Dražice OKC 500 NTR/1MPa, OKC 300 NTRR/1MPa, OKC 400 NTRR/1MPa, OKC 400 NTR/1MPa, OKC 500 NTRR/1MPa Operation And Installation Manual

...
Page 1
OPERATION AND
INSTALLATION MANUAL
INDIRECT WATER HEATERS
OKC 300 NTR/1MPa OKC 300 NTRR/1MPa
OKC 400 NTR/1MPa OKC 400 NTRR/1MPa OKC 500 NTR/1MPa OKC 500 NTRR/1MPa OKC 750 NTR/1MPa OKC 750 NTRR/1MPa OKC 1000 NTR/1MPa OKC 1000 NTRR/1MPa
Družstevní závody Dražice - strojírna s.r.o.
Dražice 69, 294 71 Benátky nad Jizerou tel.: +420 / 326 370 990 fax: +420 / 326 370 980 e-mail: prodej@dzd.cz
Page 2
- 2 -
CONTENT
1 TECHNICAL SPECIFICATION OF PRODUCT ................................................................................................. 4
1.1 FUNCTION DESCRIPTION ................................................................................................................... 4
1.2 PRODUCT DESCRIPTION .................................................................................................................... 4
1.3 TECHNICAL PARAMETERS .................................................................................................................. 5
1.3.1 TECHNICAL PARAMETERS OF HEATERS WITH ONE EXCHANGER .............................................. 5
1.3.2 TECHNICAL PARAMETERS OF HEATERS WITH TWO EXCHANGERS ........................................... 6
1.3.3 PERFORMANCE DATA ................................................................................................................ 7
1.3.4 PRESSURE LOSSES ...................................................................................................................... 9
1.4 CONSTRUCTION AND GENERAL HEATER DIMENSIONS ................................................................... 10
2 OPERATION AND FITTING INSTRUCTION ................................................................................................. 15
2.1 OPERATING CONDITIONS ................................................................................................................ 15
2.2 CONNECTING A HEATER TO A HOT WATER DISTRIBUTION ............................................................ 15
2.3 PLUMBING FIXTURE ......................................................................................................................... 16
2.4 CONNECTING A HEATER TO A HEATING SYSTEM ............................................................................ 17
2.5 PUTTING THE HEATER INTO OPERATION ........................................................................................ 18
2.6 PUTTING OUT OF SERVICE, DISCHARGE .......................................................................................... 19
2.7 INSPECTION, MAINTENANCE & CARE FOR THE APPLIANCE ............................................................ 20
2.8 SPARE PARTS.................................................................................................................................... 21
3 IMPORTANT NOTICES .............................................................................................................................. 21
3.1
INSTALLATION REGULATIONS.......................................................................................................... 21
3.2 DISPOSAL OF PACKAGING MATERIAL AND FUNCTIONLESS PRODUCT ........................................... 22
4 ASSEMBLY GUIDE FOR ZIP-FASTENER INSULATION (FOR 750 AND 1000 LITRES) ................................... 23
Page 3
- 3 -
Meaning of pictograms used in Manual
Important information for heater users.
Recommendations of manufacturer, observance of which will ensure trouble-free
operation and long service life of the product.
CAUTION!
Important notice to be observed.
READ CAREFULLY THE BELOW INSTRUCTIONS PRIOR TO THE INSTALLATION
THE HEATER!
Dear Customer,
The Works Cooperative of Dražice – Machine Plant, Ltd., would
like to thank you for your decision to use a product of our
brand. With this guide, we will introduce you to the use, construction, maintenance and other information on electrical water heaters.
The manufacturer reserves the right for engineering modification of the product. The product is designed
for permanent contact with drinkable water.
It is recommended to use the product in indoor environment with air temperatures from +2°C to 45°C and a relative humidity up to 80%.
Product’s reliability and safety is proven by tests implemented by the Engineering Test Institute in Brno.
Page 4
- 4 -
1 TECHNICAL SPECIFICATION OF PRODUCT
1.1 FUNCTION DESCRIPTION
Indirect stationary heaters lines NTR and NTRR are used for water heating in conjunction with another source of heating water, most often a gas boiler. The NTRR types combine two sources of heating water (gas boiler + a solar system or a heat pump). Their nominal performance provides sufficient amount of hot water for large flat units, premises, restaurants, and similar establishments.
