set point
temperature setting is a minimum of three degrees higher
07-01626B 2008-05 Copyright 2007 Dri-Eaz Products, Inc. 2
than the current room temperature. The EB1400 should
start within several seconds.
2. The system switch in the OFF position. The EB1400
should stop within several seconds on normal single stage
heating or cooling systems. Note: On refrigeration systems
you must wait five minutes for the automatic compressor
short cycle protection period to expire, or press the
RESET button to bypass this feature for initial testing
purposes. Pressing the RESET button will erase any user
program settings.
3. Place the system switch in the COOL position.
4. Press the v button on the keypad until the set point
temperature is a minimum of three degrees lower than the
current room temperature. The cooling system should start
within several seconds.
5. Place the fan switch in the AUTO position when using the
EB1400.
VIEWING SET TEMPERATURE
1. Press and hold ^ or v button. The current set point
temperature will be displayed in the place of the current
room temperature, and the indicator SET will be displayed.
2. The display will return to normal operating mode when the
^ or v buttons are released. The SET indicator will turn off,
indicating that the current temperature shown in the
display is the room temperature. Continuing to hold the ^
or v button for three seconds or longer will allow the user
to change the current set point temperature (See
Changing Set Temperature, below).
CHANGING SET TEMPERATURE
1. Press and hold ^ or v button for three seconds. The entire
display will flash once and the SET indicator will be
flashing. Release the ^ or v button and press the ^ or v
button again as desired to adjust the set temperature.
2. The display will return to normal operating mode after five
seconds.
3. The SET indicator will turn off in the display, indicating that
the current temperature shown in the display is the room
temperature.
HIGH TEMPERATURE SAFETY SWITCH
When the selector switch is set to HEAT, a software feature
automatically turns the unit off if the room temperature rises
above 93°F (34°C). If the temperature rises above 99°F
(37°C), the thermostat mechanically turns the unit off.
NON-VOLATILE MEMORY
In the event of a power failure, the non-volatile memory feature
of this unit allows all settings to be recovered. When AC power
is restored after an outage, all settings are retrieved from
memory and reinstated.
RESETTING THERMOSTAT
The Reset feature allows the user to completely reset the
thermostat to return to factory-set software settings.
1. To erase all entered settings, gently press RESET button
using a paper clip or a small pencil tip.
2. This will return all thermostat settings to their default values
and register all new manual switch settings for proper
operation.
DUCTING INSTRUCTIONS FOR THE EB1400
Duct A: Process air heat recovery inlet
Duct B: Process air heat recovery outlet
Duct C: Process air outlet (cool)
DUCTING: The unit is ductable for directing conditioned air
•
or heat into specific spaces.
DUCTING SIZE: Use eight inch diameter ducting and secure
•
with clamps on duct adapters.
SIDE DUCTING: When using duct on the side, ducting should
•
be run sideways out doors and windows. Put unit in corner
and duct up at an angle into ceiling tiles (not directly up).
RIGID DUCTING:Duct A requires rigid ducting (not layflat)
•
attached by clamps.
APPLICATIONS
(For more applications, please visit the EB1400 Virtual Training
Center at vtc.dri-eaz.com)
•COOLING IMMEDIATE AREA: Cold air blowing from Duct C (not
ducted) will cool overall room.
HEATING AREA:Duct B outputs heat; ducting is needed if
•
ducting warm air outside room or to focus heat in targeted
area. If not ducted outside the room then it will heat the
immediate space.
NEUTRAL AIR CONDITIONING: For neutral air conditioning duct
•
both B (heat outlet) and A (heat inlet) outside the
structure.
DEHUMIDIFYING:Spot cool with dehumidification by ducting
•
outlet C. No ducting is needed to dehumidify overall area.
SPOT COOLING: For spot cooling point outlet C air stream to
•
specific area or duct it to spot cool.
TRANSPORTING AND STORING
1. Before transporting, move Duct B ducting adapter to either
the front or back of the unit to prevent damage. Note: Do
not expose the thermostat to moisture and rain when
transporting in uncovered vehicles such as flatbed trucks.
