OPERATION AND
INSTALLATION MANUAL
INDIRECT WATER HEATERS
OKC 300 NTR/1MPa OKC 300 NTRR/1MPa
OKC 400 NTR/1MPa OKC 400 NTRR/1MPa
OKC 500 NTR/1MPa OKC 500 NTRR/1MPa
OKC 750 NTR/1MPa OKC 750 NTRR/1MPa
OKC 1000 NTR/1MPa OKC 1000 NTRR/1MPa
Družstevní závody Dražice - strojírna s.r.o.
Dražice 69, 294 71 Benátky nad Jizerou
tel.: +420 / 326 370 990
fax: +420 / 326 370 980
e-mail: prodej@dzd.cz

- 2 -
CONTENT
1 TECHNICAL SPECIFICATION OF PRODUCT ................................................................................................. 4
1.1 FUNCTION DESCRIPTION ................................................................................................................... 4
1.2 PRODUCT DESCRIPTION .................................................................................................................... 4
1.3 TECHNICAL PARAMETERS .................................................................................................................. 5
1.3.1 TECHNICAL PARAMETERS OF HEATERS WITH ONE EXCHANGER .............................................. 5
1.3.2 TECHNICAL PARAMETERS OF HEATERS WITH TWO EXCHANGERS ........................................... 6
1.3.3 PERFORMANCE DATA ................................................................................................................ 7
1.3.4 PRESSURE LOSSES ...................................................................................................................... 9
1.4 CONSTRUCTION AND GENERAL HEATER DIMENSIONS ................................................................... 10
2 OPERATION AND FITTING INSTRUCTION ................................................................................................. 15
2.1 OPERATING CONDITIONS ................................................................................................................ 15
2.2 CONNECTING A HEATER TO A HOT WATER DISTRIBUTION ............................................................ 15
2.3 PLUMBING FIXTURE ......................................................................................................................... 16
2.4 CONNECTING A HEATER TO A HEATING SYSTEM ............................................................................ 17
2.5 PUTTING THE HEATER INTO OPERATION ........................................................................................ 18
2.6 PUTTING OUT OF SERVICE, DISCHARGE .......................................................................................... 19
2.7 INSPECTION, MAINTENANCE & CARE FOR THE APPLIANCE ............................................................ 20
2.8 SPARE PARTS.................................................................................................................................... 21
3 IMPORTANT NOTICES .............................................................................................................................. 21
3.1
INSTALLATION REGULATIONS.......................................................................................................... 21
3.2 DISPOSAL OF PACKAGING MATERIAL AND FUNCTIONLESS PRODUCT ........................................... 22
4 ASSEMBLY GUIDE FOR ZIP-FASTENER INSULATION (FOR 750 AND 1000 LITRES) ................................... 23

- 3 -
Meaning of pictograms used in Manual
Important information for heater users.
Recommendations of manufacturer, observance of which will ensure trouble-free
operation and long service life of the product.
Important notice to be observed.
READ CAREFULLY THE BELOW INSTRUCTIONS PRIOR TO THE INSTALLATION
THE HEATER!
Dear Customer,
The Works Cooperative of Dražice – Machine Plant, Ltd., would
like to thank you for your decision to use a product of our
brand. With this guide, we will introduce you to the use,
construction, maintenance and other information on electrical
water heaters.
The manufacturer reserves the right for engineering modification of the product. The product is designed
for permanent contact with drinkable water.
It is recommended to use the product in indoor environment with air temperatures from +2°C to 45°C
and a relative humidity up to 80%.
Product’s reliability and safety is proven by tests implemented by the Engineering Test Institute in Brno.

- 4 -
1 TECHNICAL SPECIFICATION OF PRODUCT
1.1 FUNCTION DESCRIPTION
Indirect stationary heaters lines NTR and NTRR are used for water heating in conjunction with another
source of heating water, most often a gas boiler. The NTRR types combine two sources of heating water
(gas boiler + a solar system or a heat pump). Their nominal performance provides sufficient amount of hot
water for large flat units, premises, restaurants, and similar establishments.
In case of increased hot water consumption, these tanks heat water continuously, operating similarly to
flow heaters.
1.2 PRODUCT DESCRIPTION
The heater tank is welded from a steel sheet; it is entirely coated with hot water resistant enamel.
Magnesium anode is added in the vessel as an additional protection against corrosion, which regulates the
electric potential of the inside of the vessel and thus reduces the effects of corrosion. Inside the tank, hot
and cold water and circulation pipes; a thermostat well; and either one or two spiral steel pipe heat
exchangers (enamelled on the outside) are all welded on.
The pipe heat exchanger is only intended for the heating circuit.
On the heater side, there is a cleaning and revision opening ending with a 110 mm flange; the clearance
including eight M8 bolts is 150 mm – 300 to 500 litres, for 180 mm clearance the spacing of ten bolts is 225
mm – 750 to 1000 litres. A heating unit with various output containing an operating and safety thermostat
can be mounted in the opening. The NTR series heaters are equipped with a G 1 1/2“ aperture for inscrewing an additional heating element. Such version is used when the heater is connected to either a solar
system or a system with a heat pump, to heat water in the upper part of the heater to the temperature
required. The tank is insulated with 50-80 mm of polyurethane freon-free foam. The tank shell is made of a
steel sheet painted with a powder coating (the 400-500 l types only, other are in plastic), and the
connecting parts are metal-coated.