In case of increased hot water consumption, these tanks heat water continuously, operating similarly to flow heaters.
1.2 PRODUCT DESCRIPTION
The heater tank is welded from a steel sheet; it is entirely coated with hot water resistant enamel. Magnesium anode is added in the vessel as an additional protection against corrosion, which regulates the electric potential of the inside of the vessel and thus reduces the effects of corrosion. Inside the tank, hot and cold water and circulation pipes; a thermostat well; and either one or two spiral steel pipe heat exchangers (enamelled on the outside) are all welded on.
The pipe heat exchanger is only intended for the heating circuit.
On the heater side, there is a cleaning and revision opening ending with a 110 mm flange; the clearance including eight M8 bolts is 150 mm – 300 to 500 litres, for 180 mm clearance the spacing of ten bolts is 225 mm – 750 to 1000 litres. A heating unit with various output containing an operating and safety thermostat can be mounted in the opening. The NTR series heaters are equipped with a G 1 1/2“ aperture for in­screwing an additional heating element. Such version is used when the heater is connected to either a solar system or a system with a heat pump, to heat water in the upper part of the heater to the temperature required. The tank is insulated with 50-80 mm of polyurethane freon-free foam. The tank shell is made of a steel sheet painted with a powder coating (the 400-500 l types only, other are in plastic), and the connecting parts are metal-coated.
Page 5
- 5 -
1.3 TECHNICAL PARAMETERS
1.3.1 TECHNICAL PARAMETERS OF HEATERS WITH ONE EXCHANGER
TYPE
OKC 300
NTR/1MPa
OKC 400
NTR/1MPa
OKC 500
NTR/1MPa
OKC 750
NTR/1MPa
OKC 1000
NTR/1MPa
Tank capacity
l
300
385
485
750
975
Diameter
mm
670
700
700
910
1010
Weight
kg
108
123
173
253
337
Operating hot service
water pressure
MPa 1 1 1 1 1
Operating heating
water pressure
MPa 1,6 1,6 1,6 1,6 1,6
Max temperature of
heating water
°C 110 110 110 110 110
Max temperature of
hot service water
°C 95 95 95 95 95
Exchanger heat
surface
m2 1,5 1,8 1,9 3,7 4,5
Exchanger
performance at temperature drop 80/60 °C
kW 35 57 65 99 110
Performance number
according to DIN 4708
NL 8 15,2 19,1 30,5 38,8
Permanent HSW*
performance
l/h 1100 1395 1590 2440 2715
HSW* heating time
by exchanger at temperature drop 80/60 °C
min 24 20 23 24 26
* HSW – Hot service water 45 °C
Table 1
Page 6
- 6 -
1.3.2 TECHNICAL PARAMETERS OF HEATERS WITH TWO EXCHANGERS
TYPE
OKC 300
NTRR/1MPa
OKC 400
NTRR/1MPa
OKC 500
NTRR/1MPa
OKC 750
NTRR/1MPa
OKC 1000
NTRR/1MPa
Tank capacity
l
295
380
470
750
995
Diameter
mm
670
700
700
910
1010
Weight
kg
124
144
183
245
315
Operating hot service
water pressure
MPa 1 1 1 1 1
Operating heating
water pressure
MPa 1,6 1,6 1,6 1,6 1,6
Max temperature of
heating water
°C 110 110 110 110 110
Max temperature of
hot service water
°C 95 95 95 95 95
Upper exchanger
heat surface
m2 1 1,05 1,3 1,17 1,12
Lower exchanger
heat surface
m2 1,5 1,8 1,9 1,93 2,45
Lower/upper
exchanger performance at temperature drop 80/60 °C
kW 35/27 57/31 65/40 60/33 76/32
Performance number
according to DIN 4708 upper exchanger
NL 2,9 3,4 5,9 6,2 7,1
Performance number
according to DIN 4708 lower exchanger
NL 4,2 15,2 19,1 21 26
Permanent HSW
performance* of lower exchanger
l/h 1100 1395 1590 1460 1490
Permanent HSW
