Dražice OKCE 80, OKC 100, OKC 100/1m2, OKC 125, OKC 125/1m2 Operation And Installation Manual

...
Page 1
Operation and Installation Manual
TANK-TYPE WATER HEATERS FOR VERTICAL
MOUNTING
Combined Electric
OKCE 50 OKC 80 OKCE 80 OKC 100 OKC 100/1m2 OKCE 100 OKC 125 OKC 125/1m2 OKCE 125 OKC 160 OKC 160/1m2 OKCE 160 OKC 180 OKC 180/1m2 OKCE 180 OKC 200 OKC 200/1m2 OKCE 200
Družstevní závody Dražice – strojírna s.r.o.
Dražice 69
294 71 Benátky nad Jizerou
Tel.: 326 370 911, fax: 326 370 980
www.dzd.cz dzd@dzd.cz
Page 2
Read carefully the below instructions prior to the installation of the heater!
Dear Customer,
The Works Cooperative of Dražice – Machine Plant, Ltd., would like to thank you for your decision to use a product of our brand.
The manufacturer reserves the right for engineering modification of the product. The product is designed for permanent contact with drinkable water.
Guide Contents
1. FUNCTION DESCRIPTION ............................................................................................................... 2
2. MESSAGE FOR CUSTOMERS .......................................................................................................... 3
3. TECHNICAL DESCRIPTION ............................................................................................................. 3
4. OPERATING ACTIVITY .................................................................................................................... 3
5. SERVICING ......................................................................................................................................... 4
6. WALL MOUNTING ............................................................................................................................ 5
7. PLUMBING FIXTURE........................................................................................................................ 5
8. CONNECTION OF COMBINED HEATER TO HOT WATER HEATING SYSTEM ..................... 6
9. ELECTRIC INSTALLATION ............................................................................................................. 6
10. PUTTING THE HEATER INTO OPERATION ................................................................................. 6
11. HEATER CLEANING AND ANODE ROD EXCHANGE ................................................................ 6
12. IMPORTANT NOTICES ..................................................................................................................... 6
13. FIRE-FIGHTING REGULATIONS FOR INSTALLATION AND USE OF HEATER .................... 7
14. INSTALLATION REGULATIONS .................................................................................................... 7
15. MOST FREQUENT FUNCTION FAILURES AND THEIR CAUSES ............................................. 8
16. PRODUCT ACCESSORIES ................................................................................................................ 8
17. TECHNICAL DATA CHART.............................................................................................................9
18. PICTURES.......................................................................................................................................................10
Environment Type:
It is recommended to use the product in indoor environment with air temperatures from +2°C to 45°C and a relative humidity up to 80%.
1. FUNCTION DESCRIPTION
The heater is designed for accumulation heating of service water using electricity or thermal energy via an
exchanger (for the combined design only). Water is heated by an electric element (or a heat exchanger) in an enamelled thermally insulated accumulator at the time defined by the power supplier. The element is at the time of heating controlled by a thermostat the temperature of which can be adjusted continuously (within the range between 5°C and 74°C). Once the selected temperature is reached, heating interrupts automatically. Water accumulated in the tank is then used for consumption. The tank keeps constant pressure of water from the water main. If the combination faucet hot water valve is opened, water from the water supply conduit pressed out by cold water pressure flows out of the heater. Hot water flows out through the top part, and water flowing in remains in the bottom part of the heater. Pressure principle allows hot water withdrawal at any place from the heater (Fig. 1).
Page 3
2. MESSAGE FOR CUSTOMERS
Hot water consumption
Consumption of hot water in households depends on the number of people, amount of sanitary equipment, length, diameter and insulation of piping in the flat, or on individual habits of users. The cheapest option of water heating comes at the time when the electricity rate is reduced. Find out in what time intervals your electricity supplier provides reduced tariff and, depending on that information, select relevant volume and power input of the heater so that your hot water consumption covered the needs of your household.
