Dražice OKC 500 NTR/1MPa, OKC 300 NTRR/1MPa, OKC 400 NTRR/1MPa, OKC 400 NTR/1MPa, OKC 500 NTRR/1MPa Operation And Installation Manual

...
OPERATION AND
INSTALLATION MANUAL
INDIRECT WATER HEATERS
OKC 300 NTR/1MPa OKC 300 NTRR/1MPa
OKC 400 NTR/1MPa OKC 400 NTRR/1MPa OKC 500 NTR/1MPa OKC 500 NTRR/1MPa OKC 750 NTR/1MPa OKC 750 NTRR/1MPa OKC 1000 NTR/1MPa OKC 1000 NTRR/1MPa
Družstevní závody Dražice - strojírna s.r.o.
Dražice 69, 294 71 Benátky nad Jizerou tel.: +420 / 326 370 990 fax: +420 / 326 370 980 e-mail: prodej@dzd.cz
- 2 -
CONTENT
1 TECHNICAL SPECIFICATION OF PRODUCT ................................................................................................. 4
1.1 FUNCTION DESCRIPTION ................................................................................................................... 4
1.2 PRODUCT DESCRIPTION .................................................................................................................... 4
1.3 TECHNICAL PARAMETERS .................................................................................................................. 5
1.3.1 TECHNICAL PARAMETERS OF HEATERS WITH ONE EXCHANGER .............................................. 5
1.3.2 TECHNICAL PARAMETERS OF HEATERS WITH TWO EXCHANGERS ........................................... 6
1.3.3 PERFORMANCE DATA ................................................................................................................ 7
1.3.4 PRESSURE LOSSES ...................................................................................................................... 9
1.4 CONSTRUCTION AND GENERAL HEATER DIMENSIONS ................................................................... 10
2 OPERATION AND FITTING INSTRUCTION ................................................................................................. 15
2.1 OPERATING CONDITIONS ................................................................................................................ 15
2.2 CONNECTING A HEATER TO A HOT WATER DISTRIBUTION ............................................................ 15
2.3 PLUMBING FIXTURE ......................................................................................................................... 16
2.4 CONNECTING A HEATER TO A HEATING SYSTEM ............................................................................ 17
2.5 PUTTING THE HEATER INTO OPERATION ........................................................................................ 18
2.6 PUTTING OUT OF SERVICE, DISCHARGE .......................................................................................... 19
2.7 INSPECTION, MAINTENANCE & CARE FOR THE APPLIANCE ............................................................ 20
2.8 SPARE PARTS.................................................................................................................................... 21
3 IMPORTANT NOTICES .............................................................................................................................. 21
3.1
INSTALLATION REGULATIONS.......................................................................................................... 21
3.2 DISPOSAL OF PACKAGING MATERIAL AND FUNCTIONLESS PRODUCT ........................................... 22
4 ASSEMBLY GUIDE FOR ZIP-FASTENER INSULATION (FOR 750 AND 1000 LITRES) ................................... 23
- 3 -
Meaning of pictograms used in Manual
Important information for heater users.
Recommendations of manufacturer, observance of which will ensure trouble-free
operation and long service life of the product.
CAUTION!
Important notice to be observed.
READ CAREFULLY THE BELOW INSTRUCTIONS PRIOR TO THE INSTALLATION
THE HEATER!
Dear Customer,
The Works Cooperative of Dražice – Machine Plant, Ltd., would
like to thank you for your decision to use a product of our
brand. With this guide, we will introduce you to the use, construction, maintenance and other information on electrical water heaters.
The manufacturer reserves the right for engineering modification of the product. The product is designed
for permanent contact with drinkable water.
It is recommended to use the product in indoor environment with air temperatures from +2°C to 45°C and a relative humidity up to 80%.
Product’s reliability and safety is proven by tests implemented by the Engineering Test Institute in Brno.
- 4 -
1 TECHNICAL SPECIFICATION OF PRODUCT
1.1 FUNCTION DESCRIPTION
Indirect stationary heaters lines NTR and NTRR are used for water heating in conjunction with another source of heating water, most often a gas boiler. The NTRR types combine two sources of heating water (gas boiler + a solar system or a heat pump). Their nominal performance provides sufficient amount of hot water for large flat units, premises, restaurants, and similar establishments.
In case of increased hot water consumption, these tanks heat water continuously, operating similarly to flow heaters.