performance* of upper exchanger
l/h 670 740 970 815 780
HSW* heating time by exchanger at temperature drop 80/60 °C
(lower/upper)
min 24/16 20/14 23/16 37/28 43/37
*HSW – Hot service water 45 °C
Table 2
Page 7
- 7 -
cwt = 10°C
cwt =10°C hwt = 45°C
mth= 50°C mth = 60°C mth = 50°C mth = 60°C
UE LE UE LE °C - - - - l/h kW l/h kW l/h kW l/h kW l/10min l/10min m3/h 50 1,1 1,8 - - 431 17,1 259 10,4 - - - - 111 ­60 1,3 2,2 1,6 2,6 594 24 348 14,1 446 18 261 10,6 127 152 70 1,7 2,7 2 3,3 818 33,6 468 19,1 614 25,2 351 14,3 145 174 80 2,1 3,4 2,5 4,1 1086 44,2 629 25,9 815 33,2 472 19,4 166 199 90 2,7 4,4 3,2 5,3 1299 52,6 757 30,6 974 39,5 568 23 161 217 50 3,2 5,3 - - 493 19,6 305 12,2 - - - - 221 -
60 3,7 6 4,4 7,2 679 27,4 410 16,6 509 20,6 308 12,4 243 292 70 4,2 6,9 5 8,2 935 38,4 551 22,5 701 28,8 413 16,9 268 321 80 4,8 7,8 5,7 9,4 1241 50,5 740 30,5 931 37,9 555 22,9 294 353 90 5,8 9,6 7 11,5 1485 60,1 891 26 1114 45,1 668 19,5 316 379 50 3,8 6,2 - - 583 23,5 395 15,9 - - - - 332 ­60 4,7 7,8 5,7 9,3 790 32 531 21,5 593 24 399 16,1 360 432
70 5,9 9,7 7,1 11,7 1070 43,5 715 29,2 803 32,6 536 21,9 390 468 80 7,4 12,2 8,9 14,7 1430 58 962 39,6 1073 43,5 722 29,7 423 507
90 9 14,8 10,8 17,8 1720 70 1157 46,8 1290 52,5 868 35,1 450 540
2,7/2,7
3,0/3,0
3,0/3,0
Heating
water flow
Flow in 10 minutes
NL Power Factor
at
Permanent hot water output
Inlet
heating
water
temperatu
re
Type
LE
UE
OKC 300 NTRR/1MP a
OKC 400 NTRR/1MP a
OKC 500 NTRR/1MP a
cwt = 10°C
hwt = 45°C
hwt = 60°C
LE
UE
hwt = 45°C
cwt = 10°C
hwt = 45°C cwt =10°C hwt = 45°C
mth = 50°C mth = 60°C mth = 50°C mth = 60°C
°C - - l/h kW l/h kW l/10min l/10min m3/h 60 4,3 - 617 25,1 - - 290 ­70 5,3 8,4 888 36,1 622 26,8 322 403 80 5,3 8,4 1100 47,4 816 39,8 358 448 90 5,3 8,4 1451 59 1015 52,5 398 497 60 6,8 - 738 29,9 - - 399 ­70 10,1 12,8 990 43,2 745 32,1 443 554 80 10,1 15,2 1394 56,7 976 47,6 492 615 90 10,1 15,2 1733 70,4 1212 62,7 547 684 60 11,3 - 842 34,2 - - 500 ­70 15,2 15,8 1210 49,2 847 36,7 556 694 80 15,2 19,1 1584 64,4 1109 54,2 617 771 90 15,2 19,1 1965 79,9 1376 71,2 686 858 60 12,9 - 1279 52 - - 817 -
70 15,4 25,6 1828 74 1364 56 848 1060 80 18,3 30,5 2437 99 2065 84 880 1100
90 21 35 3046 124 2719 111 928 1160 60 16,6 - 1424 58 - - 862 -
70 19,7 32,8 2034 83 1518 62 908 1135 80 23,3 38,8 2712 110 2298 94 957 1197 90 27 45 3390 138 3026 123 1003 1254
OKC 400 NTR/1MPa
OKC 500 NTR/1MPa
OKC 750 NTR/1MPa
OKC 1000 NTR/1MPa
Type
OKC 300 NTR/1MPa
Inlet
heating
water
temperatur
e
NL Pow er Factor
at
Permanent hot water output
Flow in 10 minutes
Heating
water flow
hwt = 45°C
hwt = 60°C
cwt = 10°C
3
5
6
2,7
3
1.3.3 PERFORMANCE DATA
Table 3
UE – upper exchanger
LE– lower exchanger
cwt – cold water temperature
hwt – hot water temperature mth – medium temperature of the
heater
Table 4
UE – upper exchanger
LE – lower exchanger
cwt – cold water temperature
hwt – hot water temperature mth – medium temperature of the
heater
Page 8
- 8 -
NL Power Factor
Based on DIN, the expression of a normal flat is introduced for apartment houses in the FRG. Such a flat has four rooms; it is occupied by 3.5 people; it has a bathtub, a hand basin, and a sink. Flats of other sizes, number of occupants and different equipment are converted to normal flats using the relations given in the standard (NL). The situation in our apartment houses, massively built until the recent past, is similar.