2. Transport the unit on stairs or over rough surfaces upright
on the Unimover or hand truck and hold in place using
straps. Do not secure the unit by the handle. WARNING!
Take care when loading the unit on a hand truck; the unit
could tip over resulting in personal injury. Always place a
strap around the housing of the EB1400 and secure it to
the Unimover or hand truck before attempting to lift the
unit.
3. Store with left side of unit against the wall and keep
upright while transporting. NOTICE! Do not secure the unit
by the handles. Secure into place with a strap wrapped
around the plastic housing. Store securely to avoid any
damaging impact to internal parts.
07-01626B 2008-05 Copyright 2007 Dri-Eaz Products, Inc. 3
MAINTENANCE
WARNING! Turn off and unplug unit before cleaning or
servicing.
BEFORE EACH USE
Inspect Power Cord
Inspect power cord for cuts, fraying or damage; do not use if
damaged.
WEEKLY MAINTENANCE
Inspect Front Filter
Slide duct ring adapters for outlet D off to remove front filter for
cleaning. Slide out the filter and inspect for damage or
excessive dirt. Use a clean 3M™ HAF filter (see below).
Replace filter every four months or earlier if necessary. For
Parts and Service call your local distributor or the Dri-Eaz
Service Department at 800-932-3030 or 360-757-7776.
Use Clean 3M HAF Filters
Keep clean filters in the unit at all times to keep out dust and
protect internal components. HAF filters may be vacuumed
clean and reused up to three times before replacement.
Note: The two filters used for the unit are the same type but
different sizes. Be sure the appropriate size is installed.
MONTHLY MAINTENANCE
1. Inspect Exterior
Inspect exterior components and make sure they are
properly installed. Listen to the unit for abnormal sounds.
For Parts and Service call your local distributor, or the DriEaz Service Department at 800-932-3030 or
360-757-7776
2. Clean Exterior
Clean the housing with a damp cloth. Bring back the
original shine with a vinyl cleaner/polish like those used on
automobile plastics.
3. Inspect Back Filters
The second set of filters is in the back of the unit on the
condenser side and may only require cleaning periodically
(every three to six months depending on the cleanliness of
the air ducted or drawn into the condenser inlet). To
access these filters, use a ⅜" socket wrench to remove
the six ¼-20 bolts holding the back cover and lower
handle in place. If you need further assistance, contact the
Dri-Eaz Service Department at 800-932-3030 or
360-757-7776.
Filters 3M HAF filter
Cord Length 20 ft. (6.1 m)
Construction Rotomolded shell
Safety ETL listed to UL and CSA standards
49.5 × 33.5 × 27.25 in.
125.7 × 85.1 × 69.2 cm
470 CFM Evaporator air stream
750 CFM Condenser air stream
Specifications are subject to change without notice. Some
values may be approximate.
ACCESSORIES
Ceiling Adapter Kit (F400)
The Ceiling Adapter Kit allows the user to direct the heat
absorbed by the EB1400 during A/C operation into a
suspended ceiling space and recirculate it back through the
EB1400. Isolating the heat dissipating stream from the cooling
stream creates a neutral air pressure environment, enabling
the EB1400 to deliver maximum cooling performance in
situations where it is not possible to vent absorbed heat
outside of the structure. Kit includes two lightweight ceiling
adapter housings, four 10 foot sections of semi-rigid ducting,
and a 24 × 24 in. cardboard panel to temporarily block ceiling
openings adjacent to adapter.
Rigid Performance® Ducting (F382)
One 10 ft. section of 8 in. diameter semi-rigid ducting.
LayFlat Ducting (F268)
One 500 ft. roll 8.3 in. (ID) x 4 mil poly layflat ducting.
FOR PARTS AND SERVICE CALL YOUR LOCAL DISTRIBUTOR or
the Dri-Eaz Service Department at 800-932-3030 or
360-757-7776.
www.dri-eaz.com
07-01626B 2008-05 Copyright 2007 Dri-Eaz Products, Inc. 4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.