1.2 PRODUCT DESCRIPTION
The heater tank is welded from a steel sheet; it is entirely coated with hot water resistant enamel. Magnesium anode is added in the vessel as an additional protection against corrosion, which regulates the electric potential of the inside of the vessel and thus reduces the effects of corrosion. Inside the tank, hot and cold water and circulation pipes; a thermostat well; and either one or two spiral steel pipe heat exchangers (enamelled on the outside) are all welded on.
The pipe heat exchanger is only intended for the heating circuit.
On the heater side, there is a cleaning and revision opening ending with a 110 mm flange; the clearance including eight M8 bolts is 150 mm – 300 to 500 litres, for 180 mm clearance the spacing of ten bolts is 225 mm – 750 to 1000 litres. A heating unit with various output containing an operating and safety thermostat can be mounted in the opening. The NTR series heaters are equipped with a G 1 1/2“ aperture for in­screwing an additional heating element. Such version is used when the heater is connected to either a solar system or a system with a heat pump, to heat water in the upper part of the heater to the temperature required. The tank is insulated with 50-80 mm of polyurethane freon-free foam. The tank shell is made of a steel sheet painted with a powder coating (the 400-500 l types only, other are in plastic), and the connecting parts are metal-coated.
- 5 -
1.3 TECHNICAL PARAMETERS
1.3.1 TECHNICAL PARAMETERS OF HEATERS WITH ONE EXCHANGER
TYPE
OKC 300
NTR/1MPa
OKC 400
NTR/1MPa
OKC 500
NTR/1MPa
OKC 750
NTR/1MPa
OKC 1000
NTR/1MPa
Tank capacity
l
300
385
485
750
975
Diameter
mm
670
700
700
910
1010
Weight
kg
108
123
173
253
337
Operating hot service
water pressure
MPa 1 1 1 1 1
Operating heating
water pressure
MPa 1,6 1,6 1,6 1,6 1,6
Max temperature of
heating water
°C 110 110 110 110 110
Max temperature of
hot service water
°C 95 95 95 95 95
Exchanger heat
surface
m2 1,5 1,8 1,9 3,7 4,5
Exchanger
performance at temperature drop 80/60 °C
kW 35 57 65 99 110
Performance number
according to DIN 4708
NL 8 15,2 19,1 30,5 38,8
Permanent HSW*
performance
l/h 1100 1395 1590 2440 2715
HSW* heating time
by exchanger at temperature drop 80/60 °C
min 24 20 23 24 26
* HSW – Hot service water 45 °C
Table 1
- 6 -
1.3.2 TECHNICAL PARAMETERS OF HEATERS WITH TWO EXCHANGERS
TYPE
OKC 300
NTRR/1MPa
OKC 400
NTRR/1MPa
OKC 500
NTRR/1MPa
OKC 750
NTRR/1MPa
OKC 1000
NTRR/1MPa
Tank capacity
l
295
380
470
750
995
Diameter
mm
670
700
700
910
1010
Weight
kg
124
144
183
245
315
Operating hot service
water pressure
MPa 1 1 1 1 1
Operating heating
water pressure
MPa 1,6 1,6 1,6 1,6 1,6
Max temperature of
heating water
°C 110 110 110 110 110
Max temperature of
hot service water
°C 95 95 95 95 95
Upper exchanger
heat surface
m2 1 1,05 1,3 1,17 1,12
Lower exchanger
heat surface
m2 1,5 1,8 1,9 1,93 2,45
Lower/upper
exchanger performance at temperature drop 80/60 °C
kW 35/27 57/31 65/40 60/33 76/32
Performance number
according to DIN 4708 upper exchanger
NL 2,9 3,4 5,9 6,2 7,1
Performance number