Energy saving
Hot utility water reservoir is insulated by means of a top-quality polyurethane foam with zero CFCs content. Adjust the temperature of the heater's thermostat to that level only that you need to run your home. Thus you will reduce electricity consumption, as well as the amount of lime sediments on the walls of the receptacle and on the electric element's pit.
Emergency power consumption
If no heated water is taken from the tank, a small amount of heat leaks. This loss is measured for a period of 24 hours at the temperature of 65°C in the heater, and at 20°C in its ambient area. The resulting value is expressed in kWh/24h and indicates the amount of power needed to maintain the set temperature.
Data sheet pursuant to Directive No 442/2004 and Appendix No 7
3. TECHNICAL DESCRIPTION
The heater tank is made of a steel plate and tested by 0.9 MPa overpressure. The inside of the receptacle is
enamelled. A flange is welded onto the bottom of the tank with a flange lid screwed to it. A sealing ring is inserted between the flange lid and the flange. Thermowells for placing a heating element and sensors of regulation thermostat and safety fuse are located in the flange lid. Anode rod is mounted on M8 nut. The water reservoir is insulated by means of polyurethane foam. Electric wiring is placed underneath the plastic removable cover. The temperature of water can be set using the thermostat. In combined versions, a heat exchanger is welded in the pressure tank. The heat exchanger is only intended for the heating circuit.
4. OPERATING ACTIVITY
a) Water heating by electric energy
After the heater is connected to electric network, the heating element starts heating water. The element is
turned on and off by a thermostat. After reaching the temperature set, the thermostat switches off the electric circuit
OKC 80 C 8,9 75 2,5 4,8 0,71 OKC 100; OKC 100 /1m2 C 8,8 95 3 6 0,88 OKC 125; OKC 125 /1m2 C 8,7 120 3,8 8 1,09 OKC 160; OKC 160 /1m2 C 8,7 147 5 9,6 1,33 OKC 180; OKC 180 /1m2 C 7,7 175 5 10,6 1,39 OKC 200; OKC 200 /1m2 B 7 195 5,5 12 1,4 OKCE 50 C 9 51 1,5 3 0,45 OKCE 80 C 8,9 80 2,5 4,8 0,71 OKCE 100 C 8,8 100 3 6 0,88 OKCE 125 C 8,7 125 3,8 8 1,09 OKCE 160 C 8,7 152 5 9,5 1,33 OKCE 180 C 7,7 180 5 10,6 1,39 OKCE 200
B 7 200 5,5 12 1,4
Heat losses
kWh/24hr
Time of content
heating (hours)
Electricity consumption
for heating of the
contents from 15°C to
65°C in kWh
Heater types
Energy
efficiency
class
Heat
losses
Wh/24hr/l
Nominal
capacity (l)
Page 4
and thus discontinues water heating. The control light signals if the element is in operation (light is on) or if it is off (the light goes out). In case of longer operation without using the heated volume, the thermostat has to be set to
position 5°C to 8°C (set the “snowflake” symbol on the thermostat selector) to avoid its freezing, or electricity
supply to the heater has to be switched off. In combined versions, the stop valve on the inlet to the exchanger has to be closed, which prevents heating water in the hot water heating system.
b) Service water heating via thermal energy through heat exchanger
Closing valves of the heat exchanger must be opened which ensures heating water flow from the hot water heating system. Together with a closing valve, it is recommended to install an air outlet valve at the inlet to the heat exchanger in order to bleed the heat exchanger (Fig. 2) as needed, in particular before the beginning of the heating season. The time of heating using the heat exchanger depends on the temperature and flow of water in the hot water heating system. A combined heater is made in universal design – depending on the need of connecting the closing valves to the heating element either from the right, or from the left (Fig.2).
5. SERVICING
Service devices of heaters of 50 to 200 l capacity are located under the transparent guard of the control panel.
Thermostat knob Electric circuit closing indicator lamp Tipping transparent guard
Temperature setting
Water temperature is set by turning the thermostat knob. The desired symbol is adjusted against the fixed point on the control panel.
