drexel und weiss aerosilent topo Operating, Maintenance, Commissioning

aerosilent topo
Operating, Maintenance, Commissioning
Contents
Technical data __________________________________________________________4 Customer information ____________________________________________________5
Product description ............................................................................................................5
Proper application ..............................................................................................................5
Unsuitable application........................................................................................................ 5
Operation ______________________________________________________________6
Maintenance___________________________________________________________13
Safety notes for fi lter changes .........................................................................................13
Changing the fi lters .......................................................................................................... 13
Commissioning ________________________________________________________15
Prerequisites for commissioning ...................................................................................... 15
Initial commissioning........................................................................................................ 15
Setting the nominal air quantity ....................................................................................... 16
Setting the fan balance .................................................................................................... 17
Switching point for frost protection heating (FSH) ...........................................................17
Fault prevention / checklist ..............................................................................................18
Settings on the overall system ......................................................................................... 18
Decommissioning ............................................................................................................ 18
Important unit information (logbook) ______________________________________19
Technical data
Mains supply ..................................................................................230 VAC / 50 Hz
Recommended fuse .........................................................................................13 A
Nominal air quantity ................................................................................... 120 m
Max. air quantity at 100 Pa external ..........................................................180 m
Heat provision level ............................................................................. approx. 85%
Max. power consumption of the fans (180 m
Thermal power of the optional PWW heat register
(nominal air quantity and VL/RL 60/45) .......................................................1350 W
Sound power level at nominal air quantity and 100 Pa external:
Housing .....................................................................................................31 dB(A)
Air inlet .......................................................................................................32 dB(A)
Air vent .....................................................................................................34 dB(A)
3
/h and 150 Pa external) ............75 W
3
/h
3
/h
Weight ............................................................................................................ 68 kg
Heat recovery level of the plate heat exchanger
according to VDI 2071 with nominal volumetric fl ow .......................................85 %
Customer information
This handbook contains important notes and tips for the operation of your comfort ventilation unit which will protect you from personal injury and guarantee a long service life for the unit. The gures all depict the right-hand version of the unit (supply air connection located on the right). All instructions are equally applicable to the left-hand version (supply air connection located on the left). Please keep the operating instructions for future reference. Please pay attention to the safety notes.
Product description
The aerosilent topo comfort ventilation unit consists of a ventilation module with highly effi cient heat recovery characteristics and an optional heat register.
Proper application
The unit is designed for the ventilation and heating (optional) of living rooms and lounges in passive houses and, if applicable, for near-passive buildings depending on the calcula­tion and building design.
Unsuitable application
No uses other than those specifi ed under 'Proper usage' are permissible. The unit must not be used to dehumidify buildings under construction. Drying and heating
a building structure can cause considerable damage to the unit.. The ventilation of rooms with extremely high humidity levels, such as saunas, or heavily contaminated extract air (fumes, air with a high fat content, explosive extract air) is also not permitted..
Safety notes
WARNING: Indicates that failure to follow the recommended safety proce­dures could result in damage to the unit or personal injury.
CAUTION: Indicates that failure to observe the recommended safety proce­dures could result in damage to the unit.
NOTE: Helpful information and useful tips.
Operating, Maintenance, Commissioning
Page 5
Operation
The aerosilent topo is operated using a room operating panel. Two different room operating pa­nels are available that provide different functions:
3-level switch
3-stage timer
The 3-level switch provides simple, manual fan control. In contrast, the 3-stage timer can be used to set an individual weekly programme.
3-level switch
Selecting the fan level
You use the function button to select the required fan level. Once you have pressed the button, the LED for the activated level lights up.
0 ... System off 1 ... Reduced air quantity 2 ... Nominal air quantity 3 ... Increased air quantity
Special 'Party' mode
This function sets the ventilation unit to level 3 for one hour. Press the function button until LED "3" fl ashes. Once the hour has elapsed, the fan level automatically returns to the level that was previously set.