- 5 -
1.3 TECHNICAL PARAMETERS
1.3.1 TECHNICAL PARAMETERS OF HEATERS WITH ONE EXCHANGER
TYPE
water pressure
MPa 1 1 1 1 1
water pressure
MPa 1,6 1,6 1,6 1,6 1,6
heating water
°C 110 110 110 110 110
hot service water
°C 95 95 95 95 95
surface
m2 1,5 1,8 1,9 3,7 4,5
performance at
temperature drop
80/60 °C
kW 35 57 65 99 110
according to DIN 4708
NL 8 15,2 19,1 30,5 38,8
performance
l/h 1100 1395 1590 2440 2715
by exchanger at
temperature drop
80/60 °C
min 24 20 23 24 26
* HSW – Hot service water 45 °C
Table 1

- 6 -
1.3.2 TECHNICAL PARAMETERS OF HEATERS WITH TWO EXCHANGERS
TYPE
water pressure
MPa 1 1 1 1 1
water pressure
MPa 1,6 1,6 1,6 1,6 1,6
heating water
°C 110 110 110 110 110
hot service water
°C 95 95 95 95 95
heat surface
m2 1 1,05 1,3 1,17 1,12
heat surface
m2 1,5 1,8 1,9 1,93 2,45
exchanger
performance at
temperature drop
80/60 °C
kW 35/27 57/31 65/40 60/33 76/32
according to DIN
4708 upper
exchanger
NL 2,9 3,4 5,9 6,2 7,1
according to DIN
4708 lower
exchanger
NL 4,2 15,2 19,1 21 26
performance* of
lower exchanger
l/h 1100 1395 1590 1460 1490
performance* of
upper exchanger
l/h 670 740 970 815 780
HSW* heating time by
exchanger at
temperature drop
80/60 °C
(lower/upper)
min 24/16 20/14 23/16 37/28 43/37
*HSW – Hot service water 45 °C
Table 2

cwt = 10°C
cwt =10°C hwt = 45°C
mth= 50°C mth = 60°C mth = 50°C mth = 60°C
UE LE UE LE
°C - - - - l/h kW l/h kW l/h kW l/h kW l/10min l/10min m3/h
50 1,1 1,8 - - 431 17,1 259 10,4 - - - - 111 60 1,3 2,2 1,6 2,6 594 24 348 14,1 446 18 261 10,6 127 152
70 1,7 2,7 2 3,3 818 33,6 468 19,1 614 25,2 351 14,3 145 174
80 2,1 3,4 2,5 4,1 1086 44,2 629 25,9 815 33,2 472 19,4 166 199
90 2,7 4,4 3,2 5,3 1299 52,6 757 30,6 974 39,5 568 23 161 217
50 3,2 5,3 - - 493 19,6 305 12,2 - - - - 221 -
60 3,7 6 4,4 7,2 679 27,4 410 16,6 509 20,6 308 12,4 243 292
70 4,2 6,9 5 8,2 935 38,4 551 22,5 701 28,8 413 16,9 268 321
80 4,8 7,8 5,7 9,4 1241 50,5 740 30,5 931 37,9 555 22,9 294 353
90 5,8 9,6 7 11,5 1485 60,1 891 26 1114 45,1 668 19,5 316 379
50 3,8 6,2 - - 583 23,5 395 15,9 - - - - 332 60 4,7 7,8 5,7 9,3 790 32 531 21,5 593 24 399 16,1 360 432
70 5,9 9,7 7,1 11,7 1070 43,5 715 29,2 803 32,6 536 21,9 390 468
80 7,4 12,2 8,9 14,7 1430 58 962 39,6 1073 43,5 722 29,7 423 507
90 9 14,8 10,8 17,8 1720 70 1157 46,8 1290 52,5 868 35,1 450 540
Permanent hot water output
Inlet
heating
water
temperatu
re
cwt = 10°C
hwt = 45°C cwt =10°C hwt = 45°C
mth = 50°C mth = 60°C mth = 50°C mth = 60°C
°C - - l/h kW l/h kW l/10min l/10min m3/h
60 4,3 - 617 25,1 - - 290 70 5,3 8,4 888 36,1 622 26,8 322 403
80 5,3 8,4 1100 47,4 816 39,8 358 448
90 5,3 8,4 1451 59 1015 52,5 398 497
60 6,8 - 738 29,9 - - 399 70 10,1 12,8 990 43,2 745 32,1 443 554
80 10,1 15,2 1394 56,7 976 47,6 492 615
90 10,1 15,2 1733 70,4 1212 62,7 547 684
60 11,3 - 842 34,2 - - 500 70 15,2 15,8 1210 49,2 847 36,7 556 694
80 15,2 19,1 1584 64,4 1109 54,2 617 771
90 15,2 19,1 1965 79,9 1376 71,2 686 858
60 12,9 - 1279 52 - - 817 -
70 15,4 25,6 1828 74 1364 56 848 1060
80 18,3 30,5 2437 99 2065 84 880 1100
90 21 35 3046 124 2719 111 928 1160
60 16,6 - 1424 58 - - 862 -
70 19,7 32,8 2034 83 1518 62 908 1135
80 23,3 38,8 2712 110 2298 94 957 1197
90 27 45 3390 138 3026 123 1003 1254
Inlet
heating
water
temperatur
e
Permanent hot water output
1.3.3 PERFORMANCE DATA
Table 3
cwt – cold water temperature
hwt – hot water temperature
mth – medium temperature of the
cwt – cold water temperature
hwt – hot water temperature
mth – medium temperature of the