Notice: Adjusting the thermostat selector at the left backstop does not mean permanent shutoff of the heating element. When the heater is in use without blocking the daily rate, we do not recommend the temperature to be set above 60°C. The maximum value to select is “60“.
Limiting the regulation range; locked settings.
For various safety reasons (unintentional scalding, preventing children or unauthorised person from handling), the regulation range can be limited, or the setting on the thermostat blocked. Regulation limited - pull off the thermostat knob (it will be tough at first) and you will find two cylindrical pins
2,15mm on the back side of the knob
- pull off one pin and insert it to the corresponding hole of the selected maximum temperature.
- put the knob back on (to the stop).
Lower temperature range limit (about 5°C)
Fixed point on the control panel
Anti-freezing temperature (about 8°C)
Upper temperature range
limit (about 74°C)
”Ideal” temperature (about 60°C)
Page 5
To block the setting – set the selected temperature by pulling off the thermostat knob without changing the setting
and you will find two pins on the back side of the knob; pull both of them and fit them into the holes corresponding with the selected temperature so that the gap between the pins was without a hole, and the position was opposite the set temperature.
6. WALL MOUNTING
Prior to mounting, check the loading capacity of the wall and, depending on the type of masonry, choose a
suitable anchorage material, or reinforce the wall, if needed. The water heater shall only be mounted in vertical position so that the lower edge of the heater was placed at least 600 mm above the floor (Fig. 4, 5). In combined heaters, elbows have to be attached to the heating water inlet and outlet and, by turning them, the mounting either from the right or from the left has to be determined (Fig. 2). With regard to various types of carrying masonry and broad assortment of special anchorage material available at the market, we do not provide heaters with this material. The anchorage system has to be selected individually, depending on the conditions. We recommend an authorised company perform mounting on the
wall and anchorage, or discuss the anchorage with a professional.
7. PLUMBING FIXTURE
Connection of heaters to plumbing fixtures is illustrated on Figures 1 and 2. For potential disconnection of the heater, the service water inlets and outlets must be provided with screw coupling Js 3/4“. Safety valve is mounted on the cold water inlet identified with a blue ring. The heaters must be equipped with a drain valve. Each hot service water pressure heater must have a membrane spring loaded with a safety valve. The safety valve must be easily accessible, as close to the heater as possible. The input pipes must have at least the same clearance as the safety valve. The safety valve is placed high enough to secure dripping water drain by gravity. We recommend mounting the safety valve onto a branch pipe. This allows easier exchange without having to drain the water from the heater. Safety valves with fixed pressure settings from the manufacturer are used for the assembly. Starting pressure of a safety valve must be identical to the maximum allowed heater pressure, and at least 20% higher than the maximum pressure in the water main. If the water main pressure exceeds such value, a reduction valve must be added to the system. No stop valves can be put between the heater and the safety valve. During the assembly, follow the guide provided by the safety equipment manufacturer. It is necessary to check the safety valve each time before putting it into operation. It is checked by manual moving of the membrane from the seat, turning the make-and-break device button always to the right. After being turned, the button must click back into a notch. Proper function of the make-and-break device results in water draining through the safety valve outlet pipe. In common operation, such a check needs to be implemented at least once a month, and after each heater shutdown for more than 5 days. Water may be dripping off the drain pipe of the safety valve; the pipe must be open into the air, pointed down; environment temperatures must not drop below zero. When draining the heater, use a recommended drain valve. First, close water input into the heater. Find necessary pressure values in the following table. For proper safety valve operation, a backflow valve must be mounted on the inlet pipes, preventing spontaneous heater draining and hot water penetrating back into the water main.
When assembling the security equipment, follow ČSN 06 0830.