Flats intended for 3 to 4 people are equipped identically with normal German flats. Smaller flats tend to have smaller bathtub or a shower; larger, so-called two-generation flats tend to have an extra hand basin. Apartment buildings with luxury flats and high standard equipment, with higher number of fittings, or fittings equipped with high standard drain armatures, both hot water and heat energy needs must be adjusted.
Page 9
- 9 -
1.3.4 PRESSURE LOSSES
Page 10
- 10 -
1.4 CONSTRUCTION AND GENERAL HEATER DIMENSIONS
OKC 300 NTR/1MPa
Figure 1
OKC 300 NTRR/1MPa
Figure 2
Page 11
- 11 -
OKC 400 NTR/1MPa, OKC 500 NTR/1MPa
Figure 3
OKC 400 NTR
/1MPa
OKC 500 NTR
/1MPa
A
1591
1921 B 1523 1853 C 1111 1264
D1
597 597
D2 700 700
E 909 965 F
684 695 G 957 1040 H 369 388
Page 12
- 12 -
OKC 400 NTRR/1MPa, OKC 500 NTRR/1MPa
Figure 4
OKC 400 NTRR
/1MPa
OKC 500 NTRR
/1MPa
A 1631
1961
B
957 1040
C 275
275
D1
597 597
D2 700
700
E 1523 1853
F 1354 1604
G 1223 1409
H 1111 1264
I 1006 1114
J 909 965
K 369 380
L 220 220
M 55 55
N 25 25
Page 13
- 13 -
OKC 750 NTR/1MPa, OKC 1000 NTR/1MPa
Figure 5
OKC 750 NTR/
1MPa
OKC 1000 NTR
/1MPa
A 1998 2025
B 1887 1905
C 1417 1490
D1 750 850
D2 910 1010
E 1314 1324
F 1079 1087
G 288 295
H 99 103
I 1643 1672
J 1005 1025
K 375 385
Page 14
- 14 -
OKC 750 NTRR/1MPa, OKC 1000 NTRR/1MPa
Figure 6
OKC 750 NTRR/
1MPa
OKC 1000 NTRR/
1MPa
A 1998
2025
B
1005
1025
C 378 387
D1 750 850
D2 910
1010
E
1887 1905
F 1467
1423
G
1375 1375
H 1242 1243
I
1151 1153
J 830 884
K 402 411
L 297 297
M 99 103
N 55 45
O
1643 1672
Page 15
- 15 -
Hot water outlet
Circulation
Heating water inlet
Thermostat chamber
Heating water outlet
Cold water i nlet
Hot water outlet Heating water inlet Thermostat chamber Circulation Heating water outlet Heating water inlet
Thermostat chamber Heating water outlet Cold water i nlet
2 OPERATION AND FITTING INSTRUCTION
2.1 OPERATING CONDITIONS
The tank shall only be used in accordance with the conditions specified on the power plate
and in instructions for electric wiring. Besides legally acknowledged national regulations and standards, also conditions for connection defined in local electric and water works have to be adhered to, as well as the installation and operation manual.
The temperature at the place of heater installation must be higher than +2°C; and the room must not freeze. The appliance has to be mounted at a convenient place; it means that the appliance must be easily available for potential necessary maintenance, repair or replacement, as the case may be.