according to DIN 4708 lower exchanger
NL 4,2 15,2 19,1 21 26
Permanent HSW
performance* of lower exchanger
l/h 1100 1395 1590 1460 1490
Permanent HSW
performance* of upper exchanger
l/h 670 740 970 815 780
HSW* heating time by exchanger at temperature drop 80/60 °C
(lower/upper)
min 24/16 20/14 23/16 37/28 43/37
*HSW – Hot service water 45 °C
Table 2
- 7 -
cwt = 10°C
cwt =10°C hwt = 45°C
mth= 50°C mth = 60°C mth = 50°C mth = 60°C
UE LE UE LE °C - - - - l/h kW l/h kW l/h kW l/h kW l/10min l/10min m3/h 50 1,1 1,8 - - 431 17,1 259 10,4 - - - - 111 ­60 1,3 2,2 1,6 2,6 594 24 348 14,1 446 18 261 10,6 127 152 70 1,7 2,7 2 3,3 818 33,6 468 19,1 614 25,2 351 14,3 145 174 80 2,1 3,4 2,5 4,1 1086 44,2 629 25,9 815 33,2 472 19,4 166 199 90 2,7 4,4 3,2 5,3 1299 52,6 757 30,6 974 39,5 568 23 161 217 50 3,2 5,3 - - 493 19,6 305 12,2 - - - - 221 -
60 3,7 6 4,4 7,2 679 27,4 410 16,6 509 20,6 308 12,4 243 292 70 4,2 6,9 5 8,2 935 38,4 551 22,5 701 28,8 413 16,9 268 321 80 4,8 7,8 5,7 9,4 1241 50,5 740 30,5 931 37,9 555 22,9 294 353 90 5,8 9,6 7 11,5 1485 60,1 891 26 1114 45,1 668 19,5 316 379 50 3,8 6,2 - - 583 23,5 395 15,9 - - - - 332 ­60 4,7 7,8 5,7 9,3 790 32 531 21,5 593 24 399 16,1 360 432
70 5,9 9,7 7,1 11,7 1070 43,5 715 29,2 803 32,6 536 21,9 390 468 80 7,4 12,2 8,9 14,7 1430 58 962 39,6 1073 43,5 722 29,7 423 507
90 9 14,8 10,8 17,8 1720 70 1157 46,8 1290 52,5 868 35,1 450 540
2,7/2,7
3,0/3,0
3,0/3,0
Heating
water flow
Flow in 10 minutes
NL Power Factor
at
Permanent hot water output
Inlet
heating
water
temperatu
re
Type
LE
UE
OKC 300 NTRR/1MP a
OKC 400 NTRR/1MP a
OKC 500 NTRR/1MP a
cwt = 10°C
hwt = 45°C
hwt = 60°C
LE
UE
hwt = 45°C
cwt = 10°C
hwt = 45°C cwt =10°C hwt = 45°C
mth = 50°C mth = 60°C mth = 50°C mth = 60°C
°C - - l/h kW l/h kW l/10min l/10min m3/h 60 4,3 - 617 25,1 - - 290 ­70 5,3 8,4 888 36,1 622 26,8 322 403 80 5,3 8,4 1100 47,4 816 39,8 358 448 90 5,3 8,4 1451 59 1015 52,5 398 497 60 6,8 - 738 29,9 - - 399 ­70 10,1 12,8 990 43,2 745 32,1 443 554 80 10,1 15,2 1394 56,7 976 47,6 492 615 90 10,1 15,2 1733 70,4 1212 62,7 547 684 60 11,3 - 842 34,2 - - 500 ­70 15,2 15,8 1210 49,2 847 36,7 556 694 80 15,2 19,1 1584 64,4 1109 54,2 617 771 90 15,2 19,1 1965 79,9 1376 71,2 686 858 60 12,9 - 1279 52 - - 817 -
70 15,4 25,6 1828 74 1364 56 848 1060 80 18,3 30,5 2437 99 2065 84 880 1100
90 21 35 3046 124 2719 111 928 1160 60 16,6 - 1424 58 - - 862 -
70 19,7 32,8 2034 83 1518 62 908 1135 80 23,3 38,8 2712 110 2298 94 957 1197 90 27 45 3390 138 3026 123 1003 1254
OKC 400 NTR/1MPa
OKC 500 NTR/1MPa
OKC 750 NTR/1MPa
OKC 1000 NTR/1MPa
Type
OKC 300 NTR/1MPa
Inlet
heating
water
temperatur
e
NL Pow er Factor
at
Permanent hot water output
Flow in 10 minutes
Heating
water flow
hwt = 45°C
hwt = 60°C
cwt = 10°C
3
5
6
2,7
3
1.3.3 PERFORMANCE DATA
Table 3
UE – upper exchanger
LE– lower exchanger
cwt – cold water temperature
hwt – hot water temperature mth – medium temperature of the
heater
Table 4
UE – upper exchanger
LE – lower exchanger
cwt – cold water temperature
hwt – hot water temperature mth – medium temperature of the
heater