Safety valve
starting pressure
(MPa)
Admissible operating
water heater
pressure (MPa)
Max. pressure in
the cold water pipe
(MPa)
0.6
0.6
up to 0.48
0.7
0.7
up to 0.56
1 1 up to 0.8
Regulation limited
Setting blocked
Page 6
8. CONNECTION OF COMBINED HEATER TO HOT WATER HEATING SYSTEM (Fig. 1, 2)
It is recommended to install stop valves on the heating water inlet and outlet (for possible dismantling of the heater). The valves have to be as close to the heater as possible to avoid higher thermal losses.
9. ELECTRIC INSTALLATION
The electric wiring scheme is attached to the water heater on the side of the electric installation guard (see also Fig.
6).
Connection, repairs, and wiring inspections may only be implemented by a company authorised to such activity. Expert connection must be confirmed on the warranty certificate. The heater is connected to the 230 V/50 Hz electric network using a fixed moving conductor with a switch that turns off all network poles and the circuit breaker (protector). Installations in bathrooms, laundromats, rest rooms, and showers, 33 2000-7-701 must be obeyed. The degree of protection of electric parts of the heater is IP 45. Respect the rules of protection against electrical injuries in accordance with ČSN 33 2000–4-41.
10. PUTTING THE HEATER INTO OPERATION
After connecting a heater to the water main, hot water heating system, electric network, and after testing its safety valve (based on the valve manual attached), the heater may be put into operation.
Procedure:
a) Check both water and electric installation; for combined heaters, check the installation to a hot water
heating system. Check proper placement of operating and safety thermostat sensors. The sensors must be inserted all the way in; first the operating and then the safety thermostat.
b) Open the hot water valve on the combination faucet; c) Open the cold water inlet valve to the heater. d) As soon as the water starts running through the hot water valve, the heater is filled and the valve closes. e) In case of a leakage (flange lid), we recommend fastening the flange lid bolts and screwing the electric
wiring guard.
f) Fasten the electric installation cover. g) When heating service water with electric energy, turn the electricity on (in combined versions, the valve on
the heating water inlet into the heating element has to be shut off);
h) When heating service water with thermal energy from a hot water heating system switch electricity off and
open the valves of heating water inlet and outlet, possibly de-aerate the exchanger.
i) When commencing operation, flush the heater until the cloudiness in the water is gone. j) Make sure to fill in properly the warranty certificate.
11. HEATER CLEANING AND ANODE ROD EXCHANGE
Repetitive water heating causes limestone sediment on both the tank walls and chiefly the flange lid. The sedimentation depends on the hardness of water heated, its temperature, and amount of hot water consumed.
We recommend checking and cleaning the tank from scale and eventual replacement of the anode rod after two years of operation. The anode life is theoretically calculated for two years of operation; however, it changes
with water hardness and chemical composition in the place of use. Based on such an inspection, the next term of anode rod exchange may be determined. Have the company in charge of service affairs clean and exchange the anode. When draining water from the heater, the combination faucet valve for hot water must be open, preventing occurrence of under-pressure in the heater tank which would stop the water from draining.
12. IMPORTANT NOTICES
Without a confirmation of performed electrical installation issued by an authorised company, the
warranty certificate shall be void.
Check and exchange the Mg anode regularly. You have to apply for approval of a local power supplier to connect the heater. No stop valves can be put between the heater and the safety valve.
Page 7
If the overpressure in the water main exceeds 0.48 MPa, a pressure control valve must be mounted before the
safety valve.
All hot water outputs must have a combination faucet. Before filling the heater with water for the first time, it is recommended to fasten the flange connection nuts of
the tank.
It is not allowed to handle the thermostat, aside from temperature resetting with a control button. All electric installation handling, adjustment and replacement of the regulation elements shall only be
performed by an authorised service company.
The thermal fuse must not be turned off! In case of thermostat defect, the thermal fuse interrupts electric
power input to the heating element if the water temperature in the heater exceeds 90 °C.
As an exception, the thermal fuse may also switch off due to water overheating caused by overheating the hot
water heating system boiler (in case of a combined heater).
We recommend you operate the heater with one type of energy.