2.2 CONNECTING A HEATER TO A HOT WATER DISTRIBUTION
Scheme of heater´s water inputs and outputs
OKC 300 NTR/1MPa, OKC 400 NTR/1MPa, OKC 300 NTRR/1MPa, OKC 400 NTRR/1MPa, OKC 500 NTR/1MPa OKC 500 NTRR/1MPa, OKC 750 NTR/1MPa, OKC 1000 NTR/1MPa OKC 750 NTRR/1MPa, OKC 1000 NTRR/1MPa
Figure 7
The heater’s cold water inlet must be fitted with T-fittings with a discharge valve for any
discharge of water from the heater.
On the hot water input, each individually closable heater must have a test cock,
backflow valve, safety valve, and a manometer.
Page 16
- 16 -
2.3 PLUMBING FIXTURE
Each hot service water pressure heater must have a membrane spring loaded with a safety
valve. Nominal clearance of safety valves is defined by standard. The safety valve must be easily accessible, as close to the heater as possible. The inlet pipes must have at least the same clearance as the safety valve. The safety valve is placed high enough to secure dripping water drain by gravity. We recommend mounting the safety valve onto a branch pipe. This allows easier exchange without having to drain the water from the heater. Safety valves with fixed pressure settings from the manufacturer are used for the assembly. Starting pressure of a safety valve must be identical to the maximum allowed heater pressure and at least 20 % higher than the maximum pressure in the water main (
Table 5). If the water main pressure exceeds such value, a reduction valve must be added to the system. . No stop valves can be put between the heater and the safety valve. During the assembly, follow the guide provided by the safety equipment manufacturer.
It is necessary to check the safety valve each time before putting it into operation. It is
checked by manual moving of the membrane from the seat, turning the make-and-break device button always in the direction of the arrow. After being turned, the button must click back into a notch. Proper function of the make-and-break device results in water draining through the safety valve outlet pipe. In common operation, such a check needs to be implemented at least once a month, and after each heater shutdown for more than 5 days. Water may be dripping off the drain pipe of the safety valve; the pipe must be open into the air, pointed down; environment temperatures must not drop below zero. When draining the heater, use the recommended drain valve. First, close the water supply into the heater.
Please find necessary pressure values in the below Table 5. For proper safety valve operation, a backflow valve must be mounted on the inlets pipes, preventing spontaneous heater draining and hot water penetrating back into the water main. We recommend that the hot water distribution from the heater was as short as possible to minimise heat losses. At least one demountable joint must be mounted between the tank and every supply pipe. Adequate piping and fittings with sufficiently dimensioned maximum temperature and pressure values must be used.
SAFETY VALVE
OPERATING
PRESSURE
[MPa]
ADMISSIBLE
OPERATING
WATER
HEATER
PRESSURE
[MPa]
MAX
PRESSURE IN
THE COLD
WATER PIPE
[MPa]
0,6
0,6
up to 0,48
0,7
0,7
up to 0,56
1
1
up to 0,8
Table 5
Page 17
- 17 -
2.4 CONNECTING A HEATER TO A HEATING SYSTEM
The heater is placed on the ground, next to the heating source, or in its vicinity. The heating circuit is connected to marked inputs and outputs of the heater exchanger; deaerating valve is mounted in the highest place. It is necessary to install a filter into the circuit in order to protect the pumps, the three-way valve, and backflow flaps, and the exchanger from sedimentation. It is recommended to flush the heating circuit before the assembly. All wiring connections must be properly insulated from heat. Should the system work with priority heating of hot service water using a three-way valve, always follow the installation instructions of the three-way valve’s manufacturer.
OKC 300-1000 NTR OKC 300-1000 NTRR
heated by a gas boiler with two pumps heated by a gas boiler and solar collectors controlled by a three-way valve
Figure 8 Figure 9
Page 18
- 18 -
An example of a group heater connection for steady hot service water consumption from all tanks using Tichelmann´s method
Figure 10
2.5 PUTTING THE HEATER INTO OPERATION
Before opening the power supply, the tank must be filled with water. The process of first
heating must be executed by licensed professional who has to check it. Both the hot water outlet pipe and safety armature parts may be hot.
During the heating process the pressurised connection water that increases its volume due
to heating must drip off the safety valve. In non-pressurised connection water drips off the overflow combination faucet. When heating is finished, the set temperature and the actual temperature of consumed water should be roughly equal. After connecting the heater to the water main and electrical power system, and after checking the safety valve (following the instructions attached to the valve), the heater can be put into operation.
