DREXAN HeatTracer Design/install Manual

HD110301-1 Rev2
Page 1 of 23
Design / Install Guide
HD110301-1 Rev2
Page 2 of 23
CONTENTS
Introduction Page 3
System Overview Page 4
Fire Suppression System Freeze Protection Applications Page 5
Typical Pipe Freeze Protection System Page 5
Fire Supply Lines Page 6
Sprinkler Standpipes Page 8
Branch Lines with Sprinklers Page 9
Freezer Applications Page 10
Fire Suppression System Freeze Protection Design Guide Page 11
STEP 1 – Collect the Required Information for Each Line Page 11
STEP 2 – Design Considerations Page 12
STEP 3 – Electrical Requirements Page 13
STEP 4 – Selecting Cable Power Output Page 13
STEP 5 – Cable Components Page 17
STEP 6 – Power Distribution Page 18
Installing Self-Regulating Cable Page 19
Testing Self-Regulating Cable Page 21
Heating Cable Test Report Page 22
Troubleshooting Self-Regulating Cable Page 23
Fire Sprinkler System Freeze Protection Design / Install Guide
HD110301-1 Rev2
Page 3 of 23
INTRODUCTION
This design guide and installation manual from Drexan HeatTracer provides recommendations for designing a pipe freeze protection system for fire sprinkler piping, using Drexan HeatTracer MultiTrace cables. It provides system design and performance data, information on heat tracing monitoring and control, electrical sizing information, and various configuration recommendations. This design guide assumes the fire protection system has been designed by others qualified in the art.
MultiTrace is certified to all CSA / UL (CUS) standards for use throughout North America, as well as ATEX 2014/34/EU for global applications and is suitable for both metal and non-metal pipes, tanks and vessels. (see p.17).
This guide does not cover the following applications:
Hazardous locations as defined in the National / Canadian Electric Code
Supply voltages other than 100-130V or 208-277V
For assistance with application requirements that differ from those addressed in this document, contact your Drexan representative or Drexan directly at 1-800-663-6873.
The following instructions will provide you with a step-by-step procedure for determining the best solution for your fire sprinkler system freeze protection applications. An improperly designed and installed heat tracing system could result in cable failure and possible physical injury.
The installation manual provides general guidance for installing the heating cable and components on fire sprinkler piping. Additional installation instructions are included with the connection kits, controllers, and accessories. If you are missing any required documents, you can download them from the on-line document library at www.drexan.com.
HD110301-1 Rev2
Page 4 of 23
SYSTEM OVERVIEW
Drexan HeatTracer MultiTrace self-regulating cable is designed for freeze protection of above ground and buried supply pipes, fire standpipes, branch lines and branch lines containing sprinklers when run in areas potentially exposed to freezing temperatures.
Drexan offers 4 MultiTrace nominal cable power output options for fire sprinkler systems: 3W, 5W, 8W and 10W per foot1 for applications using 100-130V and 208-277V power. Selection of the correct power output for a given line size will ensure sprinkler systems do not overheat and that electrical energy is efficiently used, while providing the required, reliable freeze protection.
A correctly designed and specified system will comprise the following:
Heating cable correctly selected for the line size at design minimum ambient temperatures Power connections, tees and end seals based on piping configuration Monitoring and control system Power distribution panels complete with appropriate ground fault equipment protection Accessories including attachment tapes and warning labels Tools necessary for a complete installation and commissioning tests
Approvals
Drexan HeatTracer MultiTrace is CSA / UL (CUS) certified for use on fire suppression systems in North America. The system covered in this manual includes supply lines, stand pipes, branch lines and sprinkler heads.
1
at 50 degrees F
HD110301-1 Rev2
Page 5 of 23
FIRE SUPPRESSION SYSTEM FREEZE PROTECTION APPLICATIONS
Properly designed freeze protection systems maintain water temperature at a minimum of 40°F/4°C to prevent fire suppression piping from freezing.
Fire Suppression System Freeze Protection Applications
A typical freeze protection system includes the heating cables, connection kits, cable monitoring and temperature control, and power distribution.
FIG. 1 – TYPICAL FIRE / FREEZE PROTECTION SYSTEM
HD110301-1 Rev2
Page 6 of 23
Fire Supply Lines
MultiTrace is designed to maintain fire supply lines at 40°F/4°C in areas subject to freezing.
FIG. 2 – ABOVE GROUND SUPPLY PIPING
Application Requirements
The system complies with Drexan HeatTracer design and installation requirements for above ground general water piping given the following conditions are met:
Heating cable is permanently secured to insulated metal pipes using TAPE-GCR-HT glass tape
or to plastic pipes using TAPE-AL aluminum tape
The system is controlled by a Controller with integrated ground fault protection with alarm
contacts connected to a fire control panel
Heating cable is installed per manufacturer’s instructions with approved connection kits.
Approvals
CSA / UL (CUS) certified for non-hazardous locations.
HD110301-1 Rev2
Page 7 of 23
FIG. 3 – TYPICAL BURIED PIPING SYSTEM
Application Requirements
The system complies with Drexan HeatTracer design and installation requirements for buried piping given the following conditions are met:
The line is buried at least 2 feet/0.7 m deep All heating cable connections are made above ground The power connection and end seal connections are made above grade in Drexan HeatTracer
connection kits
Heating cable is protected from the pipe to the power connection box in CSA certified water-
sealed conduit with a minimum diameter of ¾” suitable for the location
The system is controlled by a Controller with integrated ground fault protection with alarm
contacts connected to a fire control panel
Closed cell waterproof thermal insulation with fire retardant waterproof covering approved
for direct burial is used over the cable and pipe
Heating cable is installed per manufacturer’s instructions with approved connection kits
Approvals
CSA / UL (CUS) certified for non-hazardous locations.