Disposal of packaging material and functionless product
A service fee for providing return and recovery of packaging material has been paid for the packaging in which the water heater was delivered. The service fee was paid pursuant to Act No. 477/2001 Coll., as amended, at EKO­KOM a.s. The client number of the company is F06020274. Take the water boiler packages to a waste disposal place determined by the town. When the operation terminates, disassemble and transport the discarded and unserviceable heater to a waste recycling centre (collecting yard), or contact the manufacturer.
13. FIRE-FIGHTING REGULATIONS FOR INSTALLATION AND USE OF HEATER
We would like to emphasise that the heater must not be connected to power supply if work
involving flammable liquids (petrol, spot remover) or gases, etc., is performed nearby.
14. INSTALLATION REGULATIONS
Regulations and instructions that must be obeyed if the heater is connected
a) to the heating system
ČSN 06 0310 – Thermal systems in buildings Designing and Installation ČSN 06 0830 – Thermal systems in buildings Protecting devices for electric network
b) to the electrical network
ČSN 33 2180 - Connecting of electric devices and appliances ČSN 33 2000-4-41 - Low voltage electric installations Protective measures to ensure safety
- Protection against electric shock
ČSN 33 2000-7-701 - Low voltage electric installations: Single-purpose devices and devices in special
premises
- Premises with tub or shower
c) to the hot water heating system
ČSN 06 0320 - Thermal systems in buildings - Hot water preparation Design and Project Engineering ČSN 06 0830 – Thermal systems in buildings Protecting devices ČSN 73 6660 – Internal water conduits ČSN 07 7401 - Water and steam for thermal energy equipments with working steam pressure up to 8 MPa ČSN 06 1010 - Tank water heaters with water and steam heating; and combined with electric heating.
Technical requirements. Testing.
ČSN 75 5455 – Calculation of water installations inside buildings ČSN EN 12897 – Water supply Indirectly heated closed tank-type water heaters
Both electric and water installation must follow and meet requirements and regulations relevant in the country of use.
Page 8
15. MOST FREQUENT FUNCTION FAILURES AND THEIR CAUSES
Water is cold
LED is on
The temperature set on the thermostat is too low Heating element failure
LED is not on
No supply voltage; thermostat failure; Safety thermostat shut off probably due to failed operation thermostat
Water is not warm enough
LED is on
failure of one of the coils in the element (contains 2)
Temperature of water is not corresponding
Defective thermostat
Water is constantly dripping of the safety valve
LED is not on
Input pressure too high; faulty safety valve
Do not try to repair the failure yourselves. Seek either expert or service help. It does not take much for an expert to remove the defect. When making a repair appointment, report the type and serial number you find on the
performance plate of your water heater.
16. PRODUCT ACCESSORIES
The product is supplied with a safety valve, 2 – 4 fastening screws M 12x30, 2-4 washers 13 (OKCE version has them mounted in the hinges on the heater) and a thermometer. The above parts are packed and placed in the packaging in the top part of the heater.
It is in your own interest to check the completeness of the accessories.