Before fist putting into service or after a longer shutdown the appliance has to be rinsed out and flushed yet before heating is activated. Before heating starts, the tank must be
completely filled with water and the system properly flushed and vented. First heating of the
tank has to be watched.
C - Circulation
1 – Back-pressure valve
2 - Pump
Page 19
- 19 -
Procedure:
1. Check both water and electric installation; for combined heaters, check the installation to a hot
water heating system. Check proper placement of operating and safety thermostat sensors. The sensors must be inserted all the way in; first the operating and then the safety thermostat.
2. Open the hot water valve on the combination faucet.
3. Open the cold water inlet valve to the heater.
4. As soon as the water starts running through the hot water valve, the heater is filled and the valve
closes.
5. In case of a leakage (flange lid), we recommend fastening the flange lid bolts.
6. Fasten the electric installation cover.
7. In case of service water heating by electric energy, turn on the electricity (for combined heaters,
the heating water valve at the heating water entry to heating insert must be closed).
8. When heating service water with electric energy from the hot water heating system, turn the
electricity off and open the valves of heating water input and output, possibly de-aerate the exchanger.
9. When commencing operation, flush the heater until the cloudiness in the water is gone.
10. Make sure to fill in properly the warranty certificate.
2.6 PUTTING OUT OF SERVICE, DISCHARGE
If the hot water heater is put out of service for a longer time, or if it is not going to be used it
has to be drained and disconnected from the electric supply network on all poles. The switch for the supply lead or the fuse cut-outs have to be shut off.
At places with permanent risk of frost the hot water heater must be drained before the cold season starts if the appliance remains out of service for several days and if the power supply is disconnected.
Drainage of service water shall be performed after closing the shut-off valve in the cold
water supply piping (through the discharge valve for safety valve combination), and with
simultaneous opening of all hot water valves of connected fittings (water can be also drained
through safety valve; for that purpose, the safety valve is turned to the "Check" position). Hot water may outflow during the drainage! If there is a risk of frost it has to be considered that not only the water in the hot water heater and in the hot water piping may get frozen but also the water in the entire cold water supply piping. It is therefore advisable to drain all fittings and piping that carry water, up to the part where the house water meter is installed (connection of the house to water main) which is not jeopardised by frost. When the tank is put in service again, it has to be ensured that it is filled with water and the water flowing
out at the hot water valves is free of bubbles.
Page 20
- 20 -
2.7 INSPECTION, MAINTENANCE & CARE FOR THE APPLIANCE
During the heating process the water that increases its volume during the heating must
visibly drip off the safety valve outlet (in non-pressurised connection this water drips off the combination faucet valve). In full heating (about 74°C) the volumetric water gain is approx.
3.5 % of the tank capacity. The function of the safety valve has to be checked regularly. If the safety valve control knob is lifted or turned to the “Control” position, the water must flow out easily, without any obstacles, from the safety valve element to the outfall line. In common operation, such a check needs to be carried out at least once a month, and after each heater shutdown that exceeds 5 days.
Caution! In doing so, the cold water supply pipe and the connection fitting of the tank may get heated! If the hot water heater does not work, or if hot water is not withdrawn, no water shall drip off the safety valve. If water drips, then the water pressure in the supply piping is either too high (if higher than 5.5 bars, a pressure control valve has to be fitted), or the safety valve is defective. Please call a specialised plumber immediately!
If water contains too many minerals, an expert has to come to remove the scale that forms
inside the tank, as well as free sediments. This has to be performed after one or two years of operation. The cleaning is carried out through the hole in the flange – dismantle the flange lid and clean the tank. A new sealing has to be used for re-fitting. Since the inside of the heater has special enamel, which must not get in contact with the scale removing agent – do
not work with a lime pump. Remove the lime layer with a timber and suck it off, or wipe it off
with a clout. After that, the appliance must be rinsed thoroughly and the heating process is checked the same as during the initial putting in operation. Do not use any abrasive cleaning agents (such as liquid sand, chemicals - acid, alkaline) or dye thinners (such as cellulose thinner, trichlor, and the like) to clean the outer shell of the heater. For cleaning use a wet clout and add a few drops of liquid cleaning agent for household applications. Repetitive water heating causes limestone sediment on both the tank walls and chiefly the flange lid. The sedimentation depends on the hardness of water heated, its temperature, and amount of hot water consumed.