Page 9
9
Type OKC 80 OKC 100 OKC 125 OKC 160 OKC 180 OKC 200
OKC 100/1m2OKC 125/1m2OKC 160/1m2OKC 180/1m2OKC 200/1m
2
OKCE 50 OKCE 80 OKCE 100 OKCE 125 OKCE 160 OKCE 180 OKCE 200
Capacity K / E l 51 75 / 80 95 / 100 120 / 125 147 / 152 175 / 180 195 /200
Max operating overpressure in the tank MPa
Maximum operating overpressure in the exchanger* MPa -
Electric connection V
Power input W
El.protection
Max temperature of HSW °C
Recommended HSW temperature
°C
Height of the heater mm 561 736 881 1046 1235 1187 1287
Diameter of the heater mm 524 524 524 524 524 584 584
Max weight of the heater without heater kg 30 42/36 52/58/42 58/64/48 66/72/58 76/82/72 81/88/76
Time of el.heating from 10°C to 60°C hod 1,5 2,5 3 3,8 5 5 5,5
Heat losses/energy efficiency class kWh/24h 0,45/C 0,71/C 0,88/C 1,09/C 1,33/C 1,39/C 1,4/B
Type OKC 80 OKC 100 OKC 125 OKC 160 OKC 180 OKC 200
Exchanger heat surface
m
2
- 0,41 0,68 0,68 0,68 0,68 0,68
Rated thermal output at heating water temperature of 80°C
and flow 720 l/h
W - 9000 17000 17000 17000 17000 17000
Time of heating by exchanger from 10°C to 60°C at flow of
720 l/hr
min - 32 23 28 35 40 45
Rated thermal output at heating water temperature of 80°C
and flow 310 l/h
W - 7000 9000 9000 9000 9000 9000
Time of heating by exchanger from 10°C to 60°C at flow of
310 l/hr
min - 50 48 55 75 77 86
Type
OKC 100/1m2OKC 125/1m2OKC 160/1m2OKC 180/1m2OKC 200/1m
2
Exchanger heat surface
m
2
- - 1,08 1,08 1,08 1,08 1,08
Rated thermal output at heating water temperature of 80°C
and flow 720 l/h
W - - 24000 24000 24000 24000 24000
Time of heating by exchanger from 10°C to 60°C min - - 14 17 23 26 28
*The OKCE series heaters do not have a heat exchanger
60
0,6
2200
1
0,6
1 PE-N 230V/50Hz
2000
IP 45
80
Page 10
9
Fig. 1
Fig. 2 Fig. 3
Fitting of hinges and indicator onto the heater
Connection on the cold water inlet must conform to ČSN 06 0830
Page 11
10
Fig. 4
OKC 80, OKC 100, OKC 125, OKC 160, OKC 180, OKC 200 OKC 100/1m2, OKC 125/1m2, OKC 160/1m2, OKC 180/1m2, OKC 200/1m2
type
OKC 80
OKC 100
OKC 125
OKC 160
OKC 180
OKC 200
OKC 100/1m2
OKC 125/1m2
OKC 160/1m2
OKC 180/1m2
OKC 200/1m2
A
736
881
1046
1235
1187
1287
B*
731
876
1041
1230
1182
1282
C
615
765 / 636
765/801
1005
793
793 D 524
524
524
524
584
584
E
501
651 / 701
651 / 701
651 / 701
685
685 F -
- / 551
- / 551
- / 831
- / 895
- / 895
G
G3/4"
G3/4" / G1"
G3/4" / G1"
G3/4" / G1"
G3/4" / G1"
G3/4" / G1"
H - - / G3/4"
- / G3/4"
- / G3/4"
- / G3/4"
- / G3/4"
I
211
211
211 / 261
211 / 261
245
245 J - - -
720 / 815
600
600
*Distance from the upper heater's edge to the end of the water inlet and outlet tubes. Check the B and N dimensions before drilling. The values behind the slash apply to heaters with a 1.08 m2 exchanger.
Upper and lower Hinge 160,180, 200L 4 anchor bolts Dimensions 450mm and E Check before drilling
Upper hinge and support 80-125L 2 anchor bolts
Page 12
11
Fig. 5
OKCE 50, OKCE 80, OKCE 100, OKCE 125, OKCE 160, OKCE 180, OKCE 200
Fig. 6
05-2011
Type
OKCE 50
OKCE 80
OKCE 100
OKCE 125
OKCE 160
OKCE 180
OKCE 200
A
561
736
881
1046
1235
1187
1287
B*
556
731
876
1041
1230
1182
1282
C
448
615
765
765
1005
793
793
D
524
524
524
524
524
584
584
E - - - -
720
600
600
*Distance from the upper heater's edge to the end of the water inlet and outlet tubes.
Upper and lower hinge 160,180, 200L 4 anchor bolts Dimensions 450mm and E Check before drilling
Upper hinge and support 50-125L 2 anchor bolts
Loading...