We recommend checking and cleaning the tank from scale and eventual replacement of the anode rod after two years of operation. The anode life is theoretically calculated for two
years of operation; however, it changes with water hardness and chemical composition in the place of use. Based on such an inspection, the next term of anode rod exchange may be determined. If the anode is only blocked with sediments clean its surface and, if used up, mount a new one. Have the company in charge of service affairs clean and exchange the anode. When draining water from the heater, the combination faucet valve for hot water must be open, preventing occurrence of under-pressure in the heater tank which would stop water from draining.
Page 21
- 21 -
2.8 SPARE PARTS
- Magnesium anode
- Contact thermometer
When ordering spare parts, give part name, type, and type number from the heater label.
3 IMPORTANT NOTICES
3.1 INSTALLATION REGULATIONS
- Without a confirmation of performed electrical installation issued by an authorised
company, the warranty certificate shall be void.
- Check and exchange the Mg anode regularly.
- No stop valves can be put between the heater and the safety valve.
- All hot water outputs must have a combination faucet.
- Before filling the heater with water for the first time, it is recommended to fasten the flange
connection nuts of the tank.
- It is not allowed to handle the thermostat, aside from temperature resetting with a control
button.
- All electric installation handling, adjustment and replacement of the regulation elements shall
only be performed by an authorised service company.
- The thermal fuse must not be turned off! In case of thermostat defect, the thermal fuse
interrupts electric power input to the heating element if the water temperature in the heater exceeds 90°C.
- As an exception, the thermal fuse may also switch off due to water overheating caused by
overheating the hot water heating system boiler.
- We recommend you operate the heater with one type of energy. In the case of instalation of
solar system to lower heat exchanger, is possible to heat up upper part of the water heater with use of electric heating device TJ, installed to 6/4 " socket approximately in height center of wessel.
Do not try to repair the failure yourselves. Seek either expert or service help. It does not
take much for an expert to remove the defect. When making a repair appointment, report the type and serial number you find on the performance plate of your water heater.
To prevent formation of bacteria (e.g. Legionella pneumophila) within stack heating it is
recommended, if absolutely necessary, to increase the temperature of HSW periodically for a transitional period of time to at least 70°C. It is also possible to make use of another way of HSW disinfecting.
Page 22
- 22 -
Both the electric and water installation must follow and meet the requirements and
regulations relevant in the country of use!
3.2 DISPOSAL OF PACKAGING MATERIAL AND FUNCTIONLESS
PRODUCT
A service fee for providing return and recovery of packaging material has
been paid for the packaging in which the water heater was delivered. The service fee was paid pursuant to Act No. 477/2001 Coll., as amended, at EKO­KOM a.s. The client number of the company is F06020274. Take the water boiler packages to a waste disposal place determined by the town. When the operation terminates, disassemble and transport the discarded and unserviceable heater to a waste recycling centre (collecting yard), or contact the manufacturer.
Page 23
- 23 -
4 ASSEMBLY GUIDE FOR ZIP-FASTENER
INSULATION (FOR 750 AND 1000 LITRES)
Two people are enough to implement the assembly; three people are required for larger boilers; the assembly must be implemented in areas with the temperature of at least 18
o
C.
If the insulation includes tank bottom insulation, the latter must be mounted first. Consequently, the insulation is inserted around the boiler; pre-pressed insulation openings must be respected.
By slight pull in the direction of the arrows, pull both sides of the zip-fastener insulation so that (Figure 11) the insulation does not slide and the insulation holes sit on the boiler inlets and outlets
It must be secured that before closing; both halves of the zip-fastener were not further 20 mm (Figure 12). No foam shall get into the zip-fastener on closing.
After the insulation coat is properly mounted and the zip closure closed properly, insert the top lid made of foam material and cover it with either a foil cover or a plastic lid. It is also possible to glue the outlet caps to connection places (Figure 13). The insulation may only be stored in dry storage places.
We take no responsibility for damages caused by not respecting this guide.
Figure 11 Figure 12 Figure 13
14-7-2015
Loading...